Catalog HA 41.

11 · 2007

Switchgear Type 8DH10


up to 24 kV, Gas-Insulated, Extendable
Medium-Voltage Switchgear
Power Transmission and Distribution
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Contents Application, Requirements

Page Features
8DH10 switchgear is a factory- Quality and environment
Application, Requirements assembled, type-tested, three-pole, Quality and environmental
Features, typical uses 2 and 3 metal-enclosed, metal-clad single- management system acc. to
busbar switchgear for in-door in- DIN EN ISO 9001 and
Technical Data stallation: DIN EN ISO 14001
Electrical data, filling pressure, • Up to 24 kV
temperature 4 and 5 Personal safety
• Feeder currents up to 630 A
Switchgear installation, shipping data 6 and 7
• Busbar currents up to 1250 A • Safe-to-touch and hermetically
Product Range sealed primary enclosure
Product range overview 8 to 15 Typical uses • HV HRC fuses and cable sealing
8DH10 switchgear is used – even ends are only accessible when
Design outgoing feeders are earthed
under severe environmental con-
Panel design 16 and 17 ditions – for power distribution in • Operation only possible when
Components secondary distribution systems, enclosure is closed
such as • Logical mechanical interlocking
3AH vacuum circuit-breaker 18 and 19
Substations, customer transfer • Capacitive voltage detecting sys-
Three-position switch-disconnector 20
substations, distribution sub- tem to verify safe isolation from
Busbars 21 stations and switching substa-
Transformers 22 to 27 supply
tions of power supply and
Cable connection 28 public utilities • Feeder earthing by means of
Low-voltage equipment 29 make-proof earthing switches
Industrial plants, such as:
Dimensions • Wind power stations Security of operation
Individual panels, panel blocks 30 to 34 • High-rise buildings • Hermetically sealed primary
Metering panel combinations 33 and 35 • Airports enclosure independent of
Floor openings and fixing points 36 to 39 environmental effects (such as
• Lignite open-cast mines pollution, humidity and small ani-
Cable connection examples 40
• Underground railway stations mals) – sealed for life:
Standards, Transport, Notes – Welded switchgear vessel
• Sewage treatment plants
Standards, specifications, guidelines 41 – Welded-in bushings and operating
• Port facilities mechanism
Transport data, classification 42
Notes 43 • Traction power supply systems • Operating mechanism parts
• Automobile industry maintenance-free
For further information, please refer to (IEC 60 694 / VDE 0670-1000)
• Petroleum industry
• Catalog HA 40.1: (Switchgear Type 8DJ and 8DH, • Operating mechanisms of switch-
General Part) • Chemical industry ing devices located outside the
• Supplements to Catalogs HA 45.31/41.11 • Cement industry switchgear vessel (primary enclo-
sure)
• Unit-type heating power stations
Invalid: Catalog HA 41.11 · 2006 • Switchgear interlocking system
• Textile, paper and food
with logical mechanical interlocks
industry
• Mechanical switch-position
• Emergency power supply
indicators integrated in the
installations
mimic diagram
Modular design
Cost-efficiency
• Individual panels and panel
Extremely low “life-cycle costs”
blocks can be freely combined
throughout the entire product
and extended – without gas work
service life as a result of:
on site
• Maintenance-free concept
• Low-voltage compartments can
be supplied in two overall heights • Climatic independence
and are wired to the panel by • Minimum space requirements
means of plug-in connections
• Maximum availability
Reliability
Security of investment
• Type and routine-tested
Innovative developments, such as:
The products and systems described in this catalog are • Standardized and manufactured
manufactured and sold according to certified quality using numerically controlled • Modular design
and enviromental management system (acc. ISO 9001 machines • Switchgear extension without gas
and ISO 14001). • More than 430,000 8DJ/ 8DH work on site
(DQS Certificate Reg. No. DQS 003473 QM UM). panels in operation worldwide • Maintenance-free 3AH vacuum
The certificate is accepted in all IQNet countries. for many years circuit-breaker
• SIPROTEC protection device family
© Siemens AG 2007

2 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Application

Typical uses
Technology
• Maintenance-free
• Climate-independent
• Partition class: Class PM
(metallic partition)
• Three-pole primary enclosure,
metal-enclosed
• Insulating gas SF6

R-HA41-013a eps
• Welded switchgear vessel without
seals, made of stainless steel,
with welded-in bushings for elec-
trical connections and mechanical
components
• Three-position switch-discon-
nector with load-break and
make-proof earthing function
• Cable connection for bushings
with outside cone
• Connection with cable plugs
– In ring-main feeders and
circuit-breaker feeders with
bolted contact (M16) Example
– In transformer feeders with Customer transfer switchgear
plug-in contact
• Option: Connection with conven-
tional cable sealing ends
– For thermoplastic-insulated
cables via elbow adapter
AKE 20 / 630 (make Siemens)
– For paper-insulated mass-
impregnated cables via commer-
cially available adapter systems
• Easy installation
• Option: Pressure absorber system
– Maintenance-free
– For rated short-time withstand
current Ik £ 20 kA
– For single and multi-panel
combinations of 700 mm to
2000 mm width (for panel type
ME1 with max. 1 adjacent panel)
– With 300 mm high pressure ab-
sorber duct below the switchgear
and
– With 115 mm deep pressure
absorber duct for pressure relief
upwards
– With screwed-on cable
compartment cover
– Possible for switchgear with stand-
R-HA41-015 eps

ard cable compartment cover


Option: Deeper cable compart-
ment cover: 105 or 300 mm
– For overall height of switchgear,
see page 6 Application
– Option: Free-standing arrange- Customer transfer substation in an
ment, for overall height of accessible switchgear building
(transformers, medium-voltage and
switchgear 2300 mm and with
low-voltage in a factory-assembled
rear cover
R-HA41-014 eps

building)
For further information concerning
the pressure absorber system,
please refer to page 39
and to Catalog HA 40.1
Standards Application
See page 41 Power supply of high-rise buildings

Siemens HA 41.11 · 2007 3


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Technical Data

Electrical data

Common Rated insulation level Rated voltage Ur kV 7.2 12 15 17.5 24


electrical data Rated short-dur. power-freq. withstand voltage Ud:
– phase-to-phase, phase-to-earth, open contact gap kV 20 28 1) 36 38 50
– across the isolating distance kV 23 32 1) 39 45 60
Rated lightning impulse withstand voltage Up:
– phase-to-phase, phase-to-earth, open contact gap kV 60 75 1) 95 95 125
– across the isolating distance kV 70 85 1) 110 110 145
Rated frequency fr 50/60 Hz
Rated normal current Ir 2) for busbar (standard) up to A 630 630 630 630 630
for busbar (option) *) A 1250 1250 1250 1250 1250
Filling pressure, Rated filling level pre for insulation 150 kPa (absolute) at 20 °C
temperature, Min. functional level pme for insulation 130 kPa (absolute) at 20 °C
partition class 3)
Ambient air temperature T Panels without secondary equipment Class “Minus 25 indoor” (-25 to +70 °C 4))
and
classification Panels with secondary equipment, Class “Minus 5 indoor” (-5 to +55 °C 4))
circuit-breaker panels
Partition class Class PM (metallic partition)
Loss of service LSC (loss of service continuity) LSC 2
continuity category 5)

Panel data
Ring-main panel Rated normal current Ir 2) for feeder (for panel types RK ... and K ...) A 400, 630 400, 630 400, 630 400, 630 400, 630
type RK, for bus sectionalizer panel type LT2 A 400, 630 400, 630 400, 630 400, 630 400, 630
bus sectionalizer
Rated short-time for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20
panel type LT2,
withstand current Ik for switchgear with tk = 3 s (option) up to kA – – 20 – 20 – 20 – 20
cable panel
type K Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50
Rated short-circuit making current Ima up to kA 50 63 50 63 50 63 50 63 50

Transformer Rated normal current Ir 2) for feeder 6) A 200 200 200 200 200
panel type TR Rated short-time for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20
withstand current Ik for switchgear with tk = 3 s up to kA – – 20 – 20 – 20 – 20
Rated peak withstand current Ip 6) up to kA 50 63 50 63 50 63 50 63 50
Rated short-circuit making current Ima 6) up to kA 25 25 25 25 25 25 25 25 25
Reference dimension “e“ of the HV HRC fuse links mm 292 7) 292 442 442 442

Circuit-breaker Rated normal current Ir 2) for feeder (for panel types LS ...) A 400, 630 400, 630 400, 630 400, 630 400, 630
panel type LS, for bus sectionalizer panel type LT1 A 400, 630 400, 630 400, 630 400, 630 400, 630
bus sectionalizer
Rated short-time for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20
type LK/LT1
withstand current Ik for switchgear with tk = 3 s up to kA – – 20 – 20 – 20 – 20
Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50
Rated short-circuit making current Ima up to kA 50 63 50 63 50 63 50 63 50
Rated short-circuit breaking current Isc 8) up to kA 20 25 20 25 20 25 20 25 20
Electrical service life of at rated normal current 10 000 operating cycles
3AH vacuum circuit-breakers at rated short-circuit breaking current 50 breaking operations

*) Not for billing metering 2) The rated normal currents apply 6) Depending on the HV HRC fuse link,
panels type ME1 to ambient air temperatures of observe the max. let-through
1) According to some national require- max. 40 °C. The 24-hour mean current of the HV HRC fuse links
ments, higher values of the rated value is max. 35 °C (according to 7) Extension tube (150 mm long)
short-duration power-frequency IEC 60 694 / VDE 0670-1000) required additionally for fuse
withstand voltage available for 3) Operating conditions according to mounting 442 mm
Ik = 20 kA with: IEC 62 271-200. 8) For the 3AH vacuum circuit-breaker
- 42 kV for phase-to-phase, For application, see also pages
phase-to-earth and open contact 2 and 41 (climate and ambient
gap as well as conditions)
- 48 kV across the isolating distance 4) Temperature range, reduced
Higher values of the rated lighting normal currents at ambient air
impulse withstand voltage temperatures > +40 °C
(for IK = 20 kA) :
- 95 kV for phase-to-phase, 5) Classification according to
phase-to-earth and open contact IEC 62 271-200 (see also page 42)
gap as well as
- 110 kV across the isolating
distance

4 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Technical Data

Electrical data

Common Rated insulation level Rated voltage Ur kV 7.2 12 15 17.5 24


electrical data Rated short-dur. power-freq. withstand voltage Ud:
– phase-to-phase, phase-to-earth, open contact gap kV 20 28 1) 36 38 50
– across the isolating distance kV 23 32 1) 39 45 60
Rated lightning impulse withstand voltage Up:
– phase-to-phase, phase-to-earth, open contact gap kV 60 75 1) 95 95 125
– across the isolating distance kV 70 85 1) 110 110 145
Rated frequency fr 50/60 Hz
Rated normal current Ir 2) for busbar (standard) up to A 630 630 630 630 630
for busbar (option) *) A 1250 1250 1250 1250 1250
Filling pressure, Rated filling level pre for insulation 150 kPa (absolute) at 20 °C
temperature, Min. functional level pme for insulation 130 kPa (absolute) at 20 °C
partition class 3)
Ambient air temperature T Panels without secondary equipment Class “Minus 25 indoor” (-25 to +70 °C 4))
and
classification Panels with secondary equipment, Class “Minus 5 indoor” (-5 to +55 °C 4))
circuit-breaker panels
Partition class Class PM (metallic partition)
Loss of service LSC (loss of service continuity) LSC 2
continuity category 5)

Panel data
Busbar earthing Rated short-time for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20
panel withstand current Ik for switchgear with tk = 3 s (option) up to kA – – 20 – 20 – 20 – 20
type SE,
Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50
busbar voltage
metering panel Rated short-circuit making current Ima up to kA 50 63 50 63 50 63 50 63 50
type MS1V/ME3

Billing metering Rated normal current Ir 2) for transfer up to A 630 630 630 630 630
panels for feeder (T with cable panel as type ME1-K) up to A 630 630 630 630 630
types ME1
for busbar metering up to A 630 630 630 630 630
and ME2
Rated short-time for switchgear with tk = 1 s up to kA – 25 20 25 20 25 20 25 20
withstand current Ik for switchgear with tk = 3 s up to kA 20 – 20 – 20 – 20 – 20
Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50

*) Not for billing metering 2) The rated normal currents apply


panels type ME1 to ambient air temperatures of
1) According to some national require- max. 40 °C. The 24-hour mean
ments, higher values of the rated value is max. 35 °C (according to
short-duration power-frequency IEC 60 694 / VDE 0670-1000)
withstand voltage available for 3) Operating conditions according to
Ik = 20 kA with: IEC 62 271-200.
- 42 kV for phase-to-phase, For application, see also pages
phase-to-earth and open contact 2 and 41 (climate and ambient
gap as well as conditions)
- 48 kV across the isolating distance 4) Temperature range, reduced
Higher values of the rated normal currents at ambient air
lighting impulse withstand temperatures > +40 °C
voltage (for Ik = 20 kA):
- 95 kV for phase-to-phase, 5) Classification according to
phase-to-earth and open contact IEC 62 271-200 (see also page 42)
gap as well as
- 110 kV across the isolating
distance

Siemens HA 41.11 · 2007 5


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Technical Data

Switchgear installation
Room planning
Switchgear installation with Switchgear installation with rear-side
Switchgear installation standard panels pressure absorber duct (option)

Wall-standing arrangement
– Single row
Switchgear room Switchgear room
– Double row (for face-to-face * 23
arrangement) 22 2 22

³2400**
Option: Free-standing *** ³1000
arrangement 3 13
³1000
For room planning and 4 15
switchgear installation, please
note: 890

³2400**
5
775 ³1000
– Floor openings: Dimensions

2300*
828
2000

see pages 36 to 39 1070 ³1000


– Direction of pressure relief
6
acc. to serial no. 13
– Respective pressure relief 7
rooms 8
9 16

300
Room dimensions see opposite
dimension drawings
10 115 ~200
>600

Door dimensions 11 17
1
12 834
The door dimensions depend
Cable basement 13 Cable basement
on the
– Number of panels in a
Side view 14 Side view
transport unit
– Design with or without ³15 18 ³15
low-voltage compartment

Switchgear fastening
³50
10

• For floor openings and fixing


19
points of the switchgear, 15
see pages 36 to 39 7 21
• Foundations:
– Steel structure
– Steel-reinforced concrete

