Contents
1 Notes on documentation. . . . . . . . . . 4 5 Commissioning . . . . . . . . . . . . . . . . 22 EN
1.1 Associated documents . . . . . . . . . . . . . . . . . 4
1.2 CE labelling . . . . . . . . . . . . . . . . . . . . . . . . . . 4 6 Operation . . . . . . . . . . . . . . . . . . . . . 23
1.3 Retention of documents . . . . . . . . . . . . . . . . 4 6.1 Control using the Basic controller . . . . . . 23
1.4 Symbols used . . . . . . . . . . . . . . . . . . . . . . . . 4 6.1.1 Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
6.1.2 Operating and error display. . . . . . . . . . . . . .24
2 Safety instructions. . . . . . . . . . . . . . . 4 6.1.3 Test mode for the Basic controller . . . . . . . . .25
6.1.4 Setting the temperature . . . . . . . . . . . . . . . . .25
3 Device description . . . . . . . . . . . . . . . 5 6.1.5 Resetting the Basic controller . . . . . . . . . . . .25
3.1 Functional description . . . . . . . . . . . . . . . . . 5 6.2 Control using the Comfort controller . . . . 26
3.1.1 How it works . . . . . . . . . . . . . . . . . . . . . . . . . . 5 6.2.1 Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
3.1.2 Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 6.2.2 Launching test mode . . . . . . . . . . . . . . . . . . .26
3.1.3 Bus mode (Comfort controller only) . . . . . . . . 5 6.2.3 General programming information . . . . . . . . .26
3.1.4 Safety equipment . . . . . . . . . . . . . . . . . . . . . . 6 6.2.4 Editable parameters. . . . . . . . . . . . . . . . . . . .27
3.1.5 Condensation . . . . . . . . . . . . . . . . . . . . . . . . . 6 6.2.5 Programming overview . . . . . . . . . . . . . . . . .28
3.1.6 Filter mats . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 6.2.6 Defining system messages
3.1.7 Door limit switch . . . . . . . . . . . . . . . . . . . . . . . 6 for evaluation . . . . . . . . . . . . . . . . . . . . . . . . .29
3.1.8 Additional interface X3 . . . . . . . . . . . . . . . . . . 7 6.2.7 Setting the master-slave identifier . . . . . . . . .30
3.2 Proper usage . . . . . . . . . . . . . . . . . . . . . . . . . 7 6.2.8 Evaluating system messages. . . . . . . . . . . . .30
3.3 Scope of supply . . . . . . . . . . . . . . . . . . . . . . 7 6.2.9 Resetting the Comfort controller . . . . . . . . . .32

4 Assembly and connection . . . . . . . . 7 7 Inspection and maintenance. . . . . . 32


4.1 Choosing the installation site . . . . . . . . . . . 7 7.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.2 Assembly instructions . . . . . . . . . . . . . . . . . 7 7.1.1 Compressed air cleaning
4.2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 SK 3304.xxx, SK 3305.xxx . . . . . . . . . . . . . . .32
4.2.2 Layout of the electronic components 7.1.2 Compressed air cleaning
in the enclosure. . . . . . . . . . . . . . . . . . . . . . . . 8 SK 3328.xxx, SK 3329.xxx, SK 3332.xxx . . . .36
4.3 Fitting the cooling unit . . . . . . . . . . . . . . . . . 8
4.3.1 Cutting out the enclosure . . . . . . . . . . . . . . . . 9 8 Storage and disposal. . . . . . . . . . . . 41
4.3.2 External mounting of the cooling unit . . . . . . . 9
4.3.3 Partial internal mounting 9 Technical specifications . . . . . . . . . 41
of the cooling unit . . . . . . . . . . . . . . . . . . . . . . 9
4.3.4 Full internal mounting of the cooling unit . . . 11 10 List of spare parts . . . . . . . . . . . . . . 45
4.4 Connecting the condensate discharge . . . 11
4.5 Notes on electrical installation . . . . . . . . . 12 11 Appendix:
4.5.1 Connection data . . . . . . . . . . . . . . . . . . . . . . 12 Cut-out and hole sizes . . . . . . . . . . . 49
4.5.2 Overvoltage protection 11.1 Dimensions for external mounting . . . . . . 49
and supply line load . . . . . . . . . . . . . . . . . . . 12 11.2 Dimensions for partial
4.5.3 Three-phase devices . . . . . . . . . . . . . . . . . . 12 internal mounting . . . . . . . . . . . . . . . . . . . . 50
4.5.4 Door limit switch . . . . . . . . . . . . . . . . . . . . . . 12 11.3 Dimensions for full internal mounting . . . 51
4.5.5 Notes on the flicker standard . . . . . . . . . . . . 12
4.5.6 Potential equalisation . . . . . . . . . . . . . . . . . . 12
4.6 Carrying out the electrical installation . . . 13
4.6.1 Bus connection
(only in conjunction with several units with
a Comfort controller) . . . . . . . . . . . . . . . . . . . 13
4.6.2 Connection X3 for serial interface. . . . . . . . . 13
4.6.3 Installing the power supply . . . . . . . . . . . . . . 14
4.7 Finalising assembly . . . . . . . . . . . . . . . . . . 22
4.7.1 Installing the filter media . . . . . . . . . . . . . . . 22
4.7.2 Fitting the cooling unit. . . . . . . . . . . . . . . . . . 22
4.7.3 Setting the filter mat monitor
(only with Comfort controller) . . . . . . . . . . . . 22

