BUILDING 1
FUNCTION HALL
Walls
Height: 3.01 meters
Width: 6.83 meters
Length: 24.2 meters
Area
Front and rear :( 24.2 m) (3.01 m) = 72.842 m²
Side: (6.83 m) (3.01 m) = 20.558 m²
Windows
Height: 1.48 meters
Length: 3.36 meters
Area:
= (1.48 m) (3.36 m)
= 4.973 m²
Number of units: Back: 6 units Top: 4 units
For Students:
Heat Gain per person= 100W
Sensible Heat Gain= 60%
From Table 4-9, Refrigeration and Air-Conditioning by Stoecker and Jones
Qoccup= 8160 W
Heat Gain from Lights,
From engineeringtoolbox.com
𝑊
Single Glass, Summer ~ U= 5.9 𝑚2 × 𝐾
NOTE: The yellow line represents the Azimuth angle based on its Elevation
angle and time as of February 20, 2019
Solar azimuth angle (ɸ) = 204° - 180° = 24°
Building angle (Ѱ) =357° - 180° = 177°
γ=ɸ +Ѱ
= 24° + 177°
= 201°
tan 62°
y = 0.05 m cos 201°, where d= 0.05 m
y = -0.1007 m
x = d tan γ
x = (0.05 m) tan 201°
x = 0.01919 m
Sunlit Area = (h – y) (w - x)
= (1.48 m – (-0.1007 m)) (3.36 m - 0.01919 m)
Sunlit Area = 5.2808 m2
For SHGFmax, use the nearest value of 16°N Latitude for the room
location of 14°N Latitude for Santa Cruz, Laguna given by ASHRAE
SC= 0.73
From Table 4-12, Refrigeration and Air-conditioning by Stoecker and Jones
Qsgb= 541.842 W
= 2053.849 W + 541.842 W
QW = 2595.691 W
Heat Gain From Doors, QD
For transmission, Qt
Qt= UA(to-ti)
Qt= 318.423 W
For Solar Heat Gain, Qsg
There is no solar heat gain from the windows since the light of the sun
is covered by the concrete slabs from 2nd floor
Vo = 17.5L/s Vm = 3.5L/s
V = Q = Vr + Vm
= 23.33 + 3.5
Q= 26.83L/s
Sensible Heat Gain, Qis
From ASHRAE Fundamentals Handbook
Qis = 1.23Q(to-ti)
Qis = 1.23(26.83)(32-25)
Qis = 406.90W
QIL = 3000(26.83)(0.021-0.0088)
QIL = 981.978 W
Qw = 1599.3681 W
For Solar Heat Gain of Wall, Qwsg
From ASHRAE Fundamentals Handbook,
A(CLTDadj)
Qwsg= 𝑅𝑡
CLTD = 19
CLTDadj = 19 + (25-25) + (32-29)
CLTDadj = 22
(41.1166 m2 )(22)
Qwsg= .759
Qwsg= 489.4833 W
OCCUPANTS 8160 W
LIGHTS 441.6 W
MOTOR 432 W
WINDOWS 2595.691W
DOOR 318.423 W
INFILTRATION 1338.878 W
WALL 2088.851 W
TOTAL 15375.443 W
FACULTY ROOM
ND
LOCATED AT THE 2 FLOOR
Walls
Height: 3 meters
Width: 5.40 meters
Length: 3.85 meters
Area
Front and rear :( 3 m) (5.40 m) = 16.2 m²
Side: (3 m) (3.85 m) = 11.55 m²
Window
Height: 1.42 meters
Length: 1.63 meters
Area:
= (1.42 m) (1.63 m) = 2.3146 m²
Number of units: 1
Door (Wood)
OTHER SPECIFICATIONS
TIME : 1:00 PM
DESIGN OUTSIDE TEMPERATURE : 32 °C
Wattage: 75 Watts
From engineeringtoolbox.com
QD= 22.938 W
Vo = 17.5L/s Vm = 3.5L/s
From Table 4-2, Refrigeration and Air-conditioning by Stoecker and Jones
~ Building Recirculated and Fresh Air Systems
