Sunteți pe pagina 1din 8

Journal of Energy Storage 12 (2017) 297–304

Contents lists available at ScienceDirect

Journal of Energy Storage


journal homepage: www.elsevier.com/locate/est

Analytical sizing methods for behind-the-meter battery storage$


Di Wua,* , Michael Kintner-Meyera , Tao Yangb , Patrick Balduccia
a
Pacific Northwest National Laboratory, Richland, WA 99354, USA
b
University of North Texas, Denton, TX 76203, USA

A R T I C L E I N F O A B S T R A C T

Article history:
Received 12 January 2017 In behind-the-meter application, battery storage system (BSS) is used to reduce a commercial or
Received in revised form 21 April 2017 industrial customer's payment for electricity use, including energy and demand charges. The potential
Accepted 22 April 2017 value of BSS in payment reduction and the optimal size can be determined by formulating and solving
Available online 4 June 2017 standard mathematical programming problems. In such mathematical programming methods, users
input system information such as load profiles, energy/demand charge rates, and battery characteristics
Keywords: to construct a standard programming problem, which typically involves a large number of constraints
Battery sizing and decision variables. The problems are then solved by optimization solvers to obtain numerical
Behind-the-meter
solutions. Such kind of methods cannot directly link the obtained optimal battery sizes to input
Energy storage system
parameters and requires case-by-case analysis. In this paper, we present an objective quantitative
Optimization
analysis of costs and benefits for customer-side BSS, and thereby identify key factors that affect optimal
sizing. We then develop simple but effective guidelines for determining the most cost-effective battery
size. The proposed analytical sizing methods are innovative, and provide engineering insights on how the
optimal battery size varies with system characteristics. We illustrate the proposed methods using
practical building load profile and utility rate. The obtained results are compared with the ones using
mathematical programming based methods for validation.
© 2017 Published by Elsevier Ltd.

1. Introduction play an even more significant role in increasing operation


flexibility and reducing energy cost.
The operation of electric power sector requires flexibility to Many studies have been devoted to various ESS technologies for
realize instantaneous balance between generation and constantly grid applications. The technical and economic characteristics of an
changing demand. Wind and solar power have been developed array of ESS technologies are reviewed and compared in [1–3],
rapidly in recent years world-wide. With their natural variability including pumped hydro, battery storage, flywheel, compressed
and uncertainty, these renewable energy resources introduce air, superconducting magnetic energy storage, and advanced
additional variation to power systems and present difficulties and capacitors. Studies [4,5] are dedicated to various battery technolo-
challenges to system operators. Energy storage system (ESS) has gies and methods of assessing their economic viability and impacts
been a candidate for meeting flexibility and reserve requirement on power systems. The identified grid applications include energy
from power grid for years. Recent developments and advances in arbitrage/load leveling, frequency regulation, load following,
energy storage and power electronics technologies are making the spinning and non-spinning reserves, T&D deferral etc. A review
application of energy storage a viable solution for increasing of several ESS technologies for wind power applications is provided
flexibility and improving reliability of power systems. When in [6]. There are also many studies focusing on the optimal
delivered via behind-the-meter application, energy storage can operation and sizing for BSS, and can be categorized into
transmission, distribution and customer-side applications.

 Transmission: In [7], the authors evaluate the economic


$
This material is based upon work supported by the U.S. Department of Energy performance of NaS batteries for energy arbitrage and flywheels
(DOE), Office of Electricity Delivery and Energy Reliability through its Energy for regulation services based on fixed utilization factors for
Storage program, and Washington State Department of Commerce Clean Energy
NYISO and PJM systems. Ref. [8] incorporates realistic CAISO
Fund. Pacific Northwest National Laboratory is operated for the DOE by Battelle
Memorial Institute under Contract DE-AC05-76RL01830. regulation signals and battery responses to yield more granular
* Corresponding author. results. In [9], the authors investigate the application of battery
E-mail address: di.wu@pnnl.gov (D. Wu).

http://dx.doi.org/10.1016/j.est.2017.04.009
2352-152X/© 2017 Published by Elsevier Ltd.
298 D. Wu et al. / Journal of Energy Storage 12 (2017) 297–304