Panel dimensions see p. 30 to 34

Weight
20
For details, please refer to page 7.
21
HA41-2286g eps

³50

HA41-2287h eps
10

* Switchgear height for version with


pressure absorber duct:
– For wall-standing arrangement Top view Top view
W 1950 mm (panel combination
without metering panel ME1)
W 2300 mm (for combination
with metering panel ME1) 1 Relief opening 9 Foundation 17 Depth of the pressure absorber
– For free-standing arrangement duct behind the panel
W 2300 mm (high end walls, rear 2 Opening (e.g. for ventilation 10 2nd cable for connection with
wall and front covers, optional as option) of double T-plugs in conjunc- 18 Wall distance
low-voltage compartment) tion with larger floor opening 19 End wall
3 Room height
and design with deep cable
** Installation conditions for internal 4 Panel depth of the standard compartment cover 20 Panel width
arc classification acc. to panel (may be 15 mm deeper 21 Width of the pressure absorber duct
IEC 62 271-200 11 Height of the cable
for free-standing arrangement, basement corresponding to – 700 mm for panel combinations
*** Height of pressure absorber duct depending on the panel design) the cable bending radius – Approx. 850 mm for metering
2100 mm with: panels type ME1
5 Control aisle D 12 Cable
– Wall-standing arrangement with 22 Standard:
metering panel ME1 6 Panel depth of panels with 13 Direction of pressure relief Low-voltage compartment
– Free-standing arrangement for all deep cable compartment for circuit-breaker panels
14 Floor openings:
panel types cover
Dimensions see pages 34 to 37 Option:
B Depending on national 7 Deep cable compartment – Low-voltage compartment
15 Option:
specifications: cover for all other panel types or
Pressure absorber duct
– For extension/panel replacement: – Front cover
Control aisle W 1000 mm 8 Standard cable compartment 16 Base height of the pressure
recommended (for Germany cover absorber duct beneath the 23 Relief outlet
W 800 mm) panel

6 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Technical Data

Shipping data
Individual panel, panel block Type Panel or panel combination Transport unit (including packing) for standard panels (without
or combinations thereof Short iden- pressure absorber system)
for standard switchgear tification B
(without pressure relief duct) Width B1 Net weight 1) Width B2 Height Depth Volume Gross weight 1)
current in mm approx. kg m m T2 m m3 approx. kg
future without / with without /with without /with without /with
LVC */ LVC * LVC */ LVC * LVC */ LVC * LVC */ LVC *

Transport of individual panels


Ring-main panel (standard) RK RK 350 150 / 210 0.70 1.60 / 2.20 1.10 1.23 / 1.69 210 / 270
RK1 RK1 500 180 / 240 0.70 1.60 / 2.20 1.10 1.23 / 1.69 240 / 300
RK2 RK1 V 500 200 / 260 0.70 1.60 / 2.20 1.10 1.23 / 1.69 260 / 320
Cable panel (standard) K K 350 145 / 205 0.70 1.60 / 2.20 1.10 1.23 / 1.69 205 / 265
Transformer panel TR TR1 500 180 / 240 0.70 1.60 / 2.20 1.10 1.23 / 1.69 240 / 300
Circuit-breaker panel (standard) LS1 LS1 500 – / 260 0.70 – / 2.20 1.10 – / 1.69 – / 320
LS2 LS1 V 500 – / 380 0.70 – / 2.20 1.10 – / 1.69 – / 440
Circuit-breaker panel BB LST1 LST1 500 280 / 340 0.70 1.60 / 2.20 1.10 1.23 / 1.69 320 / 380
Bus sectionalizer panel with circuit-breaker LT1 LK 500 – / 280 0.70 – / 2.20 1.10 – / 1.69 – / 340
LT1-V LK V 500 – / 380 0.70 – / 2.20 1.10 – / 1.69 – / 440
Bus sectionalizer panel with switch-disconnector LT2 LT 500 150 / 210 0.70 1.60 / 2.20 1.10 1.23 / 1.69 210 / 270
Busbar earthing panel SE1 SE 350 150 / 210 0.70 1.60 / 2.20 1.10 1.23 / 1.69 210 / 270
with voltage transformer SE2 SE1 V 500 250 / 310 0.70 1.60 / 2.20 1.10 1.23 / 1.69 310 / 370
Busbar voltage metering panel ME3 MS1 V 500 250 / 310 0.70 1.60 / 2.20 1.10 1.23 / 1.69 310 / 370
Billing metering with cast-resin ME1 ME1 850 250 / 310 1.08 1.60 / 2.20 1.10 1.90 / 2.61 310 / 370
panels, insulated transformers
air-insulated **
with combined ME2 ME2 600 390 / 450 1.08 1.60 / 2.20 1.10 1.90 / 2.61 450 / 510
transformers

Transport of panel blocks


Ring-main panel block R-B2 700 280 / 400 1.08 1.60 / 2.20 1.10 1.90 / 2.61 340 / 460
R-B3 1050 400 / 580 1.40 1.60 / 2.20 1.10 2.46 / 3.40 470 / 650
Transformer panel block T-B2 1000 320 / 440 1.40 1.60 / 2.20 1.10 2.46 / 3.40 390 / 510
T-B3 1500 480 / 660 2.03 1.60 / 2.20 1.10 3.57 / 4.91 560 / 740
Ring-main/transformer panel block RT-B2 700 300 / 420 1.08 1.60 / 2.20 1.10 1.90 / 2.61 360 / 480
2RT-B3 1050 450 / 630 1.40 1.60 / 2.20 1.10 2.46 / 3.40 520 / 700
3RT-B4 1400 580 / 820 2.03 1.60 / 2.20 1.10 3.57 / 4.91 660 / 900
Cable connection/transformer panel block KT-B2 700 300 / 420 1.08 1.60 / 2.20 1.10 1.90 / 2.61 360 / 480

Transport of combinations of different individual panels or panel blocks


Comprising Overall width B3 B2 T2
– a number of individual panels or
£ 850 mm 1.08 1.60 / 2.20 1.10 1.90 / 2.61 2) + 60 ***
– 1 panel block or
– a number of panel blocks or £ 1200 mm 1.40 1.60 / 2.20 1.10 2.46 / 3.39 2) + 70 ***
– individual panels with panel blocks £ 1800 mm 2.03 1.60 / 2.20 1.10 3.57 / 4.91 2) + 85 ***

£ 2350 mm 2.53 1.60 / 2.20 1.10 4.49 / 6.17 2) + 100 ***

B Short identifications of the panels have been harmonized


BB Panel type LST1: Please refer to separate Catalog HA 45.31/41.11, Supplements to Catalogs HA 45.31/41.11

1) The net weight and the gross


Transport units for shipping (top view) weight depend on the extent to
which they are equipped (e.g. with
1 T1 = Depth of individual current transformers, motor oper-
panel or of panel block ating mechanism, deep cable
compartment cover) and are
2 Individual panel or panel therefore given as mean value
block, dimension B1 x T1
2) Sum of the net weights of indi-
3 Transport unit, vidual panels and / or panel blocks
dimension B2 x T2
* Low-voltage compartment,
4 B3 = Overall width of 600 mm high, weight approx.
combination of different 60 kg depending on the panel
With individual panel individual panels type and on the extent
or panel block or panel blocks to which it is equipped
With combinations of different individual
panels and/or panel blocks ** The weights depend on the
5 B2 = Width of the
(option: Panels bolted together and busbars mounted) weights of the mounted
transport unit
transformers
*** Packing weight

Siemens HA 41.11 · 2007 7


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Technical
Product Range
Data

Product range overview

Designation of the Panel Type


individual panels width
and panel blocks

Short identifications *
current in future

Individual panels Column no.


Ring-main panel 350 RK RK
500 RK1 RK1
500 RK2 RK1 V
350 RK-U RK-U
500 RK1-U RK1-U
500 RK2-U RK1 V-U
Cable panel without earthing switch 350 K K
350 K-U K-U
Cable panel with make-proof earthing switch 350 K K
350 K-U K-U
Transformer panel 500 TR TR1
500 TR-U TR1-U
Transformer panel with plug-in voltage transformers 500 TR-V TR1-V
500 TR/V TR1/V
Circuit-breaker panel 500 LS1 LS1
500 LS1-U LS1-U
Circuit-breaker panel with plug-in busbar voltage transformers 500 LS2 LS1 V
500 LS2-U LS1 V-U
Circuit-breaker panel (with disconnecting circuit-breaker) DD 500 LST1 LST1
Bus sectionalizer (with vacuum circuit-breaker) 500 LT1 LK
500 LT1-V LK V
Bus sectionalizer (with switch-disconnector) 500 LT2 LT
Busbar earthing panel 350 SE1 SE
500 SE2 SE1 V
Busbar voltage metering panel 500 ME3 MS1 V

Billing metering panel 850 ME1 ME1


850 ME1-K ME1-K
Legend for pages 8 and 9
Billing metering panel for busbar connection 850 ME1-S ME1-S
* Short identifications of the panels cable connection 850 ME1-KS ME1-K
have been harmonized
Billing metering panel with combined transformers 600 ME2 ME2
** LV terminals as an option in the LV
compartment (compartment to be Panel blocks Column no.
ordered as an option)
D Three-position switch as Ring-main panel block 700 R-B2
three-position switch-disconnector 1050 R-B3
(switch-disconnector Transformer panel block 1000 T-B2
CLOSED-OPEN-EARTHED)
1500 T-B3
BB Three-position switch as
Ring-main/transformer panel block RK
three-position circuit-breaker 700 RT-B2
(disconnecting circuit-breaker T
CLOSED-OPEN-EARTHED), see RK
Supplements to Catalogs 1050 2RT-B3
T
HA 45.31/41.11-2007
RK
1) The equipment applies to the entire 1400 3RT-B4
panel block, but it is located in the T
first feeder panel from the left Cable connection/transformer panel block K
(cable panel without make-proof earthing switch) 700 KT-B2
2) Low-voltage terminals arranged in T
the low-voltage niche of the Cable connection/transformer panel block K
ring-main or cable feeder (cable panel with make-proof earthing switch) 700 KT-B2
T

8 Siemens HA 41.11 · 2007


Switchgear
Switchgear Type
Type 8DH10,
8DH10 up
up to
to 24
24 kV,
kV, Gas-Insulated,
Gas-Insulated, Extendable
Extendable

Product Range

Ausstattungsmerkmale
Equipment features
x /
• Basic equipment bo n ED C )
) si m a tio LOS aker + 2N PEN nd
Additional equipment B n ic r C re O O ) a
° (option), further additional ker
B
ech
a
) s ) ic e
in
d
n
to -b N
ec cuit N: 2 D
d
an ch
it
B

r
a m * B
ice rv on cir PE SE w ke
equipment on request ) re B
h
B
it-b t
g
in ox * n d d ev r-se disc NC; D/O C LO on s rea
– Not available itc rcu on er
a b t ) a g fo ch- + 2 SE ) (f
. iti ) t-b
sw ci en B in y- t O BB os itc
h B
B
B
)
ui
n n ed op ism tm ch tch ead Swi NO CL -p w d B irc se
o o w e n r it i r d e s n d c
iti iti th cha pa sw r sw cal BB : N: 2 ING ) an thre
)
re g ) a n um le
a
os os /sc ov
e e m i H B in B
B
) a
cu d re
e -p e-p a ce b m l co ition g. fo ectr ) and OPE RT c h ee n
a rth tch h a e
r pl a g / i c v
hr
e
hr
e ve p. atin in
a s e. e el B ED , EA it w e
sw swi or
t at
r t or t t co d in po r( t h S C sw bet of ) AH er
fo f n e com per term ree- ato mo itc CLO 2N o s.
e l -p ro BB
tion on c at or 3 r op )
ck al o c w p e d i i i f
ism ism tm
e as r th ndi rr
e s
n G O
+ e- pan ak ) an -po
s it d e *
lo in he he fo ce i ) fo sitio HIN 2N re os lt in ism orm nt *
h an han par ver e rm in t ic e i T : f. th ker r r m B
h e e e -p u a n sf e
n s O o a e o r a ps nt
ec ec m co et st al
s e ea -ser 1 N
v
-p AR EN n. re ak t f itc th e
hr th-
f h
ec -tra part r
n m
m m e co nt ck he a in ltag rel r ( ree C, E /OP c ha it-b bre -ou sw for or t r m t la m e
g g l e a o - a n e m
in in b m br nic rm vo nt y-
f h h
tc or t 2N SED
e cu uit lock tion out ce f or e ting rre om cov le c uip
rat r at r ca art le te - u d i t. m ir c i - i c b
e e o p b e e w sh a sw ch f O + CLO ra c
n cir ing pos ock dev cuit ra s cu ge age ca ry e
q
op op ck f m ca ltag ltag te lo as n. re ng it N pe ki - l pe a ta t d
ual ual lo co l as v o v o ra se a lli s w : 2 LST r -o loc uum arth ree ing in g
t-cir r o se v ol v ol nte nda
r e i - - a h a x. EN pe o r -e th los ock hor o a - -
an an nte bl ra w ow epa ele ec gn ot nte vac ot ele w ow ou eco
M M I Ca C- Lo L S R M Si Au OP ty M I De of C L S M R Lo L M S
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
• – • – • • – – – • – – – –
• – • – • • – – – •
° ° ° – –
° ° ° – –
° ° ° °
• – • – • • – – – •
° ° ° – –
° ° ° – –
° ° ° °
• – • – – • – – – •
° ° ° – –
° ° °
– – –
° ° –
° °
• – • – – • – – – •
° ° ° – –
° ° – – –
° ° –
°
• – • – – • – – – •
° ° ° – –
° ° – –
° ° –
°
– – – • • • – – – •
° °

°
– – –
°

°

° – –
° ° °
– – – • – • – – – •
° – – – – – –
°
– – –
° ° °– °
• – • – • • – – – •
° – – – – – –
° ° °
• – • – – • – – – •
° ° – – – –
° °
– – –
° ° °– °
• – • – • – • – •
° ° – –
° – – –
° ° °
• – • – – – • –
° •
° ° ° –
° –
° – – –
° ° °– °
• – • – • – • –
° •
° ° ° –
° –
° – – –
° ° °
• – • – – – • –
° •
° ° ° –
° –
° – – –
° ° °– °
• – • – • – – –
° •
° ° ° °