E = 60%
From ASHRAE allowable air flow rate,
Vo − Vm 17.5− 3.5
Vr = = = 23.33 L/s
𝐸 0.60
V = Q = Vr + Vm
= 23.33 + 3.5
Q= 26.83L/s
Qw =367.9418 W
For Solar Heat Gain of Wall, Qwsg
From Refrigeration and Air-Conditioning by Stoecker and Jones
A(CLTDadj)
Qwsg= 𝑅𝑡
CLTD = 6
CLTDadj = 6 + (25-25) + (32-29)
CLTDadj =9
(16.2 m2 ](9)
Qwsg= .759
Qwsg= 192.095 W
Qwt = Qw + Qwsg
367.9418 W + 192.095 W
Qwt =560.0398 W
Heat Gain From Roof, Qr
From Refrigeration and air-conditioning by Stoecker and Jones (ASHRAE)
𝐴 𝐶𝐿𝑇𝐷𝑎𝑑𝑗
Qr= 𝑅𝑟
Roof Dimensions:
h= 2 m
d= width of roof canopy = 2.5 meters
w= width of room wall + 2d
= 5.40 m + 2(2.5) m = 10.4 meters
L= length of room wall + 2d
= 3.85 m + 2(2.5) m = 8.85 meters
Qr=15739.1822
FACULTY ROOM
FACTORS HEAT GAINED
OCCUPANTS 684 W
LIGHTS 73.6 W
MOTOR 54 W
MONITORS 1300 W
WINDOWS 95.593 W
DOOR 22.938 W
INFILTRATION 1338.878 W
WALL 560.0398 W
ROOF 15739.1822 W
TOTAL 19889.231 W
DEAN’S OFFICE
ND
LOCATED AT THE 2 FLOOR OF THE OLD BUILDING
Walls
Height: 3 meters
Width: 5.40 meters
Length: 3.85 meters
Area
Front and rear :( 3 m) (5.40 m) = 16.2 m²
Side: (3 m) (3.85 m) = 11.55 m²
Window
Height: 1.42 meters
Length: 1.63 meters
Area:
= (1.42 m) (1.63 m) = 2.3146 m²
Number of units: 1
Door (Wood)
OTHER SPECIFICATIONS
TIME : 1:00 PM
DESIGN OUTSIDE TEMPERATURE : 32 °C
Qoccup= 189.6 W + 84 W
Qoccup= 684 W
where:
power rating = 130 W
Power factor = 1
Qm = (130 W) (1.00) (1 units)
Qm = 130 W
Heat Gain from copiers, Qc
From engineeringtoolbox.com
Qc = (power rating) (power factor) (no. of units)
where:
power rating = 1100 W
Power factor = 1
Qc = (1100 W) (1.00) (1 units)
Qc = 1100 W
QD= 22.938 W
Heat Gain from Infiltration
From Table 4-1, , Refrigeration and Air-conditioning by Stoecker and Jones
~ Meeting and Waiting spaces
Vo = 17.5L/s Vm = 3.5L/s
E = 60%
From ASHRAE allowable air flow rate on spaces,
Vo − Vm 17.5− 3.5
Vr = = = 23.33 L/s
𝐸 0.60
V = Q = Vr + Vm
= 23.33 + 3.5
Q= 26.83L/s
Sensible Heat Gain, Qis
From ASHRAE Sensible Heat Gain through infiltration
Qis = 1.23Q(to-ti)
Qis = 1.23(26.83)(32-25)
Qis = 406.90W
Latent Heat Gain, QIL
From ASHRAE Latent Heat Gain through infiltration,
QIL = 3000Q(W o-W i)
Wo = 0.021, Wi = 0.0088
QIL = 3000(26.83)(0.021-0.0088)
QIL = 981.978 W
Total Infiltration Heat Gain,Qit
Qit = QIS + QIL
Qit = 406.90W + 981.978 W
Qit = 1338.878 W
Qw =261.42 W
The only side of the wall subjected to direct sunlight is the rear side
From table 4-15, Type E Wall, front wall facing SE, 1PM
CLTD = 6
CLTDadj = 6 + (25-25) + (32-29)
CLTDadj =9
(16.2 m2 )(9)
Qwsg= .759
Qwsg= 192.095 W
Qwt = Qw + Qwsg
261.42 W + 192.095 W
Qwt =453.515 W
