Lighting Punch List

Project : Ketsi FSPM


Project Location : Punta Mita, México
Document Ref : 266/03954/FD
Date of Issue : 15 of February, 2019
Revision Number : 01
Ketsi FSPM - Punta Mita, México - Lighting Punch List

Fitting Location Problem Solution By


Ref

First Floor

- Entrance Signage Incorrect CCT Change LED tape to match L03 original specification AH

L03 Buffet bar Fixture not installed Install light fixture following original documentation. AH
Refer to control channel 1025 at plan 266_P001_13

U06 Art piece Lenses require cleaning while fixtures are unable to turn Clean lenses and check wiring or driver malfunction for AH
ON or be dimmed its replacement

D05 Entrance Honeycomb louvers are required. Fixtures are unable to Install compatible lamps with honeycomb louvers. AH
turn ON or be dimmed. SPJ19-05 and check wiring or driver malfunction for its
replacement
D04 Bar Wallwash trim not aimed properly. Adjust trim to be perpendicular to bar back wall, single AH
unit across the line not proper adjusted.

L04 Bar Fixture not installed Install light fixture following original documentation. AH
Refer to control channel 1014 at plan 266_P001_13

L03 Skylights Fixtures are not working properly due to drivers issues Driver has to be replaced and fixture replaces with AH
and present wrong CCT correct CCT

L03 Entrance - "DOS Wrong finish at detail interior Paint interior surfaces in matte black AH
CATRINAS" black
signage
U04 Entry - Water Feature Fixture not installed Install U04 and included on Control System - refer to AH
control channel 1031

U01 Columns Fixtures are unable to turn ON or be dimmed Check wiring or driver malfunction for its replacement AH

U05 Water feature to WC Fixtures are unable to turn ON or be dimmed Check wiring or driver malfunction for its replacement - AH
refer to control channel 1030
Ketsi FSPM - Punta Mita, México - Lighting Punch List

Fitting Location Problem Solution By


Ref

L03 Service hallway-niches Fixtures are unable to turn ON or be dimmed Check wiring or driver malfunction for its replacement - AH
refer to control channel 1004

L03 Service hallway-niches Fixtures are unable to turn ON or be dimmed Check wiring or driver malfunction for its replacement - AH
refer to control channel 1036

L03 Service hallway-niches Fixtures are unable to turn ON or be dimmed Check wiring or driver malfunction for its replacement - AH
refer to control channel 1005

D02 Kitchen Fixtures output less lumens than the version specified. Pursue warranty from manufacturer with LP aid. AH/LP

L02 Bottle up lights The first three fixtures (starting from the bar beverages Check wiring or driver malfunction for its replacement AH
entry) are unable to turn ON or be dimmed

L03 Stairs Fixtures are unable to turn ON or be dimmed Check wiring or driver malfunction for its replacement - AH
refer to control channel 1003

EX01 Bollards Fixtures are unable to turn ON or be dimmed Check wiring or driver malfunction for its replacement - AH
refer to control channel 1039

D03 North Service Entry One downlight fixture is unable to turn ON or be Check wiring or driver malfunction for its replacement - AH
dimmed refer to control channel 2067

D01 Skylight Three modules are unable to turn ON or be dimmed Check wiring or driver malfunction for its replacement AH

Second Floor

L07, L05, L06 Wood Screen Glare control detail by LP is not properly built Pending - LP Requires further information on screens AH/LP
construction and the possibility of reducing its high. /JLL

U03 Planters Lenses require cleaning Clean lenses AH


Ketsi FSPM - Punta Mita, México - Lighting Punch List

Fitting Location Problem Solution By


Ref

FL01 Upstairs Bar FL01 is not dimmable through power receptacle Lock manual dimmer on floot lamp as to avoid users to AH
change dimming setting from minimum

TL03 Table lamps Table lamps are not present Implement original specification or one of Neoz options AH/LP
at the Proposed Change List /JLL

L05 and L06 Wood screens at Drivers are visible Drivers to be properly concealed to keep aesthetic in AH
double height space site - refer to photo PUN_1464

L07 Chef terrace Fixture is unable to turn ON or be dimmed Check wiring or driver malfunction for its replacement AH

L06 - 3020 West screen Fixture is unable to turn ON or be dimmed. Fixtures are Check wiring or driver malfunction for its replacement. AH
currently Switch-Only

L05 - 3009 West screen Fixture is unable to turn ON or be dimmed. Fixtures are Check wiring or driver malfunction for its replacement. AH
currently Switch-Only

D03 East hallway One downlight presents a different CCT Match lamp with rest of the line AH

General

D04 General Specular reflectors require cleaning Clean reflectors following manufacturers suggestions AH

Linear General Incorrect CCT Supply and install correct specification which follows AH
applications specified CCT

Input Voltage General The project is runnig at 129V, instead of 127V. This Change input voltage to 120-127V AH
reduce the rated life of light fixtures, lamps and drivers.