RITTAL cooling unit assembly and operating instructions 3

Downloaded from www.Manualslib.com manuals search engine


1 Notes on documentation
1 Notes on documentation 2 Safety instructions
EN These assembly instructions are aimed at tradesper-
sons who are familiar with assembly and installation
Please observe the following general safety instruc-
tions when assembling and operating the unit:
of the cooling unit, and at trained specialists who are – Assembly, installation and servicing may only be
familiar with operation of the cooling unit. performed by properly trained specialists.
– Screw the enclosure to the floor to prevent it from
1.1 Associated documents tipping over when the cooling unit is installed.
There are two sets of instructions for the unit types – Do not obstruct the air inlet and air outlet of the
described here: cooling unit inside and outside the enclosure
– Assembly and installation instructions enclosed (see also section 4.2.2).
with the unit in the form of a paper document – To ensure problem-free opening and closing of
– Assembly, installation and operating instructions the enclosure door, use a ride-up door roller (refer
enclosed with the unit in the form of a PDF file to the accessories in the RITTAL Catalogue).
(Adobe Acrobat) on CD-ROM This raises the door slightly and balances out the
We cannot accept any liability for damage associat- weight of the cooling unit, to prevent buckling of
ed with failure to observe these instructions. Where the door and associated seal problems.
applicable, the instructions for any accessories used – The heat loss of the components installed in the
also apply. enclosure must not exceed the specific useful
cooling output of the cooling unit.
1.2 CE labelling – When transporting the enclosure with the cooling
The declaration of conformity is supplied with the unit unit externally mounted, always use an additional
as a separate document. shipping brace to support the cooling unit.
– The cooling unit must always be transported in an
1.3 Retention of documents upright position.
These instructions and all associated documents – Use only original spare parts and accessories.
constitute an integral part of the product. They must – Do not make any changes to the cooling unit other
be given to the plant operator. The plant operator is than those described in these instructions or asso-
responsible for storage of the documents so they are ciated instructions.
readily available when needed. – Risk of burn injuries! For cooling units with auto-
matic condensate evaporation, the surface of the
1.4 Symbols used thermal element will get very hot during operation,
Please observe the following safety instructions and and will remain so for some time afterwards.
other notes in this guide: – The mains connector of the cooling unit must only
Symbol for an instructed action: be connected and disconnected with the system
• The bullet point indicates that you should perform de-energised. Connect the pre-fuse specified on
an action. the rating plate.
Safety and other instructions:

Danger!
Immediate danger to life and limb!

Caution!
Potential threat to the product
and its environment.

Note:
Useful information
and special features.

