Client : MAZOON ELECTRICITY COMPANY S.A.O.

G
Consultant : M/s. RITAJ ENGINEERS & CONSULTANTS

Contractor : MODERN CENTRE ELECTRICAL & SANITARY L.L.C.


Project : UPGRADING OF AL AWABI, AL HAZIM AND WADI BANI GHAPIR PRIMARY SUBSTATIONS (33/11kV) TO 2X20MVA
GOVERNORATE
Equipment : 415V LVAC SWITCHBOARD
Manufacturer : MAJAN SWITCHGEAR CO.LLC

MAJAN SWGR.
SL.No CONSULTANT COMMENTS DRAWING PAGE
REF.
415V LVAC SWITCHBOARD

1 250A MCCB required instead of 200A (spare feeder) 4 of 15

Provide control fuse and terminals in the LV board for


2 5 of 15 and 8 of 15
kWH meter.
CT burden shall be 5VA for kWH meter and 7.5VA for
3 5 of 15 and 8 of 15
MFM.

4 MCBs rating shall be as per approved project SLD. 7 of 15

5 Description to be corrected for L2H compartment. 9 of 15


MARY SUBSTATIONS (33/11kV) TO 2X20MVA AT SOUTH AL BATINAH

Majan switchgear response. Remarks

Comply.

Separate Control fuses and CTTB's provided for kWH meter-1 and
2.

Comply.

MCB's ratings are updated as per Approved SLD (DWG. No.:


08/2016/AWB/E/1006/01/A1, REV.:B, Dated.: 14.03.17)
Corrected.