Notes

JLL JLL
AH Alpha Hardin
LP Lux Populi
Ketsi FSPM - Punta Mita, México - Proposed Change List

Fitting Location Problem Solution By


Ref

D03 General Specified lamp does not integrate glare control Implement the following specification: 12V 7.5W LED AH
MR16 GU5.3 Base 2700K 10°
(Soraa Ref: 00919) + honeycomb louver (Product Ref:
00339)
P01 Terrace and double Lamp installed presents considerable glare and poor Replace lamps following attached markup AH/LP
height space dimmability, while having a non-desired CCT 266_Markups_190215 with: /JLL

Soraa PAR30
120V 18.5W LED E27 Base 2700K 9°
(Soraa Ref: 00821) + Beam Spreader 36° (Soraa Ref:
01147) + Honeycomb Louver (Soraa Ref: 01151)

Option 1 - Edison Firework:


https://www.amazon.com/Romantic-Fireworks-Squirrel-
Decorative-
Atmosphere/dp/B07CC9BGZD/ref=sr_1_1_sspa?__mk
_es_US=%C3%85M%C3%85%C5%BD%C3%95%C3
%91&keywords=fireworks+bulb&qid=1550270192&s=ga
teway&sr=8-1-spons&psc=1

Option 2 - Edison Incandescent:


https://www.amazon.com/dp/B005JE8G12?aaxitk=TpU
FHxzlAzcIUKmY.6WsoA&pd_rd_i=B005JE8G12&pf_rd
_p=e037c154-e093-48a4-b127-
477e5e294e3f&hsa_cr_id=9252038340801&sb-ci-
n=asinImage&sb-ci-v=https%3A%2F%2Fimages-na.ssl-
images-
amazon.com%2Fimages%2FI%2F81C%2BvzEdykL.jpg
&sb-ci-a=B005JE8G12
Ketsi FSPM - Punta Mita, México - Proposed Change List

Fitting Location Problem Solution By


Ref

P03 Bar Installed lamp does not have glare control Implement the following lamp with accesories: AH

120V 7.5W LED GU10 Base 2700K 10°


(Soraa Ref: 01111) + honeycomb louver (Product Ref:
00339)

TL01 Sitting areas Current candle lights are inefficient Implement any of the below options on locations shown AH/LP
at markup 266_Markups_190215: /JLL

-Margarita
https://www.neoz.com.au/media/wysiwyg/SpecLittleMar
garita.pdf

-Cooee 1c
https://www.neoz.com.au/media/wysiwyg/SpecCooee1c.
pdf

-Magill
https://www.neoz.com.au/media/wysiwyg/SpecMagill.pdf

TH01 Bar Fixtures present flicker Electricians shall wire fixtures directly, skipping AH
electrical connection through ballast

L06 Chef's office Integration is not correct Implement sketch 266_Cheff Office Detail_190215 AH
Ketsi FSPM - Punta Mita, México - Proposed Change List

Fitting Location Problem Solution By


Ref

U03 Planters Poor installation technique has cables and drivers Burial driver is required in order to be placed inside AH
visible and attached to planters planter, refert to this link:

https://www.hevilite.com/wp-
content/uploads/2014/08/HLT-DB-50-SPEC-SHEET-
Sheet1.pdf

WF02 Trellis above stairs Some fixtures are installed above pergola beam. One Move fixtures in between pergola beams and check AH/LP
fixture is unable to turn ON or be dimmed wiring or driver malfunction for its replacement /JLL

D02 Kitchen The fixtures are underperfoming, rendering less Pursue manufacturer warranty and replace with troffer AH/LP
illuminance than expected (following schematic sketch 266_Kitchen Panel /JLL
Layout_190215):

https://www.acuitybrands.com/products/detail/753016/lit
honia-lighting/epanl-flat-panel/-
/media/products/Lithonia_Lighting/753016/document/EP
ANL-Configurable_pdf.pdf?DOC_Type=SPEC_SHEET

Code: EPANL-2x2-4800LM-80CRI-35K-MIN10

Notes

JLL JLL
AH Alpha Hardin
LP Lux Populi
Ketsi FSPM - Punta Mita, México - Maintenance Stock List

Qty Manufacturer Code Description

20 Soraa 00919 12V 7.5W LED MR16 GU5.3 Base 2700K 10°
50 Soraa 00339 Honeycomb Louver
Soraa PAR30
10 Soraa 00821 120V 18.5W LED E27 Base 2700K 9°

10 Soraa 01147 Beam Spreader 36°


10 Soraa 01151 Honeycomb Louver for PAR30
15 Soraa 01111 120V 7.5W LED MR16 GU10 Base 2700K 10°
EPANL-2x2-
5 Acuity 4800LM-80CRI- LED 2x2 Panel
35K-MIN10

Confirm puchase to LP
Ketsi FSPM - Punta Mita, México - Programing Changes

Item Change Notes

General Follow Lux Populi documentation in order to have consistency on what Current condition on site does not allow for lighting zones to be
has been installed and what has been designed in terms of name of controlled following Lux Populi's control channles (zones) naming
control channels (zones) and dimmable fixtures. system.

General Provide live and wireless live settings for next programming session with Lutron programmer shall be able to access the system through a
Lux Populi. wireless network in order to live edit dimming values following Lux
Populi's instructions on site - final programming by Lux Populi cannot
happen without such condition.
General Pre-programming table provided by Lux Populi (266_Temporary
Programming Settings_00) shall be implemented for testing by JLL
and shall be fully implemented before final programming by Lux Populi.

General All control channels (zones) shall be clearly identified and "flagged" by
Lutron prior to Lux Populi's final programming.
General Lutron shall confirm that all dimmable zones are able to dim down to 1% Flickering fixtures shall be resolved by electrician prior to Lux Populi's
without issues like flicker. final commissioning.
U04 Control channel 1031 currently controls a different lighting item Re-assign control channel 1031 to U04 fixture