based on maximum mismatch power and permissible durations


Nomenclature
in the control scheme, the optimal battery sizing procedure is
proposed. In [19], the authors develop a frequency-based
a battery equivalent capital cost with respect to energy approach to size a battery-supercapacitor energy storage system
size ($/kWh) for maintaining power balance of an isolated system with high
b battery equivalent capital cost with respect to power penetration of wind generation, thus to maintain the grid
size ($/kW) frequency stability with the stochastic wind power fluctuations.
Ecycle the maximum amount of load that can be shifted  Customer-side: Customer-side BSS is gaining popularity among
from peak hours to off-peak hours considering commercial and industrial businesses as a cost-effective solution
battery storage power capacity to reduce energy and demand charges. In such an application, the
Eoffpeak the amount of energy charged during off-peak hours battery is utilized by customers for saving energy cost, rather
Emax battery storage energy capacity than by system operators for improving distribution system
Epeak the amount of energy discharged during peak hours operation. This is also referred to as behind-the-meter BSS
ND number of days in a year because the battery is literally “behind-the-meter”, on the
NM number of months in a year owner's property, not on the side of the electric utility. This
pmax battery storage power capacity market is predicted to grow rapidly. In California Public Utilities
roffpeak off-peak rate ($/kWh) Commission's mandatory energy storage procurement targets,
rpeak peak rate ($/kWh) its IOUs are required to collectively procure 200 MW energy
Toffpeak duration (in h) of off-peak period storage in the customer-side domain by 2020 [20]. According to
Tpeak duration (in h) of peak period GTM Research, over 700 MW of distributed energy storage will
a capital recovery factor (levelized annual fixed- be deployed in the U.S. between 2014 and 2020 [21]. However,
charge rate) only few studies have been carried out for economic analysis and
b monthly demand charge rate ($/kW/month) optimal sizing of battery storage in behind-the-meter applica-
Dr saving in energy charge by cycling per unit energy tion. In [22], the authors develop a peak-shaving control
from off-peak to peak time period algorithm to determine battery charging and discharging
hround battery round-trip efficiency operation, and then calculate the economic benefits in demand
ropt optimal ratio of energy size to power size for a charge reduction for a few given battery sizes. Ref. [23] considers
battery storage system an application bundle including both energy and demand charge
reduction. One application is treated as primary and determined
first, and then the other application is evaluated. Ref. [24]
explicitly formulates a co-optimization problem considering
storage system (BSS) for relief of transmission line thermal both the energy and demand charges. Dynamic programming
constraints, and therefore increase the transfer capability. Based technique is used to solve the problem to obtain the optimal
on a case study, an economic analysis of benefits and costs is charging schedule. The charging and discharging efficiencies
provided. Ref. [10] presents control algorithms and sizing have not been modeled. These papers provide different methods
strategies for using BSS to manage energy imbalance for variable in evaluating economic benefits for a given size of battery
generation resources. The authors in [11] develop an optimal storage, but have not addressed the optimal sizing problem
control strategy of BSS for smoothing out the intermittent power considering the trade-off between economic benefit and cost.
from the wind farm. In [12], an evaluation framework and co- Therefore, the authors [25] study optimal sizing of a solar-plus-
optimization are proposed to assess BSS economic performance storage system for utility bill savings and resiliency benefits.
considering multiple grid applications simultaneously, including Rather than formulating explicit optimal sizing problem, a
energy arbitrage, balancing services, capacity value, distribution number of simulations are carried out to obtain the economic
upgrade deferral, and outage mitigation. In [13], a method is and resiliency benefits for different solar-plus-storage sizes, and
proposed for identifying the sites where BSS should be located to then select the optimal one. In [26], the authors formulate linear
perform spatial-temporal energy arbitrage most effectively and optimization problems for economic analysis and optimal sizing
the optimal size of these systems. of behind-the-meter BSS. This method explicitly models the
 Distribution and microgrid: The authors of [14] present an charging and discharging efficiencies and co-optimizes the
optimal sizing method for BSS in a microgrid, where the unit battery operation for both energy and demand charge reduction.
commitment problem with spinning reserve for microgrid is No analytical expression is given for optimal battery sizes as
formulated as a mixed linear integer problem. Ref. [15] functions of key factors such as load magnitude, energy/demand
investigates the potential of using BSS in the public low-voltage charge rate, peak/off-peak time periods, and therefore cannot
distribution grid, to defer upgrades needed to increase the provide much engineering insights on how the optimal battery
penetration of photovoltaics, where a multi-objective optimiza- size varies with those factors. This motivates the work presented
tion method is proposed to visualize the trade-offs between in this paper.
three objective functions: voltage regulation, peak power
reduction, and annual cost. An optimal scheduling and cost- This paper presents analytical sizing methods for behind-the-
benefit analysis for microgrid applications is developed in [16]. meter battery storage. The main contributions of this paper are
Dynamic programming is used to solve the optimal scheduling summarized as follows.
problem and determine the optimal BSS power and energy
ratings for both isolated and grid-connected microgrids. The  Developing analytical sizing method for battery storage is a
authors in [17] formulate an optimization problem to minimize challenging problem. Existing methods rely on standard
microgrid energy cost using BSS subject to operational con- mathematical programming for battery operation and sizing
straints. A recent optimization technique called grey wolf analysis, which cannot explicitly directly link the output to input
optimization is then applied to solve the problem and determine parameters and requires case-by-case analysis. This paper
the optimal BSS size. In [18], the authors develop a primary proposes an innovative objective quantitative analysis of costs
frequency control scheme for islanded microgrid using BSS. Then
D. Wu et al. / Journal of Energy Storage 12 (2017) 297–304 299