Heat Gain From Roof, Qr
From Refrigeration and Air Conditioning by Stoecker and Jones(ASHRAE)
𝐴 𝐶𝐿𝑇𝐷𝑎𝑑𝑗
Qr= 𝑅𝑟
Roof Dimensions:
h= 2 m
d= width of roof canopy = 2.5 meters
w= width of room wall + 2d
= 5.40 m + 2(2.5) m = 10.4 meters
L= length of room wall + 2d
= 3.85 m + 2(2.5) m = 8.85 meters
CLTD =43
CLTDadj= 43 + (25- 25) + (32- 29)
CLTDadj= 46
(92.04)(46)
Qr= 0.269
Qr=15739.1822 W
Dean’s office
FACTORS HEAT GAINED
OCCUPANTS 273.6 W
LIGHTS 73.6 W
MOTOR 54 W
MONITORS 130 W
COPIER/PRINTER 110 W
WINDOWS 95.593 W
DOOR 22.938 W
INFILTRATION 1338.878 W
WALL 453.515 W
ROOF 15739.182 W
TOTAL 18921.3062 W
CLASSROOM
ND
LOCATED AT THE 2 FLOOR OF THE OLD BUILDING
Walls
Height: 3 meters
Width: 7.78 meters
Length: 6.85 meters
Area
Front and rear :( 3 m) (7.78 m) = 23.32 m²
Side: (3 m) (3.85 m) = 11.55 m²
Window
Front
Height: 1.42 meters
Length: 1.63 meters
Area:
= (1.42 m) (1.63 m)
= 2.3146 m²
Number of units: 2
Back
Height: 1.44 meters
Length: 3.35 meters
Area:
= (1.44 m) (3.35 m) = 4.824 m²
Number of units: 2
Door (Wood)
Height : 2.00 meters
Length: 0.87 meters
Area:
= (2.00 m) (0.87 m) = 1.74 m²
Number of Units 2
Number of Bulbs in use: 8 units
Number of Fans in Use: 4 units
Number of occupants at a time: 40 students plus 1 teacher
OTHER SPECIFICATIONS
TIME : 1:00 PM
DESIGN OUTSIDE TEMPERATURE : 32 °C
For Students:
Heat Gain per person= 100W
Sensible Heat Gain= 60%
Motor Rating = 75
Voltage = 220 V
Current = 0.3409 A
From engineeringtoolbox.com
y = -0.1007 m
x = d tan γ = (0.05 m) tan 201°
x = 0.01919 m
Sunlit Area = (h – y) (w - x)
= (1.44 m – (-0.1007 m)) (3.35 m - 0.01919 m)
Sunlit Area = 5.1318 m2
For SHGFmax, use the nearest value of 16°N Latitude for the room
location of 14°N Latitude for Santa Cruz, Laguna given by ASHRAE
SC= 1.00
QD= 22.938 W
Heat Gain from Infiltration
From Table 4-1, Refrigeration and Air-conditioning by Stoecker and Jones
~ Meeting and Waiting spaces
Vo = 17.5L/s Vm = 3.5L/s
E = 60%
From ASHRAE allowable air flow rate,
Vo − Vm 17.5− 3.5
Vr = = = 23.33 L/s
𝐸 0.60
V = Q = Vr + Vm
= 23.33 + 3.5
Q= 26.83L/s
Qw =266.5607 W
CLTD = 19
CLTDadj = 19 + (25-25) + (32-29) = 22
(24 m²)(22)
Qwsg= .759
Qwsg= 695.652 W
Qwt = Qw + Qwsg
367.9418 W + 695.652 W
Qwt =1063.5938 W
Heat Gain From Roof, Qr
𝐴 𝐶𝐿𝑇𝐷𝑎𝑑𝑗
Qr= 𝑅𝑟
Roof Dimensions:
h= 2 m
d= width of roof canopy = 2.5 meters
w= width of room wall + 2d
= 5.40 m + 2(2.5) m = 10.4 meters
L= length of room wall + 2d
= 3.85 m + 2(2.5) m = 8.85 meters
CLTD =43
CLTDadj= 43 + (25- 25) + (32- 29)
CLTDadj= 46
(92.04)(46)
Qr= 0.269
Qr=15739.1822 W
CLASSROOM
FACTORS HEAT GAINED
OCCUPANTS 2841.875 W
LIGHTS 147.2 W
MOTOR 216 W