° °• °

°
• – • – – – – –
° •
° ° ° ° –
° ° –
° ° ° • –
°– °
• – • – • – – –
° •
° ° ° ° –
° ° ° ° –
°
• – • – – – – –
° •
° ° ° ° –
° ° °– ° ° •• –
°– °
– – –
° ° °• ° °

° ° ° ° °




– •





– –
° •

° ° °

°– °• °– – ° ° –
° °– °
• – – • – – – –
° •
° ° ° ° – – • –
° ° •• – –
°
• – – • – • – –
°
– •
° ° ° °
– – – • –
°

°
– –
°
• – • – – • – – – •
° ° °
– – – – • – – –
° ° –
°
• – • – – • – – – •
° ° – – – – • – – –
° ° –
°
• – – • – • – – – •
° ° – – – – – –
° ° –
°
° ° ° ° ° ° °
– – – – – – – – – – – – – – – – – –
– – –

• • – –

• – – – – – – – – – – – –
° ° – °
– – – • – – – • – – – – – – – – – – – –
° ° –° °
– – – • • – – • – – – – – – – – – – – –
° ° °
– – – • – – – – – – – – – – – – – – – –
° ° –° °
° ° °
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
– – – – – 1) – – – – –
• • • • •1)
• – • – • • – – – •1)
° 1)
° ° – – –
° ° – –
° ° ° °
• – • – • – – – •1)
° 1)
° ° – –
° °
– – –
° ° ° °
• – • – • – – –
° •1)
° 1)
° ° –
° –
° – – –
° ° ° °
• – • – • • – –
°
– •1)
° 1)
° ° –
°

° – –
° ° ° °
• – • – • – – 1)
°
1)
° ° –
°– ° °
– – –
° ° ° °
• – • – • •
2)

– –
°
– •1) 1)
° ° –
°

° – –
° ° ° °
• – • – • – – 1)
°
1)
° ° –
°– ° °
– – –
° ° ° °
• – • – • •
2)

– –
°
– •1) 1)
° ° –
°

° – –
° ° ° °
• – • – • – – 1)
°
1)
° ° –
°– ° °
– – –
° ° ° °
– – – • • •
2)

– –
°
– • 1) 1)
°

°
– –
°
– –
°
– – –
° ° ° °
– – – – –
°
1) – –
° ° ° ° °
° – – –
• • 2)

• – • – • • – –
°

1)

•1)
° °
– –
°
– – – –
° ° ° °
• – • – • 2) – – 1)
°
1)
1)

° – –
° –° – –
° ° ° °
° ° ° ° ° ° ° ° °
Siemens HA 41.11 · 2007 9
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Product Range

Ring-main, cable and transformer panels as individual panels

Ring-main panels Cable panels Transformer panels


as feeder panels as feeder panels as feeder panels
Three-position
Type RK Type TR1 switch-disconnector
option option Type K option
350 mm wide 350 mm wide 500 mm wide
HA41-2213_1d eps

HA41-2218_1d eps

HA41-2223_1d eps
Type RK1 1) 3)
500 mm wide HV HRC fuse

option option option


Option: Capacitive
Type RK1 V 1) 2) 3) voltage detecting
500 mm wide system

**
option Type RK * option Type K * option Type TR1-V B
350 mm wide 350 mm wide 500 mm wide Cable-type current
HA41-2214_1e eps

HA41-2219_1e eps

HA41-2224_1d eps
for 2nd cable* for 2nd cable * with plug-in transformer
voltage trans-
formers

4MT8 plug-in voltage


transformer at the
option option option cable connection
** **

4MT8 plug-in voltage


transformer at the
option Type RK * option Type K * option Type TR-V B connection
350 mm wide 350 mm wide 500 mm wide
HA41-2215_1d eps

HA41-2220_1d eps

HA41-2225_1d eps

(105 mm deeper
with plug-in with plug-in
cable compart-
surge surge
ment cover) Cable (not
arresters * arresters *
with plug-in included in the
voltage trans- scope of supply)
formers in-
option option stead of cable
connection
2nd cable (not
included in the
scope of supply)

as transfer panels as transfer panels as transfer panels


option Type RK-U Type K-U option Type TR1-U Plug-in
350 mm wide 350 mm wide 500 mm wide surge arrester
HA41-2216_1d eps

HA41-2226_1d eps

HA41-2278e eps

for transfer for transfer for transfer


to the right option to the right to the right
HA41-2221_1d eps

Make-proof
earthing switch

Option:
Type RK1-U 3)
Type RK1V-U 2) 3)
500 mm wide

option Type RK-U Type K-U option Type TR1-U


350 mm wide 350 mm wide 500 mm wide
HA41-2227_1d eps
HA41-2217_1d eps

for transfer for transfer for transfer


to the left option to the left to the left
HA41-2222_1d eps

Option:
Type RK1-U 3)
Type RK1V-U 2) 3)
500 mm wide
Footnotes
see page 11

10 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Product Range

Ring-main, cable and transformer panels in panel blocks DD

Ring-main panel blocks Ring-main/transformer panel blocks


Designs and options for each panel, see page 10 Designs and options for each panel, see page 10
RK RK RK TR c Three-position
Type R-B2 Type RT-B2 switch-disconnector
HA41-2228_1d eps

HA41-2232_1d eps
700 mm wide 700 mm wide
consisting of consisting of
2 ring-main panels 1 ring-main panel and
1 transformer panel HV HRC fuse

Capacitive
voltage detecting
system
BB Capacitive voltage
RK RK RK RK RK TR c detecting system at
Type R-B3 Type 2RT-B3
HA41-2233_1c eps
HA41-2229_1c eps

the busbar of the


1050 mm wide 1050 mm wide panel blocks: Only
consisting of consisting of located once in the
3 ring-main panels 2 ring-main panels and first panel of the
1 transformer panel block!

HA41-2278e eps
Cable (not
included in the
scope of supply)

RK RK RK TR c
Type 3RT-B4
HA41-2234_1c eps

Transformer panel blocks 1400 mm wide

Designs and options for each panel, see page 10 consisting of


3 ring-main panels
TR TR and
Type T-B2 1 transformer
HA41-2230_1c eps

1000 mm wide panel


consisting of
2 transformer panels

Footnotes
from page 10
B Deep cable
Cable connection/transformer panel block compartment
cover required
Designs and options for each panel, see page 10
* Depending on
TR TR TR K TR c the make/type of
Type T-B3 Type KT-B2 the cable
HA41-2235_1e eps
HA41-2231_1c eps

1500 mm wide 700 mm wide plug or arrester:


consisting of consisting of Deep cable
3 transformer 1 cable connection panel compartment
panels 1 transformer panel cover required
** Cable-type
current trans-
former on the
2nd cable:
For 300 mm
deeper cable
compartment
cover
1) Suitable for
Designs Designs voltage
• Busbar connection system for connection of individual • Busbar connection system for connection of individual transformer
panels or panel blocks: Arranged in the left-hand panel of the type 4MT8
panels or panel blocks: Arranged in the left-hand panel of the
panel block (therefore extendable at a later date) panel block (therefore extendable at a later date) 2) Suitable for
• Only either the left-hand or the right-hand panel of the panel block voltage
• Only either the left-hand or the right-hand panel of the panel block transformer
can be designed as a transfer panel with busbar connection can be designed as a transfer panel with busbar connection
type 4MT3
• Panel blocks are also available without a busbar connection • Panel blocks are also available without a busbar connection
3) Suitable for
system (extendable at a later date only via the cable feeder) system (extendable at a later date only via the cable feeder)
three-phase
current trans-
c A plug-in voltage transformer cannot be provided at the connection formers

Siemens HA 41.11 · 2007 11


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Product Range

Circuit-breaker panels as individual panels DD

Circuit-breaker panels Circuit-breaker panels with plug-in


busbar voltage transformers
as feeder panels as feeder panels Vacuum
circuit-breaker
option option option option
HA41-2236_1e eps

HA41-2238_1e eps

HA41-2244_1e eps
HA41-2242_1e eps
Three-position
option option option option switch-disconnector
1) 1) 1) 1)

option option ** option option **


Capacitive
2) 2) 2) 2)
voltage detecting
system

Type LS1 Type LS1 * Type LS1V/LS2 Type LS2 * 1)


500 mm wide 500 mm wide 500 mm wide 500 mm wide
Basic panel for 2nd cable * Basic panel for 2nd cable * 4MC63... three-
phase current
transformer

2)
option option option option
HA41-2239_1d eps

HA41-2245_1d eps
HA41-2243 _1d eps
HA41-2237_1d eps

Cable-type current
transformer
on the cable
option option option option
1) 1) 1) 1)

4MT8 plug-in voltage


option option option option transformer at the
2) 2) 2) 2)
cable connection

Type LS1 * Type LS1 B Type LS1V/LS2 * Type LS1V/LS2 B


500 mm wide 500 mm wide 500 mm wide 500 mm wide 4MT3 plug-in
with plug-in with plug-in with plug-in with plug-in voltage
surge arresters or voltage trans- surge arresters voltage trans- transformer
limiters * formers D or limiters * formers B at the busbar

as transfer panels as transfer panels Cable (not


included in the
option option scope of supply)
Type LS1-U Type LS1V-U/LS2-U
500 mm wide 500 mm wide
HA41-2246_1d eps
HA41-2240_1d eps

for transfer for transfer


to the right to the right
option option 2nd cable (not
included in the
1) 1)
scope of supply)
HA41-2278e eps

Plug-in
surge arrester
or limiter

option Type LS1-U option Type LS1V-U/LS2-U


HA41-2241_1d eps

HA41-2247_1d eps

500 mm wide 500 mm wide


for transfer for transfer
to the left to the left
option option
1) 1)

Footnotes
see page 13

12 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Product Range
Bus sectionalizer with circuit-breaker, bus sectionalizer with switch-disconnector, busbar earthing panels and
busbar voltage metering panel as individual panels DD

Bus sectionalizer Busbar earthing Busbar voltage metering


with circuit-breaker panels panel
Vacuum
circuit-breaker
option

HA41-2252_1b eps

HA41-2254_1c eps
HA41-2248_1c eps

Three-position
option switch-disconnector

Capacitive
voltage detec-
ting system

Type LK/LT1 Type SE Type MS1V/ME3


500 mm wide 350 mm wide 500 mm wide Cable-type
with vacuum current trans-
circuit-breaker former on the
screened busbar
HA41-2253_1c eps

option
HA41-2249_1e eps

Make-proof
earthing switch

option

4MT8 plug-in
voltage
transformer
at the connection

HA41-2278e eps
Type LK V/LT1-V Type SE1 V/SE2
500 mm wide 4MT3 plug-in
500 mm wide
voltage
with vacuum with plug-in transformer
circuit-breaker and voltage at the busbar
plug-in voltage transformers
transformers

Bus sectionalizer
with switch-disconnector

option
HA41-2250_1c eps

Footnotes from
page 12 and 13
option B Deep cable
compartment
cover required
BB Short identi-
fications of the
panels have
been harmo-
nized
Type LT2 * Depending on
500 mm wide the make/type of
the cable
plug or arrester:
Deep cable
compartment
cover required
** Cable-type
current trans-
former on the
2nd cable:
For 300 mm
deeper cable
compartment

Siemens HA 41.11 · 2007 13


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Product Range

Air-insulated metering panels as transfer panels

Billing metering panels Billing metering panels as end Billing metering panels for
(standard) panels, for cable connection busbar connection
Current trans-
former, cast-resin
option option option insulated
P1 P2

HA41-2262_1b eps
HA41-2258_1c eps

HA41-2266_1c eps
1)

P2 P2 Voltage transformer,
cast-resin insulated
1)
P1 P1 or on request:

Voltage transformer,
cast-resin insulated,
with HV HRC fuse
Scheme 1 Scheme 1 Scheme 1

Type ME1, 850 mm wide Type ME1-K, 850 mm wide Type ME1-S, 850 mm wide
Voltage trans-
for transfer to the right for transfer to the right for busbar metering former, cast-resin
insulated

option option option P1 P2


HA41-2259_1c eps

HA41-2263_1b eps

HA41-2267_1c eps
Fixed earthing
points for busbar
1)
earthing

HA41-2278d eps
P2 P2

P1 P1
Cable (not
included in the
scope of supply)
Scheme 2 Scheme 2 Scheme 2

Type ME1, 850 mm wide Type ME1-K, 850 mm wide Type ME1-S, 850 mm wide P1 and P2
are terminal
for transfer to the right, for transfer to the right, for busbar metering, designations
transformer terminals transformer terminals transformer terminals of the current
interchanged interchanged interchanged transformer
option option option P2 P1
HA41-2436_1a eps
HA41-2264_1b eps
HA41-2260_1c eps

1)

P1 P1

P2 P2

Scheme 3 Scheme 3 Scheme 3

Type ME1, 850 mm wide Type ME1-K, 850 mm wide Type ME1-S, 850 mm wide
for transfer to the right for transfer to the right for busbar metering,
transformer terminals
interchanged
option option option P2 P1
HA41-2261_1c eps

HA41-2437_1a eps
HA41-2265_1b eps

P1 P1
1)
P2 P2

Scheme 4 Scheme 4 Scheme 4

Type ME1, 850 mm wide Type ME1-K, 850 mm wide Type ME1-S, 850 mm wide
for transfer to the right, for transfer to the right, for busbar metering,
transformer terminals transformer terminals transformer terminals
interchanged interchanged interchanged

Note Note
Schemes 1 to 4 also feasible Schemes 1 to 4 also feasible
for transfer to the left for transfer to the left

14 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Product Range

Air-insulated metering panels as transfer panels

Billing metering panels as end Billing metering panels Billing metering panels *
panels, for cable connection as individual panels, for cable with metal-enclosed
connection combined transformers Current trans-
former, cast-resin
option option insulated

HA41-2276_1d eps
P1 P2

HA41-2473a eps
HA41-2268_1e eps

1)

2) Voltage transformer,
P2 P2 cast-resin insulated
3) or on request:
P1 P1
1) 1)
Voltage transformer,
cast-resin insulated,
with HV HRC fuses
Scheme 1 Scheme 1 Scheme 1

Type ME1-KS, 850 mm wide Type ME1-KK, 850 mm wide Type ME2, 600 mm wide 4MK plug-in
for transfer to the right for cable connection for transfer to the right combined current
transformer,
metal-enclosed
3)