and benefits for customer-side BSS with respect a few key charged during off-peak hours should be
factors.
Epeak
 Practitioners need effective rule and guidelines for investment Eoffpeak ¼ ; ð2Þ
decision making on battery storage or utility rates design to
hround
stimulate the development of battery storage. This paper where hround is the BSS round-trip efficiency. Based on (1) and (2),
provides analytical expression of optimal battery sizes and the energy arbitrage is only profitable when the rate difference
corresponding benefits, and/or develop simple but effective between peak and off-peak hours is significant enough compared
guidelines and algorithms to meet such a need. with round-trip efficiency, i.e.,
roffpeak
The rest of this paper is organized as follows: Section 2 presents < hround : ð3Þ
rpeak
the benefit and cost analysis and develops rules and guidelines for
optimal sizing. In Section 3, practical utility rate and commercial Given (3) is satisfied, according to the daily saving expressed
building load profile are used to illustrate the proposed analytical in (1), annual benefit in energy charge reduction can be expressed
sizing methods. The optimal battery storage sizes are first as
determined using the proposed analytical methods, and then  
roffpeak
compared with the results obtained using linear programming S ¼ ND Epeak rpeak  ; ð4Þ
methods for validation. Finally, Section 4 concludes the paper. hround
where ND is number of days in a year. On the other hand, the
2. Benefit-cost analysis and sizing guideline development levelized annual battery cost can be expressed as

In customer-side domain, the two main applications of BSS are C ¼ aðaEmax þ bpmax Þ; ð5Þ
energy charge and demand charge reduction. Energy charge is where a is the capital recovery factor (levelized annual fixed-
based only on the amount and time when energy is consumed. It charge rate), a is BSS capital cost with respective to energy size
reflects the operational cost in electricity generation and delivery. ($/kWh), Emax is BSS energy capacity, b is BSS capital cost with
Demand charge is based on the highest power consumption during respective to power size ($/kW), and pmax is BSS power capacity.
a billing period (typically a month). It is mainly designed to recover Therefore, levelized annual benefit can be calculated as
the investment in electricity generation and transportation
infrastructure. Separate charges for energy consumption and B ¼SC  
roffpeak ð6Þ
demand more fairly distribute power system's operational and ¼ ND Epeak rpeak   aðaEmax þ bpmax Þ:
hround
investment cost to customers. This section presents benefit and
cost analysis for both energy and demand charge and derives rules Given that there exist some Emax and pmax such that B > 0, what
and guidelines for optimal sizing. In particular, Section 2.1 analyzes is the optimal ratio between battery energy size and power size so
energy charge reduction, while Section 2.2 analyzes demand that B is maximized? In order to maximize the annual benefit B, we
charge reduction. The two applications are studied jointly in need to maximize the daily energy discharged during peak hours
Section 2.3. Epeak, which is limited by BSS energy and power capacity, as
expressed in (7).
2.1. Energy charge reduction
Epeak  min fT peak pmax ; hround T offpeak pmax ; Emax g ð7Þ
In time-of-use (TOU) pricing program, instead of a single flat where Tpeak and Toffpeak are duration of peak and off-peak period,
rate for energy use, different rates are set for specified time periods respectively. Let us first fix pmax, and let Ecycle = min{Tpeakpmax,
on an advance or forward basis. TOU programs allow consumers to hroundToffpeakpmax}. It can be shown that
respond to the rates and manage their energy cost by shifting usage  
roffpeak
to a lower cost period, which can not only help consumers save ND rpeak   aa > 0 ð8Þ
money but also reduce strain on the electric grid. Most of utilities hround
in the U.S. have launched TOU rate programs especially for is a necessary condition such that (6) is positive. Given (8) is
commercial customers. In California, a plan has been set forth to satisfied, the annual benefit B in (6) monotonically increases as
make TOU rate programs the commercial standard for all of the Epeak increases from 0 to Ecycle. Because of (7), increasing energy
state's major electric utilities. This paper considers TOU plans for size Emax beyond Ecycle only increases battery cost but cannot
energy charge. increase Epeak and therefore cannot increase saving in energy
The customer can charge the battery with cheap energy during arbitrage. Hence, the optimal energy size is
off-peak hours, and discharge the battery during peak hours when
energy price is high. This is referred to as energy arbitrage or peak Emax ¼ Ecycle ; ð9Þ
shaving. It should be noted that in energy charge reduction
application, the optimal battery operation and corresponding and optimal energy to power ratio is
benefits do not vary with load profile. In order to obtain positive ropt ¼ min fT peak ; hround T offpeak g: ð10Þ
benefits from energy arbitrage, the saving in electricity usage
during peak hours should be more than the cost of additional Replacing Epeak and Emax in (6) by roptpmax, after manipulation,
electricity consumption used to charge the battery during off-peak yields
hours, i.e., "  !#
roffpeak aa ab
rpeak Epeak  roffpeak Eoffpeak > 0; ð1Þ B ¼ ND ropt pmax rpeak   þ : ð11Þ
hround ND ND ropt
where rpeak and roffpeak are the peak and off-peak rate, respectively, The physical meaning of important terms in (11) are explained as
Epeak and Eoffpeak is the amount of energy discharged during peak follows:
hours and charged during off-peak hours, respectively. In order to
maintain energy-neutral status of battery, amount of energy  roptpmax : Optimal energy size.
300 D. Wu et al. / Journal of Energy Storage 12 (2017) 297–304

 rpeak  roffpeak : Daily energy charge savings per unit battery energy
h round

size.
 NaDa : Levelized daily battery energy investment cost per
unit energy size.
 ab : Levelized daily battery power investment cost per
ND ropt
unit energy size under optimal energy to power
ratio.