WINDOWS 830.082 W
DOOR 45.876 W
INFILTRATION 1338.878 W
WALL 1063.5938 W
ROOF 15739.1822 W
TOTAL 22705.0598 W
BUILDING 2
Walls
Height: 3 meters
Width: 8 meters
Length: 3.84 meters
Area
Front and rear :( 3 m) (8 m) = 24 m²
Side: (3 m) (3.84 m) = 11.52 m²
Window
Front 1
Height: 1.42 meters
Length: 1.63 meters
Area:
= (1.42 m) (1.63 m) = 2.3146 m²
Front 2
Height: 1.99 meters
Length: 2.00 meters
Area:
= (1.99 m) (2.00 m) = 3.98 m²
Side
Height: 0.9 meters
Length: 2.06 meters
Area:
= (0.9 m) (2.06 m) = 1.854 m²
Door (glass)
Height : 2.00 meters
Length: 1.99 meters
Area:
= (2.00 m) (1.99 m) = 3.98 m²
OTHER SPECIFICATIONS
Time : 1:00 pm
Design inside temperature: 25°c
The room is located inside the hot kitchen which make
the outside temperature higher than the surrounding
Design outside temperature: 40 °c
It is also equipped with 2 refrigerators
CALCULATIONS OF HEAT GAIN
Heat Gain from Occupants
Maximum Number of Occupants= 4
From Table 4-7 Refrigeration and Air-conditioning by Stoecker and Jones
(Standing)
Motor Rating = 75
Voltage = 220 V
Current = 0.3409 A
From engineeringtoolbox.com
Vo = 17.5L/s Vm = 3.5L/s
From Table 4-2, Refrigeration and Air-conditioning by Stoecker and Jones
~ Building Recirculated and Fresh Air Systems
E = 60%
Vo − Vm 17.5− 3.5
Vr = = = 23.33 L/s
𝐸 0.60
V = Q = Vr + Vm
= 23.33 + 3.5
Q= 26.83L/s
Sensible Heat Gain, Qis
From ASHRAE sensible heat gain through infiltration
Qis = 1.23Q(to-ti)
Qis = 1.23(26.83)(32-25)
Qis = 406.90W
Latent Heat Gain, QIL
From ASHRAE latent heat gain through infiltration
QIL = 3000Q(W o-W i)
Wo = 0.021, Wi = 0.0088
QIL = 3000(26.83)(0.021-0.0088)
QIL = 981.978 W
Total Infiltration Heat Gain,Qit
Qit = QIS + QIL
Qit = 406.90W + 981.978 W
Qit = 1338.878 W
Qw1 =221.3439 W
For the walls that are exposed to the temperature inside the hot kitchen,
(15.9654 m²+ 12.48 m²)(40−25)
Qw2 = 0.759
Qw2 = 562.162 W
Qw = Qw1 + Qw2
Qw = 221.3439 W + 562.162 W
Qw = 378.5059 W
CLTD = 19
CLTDadj = 19 + (25-25) + (32-29)
CLTDadj = 22
(24 m²)(22)
Qwsg= .759
Qwsg= 695.652 W
COLD KITCHEN
FACTORS HEAT GAINED
OCCUPANTS 684 W
LIGHTS 73.6 W
MOTOR 108 W
REFRIGERATOR 175.8 W
WINDOWS 172.1511 W
DOOR 352.23 W
INFILTRATION 1338.878 W
WALL 1074.1579 W
TOTAL 3978.817 W
FOR THE CLASSROOMS AT THE FIRST FLOOR OF BUILDING 2
THEY ARE LOCATED ON THE TWO ENDS OF THE BUILDING AND HAS
THE SAME SPECIFICATION
ROOM 101-102
Walls
Height: 3 meters
Width: 7.9 meters
Length: 7.87 meters
Area
Front and rear :( 3 m) (7.9 m) = 23.7 m²
Side: (3 m) (7.87 m) = 23.61 m²
Window
Front
Height: 0.80 meters
Length: 1.90 meters
Area:
= (1.42 m) (1.63 m) = 2.3146 m²
No. of units: 2kkk.