4 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


3 Device description
3 Device description into the hermetically sealed cooling circuit provides
effective protection against moisture, acid, dirt
Depending on the model chosen, your cooling unit
may vary in appearance from the illustrations con- particles, and foreign bodies within the cooling EN
tained in these instructions. However, the functions circuit.
are identical in principle. Condenser (3)
PSAH
8 pressure-
operated
switch
9 Condenser fan
1 Compressor Filter dryer (5)
(2)
2
10 External circuit
3
Internal circuit
Temperature
4 control
5 11
Evaporator coil (1)
6 12 Expansion valve (4)
Evaporator fan
13
Fig. 2: Cooling circuit
7
In the evaporator coil (1), the liquid coolant is con-
14
verted to a gaseous state. The energy needed for
this purpose is taken from the enclosure air in the
form of heat, which has the effect of cooling the
15 enclosure air. In the compressor (2), the coolant is
16 heavily compressed, so that it achieves a higher
Fig. 1: Device description temperature inside the condenser (3) than the ambi-
ent air. This means that excess heat may be emitted
Legend
to the ambient air via the surface of the condenser,
1 Blind nut
2 Evaporator fan as a result of which the temperature of the coolant
3 Electrical wiring plan drops and it is converted back into liquid. It is re-
4 X2 master-slave connection injected into the evaporator coil via a thermostatic
5 X3 optional serial interface expansion valve (4), which causes it to cool down
6 X1 terminal strip further, and is then once again able to absorb the
7 Air outlet hole energy from the enclosure air in the evaporator coil.
8 Front half of the enclosure The whole cycle begins again.
9 Rear half of the enclosure
10 Louvred grille for air outlet 3.1.2 Control
11 Display RITTAL enclosure cooling units are fitted with a con-
12 Infill panel troller for setting the functions of the cooling unit.
13 Louvred grille for air inlet
Depending on the design, this is either a Basic con-
14 Rating plate
15 Condensate discharge
troller (display of the operating status via LED) or a
16 Dispatch bag Comfort controller (display plus extended functions,
see chapter “6 Operation”, page 23).
3.1 Functional description
3.1.3 Bus mode (Comfort controller only)
Enclosure cooling units are designed to dissipate
The serial unit interface X2 allows you to create a bus
heat from enclosures by cooling the air inside the
connection with up to ten cooling units using the
enclosure and so protect the temperature-sensitive
master-slave cable (shielded, four-wire cable, Model
components. They are built into the side or rear
No. SK 3124.100). This allows you to implement the
panel or into the door of the enclosure.
following functions:
3.1.1 How it works – Parallel unit control (the cooling units in the network
The cooling unit (compression refrigeration system) can be switched on and off simultaneously)
is comprised of four main components (cf. Fig. 2): – Parallel door status message (“door open”)
the evaporator (1), the coolant compressor (2), the – Parallel collective fault message
condenser (3), and the control or expansion valve Data is exchanged via the master-slave connection.
(4), which are connected by suitable pipework. This During commissioning, assign an address to each
circuit is filled with a readily boiling substance, the unit that also includes the identifier “master” or
refrigerant. Coolant R134a (CH2FCF3) is chlorine- “slave”.
free. Its ozone destruction potential is 0, making it
very eco-friendly. A filter dryer (5) which is integrated