The derived analytical expression can be used for benefit


analysis and investment guidance, as illustrated with the following
example systems, whose parameters are listed in Table 1. These
parameters are developed based on the data in Refs. [22,26].
According to (4) and (11), benefit analysis and investment
guideline are explored in energy rate space and battery cost space
in Fig. 1(a) and (b), respectively, where the optimal energy to
power ratio is determined using (10).
The rate space in Fig. 1(a) is divided into three regions.

 In the yellow region, condition (3) is not satisfied, therefore


resulting in negative saving from energy arbitrage.
 In the green region, condition (3) is satisfied, but the daily energy
charge saving per unit battery energy size is not big enough to
cover the levelized daily battery energy investment cost per unit
energy size (under optimal energy to power ratio). Therefore,
investment in battery for energy cost saving is not cost-effective
either. The slope of the edge between yellow and green regions is
1/hround.
 In the white region, (11) is positive. The expected saving in
energy charge is bigger than battery cost. It is interesting to note
that the edge between intersection white and green regions has
an intersection point with y-axis. Its value (about $0.16/kWh this
case) is the levelized daily battery energy investment cost per
unit energy size (under optimal energy to power ratio).

Therefore, in order to motivate a battery storage to participate Fig. 1. Operational and sizing guideline example. (For interpretation of the
energy shifting services, the energy charging rates offered by references to color in text near the figure citation, the reader is referred to the web
version of this article.)
utilities need to at least stay in the green region. Utility rates in the
white region provide even bigger difference between peak and off-
peak prices and therefore can help customers to financially justify load monotonically increases from minimum to maximum and
their investment in battery storage. It should be noted that in white monotonically decreases from maximum to minimum. Fig. 2
region, if the battery's power size is limited, its optimal energy size illustrates the idea of demand charge reduction. Without
can be determined using the optimal ratio given in (10), and vice discharging BSS during peak hours, the demand at the meter is
versa. On the other hand, without limiting power or energy size, D0. By discharging BSS during peak hours, the net demand at the
the profit optimization problem is unbounded. meter is reduced to DT, where T denotes the time duration of
The battery cost space in Fig. 1(b) is divided into two regions. original load that is higher than or equal to DT. The height of yellow
Per unit battery investment cost becomes more expensive as it region indicates the demand reduced at the meter, which is the
goes to upper and right, and therefore resulting in more same for all months in this case. As we continue lowering demand
investment cost than savings at some point. The boundary level, the annual incremental saving in demand charge can be
between “Investment” and “No investment” regions is quite expressed as:
vertical, which means the investment decision is more sensitive DS ¼ NM bDd; ð12Þ
to energy capacity cost than power capacity cost. This property can
be expected in general for practical Tpeak and Toffpeak. where NM is the number of months in a year, b is the demand
charge rate ($/kW/month), and Dd is the incremental change in
2.2. Demand charge reduction demand reduction. The effectively reduced demand by Dd, the
minimum of required increment in energy capacity is TDd.
Demand charge is a billing mechanism used to recover the cost
of providing transmission and distribution service to customers. It
is calculated based on the highest load during a billing period Table 1
Parameters of example system.
(typically a month). The monthly peak demand can be reduced by
discharging the battery during peak hours, and therefore reducing Param. Value Param. Value
demand charge. Both case (a) & (b) a 0.1168a hround 0.77
ropt 9h ND 365
2.2.1. Similar monthly peak load shape Case (a) a 500$/kWh b 125$/kWh
Case (b) rpeak 0.145$/kWh roffpeak 0.086$/kWh
For simplicity, let us first assume peak day load shape in each
month are approximately the same. In addition, it is assumed that a
15 years lifetime with 8% discount rate.
D. Wu et al. / Journal of Energy Storage 12 (2017) 297–304 301

Fig. 3. Optimal load duration at new demand level (Topt) as a function of battery
cost, where demand charge rate (b in $/kW/month) is a parameter. The horizontal
plane is the maximal Topt limited by energy-neutral constraint.

Fig. 2. Illustration of demand charge reduction. (For interpretation of the


the peak is cut perfectly to fill the valley. The minimum demand is
references to color in text near the figure citation, the reader is referred to the achieved and Topt depends on load shape.
web version of this article.) Once Topt is determined, one can immediately find DT opt . The
corresponding optimal battery power size can be calculated as
According to (5), the corresponding minimum increment in
pmax ¼ D0  DT opt : ð18Þ
battery cost is

DC ¼ aðaT Dd þ bDdÞ: ð13Þ The optimal energy size can be calculated as


Z t0 þT opt
The incremental levelized net benefit can be calculated as Emax ¼ ½DðtÞ  DT opt dt; ð19Þ
t0
DB ¼ DS  DC ð14Þ
¼ DdðNM b  ab  aaTÞ: where D(t) is the load as a function of time, and t0 is the starting
time when load level reaches DT opt (please refer to Fig. 2).
It can be shown that

