XUAN PHU HAI INVESTMENT & CONSTRUCTION JSC
Ha My Dong A, Dien Duong, Dien Ban district, Quang Nam province, Vietnam
t (+24) 3 7475 266
e info@xuancau.com.vn
CLIENT | Xuan Phu Hai Investment & Construction JSC CONSULTANT | Boydens Engineering
General Director: Chairman:
Tổng Giám Đốc Chủ tịch
© boydens engineering
XUAN PHU HAI
HOTEL CONCEPT DESIGN
01/08/2018
LE TRUNG KIEN
PROJECT MANAGER
KIENLT@BOYDENSVN.COM
1. HVAC 4
HVAC
© boydens engineering
1. HVAC 5
© boydens engineering
1. HVAC 6
DESIGN CRITERIA
Location: Hoi An, Quang Ngai, Vietnam
Ambient Air Temperatures:
- Summer: 37.6°C Dry Bulk/ 28.3°C Wet Bulk
- Winter: No winter time in Hoi An (Boydens recommends no heating mode required in XPH project)
Air-conditioned space design conditions
- Guest room: 22°C ± 1oC
- Other function rooms: 24°C ± 1oC
- Open public area shall be applied passive design
- Sports room, Fitness : 21°C (Summer)
- Switch, computer room: 26~28C
- Kitchen: 28C
The detail temperature requirement will be provided in Design Brief
© boydens engineering
1. HVAC 7
DESIGN CRITERIA
Comparison about Ventilation rates:
FRESH AIR
REQUIREMENT
Guestroom 11 (l/s) 17 (l/s) 13.89 (l/s) 17 (l/s) 8.33 (l/s) 9.44 (l/s)
39.6 (m3/h) 61.2 (m3/h) 50 (m3/h) 61.2 (m3/h) 30 (m3/h) 35 (m3/h)
Offices 8.5 (l/s) 8.0 (l/s) 9.72 (l/s) 11.67 (l/s) 8.00 (l/s) 8.33 (l/s)
30.6 (m3/h) 28.8 (m3/h) 35 (m3/h) 42 (m3/h) 28.8 (m3/h) 30 (m3/h)
Restaurant 10 (l/s) 7 (l/s) 11.11 (l/s) 11.67 (l/s) 3~5ACH 8.33 (l/s)
36 (m3/h) 36 (m3/h) 40 (m3/h) 17 (m3/h) 30 (m3/h)
Public Areas 10 (l/s) 7 (l/s) 6.97 (l/s) 11.67 (l/s) 3~5ACH 6.97 (l/s)
36 (m3/h) 36 (m3/h) 25 (m3/h) 17 (m3/h) 25 (m3/h)
Fitness (Exercise) 22 (l/s) 20 (l/s) 13.89 (l/s) 9.44 (l/s) Not Available 11.11 (l/s)
Areas 79.2 (m3/h) 72 (m3/h) 50 (m3/h) 34 (m3/h) 40 (m3/h)
RECOMMENDATION
ASHRAE
Standard
© boydens engineering
1. HVAC 8
The duct insulation shall be closed cell elastomeric foam materials with the minimum thickness followed QCVN 09/2013
RECOMMENDATION
© boydens engineering
1.HVAC – COOLING PRODUCTION 9
1. Hotel
• Little distance between guests
• Available shafts and trays
• Lower peak power per guest
Comfort
Cost Energy
© boydens engineering
1.HVAC – COOLING PRODUCTION 10
Hotel
Chiller system
RECOMMENDATION
© boydens engineering
1.HVAC 11
AHU FCU
CHILLER PIPING
DOMESIC HOT WATER
CONDENSER PIPING
04 CHILLER PUMP 03 WATER-COOLED CHILLER 04 CONDENSER PUMP WATER SOURCE HEAT PUMPs
RECOMMENDATION
© boydens engineering
1.HVAC 12
HYGIENIC VENTILATION
AHU
AHU
AHU
© boydens engineering
1.HVAC 13
HYGIENIC VENTILATION
© boydens engineering
1.HVAC 14
CHILLER 300,000
PUMP 12,000
MATERIAL 172,000
TOTAL 925,000
© boydens engineering
2.PLUMBING 15
PLUMBING
© boydens engineering
2.PLUMBING 16
© boydens engineering
2. PLUMBING 17
DESIGN CRITERIA
Comparison about water demand
HOT/COLD WATER
REQUIREMENT
Storage capacity two day one day two day one day one day one day
© boydens engineering
2.PLUMBING 18
DESIGN CRITERIA
Location: Hoi An, Quang Ngai, Vietnam
Water consumption
- Hotel: 300 litres/person/day
- Staff: 50 litres/staff/day
Hot water
- Hotel: 100 l/person/day
- Hot water temperature of the distribution: 55-60°C
- Time for hot water to reach the tap:
o Bedroom: less than 05 seconds
o Service area: less than 10 seconds
Water pressure
- Minimum: 2.4 Bar
- Maximum: 3.5 Bar
Water velocity: From 0.5-1.2 m/s
© boydens engineering
2.PLUMBING 19
© boydens engineering
2.PLUMBING 20
© boydens engineering
2.PLUMBING 21
DHW PIPING
HOTWATER
RECIRCULATING PUMP
DISCHARGE STACK
SECONDARY VENTILATED
© boydens engineering
2.PLUMBING 23
© boydens engineering
2.PLUMBING 24
© boydens engineering
2.PLUMBING 25
Hotel
Overflow
Run-off rainwater
To Sewer
Discharge
Column A - QCVN14:2008/BTNMT
© boydens engineering
2.PLUMBING 26
© boydens engineering
2.PLUMBING 27
STEAM PIPING
STEAM BOILER
RECOMMENDATION
© boydens engineering
3.ELECTRICAL 28
ELECTRICAL
© boydens engineering
3.ELECTRICAL 29
© boydens engineering
3.ELECTRICAL 30
© boydens engineering
3.ELECTRICAL 31
MV INCOMING
© boydens engineering
3.ELECTRICAL 32
TRANSFORMER
GENERATOR
Generator is used to provide standby electrical power generation to the building and specific
selected systems, as later described, during periods of loss of the normal incoming electricity
supply and emergency situations. Generator must be sized to maintain 100% loads.