HA41-2277_1d eps
option option P1 P2
HA41-2474a eps
HA41-2269_1e eps

2) 4MK plug-in
1) 1)
combined voltage
3) transformer,
P2 P2
metal-enclosed
P1 P1

Fixed earthing
Scheme 2 Scheme 2 Scheme 2 points for busbar
earthing

HA41-2278e eps
Type ME1-KS, 850 mm wide Type ME1-KK, 850 mm wide Type ME2, 600 mm wide
for transfer to the right, for cable connection, for transfer to the right,
transformer terminals transformer terminals transformer terminals
interchanged interchanged interchanged Cable (not
included in the
HA41-2438_1b eps

option option P2 P1 scope of supply)


HA41-2270_1e eps

HA41-2475a eps

2) P1 and P2
1) 1)
are terminal
3) designations
P1 P1
of the current
P2 P2 transformer

Scheme 3 Scheme 3 Scheme 3

Type ME1-KS, 850 mm wide Type ME1-KK, 850 mm wide Type ME2, 600 mm wide
for transfer to the right for cable connection for transfer to the left
HA41-2439_1b eps

option option P2 P1
HA41-2271_1e eps

HA41-2476a eps

2)
P1 P1
3)
P2 P2
1) 1)

Scheme 4 Scheme 4 Scheme 4

Type ME1-KS, 850 mm wide Type ME1-KK, 850 mm wide Type ME2, 600 mm wide
for transfer to the right, for cable connection, for transfer to the left,
transformer terminals transformer terminals transformer terminals
interchanged interchanged interchanged

Note * Mainly for connection to


bus sectionalizer with switch-disconnector
Schemes 1 to 4 also feasible
LT1, LT1-V and LT2
as left-hand end panel
for transfer to the left

Siemens HA 41.11 · 2007 15


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Design

Panel design (examples)

Ring-main panel Section Transformer panel Section


HA41-2279e eps

HA41-2280d eps
61 1 61
1

2 62
31
2 32
62 34
33
3 23 3
11 11
4 38 23
12 12
5 24 5 35
13 13
6 6
14 14
7 15 7 15
15 15
8
9 25 9 36
16 16
17 17 37
26
18 18
10 27 10 27

19 28 19 28
20 20
29 29
21 21
22 22
Type RK Type TR

Legend for pages 16 and 17


Billing metering panel, air-insulated Section 1 Option: Low-voltage compartment
2 Niche for customer-side low-voltage equipment,
HA41-2281e eps

with hinged cover


3 Switch-position indicator for load-break
function “CLOSED – OPEN”
61
1 4 Switch-position indicator for earthing
function “OPEN – EARTHED”
62 5 Ready-for-service indicator
2 2
6 Rating and type plate

40 7 Mimic diagram
11 62 8 Option: Short-circuit / earth-fault indicator
9 Sockets for voltage detecting system
39
39
10 Arrangement of the busbars
6 11 Feeder designation label
12 Option: Locking device for three-position
41 switch-disconnector
7 62 42 13 Manual operation for the mechanism of
the earthing function
14 Manual operation for the mechanism of
the load-break function
15 Interlock of the cable compartment cover
16 Arrangement of the cable connections
17 Busbar system
22
18 Switchgear vessel filled with gas
30
19 Busbar connection
Type ME1 20 Pressure relief device

16 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Design

Panel design (examples)

Circuit-breaker panel Section

21 Partition for busbar


HA41-2282e eps

22 Earthing busbar with earthing connection


23 Three-position switch-disconnector
24 Spring-operated mechanism
25 Bushing for cable plug with bolted contact (M16)
43 26 Option: Cable T-plug
44 61
27 Cable compartment cover
45 28 Cable compartment
46 62 29 Cable bracket
47 30 Earthing connection for earthing accessories
48 7 46
49 31 HV HRC fuse assembly, cover removed
51
50 52 32 Handle for replacing HV HRC fuse links
11 12, 53 33 Interlock for HV HRC fuse assembly
5 13 34 Cover of the HV HRC fuse compartment
6 63 24
35 Spring-operated / stored-energy mechanism
8 3
15 36 Bushing for cable plug with plug-in contact
9 4
37 Cable elbow plug with plug-in contact
15 14 25
38 Switch-position indicator for load-break function
23 “CLOSED – OPEN” and, if applicable,
26
16 “HV HRC fuse tripped” or “shunt release tripped”
54
10 17 39 Cover for access to the busbar connection and to
27 the instrument transformers, screwed on
18
28
19 40 4MR voltage transformer
29
20 41 4MA7 current transformer
55
21 42 Cover to busbar connection
22 compartment, screwed on
Type LS1 (without voltage transformers) 43 Option: SIPROTEC bay control unit
44 Low-voltage compartment (standard)
HA41-2283c eps

Vacuum circuit-breaker:
45 Opening for the hand crank
– for closing with manual operating mechanism
– for emergency operation with motor operating
mechanism
46 Operating mechanism box
47 Mechanical “ON” pushbutton (not supplied with
61 spring-operated mechanism)
48 Mechanical “OFF” pushbutton
56 49 Operating cycle counter
50 “Spring charged” indicator
57
51 Vacuum interrupter
52 Switch-position indicator

53 Option: Interlock between vacuum circuit-breaker


and three-position switch-disconnector
54 Option: Three-phase current transformer
(protection transformer)
55 Cable-type current transformer
56 4MT3 plug-in voltage transformer at the busbar
58
57 Bushing for connection of plug-in voltage transformers
58 Plug-in connection according to EN 50 181 /
DIN EN 50 181 as interface type “A”
59
59 Option: 4MT8 plug-in voltage transformer at the connection
60 Deep cable compartment cover
60 61 Wiring duct, removable, for control cables and/or bus wires
62 Cover screwed on
63 Option: Interlock between three-position
Type LS2-V (with voltage transformers) switch-disconnector and circuit-breaker

Siemens HA 41.11 · 2007 17


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Components

3AH vacuum circuit-breaker


Features Operating mechanism
• According to IEC 62 271/ functions
VDE 0671-100
(standards see page 41) Motor operating mechanism 1)
(M1 *) 1 8
• Application of all 8DH10
switchgear in hermetically In the case of the motor oper-
sealed vessel in conformity ating mechanism, the closing 2
spring is charged by means of 10
with the system 3
a motor and latched in the 11
• Climate-independent vacuum 4
charged position (the “spring
interrupter poles in the charged” indication is visible). 5
gas-filled switchgear vessel Closing is effected either by 6
13
• Maintenance-free for indoor means of an ON pushbutton or 7
installation according to a closing solenoid. The closing
IEC 60 694/ VDE 0670-1000 spring is recharged automati-
(standards see page 41) cally (for auto-reclosing).
15
• Individual secondary equipment
Manual operating stored-
• A metal bellows is used for energy mechanism
gasketless separation of the The closing spring is charged
SF6-insulation and the operat- by means of the hand crank sup-
ing mechanism – as already plied until latching of the closing
used with success for over latch is indicated
R-HA41-016 eps

100000 vacuum interrupters (= “spring charged” indication).


Switching duties and Subsequently the vacuum
operating mechanisms circuit-breaker can be closed
Operating mechanism of the vacuum circuit-breaker
The switching duties of the either manually or electrically (for the legend, see page 19)
vacuum circuit-breaker are de- and the closing spring can be
pendent, among other factors, on recharged manually. The “possi-
its type of operating mechanism. bility to close” is thus stored
Three operating mechanism ver- once more (for auto-reclosing). Differentiation features between the vacuum circuit-breakers
sions are available: depending on the operating mechanism version
Manual spring-operated Operating Motor operating Manual Manual spring-
• Motor operating stored-energy
mechanism mechanism stored-energy operating operated
mechanism
(= spring CLOSED, stored-energy version mechanism stored-energy mechanism
– For auto-reclosing (K), mechanism
OPEN)
– For synchronization and Typical uses Utility Classic transfer Simple utility
rapid load transfer (U) The closing spring of the vacuum substations substations and substations
circuit-breaker is charged by and industrial substations (circuit-breaker
• Manual operating stored-
means of the hand crank sup- plants without auxiliary employed as
energy mechanism voltage supply transformer
plied until the vacuum circuit-
– For auto-reclosing (K) switch)
breaker closes. Subsequently
• Manual spring-operated me- either manual or electrical open- Mechanism Stored-energy Stored-energy Spring
chanism (= spring CLOSED, function CLOSED, CLOSED, CLOSED,
ing is possible.
stored-energy stored-energy stored-energy
stored-energy OPEN)
Vacuum circuit-breakers with OPEN OPEN OPEN
– Not for auto-reclosing (K)
spring-operated mechanism are Mechanism With motor 1), With hand With hand
– For normal closing and
not suitable for auto-reclosing. operation manual (emer- crank crank
– For storage of one opening gency) opera-
operation tion at the panel
Trip-free mechanism
including anti-
Further operating mechanism The vacuum circuit-breaker pumping
features is fitted with a trip-free Closing the Electrically 2) or Mechanically Mechanically
• Located outside the switch- mechanism. vacuum mechanically at at the panel at the panel
gear vessel in the operating circuit-breaker the panel with with push- with hand
mechanism box and behind pushbutton button, option: crank (charging
1) Motor rating at electrically 2) process)
the control board 24 V to 220 V DC: 350 W Closing Always provid- Option Without
• Stored-energy spring 110 V and 230 V AC:400 VA solenoid, e.g. ed, with elec-
mechanism for 10000 2) With closing solenoid for remote trical signal
operating cycles * Item designation electrical “closing spring
closing charged”
Abbreviations for switching
Rated O-t-CO O-t-CO O or CO
duties and applications: CO = CLOSE operation with subsequent
operating or
OPEN operation at the shortest
U = Synchronization and sequence O-t-CO-t’-CO
internal close-open time of the
rapid load transfer
vacuum circuit-breaker Auto- Suitable (multi- Suitable (only –
(make time £ 90 ms)
reclosing (K) ple auto-reclos- with closing
K = Auto-reclosing t = Dead time 0.3 s
ing possible) solenoid)
O = OPEN operation t‘ = Dead time 3 min

For further technical data and description of typical applications,


please refer also to Catalog HG 11.11 “3AH Vacuum Circuit-Breakers”

18 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Components

Secondary equipment of the 3AH vacuum circuit-breaker


The scope of the 3AH vacuum Circuit-breaker tripping signal
circuit-breaker secondary equip- (standard)
ment depends on the type of appli- • For electrical signalling (as pulse
cation and offers a wide range of > 10 ms), e.g. to remote control
options, thus allowing even the 9
systems, in the case of automatic 1
highest requirements to be satis- tripping (e.g. protection)
fied.
• Via limit switch (S6 *) and
Closing solenoid cut-out switch (S7 *) 3
11
• Type 3AY15 10 (Y9 *) Varistor module
• For electrical closing 5 17
• To limit overvoltages to approx.
500 V for protection devices 13
Shunt releases (when inductive devices are
• Types: mounted in the vacuum circuit-
– Standard: 3AY15 10 (Y1 *) breaker)
– Option: 3AX11 01 (Y2 *), • For auxiliary voltages W 60 V DC
with energy store
• Tripping by protection device or Auxiliary switch
electrical operation • Type 3SV9 (S1 *)
Current-transformer • Standard: 6 NO+6 NC, of which
operated release 2 NO+2 NC+2 changeover
contacts are free 1)
HA41-2296b eps

• Type 3AX11 04 (Y6 *) for trip-


ping pulse W 0.1 Ws in con- • Option: 12 NO+12 NC, of which
junction with suitable protec- 7 NO+4 NC+2 changeover
contacts are free 1) Basic equipment with manual spring-operated mechanism
tion systems, e.g. 7SJ4 protec-
tion system, 4MC6.. transformer
protection system, SEG relay Position switch
(other designs on request) • Type 3SE4 (S4 *) 8
1
• Used where no external • For signalling “closing spring
auxiliary voltage is available, charged” 2 10
tripping by protection device
• Only in conjunction with stored- 3
energy mechanisms 11
Undervoltage release 4
• Type 3AX11 03 (Y7 *) 5 12
Mechanical interlocking
6
• Comprising: • Dependent on the type of 13
– Energy store and unlatching 7
operating mechanism
mechanism
• Option: Switchgear interlocking
– Electromagnetic system which is 14
permanently connected to voltage with the three-position switch-
while the vacuum circuit-breaker disconnector (option: Closing 15
is closed; tripping is initiated lock-out for the three-position
switch-disconnector in circuit- 16
when this voltage drops
breaker panels type LS and LT1)
• Connection to voltage trans-
• Option: Operating mechanism
formers possible
with mechanical interlocking as
– Spring-operated mechanism:
HA41-2297a eps

Anti-pumping (standard)
(mechanical and electrical) Hand crank opening is blocked
– Stored-energy mechanism with
• Function: If constant CLOSE and closing solenoid (Y9 *) and
OPEN commands are present at Maximum equipment with motor operating stored-energy mechanism
pushbutton (S12 *): The push-
the vacuum circuit-breaker at button (S12 *) operated by the
the same time, the vacuum cir- mechanical interlock prevents a Secondary equipment (view into the operating mechanism box)
cuit-breaker will return to the continuous command to the 1 Gear 11 Circuit-breaker “OPEN”
open position after closing. It closing solenoid 2 Position switch (S4 *) 12 Option: 2nd release
remains in this position until a
• During operation of the three- 3 Closing spring 13 1st release (Y1 *)
new CLOSE command is given.
In this manner, continuous clos- position switch-disconnector 4 Motor (M1 *) 14 Option: Mechanical inter-
ing and opening (= pumping) is from CLOSED to OPEN: locking with interrogation
5 Operating cycle counter
avoided. Vacuum circuit-breaker of the three-position
cannot be closed. 6 “Closing spring charged” indicator switch-disconnector
7 Closing solenoid (Y9 *) 15 Operating rod with contact
1) For utilization * Item Abbreviations: pressure springs
8 Option: Auxiliary switch
by the designation NO = normally-open contact
12 NO+12 NC 16 Interlocking to the three-
customer NC = normally-closed contact
position switch-disconnector
9 Auxiliary switch
For further technical data and description of typical applications, 6 NO+6 NC (S1 *) 17 Actuation for closing the
please refer also to Catalog HG 11.11 “3AH Vacuum Circuit-Breakers” vacuum circuit-breaker
10 Circuit-breaker “CLOSED”

