DESIGN OF ISOLATED FOOTING

EXTERIOR FOOTING F2
DATA
DESCRIPTION Value Unit
Soil Bearing Capacity, qₐ* 120 kPa
Steel Strength, fy 276 Mpa
Concrete Strength, f'c 28 Mpa
Unit Weight of Soil Above the Footing, δs 15.2 kN/m³
Unit Weight of Concrete, δc 24 kN/m³
Dead Load, DL 528.43 kN
Live Load, LL 66 kN
Earthquake Load, EL 405.2 kN
Bending Moment, MEL 130.35 kN-m
Column Size 350 mm
Excavated Depth of Footing, h 1.8 m
Diameter of Main Bar, db 25 mm
Diameter of Column Bar, dc 25 mm
Steel Covering 75 mm
Factored Load, Pu 1105.316 kN
Beta Factor, ϕ 0.85
* See National Building Code of the Philippines, Table 7.04 -(A) for the value of qa

Trial Depth of Footing: 300 mm


Effective Depth: d = trial depth - steel covering - 1.5(diameter of main bar)
d = 187.5 mm

Effective Soil Bearing Capacity:

qe = 90 kPa

Dimension of Footing:

12 m²

3.46 m
Combined Axial Load and Bending:

P = PU = 999.63 kN
M= 130.35 kN-m

-64.49 kPa

-110.92 kPa

Check if the effective depth of footing is adequate for wide beam shear:

1.37 m

64.49
46.44
2.09 m
110.92
By Ratio and Proportion:
28.08 kPa
92.57 kPa

482.70 kN
>

SAFE
572.82 kN

486.90 kN

Steel Requirements:

1.56 m

64.49

46.44
1.91 m
110.92

By Ratio and Proportion:

25.56 90.05 kPa

273.91 kN-m
2.50 Mpa
Steel Ratio: 1

0.000923517

0.005072

0.037653

0.005072

3294.66 mm²

7 25

Check Development Length:

512.07 mm

414 mm

3464.10 75 3389.10 > 512.07


OK!

Verify if dowels or column bars extension are necessary:

999.63 kN

Permissible Bearing Stress:

2040.85 kN

But this may be multiplied by

0.35 0.35 0.1225

3.46 3.46 12

9.90 > 2

4081.7 kN > 999.63 kN

No Need for Dowels but Provide Minimum

Minimun area of dowel or extension bar required by the Code:

612.5 mm²

25
Details:
1
0.5