Generator system feeds only emergency load in case of fire.
Generator system feeds all load in the event of a fault in the normal supply.
Daily fuel tank size: for 8 hours (full load)
Storage fuel tank size: for 48 hours (full load)
© boydens engineering
3.ELECTRICAL 33
COUPLING
ATS ATS
SYN PANEL
BACK UP GENERATOR
(100% LOAD)
© boydens engineering
3.ELECTRICAL 34
LV DISTRIBUITION BOARD
© boydens engineering
3.ELECTRICAL 35
EARTHING SYSTEM
© boydens engineering
3.ELECTRICAL 36
LIGHTING
© boydens engineering
3.ELECTRICAL 37
LIGHTING CONTROL
© boydens engineering
3.ELECTRICAL 38
©©
boydens
boydens engineering
engineering
4.EXTRA LOW VOLTAGE 39
© boydens engineering
4.EXTRA LOW VOLTAGE 40
© boydens engineering
4.EXTRA LOW VOLTAGE 41
COMMUNICATION SYSTEM
Use both wired and wireless networks. Access points for public
areas and in each guestrooms.
SWITCH
IP PHONE DATA CABLE
© boydens engineering
4.EXTRA LOW VOLTAGE 42
© boydens engineering
4.EXTRA LOW VOLTAGE 43
© boydens engineering
4.EXTRA LOW VOLTAGE 44
Main targets:
o Coordinate the operations of all systems to ensure the
highest efficiency (ex: energy saving).
o Monitor the operation of the system to ensure the fastest
error detection and fixing.
© boydens engineering
5.FIRE PROTECTION 45
FIRE PROTECTION
© boydens engineering
5.FIRE PROTECTION 46
© boydens engineering
5.FIRE PROTECTION 47
© boydens engineering
5.FIRE PROTECTION 48
DESIGN CRITERIA
Automatic Sprinkler System
- K-factor
o Basement (OH group 2) : K= 80 lpm/bar
o Hotel area (OH group 1) : K=0.92
Drencher System (if needed)
- Q=01 l/s.m
Fire hose reel system
- Q=2.5l/s with pressure 06 mH2O per Fire hose reel cabinet
- Every point in a floor shall be reached by 02 Fire hose reels.
- 01 Angle Valve DN50 in each Fire hose reel cabinet
Fire hydrant
- Q=10l/s per Fire hydrant
- Pressure: Min 10 mH2O
©©boydens
boydens engineering
engineering
4.FIRE PROTECTION 49
SPINKLER HEAD
FIRE HOSE REEL
SIDE WALL
SPINKLER HEAD
FIRE PUMP
(GROUND FLOOR )
ALARM VALVE
© boydens engineering
5.FIRE PROTECTION 50
Heat Detector
©©boydens
boydens engineering
engineering
5.FIRE PROTECTION 51
©©boydens
boydens engineering
engineering
5. FIRE PROTECTION 52
DESIGN CRITERIA
Comparison about Fire protection standard:
NFPA Hotel, 139 0.068 12.1 30 D150 D65 D25 9.45 152
Restaurant 139 0.1 12.1 60-90 D150 D65 D40 9.45 152
The QUDOS project must be complied with at least TCVN. But follow NFPA and Amari’s requirement, the project
need to be equipped with the private Hosereel system.
The additional cost for Hosereel system is about ($US)30,000.