Siemens HA 41.11 · 2007 19


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Components

Three-position switch-disconnector
Features
• Switch positions: CLOSED –
OPEN – EARTHED
• Switching functions as

R-HA41-012 eps
general-purpose switch-
disconnector (class E3)
according to
– IEC 60 265-1/ VDE 0670-301
– IEC 62 271-102/ VDE 0671-102
(standards see page 41)
• Designed as a multi-chamber
switch with the functions
– Switch-disconnector and
– Make-proof earthing switch
• Operation via gas-tight welded-in
metal bellows at the front of the
switchgear vessel

Three-position switch-disconnector

EARTHED
HA41-2288a eps

OPEN

SF6 insulation

1 2 3 4 5 6 CLOSED

Detachable lever mechanism


with three-position switch-disconnector
Switch positions
1 Three-position switch-disconnector
2 Coupling linkage
3 Switchgear vessel
4 Operating mechanism rocker
5 Detachable lever mechanism
6 Operating lever inserted

For further details, please refer to


Catalog HA 40.1 “Switchgear
Types 8DJ and 8DH for Secondary
Distribution Systems up to 24 kV,
Gas-Insulated (General Part)”

20 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Components

Busbars
Features
• Safe-to-touch as a result of
use of metal covers

R-HA41-017a eps
• Plug-in type
• Consisting of round-bar
copper, insulated by means of
silicone rubber
• Busbar joints with cross and
end adapters, insulated by 2 8
means of silicone rubber
• Insensitive to pollution and 3
condensation
• Switchgear extension or
panel replacement is possi- 7
ble without gas work
• Special busbar connections
to metering panels type ME1
are possible. Connection to
the
– Cable connection bushings
of the adjacent panel Busbar compartments over 2 panels
with busbar connections, busbar covers removed
or to the
– Busbar bushings
• Busbar arrangement in panel
blocks within the switchgear 7
vessel filled with gas
HA41-2289b eps

8
• Option screened busbar:
– Field control by means of 9
electrically conductive layers
on the silicone-rubber
insulation 1 10
– Installation of 4MC70 32 2
current transformers is thus
possible 3
– Independent of the site 4
altitude
5
• Option: Capacitive voltage
detecting system for the
Top view
busbar, refer also to the
6
product range, pages 10
to 15
Insulated plug-in type busbar
unscreened design

Busbar system
1 End adapter
2 Cross adapter
3 Busbar insulation of silicone rubber
4 Threaded bolt M12 / M16
5 Busbar, Cu, diameter 32 mm
6 Stopper

Switchgear vessel
7 Primary enclosure panel 1
8 Primary enclosure panel 2
9 Bushing
10 Capacitive tap at the bushings,
earthed (standard)

Siemens HA 41.11 · 2007 21


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Components

4MT3 * and 4MT8 * plug-in voltage transformers for panel types LS, TR, SE and ME3

Panel section
type LS2-V

R-HA41-019 eps
HA41-2290b eps

R-HA41-018a eps
4MT3 plug-in
voltage
1
transformer
(for the busbar)

R-HA41-020 eps
2

4MT8 plug-in
voltage
transformer
(at the cable
1 4MT3 * for the busbar 4MT8 plug-in voltage transformer connection)
2 4MT8 * at the cable connection mounted on cable T-plug (in panel type LS1-V)

Common features Technical data


4MT3 * and 4MT8 * voltage transformers
• According to IEC 60 044-2/ VDE 0414-2
Primary data Secondary data for 4MT3 voltage transformers
• Designed as single-pole voltage trans-
formers, plug-in type Max. equipment operating 12 kV Rated voltage 100/ 3 V
voltage Um (= 1.2 x UN) 110/ 3 V (option)
• Inductive type
Rated voltage UN at max. 3.3/ 3 kV at 10 kV Rated voltage for 100/3 V
• Climate-independent rated short-duration 3.6/ 3 kV at 20 kV auxiliary winding (option) 110/3 V (option)
power-frequency 4.8/ 3 kV at 20 kV Rated thermal 6A
• Secondary connection by means of withstand voltage Ud 5.0/ 3 kV at 20 kV limit current
plugs inside the panel 6.0/ 3 kV at 20 kV (measuring winding)
• Connection with plug-in contact 6.6/ 3 kV at 20 kV Rated long-time thermal 4A
• Installation behind metallic cover 7.2/ 3 kV at 28 kV current (8 h)
10.0/ 3 kV at 28 kV
11.0/ 3 kV at 28 kV Rating VA 25 15 60 100 150
Features type 4MT3
Rated lightning impulse 3.6 kV / 20 kV Class 0.2 0.5 0.5 1 1
• Inside-cone system, metal-coated withstand voltage Up 7.2 kV / 60 kV
12 kV / 75 kV
Secondary data for 4MT8 voltage transformers
Features type 4MT8 Rated voltage factor (8 h) 1.9 x UN
Rated voltage 100/ 3 V
• Outside-cone system, metal-enclosed Max. equipment operating 24 kV 110/ 3 V (option)
voltage Um (= 1.2 x UN)
• For deep cable compartment cover Rated voltage for 100/3 V
Rated voltage UN at max. 13.8/ 3 kV at 38 kV auxiliary winding (option) 110/3 V (option)
rated short-duration 15.0/ 3 kV at 38 kV
Installation power-frequency
Rated thermal 4A
17.5/ 3 kV at 50 kV limit current
• Safe-to-touch arrangement due to withstand voltage Ud 20.0/ 3 kV at 50 kV (measuring winding)
metallic cover 22.0/ 3 kV at 50 kV
Rated long-time thermal 4A
• Arrangement on the switchgear Rated lightning impulse 17.5 kv / 95 kV current (8 h)
vessel for busbar metering: withstand voltage Up 24 kV / 125 kV
Rating VA 15 15 30 30 100
– 4MT3 voltage transformer for panel Rated voltage factor (8 h) 1.9 x UN
Class 0.2 0.5 0.5 1 3
types LS1 V/LS2, SE1V/SE2, MS1 V/ME3
and LK V/LT1
Combination of 4MT8 * voltage transformers with cable T-plugs (screened, without metal housing)
• Arrangement at the cable connection:
– 4MT8 voltage transformer, pluggable Make Type Combination Make Type Combination
on screened cable T-plug, for panel Euromold (K) 400 TB/G yes Südkabel SEHDT (13/23) yes
types LS1-V, LS2-V and TR-V (deep (K) 440 TB, AGT 10/20 Südkabel SET (12/24) on request
cable compartment cover required) nkt cables ASTS 10/630, yes Cooper DT 400 P yes
– 4MT8 voltage transformer, directly ASTS 20/630
Tyco Electronics RSTI-L56xx for:
pluggable via adapter on the bushing Prysmian FMCTs-400, FMCTg-400 yes
• 35-300 mm2 on request
Kabel und
with plug-in contact (interface type “A”), (M12) (add.measures)
Systeme
for panel type TR-V (deep cable com- • > 300 mm2 on request
partment cover required) (M16)

* Disassembly is necessary in order to perform voltage tests on the switchgear on site (max. 80 % Ud)

22 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Components

4MC63 three-phase current transformer for panel type LS

Panel section
type LS1

R-HA41-021b eps
HA41-2291b eps

R-HA41-022 eps
1

4MC63 three-phase
current transformer
1 4MC63 three-phase 4MC63 three-phase current transformer
current transformer on the bushings of the cable connection

Features Technical data


• According to IEC 60 044-1/ 4MC63 10 three-phase current transformer 4MC63 11 three-phase current transformer
VDE 0414-1 for IN £ 150 A and ID = 630 A for IN £ 400 A and ID = 630 A

• Designed as three-pole Primary data Primary data


ring-core current transformer Max. equipment operating 0.72 kV Max. equipment operating 0.72 kV
voltage Um voltage Um
• Free of dielectrically
stressed cast-resin parts Rated current IN A 150 100 75 50 Rated current IN A 400 300 200
(due to design) Rated short-duration 3 kV Rated short-duration 3 kV
power-frequency with- power-frequency with-
• Insulation class E stand voltage (winding test) stand voltage (winding test)
• Inductive type Rated thermal short-time 25 kA Rated thermal short-time 25 kA
withstand current Ith withstand current Ith
• Climate-independent
• Secondary connection by Rated continuous 630 A Rated continuous 630 A
means of a terminal strip thermal current ID thermal current ID
inside the panel
Transient overload 1.5 x ID / 1 h Transient overload 2 x ID / 0.5 h
Installation current current

• Arranged outside the switch- Rated peak withstand unlimited Rated peak withstand unlimited
current Idyn current Idyn
gear vessel on the bushings
of the cable connection Secondary data Secondary data
• Mounted at the factory Rated current A 1 0.67 0.5 0.33 Rated current A 1 0.75 0.5
Rating VA 2.5 1.7 1.25 0.8 Rating VA 4 3 2
Other designs
Rated current (option) 5A Rated current (option) 5A
(option)
Current at ID 4.2 A Current at ID 1.575 A
Three-phase current trans-
Protec- Class 10 P Protec- Class 10 P
former for protection equip- tion tion
ment based on the current- Overcurrent factor 10 Overcurrent factor 10
core core
transformer operation principle:
• 7SJ4x protection system
as definite-time overcurrent
protection
• Definite-time overcurrent pro-
tection relay make SEG, type
WIP 1 or type WIC

Other values on request Other values on request

Siemens HA 41.11 · 2007 23


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Components

4MC70 33 and 4MC70 31 cable-type current transformers for panel types LS, RK and TR

Front Panel section


view type LS1

R-HA41-025 eps
R-HA41-023a eps
HA41-2292b eps

4MC70 31 cable-type
current transformer

R-HA41-024a eps
4MC70 33 cable-type
current transformers,
4 different overall heights

2 2

1 1
*

4MC70 33 cable-type current transformer


for the cables at the panel connection
1 Cable-type current transformer
2 Cable shield

Features Technical data


• According to IEC 60 044-1/ 4MC70 33 cable-type current transformer 4MC70 31 cable-type current transformer
VDE 0414-1
Primary data Primary data
• Designed as single-pole ring- Max. equipment operating 0.72 kV Max. equipment operating 0.72 kV
core current transformers voltage Um voltage Um
• Free of dielectrically stressed Rated current IN 30 A to 600 A Rated current IN 50 A to 600 A
cast-resin parts (due to design) Rated short-duration 3 kV Rated short-duration 3 kV
power-frequency with- power-frequency with-
• Insulation class E stand voltage (winding test) stand voltage (winding test)
• Inductive type Rated thermal short-time 25 kA Rated thermal short-time 25 kA
• Climate-independent withstand current Ith withstand current Ith

• Secondary connection by Rated continuous 1.0 x IN Rated continuous 1.0 x IN


means of a terminal strip thermal current ID option: 1.2 x IN thermal current ID option: 1.2 x IN
inside the panel
• Only for shielded cables Transient overload 1.5 x ID / 1 h or Transient overload 1.5 x ID / 1 h or
current 2 x ID / 0.5 h current 2 x ID / 0.5 h
Installation Rated peak withstand unlimited Rated peak withstand unlimited
current Idyn current Idyn
• 4MC70 33 cable-type current
transformer for panel type LS Secondary data Secondary data
• 4MC70 31 cable-type current Rated current 1 A (option: 5 A) Rated current 1 A (option: 5 A)
transformer for panel types Meas- Class 0.2 0.5 1 Meas- Class 1
RK and TR uring Overcurrent factor FS10 (option: FS5) uring Overcurrent factor FS5 (option: FS10)
core core
• Arranged outside the switch- Rating 2.5 VA to 10 VA Rating 2.5 VA to 10 VA
gear vessel around the cable Pro- Class 10 P 5P Option: Secondary tap 1:2
at the panel connection tection Overcurrent factor 10 10
core
• Transformers mounted on a Rating 2.5 VA to 10 VA
supporting plate at the fac- Option: Secondary tap 1:2
tory; final assembly around (e.g. 150 A – 300 A)
the cables on site
Dimensions Dimensions
• For double cable: 300 mm
deeper cable compartment Overall height H, mm 50 100 170 285 Overall height H 89 mm
dependent on the
cover
core data
* Max. 230 mm, depending on Outside diameter 145 mm Width x depth 85 mm x 114 mm
the core data of the 4MC70 33 Inside diameter 55 mm Inside diameter 40 mm
cable-type current transformer,
overall heights 170 and 285 mm For cable diameter 50 mm For cable diameter 36 mm
(observe floor openings on page 36)
Other values on request Other values on request

24 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Components

4MC70 32 bus-type current transformers for panel type LT (for screened busbars only)

Panel section
type LT1
HA41-2293b eps

R-HA41-026a eps

R-HA41-027 eps
1

4MC70 32 bus-type
1 4MC70 32 bus-type current transformer
current transformer 4MC70 32 bus-type current transformer,
mounted on screened busbars, in some cases
between the panels

Features Technical data


• Used exclusively for 4MC70 32 bus-type current transformer
screened busbars
Primary data
• Preferably in combination Max. equipment operating 0.72 kV
with panel type ME2 voltage Um
• According to IEC 60 044-1/ Rated current IN 200 A to 600 A
VDE 0414-1 Rated short-duration 3 kV
power-frequency with-
• Designed as single-pole
stand voltage (winding test)
ring-core current trans-
Rated thermal short-time 25 kA
formers
withstand current Ith
• Free of dielectrically
stressed cast-resin parts (due Rated continuous 1.0 x IN
to design) thermal current ID option: 1.2 x IN
• Insulation class E
Transient overload 1.5 x ID / 1 h or
• Inductive type current 2 x ID / 0.5 h
• Climate-independent Rated peak withstand unlimited
current Idyn
• Secondary connection by
means of a terminal strip Secondary data
inside the panel Rated current 1 A (option: 5 A)
Meas- Class 0.2 0.5 1
Installation uring Overcurrent factor FS10 (option: FS5)
• Arranged outside the core
Rating 2.5 VA to 10 VA
switchgear vessel only on
the screened busbars Pro- Class 10 P 5P*
tection Overcurrent factor 10 10
• Installation of the bus-type core
Rating 2.5 VA to 15 VA
current transformers either
between the panels or alter- Option: Secondary tap 1:2
natively (e.g. 150 A – 300 A)