RITTAL cooling unit assembly and operating instructions 5

Downloaded from www.Manualslib.com manuals search engine


3 Device description
3.1.4 Safety equipment 3.1.6 Filter mats
– In the cooling cycle, the cooling unit has a tested The cooling unit condenser is finished all over with a
EN pressure-operated switch to EN 12 263 which is dirt-repelling, easy-to-clean RiNano coating. In many
set to maximum PS (admissible pressure); this cases, therefore, the use of filter media is unneces-
operates via an automatic reset device whenever sary, particularly in the case of dry dusts.
the pressure drops again. For dry, coarse dust and lint in the ambient air, we
– Temperature monitoring prevents the evaporator recommend installing an additional PU foam filter
coil from icing over. If there is a risk of icing, the mat (available as an accessory) in the cooling unit.
compressor switches itself off and automatically Depending on the incidence of dust, you will need
switches itself back on again at higher tempera- to replace the filter from time to time.
tures. For air containing oil condensation, we recommend
– The refrigerant compressor and the fans are the use of metal filters (also available as an accesso-
equipped with thermal winding shields to protect ry). These may be cleaned with suitable detergents
against excess current and excess temperatures. and reused.
– In order to allow a reduction of pressure inside the Function of the filter mat monitor:
compressor and hence a safe restart, once it has Dirt on the filter mat is automatically determined by
been switched off (e.g. upon reaching the set tem- measuring the temperature difference in the external
perature via the door limit switch function or via de- circuit of the cooling unit. As the level of filter mat soil-
energising), the device will switch back on with a ing rises, the temperature difference will increase.
delay of 180 seconds. The nominal value of the temperature difference in
– The device has floating contacts on the connection the external circuit adapts automatically to the rele-
pins (terminals 3 – 5), via which system messages vant operating points in the performance diagrams.
from the device may be polled, e.g. using a PLC Hence there is no need to readjust the nominal value
(1x change-over contact Basic controller, 2 x nor- for different operating points of the cooling unit.
mally open contacts Comfort controller).
3.1.7 Door limit switch
3.1.5 Condensation The cooling unit may be operated with a floating door
At high levels of humidity and low temperatures in- limit switch connected. The door limit switch is not in-
side the enclosure, condensation may form on the cluded with the supply (available as an accessory,
evaporator coil. Model No. PS 4127.000).
The cooling units (except SK 3302.xxx, SK 3303.xxx The door limit switch function causes the fans and
and SK 3361.xxx) have automatic, electric conden- the compressor in the cooling unit to be switched off
sate evaporation. The thermal component used for after approximately 15 seconds when the enclosure
this purpose is based on self-regulating PTC tech- door is opened (contacts 1 and 2 closed). This pre-
nology. Condensate arising on the evaporator coil vents the formation of condensation inside the enclo-
is collected in a tank in the external circuit of the cool- sure while the enclosure door is open. In order to
ing unit, and partially evaporated via the airflow. prevent damage to the unit, it is equipped with an
When the water level rises, the water enters the PTC ON delay: The evaporator fan cuts back in with a de-
thermal component and is evaporated (through-flow lay of approximately 15 seconds after the door has
heater principle). The water vapour streams out of been closed, while the condenser fan and compres-
the cooling unit with the airflow from the external fan. sor switch on after approximately 3 minutes.
The PTC thermal component is permanently con-
nected and has no switchpoint. It is protected Note:
against short-circuits with miniature fuses (F1.1,
– No external voltage must be applied to
F1.2). If the fuse has tripped, any condensation is
the door contacts (terminals 1 and 2).
drained off via the safety overflow.
– For Basic controller cooling units with
For unit types SK 3302.xxx, SK 3303.xxx and
230/115 V and 400 V/2-phase connec-
SK 3361.xxx, the condensation is routed downwards
tion, the evaporator fan remains opera-
out of the unit via a drain pipe on the evaporator coil
tional even with the door open.
divider panel. For this purpose, a hose must be con-
nected to the condensate nozzle (see “4.4 Connect-
ing the condensate drain”, page 11). External con-
densate evaporators are available as accessories
for these unit types (refer also to the accessories in
the RITTAL Catalogue).

6 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


4 Assembly and connection
3.1.8 Additional interface X3 4 Assembly and connection
Note: 4.1 Choosing the installation site
EN
The electrical signals at the interface are of When choosing the installation site for the enclosure,
an extra-low voltage (not extra-low safety please observe the following:
voltages to EN 60 335). – The site for the enclosure, and hence the arrange-
An additional interface card may be connected to ment of the cooling unit, must be carefully selected
the 9-pole SUB-D connector X3 in order to incor- so as to ensure good ventilation (distances bet-
porate the cooling unit into higher-level monitoring ween units and distances between the unit and the
systems (available as an accessory, interface card wall must be at least 200 mm in each case).
Model No. SK 324.200). – The cooling unit must be installed and operated in
a vertical position (maximum deviation: 2°).
3.2 Proper usage – The site must be free from excessive dirt and
RITTAL enclosure cooling units were developed and moisture.
designed in accordance with the state-of-the-art and – The ambient temperature must not exceed 55°C.
the recognised rules governing technical safety. – It must be possible to fit a condensate discharge
Nevertheless, if used improperly, they may pose a (see “4.4 Connecting the condensate discharge”,
threat to life and limb or cause damage to property. page 11).
The unit is only intended for cooling enclosures. Any – The mains connection data as stated on the rating
other use is deemed improper. The manufacturer will plate of the unit must be guaranteed.
not be liable for any damages caused as a result of
improper use, or for incorrect assembly, installation 4.2 Assembly instructions
or use. All risk is borne solely by the user.
Proper usage also includes the observation of all 4.2.1 General
valid documents and compliance with the inspection – Check the packaging carefully for signs of damage.
and servicing conditions. Traces of oil on damaged packaging are an indi-
cation of refrigerant loss and leakages. Packaging
3.3 Scope of supply damage may be the cause of a subsequent func-
The unit is supplied in a packaging unit in a fully tional failure.
assembled state. – The enclosure must be sealed on all sides (IP 54).
Please check the delivery for completeness: Increased condensation will occur if the enclosure
is not airtight.
Qty. Description
– In order to avoid excessive condensation inside
1 Enclosure cooling unit the enclosure, we recommend installing a door
1 Dispatch bag: limit switch (e.g. PS 4127.000) which deactivates
1 – Assembly and installation instructions the cooling unit when the enclosure door is opened
1 – Assembly, installation and operating (see “3.1.7 Door limit switch”, page 6).
instructions on CD-ROM
1 – Self-adhesive tape
1 – Connector X1
4 – 10 – Threaded rods
1 – Declaration of conformity
– Nuts, washers
1 Drilling template
Tab. 1: Scope of supply