© boydens engineering
5. FIRE PROTECTION 53
DESIGN CRITERIA
Comparison about Fire protection standard:
© boydens engineering
5.FIRE PROTECTION 54
DESIGN CRITERIA
Automatic Spinkler System
- K-factor
o Restaurant (OH group 1 ) : K= 80 lpm/bar
o Hotel area (Light) : K=56 lpm/bar
Drencher System
- Q=01 l/s.m
Fire hose reel system
- Q=2.5l/s with pressure 06 mH2O per Fire hose reel cabinet
- Every point in a floor shall be reached by 02 Fire hose reels.
- 01 Angle Valve DN50 in each Fire hose reel cabinet
Fire hydrant
- Q=15l/s per Fire hydrant
- Pressure: Min 10 mH2O
© boydens engineering
5.ENERGY OPTIMISATION 55
ENERGY OPTIMISATION
© boydens engineering
5.ENERGY OPTIMISATION 56
GENERAL RECOMMENDATIONS
Avoid oversizing
© boydens engineering
5.ENERGY OPTIMISATION 57
MECHANICAL
© boydens engineering
5.ENERGY OPTIMISATION 58
ELECTRICAL
© boydens engineering
5.ENERGY OPTIMISATION 59
Amari STANDARD
PV PANELS
Quantity:
1000 Panels of 220 Wp
220 kWp installed
Investment $ 550.000
Electricity production: 9%
Payback 18y
Why is the payback low?
1. Low electricity price
2. No subsidies from the government
3. Prices of PV installers in Vietnam is still high due to the low demand
Electricity Price: 0.11 USD/kWh
Energy Inflation: 5.6%
© boydens engineering
6.ACOUSTIC 60
NOISE CONTROL
©©boydens
boydens engineering
engineering
6.ACOUSTIC 61
©©boydens
boydens engineering
engineering
62
PASSIVE DESIGN
FOR HOTEL
(RESULT OF STUDYING)
© boydens engineering
© boydens engineering
CONTROLLING THE SOLAR GAINS 63
© boydens engineering
Good
Overlit
© boydens engineering
65
© boydens engineering
CONTROLLING THE SOLAR GAINS 66
© boydens engineering
BUILDING ENVELOPE
100 mm
200 mm
300 mm
400 mm
WALL THICKNESS
© boydens engineering
BUILDING ENVELOPE 68
27 37
36
26
35
25
34
24 33
32
23
Temperature (°C)
Temperature (°C)
31
22
30
21
29
20 28
27
19
26
18
25
17 24
Sun Mon Tue Wed Thu Fri Sat Sun Sun Mon Tue Wed Thu Fri Sat Sun
Date: Sun 03/Jan to Sat 09/Jan Date: Sun 04/Jul to Sat 10/Jul
CLIMATE 1 CLIMATE 2
© boydens engineering
COMFORT RESULTS 69
27
26
25
24
Temperature (°C)
23
22
Warmer in
dry climate
21
100 mm
20 200 mm
Sun Mon Tue Wed Thu Fri Sat Sun
Date: Sun 03/Jan to Sat 09/Jan 300 mm
Air temperature: 47 Space (Hotel 100mm.aps) Air temperature: 47 Space (HOTEL AC 400mm.aps) Air temperature: 47 Space (HOTEL AC 300mm.aps) Air temperature: 47 Space (HOTEL AC 200mm.aps)
400 mm
© boydens engineering
COMFORT RESULTS 70
37
36
Cooler in
hot climate 35
34
33
32
Temperature (°C)
31
30
29
28
27
100 mm
26
25 200 mm
Sun Mon Tue Wed Thu Fri Sat Sun
Date: Sun 04/Jul to Sat 10/Jul 300 mm
Air temperature: 47 Space (Hotel 100mm.aps) Air temperature: 47 Space (HOTEL AC 400mm.aps) Air temperature: 47 Space (HOTEL AC 300mm.aps) Air temperature: 47 Space (HOTEL AC 200mm.aps)
400 mm
© boydens engineering
BUILDING ENVELOPE
GREEN ROOF
© boydens engineering
COMFORT RESULTS 72
27.0
26.5
26.0
25.5
Temperature (°C)
25.0
24.5
24.0
23.5
23.0
Normal
22.5
Sun Mon Tue Wed Thu Fri Sat Sun Green
Date: Sun 10/Jan to Sat 16/Jan
Air temperature: 41 01 Livingroom (Villa Normal Roof.aps) Air temperature: 41 01 Livingroom (VILLA GREEN ROOF.aps)
© boydens engineering
COMFORT RESULTS 73
40
38
36
34
Temperature (°C)
32
30
28
26
Normal
24
Sun Mon Tue Wed Thu Fri Sat Sun Green
Date: Sun 11/Jul to Sat 17/Jul
Air temperature: 41 01 Livingroom (Villa Normal Roof.aps) Air temperature: 41 01 Livingroom (VILLA GREEN ROOF.aps)
© boydens engineering
HOTEL 56
© boydens engineering
HOTEL 57
© boydens engineering
THANK YOU