• Supplied loosely (including Dimensions


the busbar connections), if Overall width B, 80 mm 150 mm
the mounting position of the dependent on the
bus-type current transformers core data
lies at the joint of a transport Outside diameter 125 mm
unit Inside diameter 55 mm

Other values on request * On request

Siemens HA 41.11 · 2007 25


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Components
4MA7 current transformers and 4MR voltage transformers
for air-insulated billing metering panels type ME1

R-HA41-029a eps
R-HA41-028 eps

Panel section type ME1


HA41-2294c eps

4MR14 voltage
1 transformer

R-HA41-030a eps
2

4MA7 current
transformer
1 4MR voltage transformer 4MR voltage transformers and
2 4MA7 current transformer 4MA7 current transformers installed in
billing metering panel type ME1

Technical data
Features 4MA7 single-pole current transformer 4MR single-pole voltage transformer

4MA7 current transformer Primary data Primary data


• According to IEC 60 044-1/ Max. equipment operating 12/ 24 kV Max. equipment operating 12 kV
VDE 0414-1 voltage Um 17.5 kV voltage Um (= 1.2 x UN)
Rated short-duration 28/ 50 kV Rated voltage UN at max. 3.3/ 3 kV at 10 kV
• Dimensions according to power-frequency 38 kV rated short-duration
DIN 42 600-8 (small design) 3.6/ 3 kV at 20 kV
withstand voltage Ud power-frequency 4.8/ 3 kV at 20 kV
withstand voltage Ud
• Designed as single-pole Rated lightning impulse 75/ 125 kV 5.0/ 3 kV at 20 kV
indoor block-type current withstand voltage Up 95 kV 6.0/ 3 kV at 20 kV
6.6/ 3 kV at 20 kV
transformers Rated current IN 25 A to 600 A
7.2/ 3 kV at 28 kV
• Cast-resin insulated Rated thermal short-time up to 25 kA
10.0/ 3 kV at 28 kV
withstand current Ith
• Insulation class E 11.0/ 3 kV at 28 kV
Rated continuous 1.0 x IN
Rated lightning impulse 3.6 kV / 20 kV
• Secondary connection by thermal current ID option: 1.2 x IN
withstand voltage Up 7.2 kV / 60 kV
means of screw-type Rated peak withstand max. 2.5 x Ith 12 kV / 75 kV
terminals current Idyn Rated voltage 1.9 x UN
factor (8 h)
4MR voltage transformer Secondary data
Max. equipment operating 24 kV
• According to IEC 60 044-2/ Rated current 1 A or 5 A voltage Um (= 1.2 x UN)
VDE 0414-2 Meas- Class 0.2 0.5 1 Rated voltage UN at max. 13.8/ 3 kV at 38 kV
uring Overcurrent factor FS5 or FS10 rated short-duration 15.0/ 3 kV at 38 kV
• Dimensions according to core
Rating 10 VA to 15 VA power-frequency 17.5/ 3 kV at 50 kV
DIN 42 600-9 (small design) withstand voltage Ud
Pro- Class 5 P or 10 P 20.0/ 3 kV at 50 kV
• Designed as indoor 22.0/ 3 kV at 50 kV
tection Overcurrent factor 10
voltage transformers: core Rated lightning impulse 17.5 kV / 95 kV
– Type 4MR, single-pole Rating 5 VA to 15 VA withstand voltage Up 24 kV / 125 kV
– Option: Type 4MR, two-pole Rated voltage 1.9 x UN
• Cast-resin insulated factor (8 h)

• Insulation class E
Secondary data
• Secondary connection by Rated voltage 100/ 3 V
means of screw-type 110/ 3 V (option)
terminals 120/ 3 V (option)
Rated voltage for auxiliary 100/3 V
winding (option) 110/3 V (option)
120/3 V (option)
Rating 20 VA 50 VA 100 VA
Class 0.2 0.5 1

Other values on request Other values on request

26 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Components
4MK * metal-enclosed combined transformers
for billing metering panels type ME2

R-HA41-032 eps
R-HA41-031a eps
1

1 4MK3
Panel section type ME2 combined
voltage
HA41-2295b eps

transformer
2 4MK1
combined
1 current
transformer
2

4MK combined
transformer
1 4MK3 combined voltage 4MK combined transformers installed in
transformer billing metering panel type ME2
2 4MK1 combined current
transformer
Technical data
4MK1 combined current transformer 4MK3 combined voltage transformer

Features Primary data Primary data


• 4MK * combined Max. equipmen+t 12 kV 24 kV Max. equipment operating 12 kV
transformer, comprising operating voltage Um voltage Um (= 1.2 x UN)
– 4MK1 combined current Rated short-duration 28 kV 50 kV Rated voltage UN at max. 3.3/ 3 kV at 10 kV
transformer power-frequency rated short-duration 3.6/ 3 kV at 20 kV
withstand voltage Ud power-frequency 3 kV at 20 kV
– 4MK3 combined voltage withstand voltage Ud
4.8/
transformer Rated lightning impulse 75 kV 125 kV 5.0/ 3 kV at 20 kV
withstand voltage Up 6.0/ 3 kV at 20 kV
• According to IEC 60 044-3/ Rated current IN 50 A to 600 A 6.6/ 3 kV at 20 kV
VDE 0414-5 7.2/ 3 kV at 28 kV
Rated thermal short-time up to 25 kA
• Designed as indoor trans- withstand current Ith 10.0/ 3 kV at 28 kV
11.0/ 3 kV at 28 kV
formers, single-pole Rated continuous 1.0 x IN
combination thermal current ID option: 1.2 x IN Rated lightning impulse 3.6 kV / 20 kV
withstand voltage Up 7.2 kV / 60 kV
• Metal-enclosed Rated peak withstand max. 2.5 x Ith 12 kV / 75 kV
current Idyn
• Insulation class E Rated voltage 1.9 x UN
factor (8 h)
• Inductive type Secondary data
Max. equipment operating 24 kV
• Secondary connection by Rated current 1 A or 5 A
voltage Um (= 1.2 x UN)
means of screw-type Meas- Class 0.2 0.5 1
Rated voltage UN at max. 13.8/ 3 kV at 38 kV
terminals uring Overcurrent factor FS5 or FS10 rated short-duration 15.0/ 3 kV at 38 kV
core
Rating 10 VA to 15 VA power-frequency 17.5/ 3 kV at 50 kV
Panel type ME2 withstand voltage Ud 20.0/ 3 kV at 50 kV
Pro- Class 10 P
22.0/ 3 kV at 50 kV
• For combination with tection Overcurrent factor 10
core Rated lightning impulse 17.5 kV / 95 kV
left-hand panels Rating 5 VA or 15 VA withstand voltage Up 24 kV / 125 kV
– As individual panels or
Secondary multiratio option Rated voltage 1.9 x UN
– As panel blocks (on request)
factor (8 h)
• For combination with
right-hand panels as end Secondary data
panels or panel blocks Rated voltage 100/ 3 V
110/ 3 V (option)
Rated voltage for auxiliary 100/3 V
winding (option) 110/3 V (option)

Rating 30 VA 75 VA 150 VA
Class 0.2 0.5 1

* Available only as a combination of


Other values on request Other values on request
current and voltage transformers

Siemens HA 41.11 · 2007 27


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Components

Cable connection
Features
Cable connection · Examples
• Bushings with outside cone
• Uniform cable connection L1 L2 L3 L1 L2 L3
Cable connections in
height 575 mm ring-main panels
• With cable bracket, e.g. 1 Prepared for cable
type C40 according to plugs with bolted
contact (M16)
DIN EN 50 024 1 2
2 Phase L1:
• Access to the cable compart- 3
Make Euromold,
ment only if the feeder has 4 type K400 LB as
been isolated and earthed cable elbow plug
3 Phase L2:
Special features Make Euromold,
type K400 TB as
– In ring-main panels cable T-plug
– In circuit-breaker panels
4 Phase L3:

R-HA41-034 eps
R-HA41-033 eps

– In cable panels:
Make Euromold,
• With bolted contact (M16) type AGT 20/630 as
as interface type “C” cable T-plug
according to EN 50181/ Cable compartment, as-delivered Cable plugs with For options A, B, C
DIN EN 50181 condition * bolted contact (M16) and E, see below

• For thermoplastic-
insulated cables L1 L2 L3 L1 L2 L3 Cable connections in
• For paper-insulated circuit-breaker panels
mass-impregnated cables 5 Prepared for cable
with adapter systems plugs with bolted
contact (M16)
• For conventional cable 5 6
sealing ends via elbow 6 Phase L1:
7
Elbow adapter,
adapter AKE 20/630 make Siemens,
8
(make Siemens) type AKE 20/630
• For cable T-plugs or cable 7 Phase L2:
elbow plugs with bolted con- Make Euromold,
tact (M 16) type K400 TB as
cable T-plug
• For connection cross-
8 Phase L3:
R-HA41-035 eps

R-HA41-036 eps

sections up to 300 mm² Make Euromold,


(standard) type AGT 20/630 as
cable T-plug
• Cable routing downwards,
cable connection at front Cable compartment, Cable plugs with For options A, B, C,
as-delivered condition * bolted contact (M16) E and F, see below
• For rated normal currents of
400/630 A
L1 L2 L3 L1 L2 L3
– In transformer panels:
Cable connections in
• With plug-in contact as transformer panels
interface type “A” 9 Prepared for cable
according to EN 50 181/ 10 elbow plugs with plug-in
DIN EN 50 181 9 contact
11
• For cable elbow plugs 12
10 Phase L1:
Make Euromold,
with plug-in contact
type AWGL
• For thermoplastic- 11 Phase L2:
insulated cables Make Euromold,
type K158 LR
• For connection cross-
sections up to 120 mm² 12 Phase L3:
Make Euromold,
R-HA41-038 eps
R-HA41-037 eps

• For rated normal currents type AGW 20/250


of 200 A (with metal housing)
For options A, D and F,
Options Cable compartment, Cable elbow plugs with see below
See figures on the right as-delivered condition * plug-in contact

Options D Bushings as interface type “C” according to


EN 50 181 / DIN EN 50 181 for cable plugs with bolted contact (M16)
A Mounted cable clamps
E Suitable for connection of plug-in surge arresters in conjunction with
B Short-circuit / earth-fault indicator
corresponding cable T-plugs
* Cable plugs, cable sealing ends C Double cable connection with
F Suitable for connection of 4MT8 metal-enclosed voltage
and cable clamps are not corresponding cable plugs and
transformers in conjunction with corresponding cable T-plugs;
included in the scope of supply deep cable compartment cover
deep cable compartment cover is required

28 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Components

Low-voltage equipment
Low-voltage compartment *
Low-voltage compartment
• Overall height
– Standard 600 mm
– Option 900 mm
• Partitioned safe-to-touch from
the high-voltage part of the 1
panel
• Installation on the panel: 2 3
– Standard for circuit-breaker
panel type LS and bus section-
alizer with switch-disconnector
type LT1
– Option for all other panel 4

R-HA41-041a eps
R-HA41-039a eps

types, depending on the


scope of the secondary
equipment
• For accommodation of protec-
Low-voltage compartment Electronic control board with
tion, control, measuring and of a circuit-breaker panel multifunction protection device
metering equipment, e. g. type LS SIPROTEC 4 7SJ63
suitable for multifunction pro-
tection device SIPROTEC 4

R-HA41-040 eps
7SJ63 1 LEDs

• Electronic control board 2 LCD


of the multifunction protec- 3 Navigation keys
tion device SIPROTEC 4 7SJ63 4 Function keys
with the following features:
1 User-programmable LEDs
with application-specific label,
for displaying any desired
process and equipment data
2 LCD for process and
equipment data, e.g. for
– Measuring and metering
values
– Binary information on status of Open low-voltage compartment
switchgear and switching with (optional) equipment
device
– Protection data
– General indications
– Alarms
3 Keys for navigation in the Low-voltage niche
menus and for entering values
4 Four user-programmable
1 Low-voltage
function keys for frequently niche
performed actions
2 Equipment
1 (option)
Low-voltage niche
• Only inside billing metering 2
panels type ME1
• Option: For accommodation,
e.g. of voltage transformer,
m.c.b.s

Low-voltage cables
• Control cables of the panel to
the low-voltage compartment
R-HA41-042 eps

are connected via multi-pole,


coded module plug connectors
• Option: Plug-in bus wires from
panel to panel are routed in Low-voltage niche of a
billing metering panel type ME1
the separate wiring duct on with open cover
the panel

* Door hinge on the left (standard)

Siemens HA 41.11 · 2007 29


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Dimensions

Ring-main, cable, transformer and circuit-breaker panels as individual panels

600 (900****)
600 (900)*
426***

60
4 4

2000 (2300****)
2000 (2300)*

553

1400
1400

553
312 312

215 110 110


215 110 110

~565
575

HA41-2301e eps
HA41-2298g eps

40
40

350 ³15 ~560** 500 ³15 ~560**


Ring-main panel 750 Circuit-breaker panel 750
type RK 775 type LS1 775

600 (900****)
600 (900)*

426***
60

4 4
2000 (2300****)
2000 (2300)*

1
553
2
1400

553
1400

312 312
3
215 110 110

215 110 110

~565
575

HA41-2302e eps
HA41-2299g eps

40
40

350 ³15 ~560** 500 ³15 ~560**


Cable panel 750 Circuit-breaker panel 750
type K 775 type LS1 V/LS2 775
600 (900)*

60

Cable panel type K:


1 Option: Earthing function
2 Interlock of cable compartment cover
if earthing function is available
2000 (2300)*

4 3 Cable compartment cover screwed on (without earthing function)


4 Cover screwed on

* Option:
1400

515
312 With low-voltage compartment
** Dependent on the type of
cable plug
215 110 110

~565

*** Available mounting depth


HA41-2300f eps

for low-voltage equipment


40

**** Option: With high


low-voltage compartment 900 mm
500 ³15 ~520**
750
Transformer panel
775
type TR 1

30 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Dimensions

Ring-main, cable and transformer panels in panel blocks

HA41-2304c eps

HA41-2305c eps
HA41-2303c eps

4 4
4 4 4

2000 (2300)*
2000 (2300)*
2000 (2300)*

1400
1400
1400

RK RK RK RK RK TR TR

700 1050 1000


Ring-main Ring-main Transformer
panel block type R-B2 panel block type R-B3 panel block type T-B2
HA41-2306c eps