RITTAL cooling unit assembly and operating instructions 7

Downloaded from www.Manualslib.com manuals search engine


4 Assembly and connection
4.2.2 Layout of the electronic components x
in the enclosure
EN
Caution!
Risk of condensation!
When arranging the components inside
the enclosure, please ensure that the
cold airflow from the cooling unit is not
directed at active components. Please
also ensure that the cold airflow is not
directed at the warm exhaust airflow
from active components such as con-
verters. This may lead to an air short-
circuit and therefore prevent adequate
climate control, or may even cause the
cooling unit’s internal safety devices to Fig. 4: Air circulation inside the enclosure
cease cooling operation.
4.3 Fitting the cooling unit
The enclosure cooling unit may optionally be exter-
nally mounted on the enclosure (1), partially internal-
ly mounted (2) or fully internally mounted (3):

1 2 3

Fig. 3: Never direct the cold airflow at active components


Fig. 5: Installation method
Air diversion components are available as accesso-
ries – please refer to the RITTAL catalogue “System To this end, cut the side panel or door of the enclo-
climate control”. sure as per the drilling template included with the
It is important to ensure even air circulation inside the supply, and drill the relevant holes.
enclosure. Under no circumstances should air inlet
and outlet openings be obstructed, otherwise the Note:
cooling performance of the unit will be reduced. Units of type SK 3302.xxx can only be either
Ensure the distance “x” (see Fig. 4) from electronic externally mounted or fully internally moun-
components and other installed enclosures so that ted.
the required air circulation is not obstructed and pre- Units of type SK 3332.xxx can only be either
vented. externally mounted or partially internally
mounted.
For mounting the units SK 3328.xxx,
SK 3329.xxx and SK 3332.xxx in the TS side
panel or rear panel, we recommend the use
of enclosure panel fasteners TS 8800.071
(see RITTAL Catalogue).

8 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


4 Assembly and connection
4.3.1 Cutting out the enclosure
• Stick the supplied drilling template onto the side
panel or door of the enclosure using adhesive EN
tape.
There are dimensioning lines on the drilling template
to suit the various installation options for your cooling
unit.
• Using the dimension drawings (see Appendix),
identify the valid lines and dimensions for your
installation type on the drilling template.

Risk of injury! Fig. 8: Secure the cooling unit


(SK 3302.1xx “external mounting” only)
Carefully deburr all drilled holes and
cut-outs to prevent injuries caused by Only for SK 3302.xxx:
sharp edges. • Before installing, remove the four screws as shown.
• Mark, drill and deburr the holes.
• Make the cut-outs including the line width as per
the drilling template. 4x
Deburr the cut-outs.

4.3.2 External mounting of the cooling unit


• Cut the supplied sealing tape to the correct length
and stick it carefully along the back of the unit so
that no gaps are left at the joints.

Fig. 9: Only for SK 3302.xxx: Remove the four screws

4.3.3 Partial internal mounting of the cooling unit


• Carefully remove the louvred grille and, where
Fig. 6: Attach the sealing tape applicable, the infill panel, from the enclosure by
pulling forwards.
• Screw the supplied grub screws into the blind nuts
on the rear of the unit. • Carefully disconnect the connector from the rear of
the display and gently push it inwards through the
• Secure the unit using the supplied washers and
cable gland.
nuts.