Rear
Height: 1.46 meters
Length: 2.96 meters
Area:
= (1.46 m) (2.96 m) = 4.3216 m²
No. of units: 2
Door (wood)
Height : 2.08 meters
Length: 0.99 meters
Area:
= (2.08 m) (0.99 m)
= 2.059 m²
No. of units: 2
For Students:
Heat Gain per person= 100W
Sensible Heat Gain= 60%
For Teacher:
Heat Gain per person= 175W
Sensible Heat Gain= 50%
From Table 4-9 Refrigeration and Air-conditioning by Stoecker and Jones
y = 0.1037m
x = d tan γ
x = (0.05 m) tan 25°
x = 0.0233 m
Sunlit Area = (h – y) (w - x)
= (1.46 m – 0.1037 m) (2.96 m – 0.0233 m)
Sunlit Area = 3.983 m2
For SHGFmax, use the nearest value of 16°N Latitude for the room
location of 14°N Latitude for Santa Cruz, Laguna given by ASHRAE
SHGFmax= 810 BTU/ ft2 day = 106.482 W/m2
From table 4-11. Refrigeration and Air-conditioning by Stoecker and Jones
Shading Coefficient
SC= 1
From Table 4-12, Refrigeration and Air-conditioning by Stoecker and Jones
QD= 54.286 W
Vo = 17.5L/s Vm = 3.5L/s
From Table 4-2, Refrigeration and Air-conditioning by Stoecker and Jones
~ Building Recirculated and Fresh Air Systems
E = 60%
Vo − Vm 17.5− 3.5
Vr = = = 23.33 L/s
𝐸 0.60
V = Q = Vr + Vm
= 23.33 + 3.5
Q= 26.83L/s
Qw =504.8337 W
For Solar Heat Gain of Wall, Qwsg
from ASHRAE handbook of fundamentals
A(CLTDadj)
Qwsg= 𝑅𝑡
CLTD = 19
CLTDadj = 19 + (25-25) + (32-29)
CLTDadj =22
(14.6768 m²)(22)
Qwsg=
.759
Qwsg= 425.4145 W
Qwt = Qw + Qwsg
504.8337 W + 425.4145 W
Qwt =930.2482 W
CLASSROOM
OCCUPANTS 2841.875 W
LIGHTS 147.2 W
MOTOR 216 W
WINDOWS 734.762 W
DOOR 54.286 W
INFILTRATION 1338.878 W
WALL 930.248 W
TOTAL 6263.249 W
SECOND FLOOR CLASSROOMS
(they have same size as the one in first floor)
Walls
Height: 3 meters
Width: 7.9 meters
Length: 7.87 meters
Area
Front and rear :( 3 m) (7.9 m) = 23.7 m²
Side: (3 m) (7.87 m) = 23.61 m²
Window
Front
Height: 0.80 meters
Length: 1.90 meters
Area:
= (1.42 m) (1.63 m)
= 2.3146 m²
No. of units: 2
Rear
Height: 1.46 meters
Length: 2.96 meters
Area:
= (1.46 m) (2.96 m)
= 4.3216 m²
No. of units: 2
Door (wood)
Height : 2.08 meters
Length: 0.99 meters
Area:
= (2.08 m) (0.99 m)
= 2.059 m²
No. of units: 2
For Students:
Heat Gain per person= 100W
Sensible Heat Gain= 60%
For Teacher:
Heat Gain per person= 175W
Sensible Heat Gain= 50%
From Table 4-9 Refrigeration and Air-conditioning by Stoecker and Jones
For Students:
Qp= 100W (1-0.79)
Qp= 21W
Qol= 21W x 40 x 1