HA41-2307c eps

HA41-2308c eps
4 4

4 4 4
2000 (2300)*

2000 (2300)*

2000 (2300)*
1400

1400

1400

TR TR TR RK TR RK RK TR

1500 700 1050


Transformer Ring-main/transformer Ring-main/transformer
panel block type T-B3 panel block type RT-B2 panel block type 2RT-B3
HA41-2309c eps

HA41-2310c eps

4 4
4 4
2000 (2300)*

2000 (2300)*

1 Cable panel type K:


1 Option: Earthing function
2 2 Interlock of cable compartment cover
1400

if earthing function is available


1400

3 3 Cable compartment cover screwed on


(without earthing function)
4 Cover screwed on
RK RK RK TR K TR
* Option:
With low-voltage compartment
1400 700
Ring-main/transformer Cable connection/transformer
panel block type 3RT-B4 panel block type KT-B2

Siemens HA 41.11 · 2007 31


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Dimensions
Bus sectionalizers with circuit-breakers, bus sectionalizers with switch-disconnectors and
busbar voltage metering panel as individual panels

600 (900****)

600 (900)*
426***

60
1
1
2000 (2300****)

2000 (2300)*
1400

1400
312
1 312
1
215 110 110

215 110 110


HA41-2311e eps

HA41-2315e eps
40

40
500 ³15 750
775 500 ³15 750
Bus sectionalizer with
Voltage metering 775
circuit-breaker type LK/LT1
panel type MS1V/ME3
600 (900****)

426***

1
2000 (2300****)

1400

312
1
215 110 110
HA41-2312e eps

40

500 ³15 750


775
Bus sectionalizer with
circuit-breaker type LKV/LT1
600 (900)*

60

1
2000 (2300)*

1400

312
1 1 Cover screwed on
215 110 110

* Option: With low-voltage compartment


HA41-2313e eps

*** Available mounting depth for


low-voltage equipment
40

**** Option: With high


500 ³15 750 low-voltage compartment 900 mm
Bus sectionalizer with 775
switch-disconnector type LT2

32 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Dimensions
Busbar earthing panels Billing metering panel ME2 as individual panel and
as individual panels metering panel combin. with billing metering panel

600 (900)*
600 (900)*
339***

60
60
1 1

2000 (2300)*
2000 (2300)*

1400
1400

312
1 1
215 110 110

215 110 110


HA41-2316e eps

HA41-2323f eps
40

40
312

350 ³15 750 600 ³15 750


Earthing panel 775 Billing metering 775
type SE panel type ME2

Metering panel combination


600 (900)*

Only individual Billing metering Individual panel


panel or panel block, 1) panel or panel block,
60

on the left type ME2 on the right


2000 (2300)*

1
1400

1400
312
1
215 110 110
HA41-2317e eps

HA41-2477a eps
40

500 ³15 750 600


Connection Connection
Earthing panel 775 at the busbar at the busbar
type SE1 V/SE2
Billing metering panel type ME2 with
individual panel attached on the left
and panel block attached on the right
(example)

1 Cover screwed on

* Option: * Option:
With low-voltage compartment With low-voltage compartment
*** Available mounting depth
for low-voltage equipment
1) Panel block on request

Siemens HA 41.11 · 2007 33


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Dimensions

Billing metering panels type ME1... as individual panels

600 (900)*

600 (900)*
60

60
1 1
2000 (2300)*

2000 (2300)*
1 1
1400

1400
312
1135

1135
1 1
255 255 255 255
215 110 110

675

675
HA41-2319f eps

HA41-2320f eps
40

40
850 ³15 750 850 ³15 ~145**
775 750
Billing metering panel Billing metering panel
type ME1 type ME1-K 775

600 (900)*

60
1
2000 (2300)*

1
1400

312

1135
1
255 255
215 110 110

675
HA41-2321f eps

40

850 ³15 750


Billing metering panel 775
type ME1-S
600 (900)*

60

1
2000 (2300)*

1
1400

312
255 255
1135

1
215 110 110

675
HA41-2322g eps

1 Cover/cable compartment cover screwed on


40

* Option:
With low-voltage compartment
** Dimension for cable routing: 323 mm for combination of 850 ³15 ~600
panel type ME1-K with pressure absorber duct Billing metering panel 750
type ME1-KS 775

34 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Dimensions

Metering panel combinations with billing metering panels type ME1...


Possible panel arrangements
Billing metering panels with individual panels
The following types of individual panels
or panel blocks attached on the left and right (examples)
or panel blocks can be attached to billing
metering panels – on the right or left:
Possiblity 1
Individual panel Billing metering Individual panel
or panel block, panel or panel block, Possibility 1
on the left type ME1 on the right
• Types attached on the left
with connection at the feeder
– Individual panel type
RK-U, K-U, TR-U, LS1-U or LS2-U
– Panel block type
R-B2 or R-B3 (in RK-U panel),
T-B2 or T-B3 (in TR-U panel),
RT-B2, 2RT-B3 or 3RT-B4 (in TR-U panel)

1400
or KT-B2 (in TR-U panel)
• Types attached on the right
with connection at the busbar
HA41-2441b eps

– Individual panel type


RK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT
– Panel block type
850
R-B2, R-B3, T-B2, T-B3, RT-B2, 2RT-B3, 3RT-B4
Connection Connection or KT-B2
at the feeder * at the busbar

Possibility 2
• Types attached on the left
Possiblity 2 with connection at the busbar
Only Billing metering Individual panel – Individual panel type
individual panel, panel or panel block, RK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT
on the left type ME1 on the right
– Panel blocks cannot be attached
• Types attached on the right
with connection at the feeder
– Individual panel type
RK-U, K-U, TR-U, LS1-U or LS2-U
– Panel block type
R-B2 or R-B3 (in RK-U panel),
1400

T-B2 or T-B3 (in TR-U panel),


L3 L2 L1 RT-B2, 2RT-B3 or 3RT-B4 (in RK-U panel)
L3 or KT-B2 (in K-U panel)
L2
L1
HA41-2442b eps

Possibility 3
• Types attached on the left
with connection at the busbar
Connection 850 Connection – Individual panel type
at the busbar at the feeder ** RK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT
– Panel blocks cannot be attached
Possiblity 3 • Types attached on the right
with connection at the busbar
Only Billing metering Individual panel
– Individual panel type
individual panel, panel or panel block, RK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT
on the left type ME1-S on the right – Panel block type
R-B2, R-B3, T-B2, T-B3, RT-B2, 2RT-B3, 3RT-B4
or KT-B2
1400

L3 L2 L1
L3
L2
L1
HA41-2443b eps

Connection inside the panel block:


* Only possible in the right-hand feeder
850
Connection Connection ** Only possible in the left-hand feeder
at the busbar at the busbar

Siemens HA 41.11 · 2007 35


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Dimensions

Floor openings (dimensions in red) and fixing points

Standard (for special versions, see pages 38 and 39)

350 850
14 x 28 4 14 x 28 4
175 275 300
2 2
31

55

63

31

55

63
• For ring-main panels • For billing metering
³15

³15
1 type RK 1 panels
233 122 69

233 122 69
• For cable panels – Type ME1
3 6
– Type ME1-K
480

type K
8 35 8 35 3 – Type ME1-S
623
713
610

• For busbar earthing


775

775

623
713
610
110 110 255 255 – Type ME1-KS
panel – Type ME1-KK
10 7 7
47 197

type SE
150

47 197
HA41-2325e eps

HA41-2329e eps
19 106 100 19 206 375 231 19
28 x 14 4 28 x 14 4
40 270 40 770

For individual panels For individual panels

500 700
14 x 28 4 • For circuit-breaker panel types 14 x 28 4
250 LS1 and LS2 for ring-main pan- 175 350
2 2
els type RK1 each without ca-
31

63
55

³15
³15

31

55

63
ble-type current transformers • For ring-main
1 1 panel block
233 122 69

233 122 69

• For transformer type R-B2


3 panels type TR1 40 40 3
480

480

8 35 35
• For ring-main/
• For bus sectionalizer with cir- 8 350
623
713
610

623
713
610
transformer
775

775

150 150 cuit-breaker type LK and bus 110 110 110 110 panel block
10 7 sectionalizer with switch-dis- 10 7 type RT-B2
47 197
150

47 197
150

connector type LT
• For cable connection/
• For busbar earthing
HA41-2326e eps

transformer
panel type SE2 panel block
19 106 125 125 19 106 100
28 x 14 4 • For busbar voltage 28 x 14 4 type KT-B2
HA41-2632 eps

40 420 19
metering panel type ME3 350 312
For individual panels
40 620
For panel blocks

500 1000
14 x 28 4 14 x 28 4
250 250 500
2 2
³15

31

55

63

31

55

63

• For transformer
³15

• For circuit-breaker
1 panel types LS1 and LS2 1 panel block
233 122 69

233 122 69

each with cable-type type T-B2


3 40 40 3
480

current transformers
480

8 35 8 35 500
623
713
425

623
713
610

150 150
775

775

150 150 150 150


10
7
10 7
47 197
150

47 197
150
50 135
HA41-2327d eps

19 106 125 125 19 106 125 125


4 4
HA41-2331e eps

28 x 14 28 x 14
40 420 19
5 500 462
15 470
40 920
For individual panels For panel block

600
14 x 28 4
2 1 Wall distance
31

55

63
³15

• For billing metering


1 panels 2 Fixing frame (base) of an individual panel or panel block
233 122 69

type ME2 3 Floor opening for high-voltage cables (and, if applicable,


control cables)
35 3
8 4 Fixing points
623
713
610
775

5 For 4MC70 33 cable-type current transformer with outside diameter


47 197

145 mm for arrangement beneath the panel


6 Position of the incoming cables for metering panels type ME1...
HA41-2328d eps

7 Position of the incoming cables for the feeder


19 131 300
28 x 14 4 8 Overall panel depth
40 520
B Cutout in the fixing frame for extended floor opening for
For individual panels
panel with cable-type current transformers

36 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Dimensions

Floor openings (dimensions in red) and fixing points

Example for fixing


panels on the floor
1050
14 x 28 4
175 350
2
31

55

63
• For ring-main
³15

1 panel block
233 122 69

40 40 40 40
type R-B3
3
• For ring-main/
480

8 35

HA41-2609a_en eps
350 350
623
713
610
transformer
775

110 110 110 110 110 110 panel block


10 7 type 2RT-B3
47 197
150

19 106 100
28 x 14 4
HA41-2633 eps

19 19
350 350 312
40 970
For panel blocks

1400
14 x 28 4
175 350
2 9 “A”
31

55

63

• For ring-main/
³15

1 transformer
233 122 69

40 40 40 40 40 40
panel block 31 69 122 233 197 47
3 type 3RT-B4 approx. 610
480

8 35 350 350 350


623
713
610
775

110 110 110 110 110 110 110 110


10 7
47 197
150

19 106 100
28 x 14 4
HA41-2634 eps

19 19 19
350 350 350 312
40 1320
For panel block

1500 Detail “A”


14 x 28 4
250 500
2
• For trans- 14 x 28 4
31

55

63
³15

former
HA41-2608a eps

1
233 122 69

panel block
40 40 40 40 3 type T-B3
480

8 35 500 500 3
623
713
610
775

150 150 150 150 150 150


10 7
47 197
150

19 106 125 125 4 9


HA41-2334e eps

19 19 28 x 14
500 500 462
40 1420
For panel block

31 69 122 233 197 47

1 Wall distance
2 Fixing frame (base) of an individual panel or panel block
3 Floor opening for high-voltage cables (and, if applicable, control cables)
4 Fixing points
7 Position of the incoming cables for the feeder
8 Overall panel depth (including cable compartment cover)
9 Fixing support
B Cutout in the fixing frame for extended floor opening for
panel with cable-type current transformers

Siemens HA 41.11 · 2007 37


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Dimensions

Floor openings (dimensions in red) and fixing points

Special versions Legends and footnotes see page 39

350
14 x 28 4
175
2
• For ring-main panels
31

55

63
³15

1 type RK
233 122 69

3
• For cable panels
480

type K
8 35
623
713
425
775

110 110 7
10
150
47 197

50 135
HA41-2478a eps

19 106 100
28 x 14 4
40 270
11, 12
15 320
For individual panels with cable-type current transformers
or surge arresters

350 500
14 x 28 4 14 x 28 4
175 250
2 2
³15

31

55

63

³15

• For ring-main panels


31

• For ring-main panels

55

63
1 type RK 1 type RK1
233 122 69

233 122 69

3 • For cable panels 3 • For circuit-breaker panels


480

480

type K type LS1 and LS2


8 35 8 35
648
713
635

648
713
635
775

775

110 110 150 150


~101*

10 10 ~101*
197
150

197
150

7 7
HA41-2479b eps

HA41-2482b eps

19 4 19
28 x 14 28 x 14 4
40 270 420 40
10, 11 10, 11
For individual panels with double cable connection or surge arresters make Tyco Electronics, type RDA 24
(panel depth 775 mm), standard or 25 mm deeper cable compartment cover

350 500
14 x 28 4 14 x 28 4
175 250
2 2
³15

31

55

63
³15

31

55

63

• For ring-main panels • For ring-main panels


1 type RK 1 type RK1
233 122 69
233 122 69

3 • For cable panels 3 • For circuit-breaker panels


480
480

35
type K 35 type LS1 and LS2
8 8
728
818
715

728
818
715

110 110 150 150


880
880

7 10
7
10
42 110 197
150
42 110 197
150

~190*
~190*

HA41-2483b eps
HA41-2480b eps

19 106 100 28 x 14 4 19 106 125 125 28 x 14 4


40 270 40 420
10 10
For individual panels with double cable connection (panel depth 880 mm), 105 mm deeper cable compartment cover

350 500
14 x 28 4 14 x 28 4
175 250
2 2
³15
31

55

63

31

55

63
³15

• For ring-main panels • For ring-main panels


1 type RK 1 type RK1
233 122 69

233 122 69

3 • For cable panels 3 • For circuit-breaker panels


480

480

35 type K 35 type LS1 and LS2


110 110 150 150
923
1013
900

8
923
1013
900

8
10 10
1075

1075

7 7
65 150 130 197
150

65 150 130 197


150
~245*

~245*

6 6
10 10
HA41-2481b eps

HA41-2484b eps

19 106 100 19 106 125 125


28 x 14 4 28 x 14 4
40 270 40 420
For individual panels with double cable connection (panel depth 1075 mm), 300 mm deeper cable compartment cover