Fig. 7: Secure the cooling unit


(all models except SK 3302.1xx)

Fig. 10: Remove the louvred grille & disconnect the display
RITTAL cooling unit assembly and operating instructions 9

Downloaded from www.Manualslib.com manuals search engine


4 Assembly and connection
Risk of damage!
EN Stability of the cooling unit is only
guaranteed in its assembled state.
Brace the rear enclosure half to prevent
it from falling over before removing the
front enclosure half.
• Loosen the four nuts on the front enclosure half and
pull the enclosure forwards by approx. 5 cm.
• Loosen the flat-pin connectors of the PE conductor
between the two enclosure halves.
• Disconnect the fan connection.
• Remove the front enclosure tray completely.

Fig. 13: Secure the cooling unit


• Connect the fan connector and PE conductor.
• Mount the front enclosure tray using the washers
and nuts.

Fig. 11: Remove the cover


• Remove the four spacer bolts.
• Cut the supplied sealing tape to the correct length
and stick it carefully along the inside of the rear
enclosure half so that no gaps are left at the con-
nection points.

Fig. 14: Connect the display connector


• Carefully connect the display connector.
• Push the louvred grille and, where applicable,
the infill panel, onto the enclosure.

Fig. 12: Attach the sealing tape

• Push the rear enclosure half into the mounting cut-


out and secure it with the four spacer bolts.
• Push the display cable through the cable gland of
the front enclosure half.

10 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


4 Assembly and connection
4.3.4 Full internal mounting of the cooling unit
• Carefully remove the louvred grille and the infill
panel from the enclosure by pulling forwards. EN
• Carefully disconnect the connector from the rear of
the display.

Fig. 17: Secure the cooling unit


• Where necessary, additionally secure the unit
using the supplied mounting plates as shown in
Fig. 17.
• Carefully connect the display connector.
Fig. 15: Remove the louvred grille and disconnect • Push the louvred grille and, where applicable,
the display
the infill panel, onto the enclosure.
• Cut the supplied sealing tape to the correct length
and stick it carefully along the front enclosure half 4.4 Connecting the condensate discharge
so that no gaps are left at the connection points. Unit types SK 3302.xxx, SK 3303.xxx and
SK 3361.xxx support the installation of a condensate
discharge hose (Ø 1/2˝).
The condensate discharge
– must be laid with a suitable and constant gradient
(no siphoning)
– must be laid without kinks
– must not have a reduced cross-section if extended.
The condensate hose is available as an accessory
(refer also to Accessories in the RITTAL Catalogue).

Fig. 16: Attach the sealing tape


• Loosen the four nuts and washers from the front
enclosure half.
• Push the unit into the mounting cut-out from the
inside of the enclosure, and secure it to the en-
closure from the outside using the washers and
nuts.

Fig. 18: Connecting the condensate discharge


• Connect a suitable hose to the condensate nozzle
and secure using a hose clip.
• Lay the condensate hose into a pay-off or into the
external condensate evaporator (refer to accesso-
ries in the RITTAL Catalogue).