NM b  ab > 0 ð15Þ 2.2.2. Distinct monthly peak load shape


In practice, the peak day load shape in each month could be
is a necessary and sufficient condition to receive positive net quite different. In this case, an incremental reduction in demand
benefit in demand charge reduction. Given (15) is satisfied, the Dd in each month could be associated with different T and
incremental benefit decreases as T increases, but the total benefit therefore requires different amount of increment in BSS energy
increases with T as long as DB  0. The maximum benefit is capacity. Hence, the proposed method in Section 2.2.1 cannot be
obtained when DB = 0, i.e., used to determine the optimal sizes of BSS in this case.
Given (15) is satisfied, there always exist BSS energy and power
NM b b
T opt ¼  ; ð16Þ sizes such the net-benefit is positive. For month i, let Di0 denote the
aa a
original monthly load level, DiT i denote the corresponding reduced
which is independent of load shape. The demand charge rate
offered by utility need to satisfy (17) for battery storage to monthly load level, and Ti denote the time duration of original load
participate peak demand reduction. that is higher than or equal to DiT i . It is not difficult to see that the
BSS power capacity only needs to be
b > ab=NM : ð17Þ
Fig. 3 plots Topt as a function of a and b (BSS investment cost per pmax ¼ max ðDi0  DiT i Þ; ð20Þ
i
kWh and per kW), for a set of b (demand charge rate). As can be
seen, larger demand charge rate generates more incentives for because bigger power capacity increases BSS cost and smaller
demand reduction, and therefore increment in Topt. In addition, power capacity cannot achieve the reduced load level DiT i for all the
higher battery cost for per unit energy and power (a and b) reduced months. Let imax denote the month index when the maximum is
the cost-effectiveness of demand charge reduction, and therefore achieved for (20).
reducing Topt. Moreover, Topt is not sensitive to b, because the Now, assuming the BSS energy size is increased by DE, the
second term on RHS of (16) is typically small compared with the monthly demand reduction is DT Ei and the annual saving in demand
first term. As T and the energy discharged during peak hours
charge is
increase, at some point, there is not enough time to recharge the
battery during off-peak hours to maintain BSS energy-neutral X
NM
DE
status over long term. This creates another constraint that limits T. DS ¼ b :
i¼1
Ti
Given practical demand charge rate and battery cost, energy-
neutral constraint is inactive, and Topt is directly determined by It should be noted that effective demand reduction requires
(16). However, in extreme cases where battery is very cheap additional power capacity, which is set by month imax, and the
compared with demand charge rate, energy-neutral constraint required increment in power capacity is TD
i
E
. Therefore, the annual
determines Topt. In that case, the net-load at the meter is flat, i.e.,
max
302 D. Wu et al. / Journal of Energy Storage 12 (2017) 297–304

levelized incremental BSS cost becomes difference between (23) and (14) is NDDr T, which is the
  incremental saving from energy charge reduction. In practice,
DE
D C ¼ a aD E þ b NMb  ab is always positive, and NDDr  aa is typically negative.
T imax
Therefore, the incremental benefit decreases as T increases, but the
The incremental levelized annual benefit can be calculated as cumulative benefit increases with T as long as DB  0. The
maximum benefit is obtained when DB = 0, i.e.,
DB ¼ DS  DC !
XNM
1 b NM b  ab
¼ DE b  aða þ Þ T opt ¼ : ð24Þ
T T imax ð21Þ aa  ND Dr
i¼1 i
|fflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflffl{zfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflffl}
L
Compared with demand charge only case, saving from energy
charge helps to increase Topt and therefore the battery size. Once
The benefit increases as long as DB  0. Based on this analysis, Topt is obtained, one can calculate the battery size using (18) and
Algorithm 1 is developed to find the optimal BSS sizes. The sizing (19). In extreme cases when NDDr > aa, (23) is always positive and
analysis is based on the calculation of incremental benefit as a the problem is theoretically unbounded.
function of DE. Therefore, DE should be small. The proposed
algorithm uses binary search method on DE, and therefore ensures 2.3.2. Distinct monthly peak load shape
the accuracy for any initial value. Nevertheless, too small or too When the peak day load shape varies significantly from month
large initial value of DE could increase the iteration numbers. In to month, the analysis in Section 2.2.2 can be modified to include
this study, the initial value of DE is chosen as one percent of the energy charge component. In this case, the calculation in (21) is
peak hour load. In Algorithm 1, the initial Emax should be small modified to include saving in energy charge, and the increment in
enough to ensure that we start with a positive marginal benefit. We levelized annual benefit becomes
then gradually adjust Emax until it results in a zero marginal benefit. !
X
NM
1 b
The initial value of Emax also needs to be bigger than DE. In this DB ¼ DE N D Dr þ b  aða þ Þ ð25Þ
T T imax
study, we set the initial Emax as four times of initial DE. The i¼1 i
corresponding levelized annual benefit can be calculated as |fflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflffl{zfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflffl}
L0
X
NM
Emax
B¼b  aðaEmax þ bpmax Þ: ð22Þ Hence, the optimal BSS scale can be determined using Algorithm 1
i¼1
Ti by replacing L in (21) at line 5 with L0 in (25).

