Sunteți pe pagina 1din 1

Occidental COMMENT SHEET

of Oman Inc.
Additional Compressors & GDU at Wadi Latham
OXY Project Code 1212153 PAGE
Equipment GDU Package 1 of 1
Job No.: 24000089278

Comments on CRS for POWER CABLE LIST REV00


VEND
OXY OXY
SR. VENDOR REPLY 1 OR VENDOR
COMMENTS / QUERY OXY RESPONSE 1 RESPONSE RESPONSE
NO (23/04/19) REPL REPLY 3
2 3
Y2
Equipment loads ups are already indicated on the
Vendor to clarify and Noted. Vendor to indicate “UPS” or
document "1061-10-LST-00003 ELECTRICAL
1. mention the equipment “Non UPS” as applicable in the notes
EQUIPMENT LIST REV00". Loads shall not be
loads ups . Column for the reference purpose.
indicated in this document.
motor start / stop / em.stop
2. Noted. It shall be added in the comments column. Noted.
(typical)
motor temperature winding
3. Noted. It shall be added in the comments column. Noted.
(typical)
Please see page 5 of this document. This is the cable
sizing calculation for each cable. This calculation
shall be completed when all loads are final and
1.Vendor to provide the
cables are tabulated (Without cable data is not Open. Not acceptable, Vendor to
cable sizing calculation for
possible to be done). Please see column "voltage consider the de-rating factors for the
4. the each type of cable. (de-
Drop (%) " on this page, it is its calculation. cable sizing.
rating factor & voltage drop
Regarding the de-rating factor no factor shall be
calculation.
considerated. We already design with a 20% over
current on each cable. For a cable to be suitable the
current shall be 120% more than the rated one.
2.Vendor to provide the
Cable catalogues and related documents to be Open. Provide the cable catalogue
5. cable catalogues and related
included in the quality book. for the sizing calculation purpose.
documents.

Page 1 of 1