38 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Dimensions

Floor openings (dimensions in red) and fixing points

Special versions in combination with pressure absorber system

500 13
2
• For ring-main panels
type RK and RK1
115
215

• For cable panels


~635***

550

type K
~675**
122

3
8 • For circuit-breaker panels
713
828

834
890
233

7 type LS1 and LS2


• For transformer panels
200
47 197

type TR
HA41-2485b eps

14
19 106 125 125
15
40 420 28 x 14 4
For individual panels with single cable connection
500 13 500 13
2 2
• For ring-main panels • For ring-main panels
type RK and RK1 type RK and RK1
115

115
215

215

• For cable panels • For cable panels


~675***

550

type K ~675*** type K


122

550
122

3
8 • For circuit-breaker panels • For circuit-breaker panels
719

834

8 3
890
233

233

7 type LS1 and LS2 type LS1 and LS2

824

939
995

7
240
~101*
47 197

65 85 197

10
343
~190*

10
HA41-2486b eps

14
19
HA41-2487b eps

106 125 125


40
28 x 14 4 14
420 19 106 125 125
40
28 x 14 4
For individual panels with double cable connection 420
standard or 25 mm deeper For individual panels with double cable connection
cable compartment cover 105 mm deeper cable compartment cover
500 13
2
• For ring-main panels 1 Wall distance
type RK and RK1
115

2 Fixing frame (base) of an individual panel or


215

• For cable panels panel block


~675**

type K
550
122

3 Floor opening for high-voltage cables (and, if


3 • For circuit-breaker panels applicable, control cables)
233

8 type LS1 and LS2


4 Fixing points
• For transformer panels
1190

7 7 Position of the incoming cables for the feeder


197

type TR, however connec-


1013
1128
~245*

tion with bolted contact 8 Overall panel depth (including cable compartment cover)
514
65 150 130

10 (M16)
10 Position of 2nd cable
11 For surge arrester
HA41-2488b eps

12 For cable-type current


transformers with outside
19 106 125 125 14
diameter up to 90 mm
40 420 28 x 14 4 13 Pressure absorber duct
For individual panels with double cable connection 14 Front edge of base of the pressure absorber system
300 mm deeper cable compartment cover
15 Front edge of panel without cable compartment cover
* Dependent on the type of cable plug employed
** For panel types RK, K and LS
*** For panel types TR, connection with plug-in contact
D Cutout in the fixing frame for extended floor opening
for panel with cable-type current transformers

Siemens HA 41.11 · 2007 39


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Dimensions
Cable connection examples in ring-main, cable and circuit-breaker panels
(non-binding examples, for further examples see Catalog HA 40.1)

Cable connection in Cable connection with Connection in 1 Elbow adapter, make Siemens,
ring-main panel surge arresters circuit-breaker panel type AKE 20/630 with
conventional cable sealing end,
make Lovink Enertech, type IAE 20
HA41-2339d eps

HA41-2620 eps

HA41-2346d eps
2 Cable T-plug, make Euromold,
type (K)400 TB/G

3 Cable T-plug, make Euromold,


type (K)400 TB/G
6 4 Cable T-plug, make Euromold,
553*** 1 553*** 13 type (K)400 TB/G as 2nd cable
(option: Cable elbow plug
type (K)400 LB/G);
290* always same make required
5

~565
575

575
5 Surge arrester,
make Euromold,
type 300 SA-5 or 300 SA-10

~560** 6 Cable plug,


~560** 560
63 make Euromold,
610 63 610 63 610
type 430 TB
750 750 750
775 775 775 7 Cable plug,
Standard cable compartment cover Standard cable compartment cover Standard cable compartment cover make Tyco Electronics,
type RICS 5139
8 Surge arrester,
553***
HA41-2340d eps

make Tyco Electronics,


HA41-2490a eps
HA41-2343d eps

14
553*** 2 553*** 7 type RDA 21 (for type RDA 24,
15
a floor opening of 635 mm
instead of 610 mm is required)
290*
9 Cable T-plug,
~565
575

575

make Südkabel,
type SET (12/24)
and
~560** ~560** 8 ~560 101 10 Surge arrester,
63 610 63 610 63 635 make Südkabel,
750 750 750 type MUT (13/23)
775 775 775 or:
Standard cable compartment cover Standard cable compartment cover Standard cable compartment cover 9 Cable connector,
300**** make nkt cables, type AB 24-630
18 553*** and
HA41-2347d eps
HA41-2489 eps

HA41-2344e eps

19 16
553*** 553*** 9 10 Surge arrester,
18 make nkt cables, type ASA 24-5

11 Cable T-plug, make Euromold,


type (K)400 TB/G
~565
575
575

12 Surge arrester, e.g.


make Euromold,
type 400 Pb
or similar designs
~560** ~190** ~560** 10 ~560** 17
63 715 63 610 63 610 13 Busbar system
852 772 897 for billing metering panel
880 800 925 type ME1
105 mm deeper 25 mm deeper 150 mm deeper 14 Cable T-plug,
cable compartment cover cable compartment cover cable compartment cover make nkt cables, type CB 24-630
15 Coupling connector,
3
make nkt cables, type CC 24-630
HA41-2341c eps

HA41-2345c eps

553*** 4 553*** 11 16 Cable T-plug,


make Euromold, type (K)400 TB/G
* Max. mounting space 17 4MT8 plug-in voltage transformer
for cable plugs
18 Cable T-plug,
** Dependent on the type
575
575

make Südkabel,
of cable plug type SET 24
*** Dimension for bushing as 19 Coupling insert,
interface type “C” with make Südkabel,
~560** ~245** ~560** 12 bolted contact (M16)
63
type KU 23.2
63 900 610
**** Mounting depth for
1047 897
combination of cable T-plug
1075 925 and surge arrester
300 mm deeper cable compartment 150 mm deeper
cover for double cable connection cable compartment cover

40 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Standards

Standards, specifications, guidelines


Overview of standards (July 2007)

IEC standard VDE standard EN standard


Switchgear 8DH10 IEC 60 694 VDE 0670-1000 EN 60 694
IEC 62 271-200 VDE 0671-200 EN 62 271-200
Switching devices Circuit-breaker IEC 62 271-100 VDE 0671-100 EN 62 271-100
Disconnector and IEC 62 271-102 VDE 0671-102 EN 62 271-102
earthing switch
Switch-disconnector IEC 60 265-1 VDE 0670-301 EN 60 265-1
Switch-disconnector / IEC 62 271-105 VDE 0671-105 EN 62 271-105
fuse combination
HV HRC fuses IEC 60 282-1 VDE 0670-4 EN 60 282
Voltage detecting systems IEC 61 243-5 VDE 0682-415 EN 61 243-5
Degree of protection – IEC 60 529 VDE 0470-1 EN 60 529
Insulation – IEC 60 071 VDE 0111 EN 60 071
Instrument transformers Current transformers IEC 60 044-1 VDE 0414-1 EN 60 044-1
Voltage transformers IEC 60 044-2 VDE 0414-2 EN 60 044-2
Combined transformers IEC 60 044-3 VDE 0414-5 EN 60 044-3
Installation – IEC 61 936-1 VDE 0101 –

Standards Degree of Type of Internal arc classification Climate and ambient


The 8DH10 switchgear protection protection (option) conditions
complies with the relevant IP 3X Enclosure of live parts
(option) under high voltage in
The possibility of arc faults in 8DH10 switchgear types are
standards and specifications switchgear with gas-insulated switchgear type fully enclosed and insensitive to
applicable at the time of locking device 8DH is improbable and a mere climatic conditions.
type tests. fraction of that typical of earlier
IP 3XD Live parts under high • Climatic tests fulfilled in
In accordance with the (on request) voltage in switchgear switchgear types, due to: accordance with IEC 60 932
harmonization agreement with locking device
• Use of gas-filled switchgear (report)
reached by the countries of the IP 65 Live parts under high
voltage in switchgear
compartments • All medium-voltage devices
European Community, their
national specifications
without HV HRC fuses • Use of suitable switching (except for HV HRC fuses)
conform to the IEC standard. devices such as three- are installed in a gas-tight,
position switches with make- welded stainless steel
Dielectric strength Type of service location proof earthing switch switchgear vessel which is
See also Catalog HA 40.1 8DH10 switchgear can be • Logical mechanical interlocks filled with SF6 gas
“Standards”. used as indoor installations in • Use of metal-coated voltage • Live parts outside the switch-
accordance with IEC 61 936 transformers and three-phase gear vessel are provided with
Terms
(Power installations exceeding ring-core current transformers. single-pole enclosure
“Make-proof earthing switches” 1 kV AC) and VDE 0101:
Optionally, switchgear type • At no point can creepage
are earthing switches with
• Outside lockable electrical 8DH can be designed with in- currents flow from high-
short-circuit making capacity
service locations at places ternal arc classification: voltage potentials to earth
according to IEC 62 271-102/
which are not accessible to • Operating mechanism parts
VDE 0671-102. • Internal arc classification IAC
the public. Enclosures of which are functionally impor-
Protection against solid for- switchgear can only be • Type of accessibility A tant are made of corrosion-
eign objects, electric shock removed with tools. (for authorized personnel proof materials
and ingress of water • Inside lockable electrical only)
• Bearings in operating mech-
The switchgear types 8DH10 service locations. A lockable • Accessible sides anisms are designed as dry-
fulfill acc. to the standards electrical service location is a – Side F (front) type bearings and do not
IEC 60 694 VDE 0670-1000 place outdoors or indoors that – Side L (lateral) require lubrication
DIN EN 60 694 is reserved exclusively for – Side R (rear) as an option for
housing electrical equipment switchgear with pressure • Suitable instrument trans-
IEC 62 271- VDE 0671-200
200 and which is kept under lock absorber former designs
IEC 60 529 DIN EN 60 529 and key. Access is restricted • Plug-in busbar system,
• Arc test current up to 21 kA /1 s
to authorized personnel and insulated or screened
the following degrees of pro- persons who have been prop-
• Operating conditions accord-
tection (for explanations re- erly instructed in electrical
engineering. Untrained or ing to IEC 62 271-200,
garding the degrees of protec-
unskilled persons may only among other, relative air
tion, please refer to Catalog HA
enter under the supervision of humility: 95 %
40.1, page 38)
authorized personnel or prop- (24-hour mean value)
Degree of Type of
protection protection erly instructed persons. • Metering panel ME1
IP 2X Live parts under high (air-insulated) according to
(standard) voltage in switchgear IEC 60 694: “Normal operat-
with HV HRC fuses ing conditions”

Siemens HA 41.11 · 2007 41


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Standards, Transport

Transport data, classification


Transport Classification of 8DH10 switchgear according to IEC 62 271-200
8DH10 switchgear is delivered
in transport units containing Design and construction
individual panels or several Partition class PM (metallic partition)
panels. Loss of service continuity category 1)
Panels
The following must be noted: – With HV HRC fuses LSC 2A
• Transport facilities on site – Without HV HRC fuses LSC 2B
Accessibility to compartments Access option
• Transport dimensions and (enclosure)
weights – Busbar compartment – Tool-based
– Switching-device compartment – Non-accessible
• Size of door openings in – Low-voltage compartment – Tool-based
building – Cable compartment 2)
– Panel without HV HRC fuses – Interlock-controlled
Packing – Panel with HV HRC fuses (TR…) – Interlock-controlled
– Panel type K – Tool-based
Place of destination inside – Panel without cable connection – Interlock-controlled and tool-based
Germany or other European (e.g. type RK-U, LS1-U)
countries
• Means of transport: Internal arc classification (option)
Rail and truck Designation of Rated voltage 7.2 kV to 24 kV
internal arc classification IAC
• Type of packing: for
– Panels on open pallets – Wall-standing arrangement (standard) IAC A FL 21 kA, 1 s
– Open packing with PE – Free-standing arrangement (option) IAC A FLR 21 kA, 1 s
protective foil Type of accessibility A Switchgear in closed electrical service location,
access “for authorized personnel only“ (acc. to IEC 62 271-200)
Place of destination overseas –F Front
• Means of transport: –L Lateral
–R Rear (for free-standing arrangement)
Ship
Arc test current Up to 21 kA
• Type of packing: Test duration 1s
– Panels on open pallets
– In closed crates with sealed
upper and lower PE protective 1) The loss of service continuity 2) For 8DH10 switchgear with
foil category is always refered to the pressure absorber:
– With desiccant bags complete switchgear, i.e. the panel Access to cable compartment is
with the lowest category defines tool-based and interlock-controlled.
– With sealed wooden base the loss of service continuity For metering panels type ME1... :
– Max. storage time: 6 months category of the complete Access to cable compartment is
switchgear. tool-based.

42 Siemens HA 41.11 · 2007


Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Notes

If not stated otherwise on the


individual pages of this catalog,
we reserve the right to include
modifications, especially
regarding the stated values,
dimensions and weights.
Drawings are not binding.
All product designations used
are trademarks or product
names of Siemens AG or other
suppliers.
If not stated otherwise, all
dimensions in this catalog are
given in mm.

Responsible for
Technical contents:
Christoph Maul
Siemens AG, Dept. PTD M 2 PPM
Erlangen
General editing:
Gabriele Pollok
Siemens AG, Dept. PTD CC M
Erlangen

Siemens HA 41.11 · 2007 43


Siemens AG For questions concerning Subject to change without notice
Power Transmission and Distribution Power Transmission and Distribution: Order No.: E50001-K1441-A101-A7-7600
Medium Voltage Division You can contact our Customer Support Printed in Germany
Dispo 31606
Postfach 32 40 Center 24 hours a day, 365 days a year.
KG 10.07 7.0 40 En
91050 Erlangen Tel.: +49 180/524 70 00 102773 6101/6487
Germany Fax: +49 180/524 24 71
(Charges depending on provider)
www.siemens.com/ E-Mail: support.energy@siemens.com
medium-voltage-switchgear www.siemens.com/energy-support

The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases.
The required features should therefore be specified in each individual case at the time of closing the contract.