3. Case studies
Algorithm 1. Battery sizing for demand charge reduction with
distinct monthly peak load shape. In this section, practical utility rate and commercial building
load profile are used to illustrate the proposed analytical sizing
1: Initialize Emax that is small enough to ensure positive benefit and DE
methods. Commercial buildings can be categorized based on their
2: repeat
3: principal building activities, including office, retail, warehouse,
Based on current Emax, calculate Ti and DiT i for each month i.
4: education, hotel, healthcare, grocery, restaurant, bank, and others.
For obtained DiT i , determine pmax, imax, and T imax using (20).
5:
The potential benefits and optimal sizes of BSS depend on building
Calculate L in (21).
6: if L  0 then electricity use pattern, which varies with building type and
7: Emax Emax + DE geographical location. The study in [27] develops a library of
8: else building load profiles, consisting of 68 building load data sets for
9: Emax Emax  DE six building types (office, retail, school, hotel, hospital and
10: DE DE/2
11: end if
warehouse) and four locations in different climate zones (San
12: until DE is small enough Francisco, Chicago, Houston, and New York City) from three
13: return Emax, pmax research institutes. Office buildings represent the most important
building type, accounting for about one fifth of total floor space and
building in the U.S. [28], and thereby we select office building load
profile in Houston to illustrate and validate the proposed analytical
2.3. Energy and demand charge reduction sizing methods in this paper.
The optimal battery storage sizes are first determined using the
In the case where both energy and demand charge reduction are proposed analytical methods, and then compared with the results
considered, BSS sizes and charging/discharging operation should obtained using linear programming methods presented in [26] for
be analyzed considering net-benefits from both applications. In validation. In particular, Section 3.1 and Section 3.2 study energy
practice, it is safe to assume that demand reduction occurs during charge reduction and demand charge reduction, respectively. The
peak-hours, and therefore discharging BSS during peak hours can two applications are studied jointly in Section 3.3.
help to reduce both energy and demand charges.
3.1. Energy charge reduction
2.3.1. Similar monthly peak load shape
In this case, calculation in (14) is modified to include energy In this subsection, optimal sizing and potential benefits of BSS
charge saving, and the increment in levelized benefit becomes are studied considering energy charge reduction only. The
assumed capital recover factor (a), round-trip efficiency (hround),
DB ¼ ðND T DdDr þ NM bDdÞ  aðaT Dd þ bDdÞ ; ð23Þ and battery capital cost (a and b) are the same as Case (b) listed in
¼ Dd½NM b  ab þ ðND Dr  aaÞT Table 1. The assumed charging and discharging efficiencies
(including both battery and inverter) are 0.887 and 0.868,
where Dr ¼ rpeak  hoffpeak , which is the reduced energy cost by
r
round respectively, which are needed in the linear programming
cycling per unit energy from off-peak to peak hours. The only methods. The peak hours are from 7am to 4pm, with a duration
D. Wu et al. / Journal of Energy Storage 12 (2017) 297–304 303

Fig. 6. Annual saving vs. levelized annual cost with optimal BSS sizes.
Fig. 4. Levelized annual net-benefit vs BSS energy capacity.
building load profile in Houston used in this paper, the peak day
of 9 h. The other hours are off-peak hours. Positive net-benefit from load shape in different months are quite different. Therefore,
energy charge reduction requires that off-peak and peak rates fall Algorithm 1 is used to find the optimal energy and power size,
in the write region in Fig. 1(a), Herein, it is assumed off-peak and which are 43.6 kWh and 18.2 kW, respectively. The corresponding
peak energy charge rates (roffpeak and rpeak) are 0.07$/kWh and 0.26 levelized annual net-benefit can be calculated by (22), which is
$/kWh, respectively. $2003. This optimal size and the corresponding benefit are the
With these parameters, one can verify that the necessary same as those obtained using the linear programming methods
condition of positive benefit in (8) is satisfied. The optimal energy presented in [26].
to power ratio can be determined by (10), which is 9 h. As analyzed The annual benefits are explored in the energy and power
in Section 2.1, in white region, without limiting power or energy capacity space, as plotted in Fig. 5. It can be observed that benefits
size, the profit optimization problem is unbounded. Therefore, the do not vary significantly with energy or power size around the
BSS maximum power is assumed to be 50 kW in this case, and the optimum. In other words, a few different sizes of BSS generate
corresponding optimal energy size is 450 kWh. The levelized approximately the same performance on economic benefits. In
annual net-benefit can be calculated using (11), which is $754.7. such a case, rather than simply taking the optimum, other factors
Next, optimal sizing is studied using the linear programming such as available models from BSS manufactures, budget and space
methods presented in [26]. The benefits for different BSS energy constraints should be considered to select the most appropriate
capacity are explored, as plotted in Fig. 4. The result is consistent BSS size among a few good candidates.
with the analysis in Section 2.1. Because the necessary condition in
(8) is satisfied in this example, the net-benefit monotonically 3.3. Energy and demand charge reduction
increases as Emax increases from 0 to Ecycle = min{Tpeakpmax,
hroundToffpeakpmax}, which is 450 kWh in this example. The net- In this subsection, optimal sizing is studied considering both
benefit reaches the maximum when BSS energy capacity equal energy and demand charge reduction. All the parameters are the
450 kWh, i.e., the optimal energy to power ratio is 9 h, and then same as Section 3.2, and the off-peak and peak energy charge rates
decreases as Emax increases. The corresponding maximum annual are assumed to be 0.86$/kWh and 0.145$/kWh, respectively. Using
benefit is the same as calculated using the proposed analytical the method proposed in Section 2.3.2, the optimal energy and
method. power sizes are found to be 76.4 kWh and 23.7 kW, respectively.
The corresponding levelized annual net-benefit is $2715.1.
3.2. Demand charge reduction Compared with the demand charge only case, additional saving
from energy charge helps increase BSS sizes and the corresponding
In this subsection, optimal sizing and potential benefits are net-benefit. Fig. 6 plots the annual saving from energy and demand
studied considering demand charge reduction only. The same charge reduction, as well as levelized annual cost for the optimal
parameters in previous subsection are used here. In addition, the BSS sizes. As can be seen, the demand charge reduction dominates
demand charge rate is assumed to be $30/kW/month. For the office the total saving and contributes much more to net-benefit. This
result is quite typical for practical utility rates and existing BSS
technologies.