Qol= 840W
For Teacher:
Qp= 175W (1-0.79)
Qp= 36.75 W
Qol= 36.75 x 1 x 1
Qol= 36.75 W
Qol total= 840 + 36.75
Qol total= 876.75 W
For Students:
Qoccup= 1896W + 840W
Qoccup= 2736W
For Teacher:
Qoccup= 69.125 W + 36.75 W
Qoccup= 105.875 W
y = 0.1038 m
x = d tan γ = (0.05 m) tan 25°
x = 0.0233 m
Sunlit Area = (h – y) (w - x)
= (1.46 m – 0.1038m) (2.96 m – 0.0233 m)
Sunlit Area = 3.983 m2
For SHGFmax, use the nearest value of 16°N Latitude for the room
location of 14°N Latitude for Santa Cruz, Laguna given by ASHRAE
SHGFmax= 810 BTU/ ft2 day = 106.482 W/m2
SC= 1
From Table 4-12, Refrigeration and Air-conditioning by Stoecker and Jones
~13:00 Window facing SE
CLF= 0.33
~13:00 Window facing NW
CLF= 0.22
FOR THE BACK WINDOWS,
Qsgb= (106.482) (1)(0.22) (3.983 m2) ( 2)
Qsgb= 186.612 W
Ad(to−ti)
QD= 𝑅𝑡
QD= 54.286 W
Heat Gain from Infiltration
From Table 4-1, Refrigeration and Air-conditioning by Stoecker and Jones ~
Meeting and Waiting spaces
Vo = 17.5L/s Vm = 3.5L/s
From Table 4-2, Refrigeration and Air-conditioning by Stoecker and Jones ~
Building Recirculated and Fresh Air Systems
E = 60%
Vo − Vm 17.5− 3.5
Vr = = = 23.33 L/s
𝐸 0.60
V = Q = Vr + Vm = 23.33 + 3.5
Q= 26.83L/s
Sensible Heat Gain, Qis
Qis = 1.23Q(to-ti)
Qis = 1.23(26.83)(32-25)
Qis = 406.90W
Latent Heat Gain, QIL
QIL = 3000Q(W o-W i)
Wo = 0.021, Wi = 0.0088
QIL = 3000(26.83)(0.021-0.0088)
QIL = 981.978 W
Total Infiltration Heat Gain,Qit
Qit = QIS + QIL
Qit = 406.90W + 981.978 W
Qit = 1338.878 W
Heat Gain from Walls
(one side of the room is attached to the dean’s office)
For Transmission:
𝐴(𝑡𝑜−𝑡𝑖)
Qw = 𝑅𝑡
Qw =504.8337 W
For Solar Heat Gain of Wall, Qwsg
A(CLTDadj)
Qwsg= 𝑅𝑡
Qwsg= 425.4145 W
Qwt = Qw + Qwsg
504.8337 W + 425.4145 W
Qwt =930.2482 W
Heat Gain From Roof, Qr
𝐴 𝐶𝐿𝑇𝐷𝑎𝑑𝑗
Qr= 𝑅𝑟
Roof Dimensions:
h= 2 m
d= width of roof canopy = 2.5 meters
w= width of room wall + 2d
= 7.90 m + 2(2.5) m = 12.9 meters
L= length of room wall + 2d
= 7.87 m + 2(2.5) m = 12.87 meters
(166.023)(46)
Qr= 0.269
Qr=28390.550 W
ROOM 201 AND 206
OCCUPANTS 2841.875 W
LIGHTS 147.2 W
MOTOR 216 W
WINDOWS 770.762 W
DOOR 54.286 W
INFILTRATION 1338.878 W
WALL 930.2482 W
ROOF 28390.550 W
TOTAL 34689.799 W
FOR THE ROOMS 202,203,204,205
Walls
Height: 3 meters
Width: 7.9 meters
Length: 7.87 meters
Area
Front and rear :( 3 m) (7.9 m) = 23.7 m²
Side: (3 m) (7.87 m) = 23.61 m²
Window
Front