4. Conclusions

This paper presents innovative analytical sizing methods for


behind-the-meter BSS to reduce the electricity bill in energy and
demand charges, considering the trade-off between benefits and
costs. The proposed methods are based on objective quantitative
analysis and result in simple but effective rules and guidelines that
can be used to determine the most cost-effective battery size or
guide utility rate design for stimulating energy storage develop-
ment. With the proposed methods, optimal sizing and analysis
have been performed using typical commercial building load
profile and utility rates in a few cases. It is found that with much
simplified procedures, the proposed analytical sizing methods can
Fig. 5. Net-benefit with different battery sizes. not only effectively identify the most cost-effective BSS sizes as
304 D. Wu et al. / Journal of Energy Storage 12 (2017) 297–304

other existing methods for a given system, but also provide [13] R. Fernandez-Blanco, Y. Dvorkin, B. Xu, Y. Wang, D.S. Kirschen, Optimal energy
important engineering insights on how different factors affect the storage siting and sizing: a WECC case study, IEEE Trans. Sustain. Energy (99)
(2016) 1, doi:http://dx.doi.org/10.1109/TSTE.2016.2616444.
optimal sizing and the net-benefits. [14] S.X. Chen, H.B. Gooi, M.Q. Wang, Sizing of energy storage for microgrids, IEEE
Trans. Smart Grid 3 (1) (2012) 142–151, doi:http://dx.doi.org/10.1109/
References TSG.2011.2160745.
[15] J. Tant, F. Geth, D. Six, P. Tant, J. Driesen, Multiobjective battery storage to
improve PV integration in residential distribution grids, IEEE Trans. Sustain.
[1] P.F. Ribeiro, B.L. Johnson, M. Crow, A. Arsoy, Y. Liu, Energy storage systems for
Energy 4 (1) (2013) 182–191, doi:http://dx.doi.org/10.1109/TSTE.2012.2211387.
advanced power applications, Proc. IEEE 89 (12) (2001) 1744–1756, doi:http://
[16] T.A. Nguyen, M.L. Crow, A.C. Elmore, Optimal sizing of a Vanadium Redox
dx.doi.org/10.1109/5.975900.
battery system for microgrid systems, IEEE Trans. Sustain. Energy 6 (3) (2015)
[2] I. Hadjipaschalis, A. Poullikkas, V. Efthimiou, Overview of current and future
729–737, doi:http://dx.doi.org/10.1109/TSTE.2015.2404780.
energy storage technologies for electric power applications, Renew. Sustain.
[17] S. Sharma, S. Bhattacharjee, A. Bhattacharya, Grey wolf optimisation for
Energy Rev. 13 (6–7) (2009) 1513–1522, doi:http://dx.doi.org/10.1016/j.
optimal sizing of battery energy storage device to minimise operation cost of
rser.2008.09.028.
microgrid, IET Gener. Transm. Distrib. 10 (3) (2016) 625–637, doi:http://dx.doi.
[3] S. Vazquez, S.M. Lukic, E. Galvan, L.G. Franquelo, J.M. Carrasco, Energy storage
org/10.1049/iet-gtd.2015.0429.
systems for transport and grid applications, IEEE Trans. Ind. Electron. 57 (12)
[18] M.R. Aghamohammadi, H. Abdolahinia, A new approach for optimal sizing of
(2010) 3881–3895, doi:http://dx.doi.org/10.1109/TIE.2010.2076414.
battery energy storage system for primary frequency control of islanded
[4] K.C. Divya, J. Østergaard, Battery energy storage technology for power systems
microgrid, Int. J. Electr. Power Energy Syst. 54 (2014) 325–333, doi:http://dx.
– an overview, Electr. Power Syst. Res. 79 (4) (2009) 511–520, doi:http://dx.doi.
doi.org/10.1016/j.ijepes.2013.07.005.
org/10.1016/j.epsr.2008.09.017.
[19] Y. Liu, W. Du, L. Xiao, H. Wang, S. Bu, J. Cao, Sizing a hybrid energy storage
[5] B. Dunn, H. Kamath, J.-M. Tarascon, Electrical energy storage for the grid: a
system for maintaining power balance of an isolated system with high
battery of choices, Science 334 (6058) (2011) 928–935, doi:http://dx.doi.org/
penetration of wind generation, IEEE Trans. Power Syst. 31 (4) (2016) 3267–
10.1126/science.1212741 arXiv: http://www.sciencemag.org/content/334/
3275, doi:http://dx.doi.org/10.1109/TPWRS.2015.2482983.
6058/928.full.pdf.
[20] Decision Adopting Energy Storage Procurement Framework and Design
[6] F. Díaz-González, A. Sumper, O. Gomis-Bellmunt, R. Villafáfila-Robles, A review
Program, 2013. Available online at http://docs.cpuc.ca.gov/PublishedDocs/
of energy storage technologies for wind power applications, Renew. Sustain.
Published/G000/M079/K533/79533378.PDF.
Energy Rev. 16 (4) (2012) 2154–2171, doi:http://dx.doi.org/10.1016/j.
[21] GTM, Distributed Energy Storage 2014: Applications and Opportunities for
rser.2012.01.029.
Commercial Energy.
[7] R. Walawalkar, J. Apt, R. Mancini, Economics of electric energy storage for
[22] J. Neubauer, M. Simpson, Deployment of Behind-the-meter Energy Storage for
energy arbitrage and regulation in New York, Energy Policy 35 (4) (2007)
Demand Charge Reduction Tech. Rep. NREL/TP-5400-63162, National
2558–2568, doi:http://dx.doi.org/10.1016/j.enpol.2006.09.005.
Renewable Energy Laboratory, January 2015.
[8] N. Lu, M.R. Weimar, Y.V. Makarov, C. Loutan, An evaluation of the NaS battery
[23] A. Nourai, et al., Tool Development for Estimating Value of Grid-connected
storage potential for providing regulation service in California, Proc. IEEE
Energy Storage in Bundled Services Tech. rep., KEMA, 2013.
Power Systems Conf. Expos. (2011) 1–9, doi:http://dx.doi.org/10.1109/
[24] Y. Yoon, Y.-H. Kim, Charge scheduling of an energy storage system under time-
PSCE.2011.5772494.
of-use pricing and a demand charge, Sci. World J. (2014), doi:http://dx.doi.org/
[9] A.D. Del Rosso, S.W. Eckroad, Energy storage for relief of transmission
10.1155/2014/937329.
congestion, IEEE Trans. Smart Grid 5 (2) (2014) 1138–1146, doi:http://dx.doi.
[25] T. Simpkins, K. Anderson, D. Cutler, D. Olis, Optimal sizing of a solar-plus-
org/10.1109/TSG.2013.2277411.
storage system for utility bill savings and resiliency benefits, IEEE PES
[10] X. Ke, N. Lu, C. Jin, Control and size energy storage systems for managing
Innovative Smart Grid Technologies Conference (ISGT) (2016) 1–6, doi:http://
energy imbalance of variable generation resources, IEEE Trans. Sustain. Energy
dx.doi.org/10.1109/ISGT.2016.7781237.
6 (1) (2015) 70–78, doi:http://dx.doi.org/10.1109/TSTE.2014.2355829.
[26] D. Wu, M. Kintner-Meyer, T. Yang, P. Balducci, Economic analysis and optimal
[11] S. Teleke, M.E. Baran, A.Q. Huang, S. Bhattacharya, L. Anderson, Control
sizing for behind-the-meter battery storage, Proc. IEEE Power Energy Soc.
strategies for battery energy storage for wind farm dispatching, IEEE Trans.
Gene. Meet., Boston, MA, 2016, doi:http://dx.doi.org/10.1109/
Energy Convers. 24 (3) (2009) 725–732, doi:http://dx.doi.org/10.1109/
PESGM.2016.7741210.
TEC.2009.2016000.
[27] C. Sun, K. Temple, T. Rossi, J.E. Braun, Interaction Between Dynamic Electric
[12] D. Wu, C. Jin, P. Balducci, M. Kintner-Meyer, An energy storage assessment:
Rates and Thermal Energy Storage Control Tech. rep., ASHRAE, 2006.
using optimal control strategies to capture multiple services, Proc. IEEE Power
[28] U.S. Energy Information Administration, Commercial Buildings Energy
Energy Soc. Gene. Meet., Denver, CO, 2015, doi:http://dx.doi.org/10.1109/
Consumption Survey, (2012) .
PESGM.2015.7285820.

S-ar putea să vă placă și