Height: 0.80 meters
Length: 1.90 meters
Area:
= (1.42 m) (1.63 m) = 2.3146 m²
No. of units: 2
Rear
Height: 1.46 meters
Length: 2.96 meters
Area:
= (1.46 m) (2.96 m) = 4.3216 m²
No. of units: 2
Door (wood)
Height : 2.08 meters
Length: 0.99 meters
Area:
= (2.08 m) (0.99 m) = 2.059 m²
No. of units: 2
For Students:
Heat Gain per person= 100W
Sensible Heat Gain= 60%
For Teacher:
Heat Gain per person= 175W
Sensible Heat Gain= 50%
From Table 4-9 Refrigeration and Air-conditioning by Stoecker and Jones
y = 0.1038 m
x = d tan γ
x = (0.05 m) tan 25°
x = 0.0233 m
Sunlit Area = (h – y) (w - x)
= (1.46 m – 0.1038 m) (2.96 m – 0.0233 m)
Sunlit Area = 3.983 m2
For SHGFmax, use the nearest value of 16°N Latitude for the room
location of 14°N Latitude for Santa Cruz, Laguna given by ASHRAE
SHGFmax= 810 BTU/ ft2 day = 106.482 W/m2
From table 4-11, Refrigeration and Air-conditioning by Stoecker and Jones
SC= 1
From Table 4-12, Refrigeration and Air-conditioning by Stoecker and Joneas
QD= 54.286 W
Heat Gain from Infiltration
From Table 4-1, Refrigeration and Air-conditioning by Stoecker and Jones ~
Meeting and Waiting spaces
Vo = 17.5L/s Vm = 3.5L/s
From Table 4-2, Refrigeration and Air-conditioning by Stoecker and Jones ~
Building Recirculated and Fresh Air Systems
E = 60%
Vo − Vm 17.5− 3.5
Vr = = = 23.33 L/s
𝐸 0.60
V = Q = Vr + Vm = 23.33 + 3.5
Q= 26.83L/s
Sensible Heat Gain, Qis
Qis = 1.23Q(to-ti)
Qis = 1.23(26.83)(32-25)
Qis = 406.90W
Latent Heat Gain, QIL
QIL = 3000Q(W o-W i)
Wo = 0.021, Wi = 0.0088
QIL = 3000(26.83)(0.021-0.0088)
QIL = 981.978 W
Total Infiltration Heat Gain,Qit
Qit = QIS + QIL
Qit = 406.90W + 981.978 W
Qit = 1338.878 W
Heat Gain from Walls
(one side of the room is attached to the dean’s office)
For Transmission:
𝐴(𝑡𝑜−𝑡𝑖)
Qw = 𝑅𝑡
Qw =287.0867 W
For Solar Heat Gain of Wall, Qwsg
A(CLTDadj)
Qwsg= 𝑅𝑡
Qwsg= 425.4145 W
Qwt = Qw + Qwsg
287.0867 W + 425.4145 W
Qwt = 712.5012 W
Heat Gain From Roof, Qr
𝐴 𝐶𝐿𝑇𝐷𝑎𝑑𝑗
Qr= 𝑅𝑟
Roof Dimensions:
h= 2 m
d= width of roof canopy = 2.5 meters
w= width of room wall + 2d
= 7.90 m + 2(2.5) m = 12.9 meters
L= length of room wall + 2d
= 7.87 m + 2(2.5) m = 12.87 meters
Qr=28390.550 W
202,203,204,205 CLASSROOM
FACTORS HEAT GAINED
OCCUPANTS 2841.875 W
LIGHTS 147.2 W
MOTOR 216 W
WINDOWS 770.762 W
DOOR 54.286 W
INFILTRATION 1338.878 W
WALL 712.501 W
ROOF 28390.550 W
TOTAL 34472.644 W