RITTAL cooling unit assembly and operating instructions 11

Downloaded from www.Manualslib.com manuals search engine


4 Assembly and connection
4.5 Notes on electrical installation 4.5.3 Three-phase devices
– The three-phase version of models SK 3304.xxx,
EN When performing the electrical installation, it is im-
portant to observe all valid national and regional reg- SK 3305.xxx, SK 3328.xxx, SK 3329.xxx and
ulations as well as the provisions of the responsible SK 3332.xxx must be connected to a TN network
power supply company. Electrical installation must with star earthing via a circuit-breaker for plant
only be carried out by a qualified electrician who is re- protection (current setting as per the rating plate).
sponsible for compliance with the existing standards Three-phase units with special voltages must be
and regulations. protected with a circuit-breaker for transformer
protection (category AC-3) as per the rating plate.
4.5.1 Connection data – Units designed for three phase 400/460 V feature
– The connected voltage and frequency must additional monitoring of the rotary field or the
correspond to the values stated on the rating plate. absence of a phase. If the rotary field is incorrect or
– The cooling unit must be connected to the mains a phase is absent, the unit will not run.
via an all-pin isolating device, which ensures at
least 3 mm contact opening when switched off. 4.5.4 Door limit switch
– No additional temperature control may be connec- – Each door limit switch must only be assigned to one
ted upstream of the unit at the supply end. cooling unit.
– Install the pre-fuse specified on the rating plate – Several door limit switches may be connected in
to protect the cable and equipment from short- parallel and operated on one cooling unit.
circuits. – The minimum cross-section for the connection
– The mains connection must ensure low-noise cable is 0.3 mm2 for a cable length of 2 m.
potential equalisation. – The line resistance to the door limit switch must not
exceed a maximum of 50 Ω.
4.5.2 Overvoltage protection and supply line – The door limit switch only supports a floating
load connection; no external voltages.
– The unit does not have its own overvoltage pro- – The contact of the door limit switch must be closed
tection. Measures must be taken by the operator at when the door is open.
the supply end to ensure effective lightning and The safety extra-low voltage for the door limit switch is
overvoltage protection. The mains voltage must not provided by the internal power pack: Current
exceed a tolerance of ±10%. approx. 30 mA DC.
– In accordance with IEC 61 000-3-11, the unit is • Connect the door limit switch to terminals 1 and 2 of
intended solely for use at sites with a continuous the connector.
current-carrying capacity (incoming mains power
supply) of more than 100 A per phase and with 4.5.5 Notes on the flicker standard
a supply voltage of 400/230 V. If necessary, the The flicker limits specified in standard EN 61 000-3-3
power supply company must be consulted to or -3-11 are adhered to, provided the supply im-
ensure that the continuous current-carrying capa- pedance is less than approx. 1.5 Ω.
city at the point of connection to the public grid is Where necessary, the unit operator should measure
sufficient for connection of such a unit. the connected impedance or consult the responsible
– The fans and compressors in single- and three- power supply company. If there is no way of influenc-
phase units are intrinsically safe (thermal winding ing the supply impedance and sensitive installed
protection). The same also applies to the transfor- components (e.g. BUS) are subjected to interference,
mer versions of types SK 3304.110, SK 3304.510, a line reactor or starting-current limiting device should
SK 3305.110, SK 3305.510, SK 3328.110, be connected upstream of the cooling unit to restrict
SK 3328.510, SK 3329.110 and SK 3329.510 the startup current of the cooling unit.
and to special-voltage units which are likewise
equipped with a transformer. 4.5.6 Potential equalisation
– Install the slow pre-fuse specified on the rating RITTAL recommends connecting a conductor with a
plate (miniature circuit-breaker with “K” charac- nominal cross-section of at least 6 mm2 to the poten-
teristic, circuit-breaker for plant or transformer tial equalisation connection point on wall-mounted
protection) to protect the cable and equipment from cooling units, and incorporating it into the existing po-
short-circuits. Select a suitable circuit-breaker in tential equalisation system.
accordance with the information specified on the According to the standard, the PE conductor in the
rating plate: Set it to the minimum specified value. mains connection cable is not classified as an equi-
This will achieve the best short-circuit protection for potential bonding conductor.
cables and equipment.
Example: Specified setting range 6.3 – 10 A;
set to 6.3 A.

12 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


4 Assembly and connection
4.6 Carrying out the electrical installation 4.6.2 Connection X3 for serial interface
The interface card (Model No. SK 3124.200) may be
4.6.1 Bus connection connected to X3. This is used to evaluate system EN
(only in conjunction with several units messages in a PLC, for remotely setting parameters
with a Comfort controller) and monitoring, or for integration into the facility
When using several cooling units, the serial device management system.
interface X2 can be used to connect up to ten cool-
ing units with the bus cable (Model No. SK 3124.100).

Note:
The electrical signals at the X2 interface are
of an extra-low voltage (not extra-low safety
voltages to EN 60 335-1).
When interconnecting, please note the following:
– De-energise the cooling units to be connected.
– Ensure proper electrical insulation.
– Make sure the cables are not laid in parallel to
power lines.
– Make sure that the lines are short.

Caution!
Regarding the last slave unit in the
group, do not, under any circumstances,
connect the remaining socket of the
Y cable SK 3124.100 into interface X3
of the cooling unit!

RITTAL cooling unit assembly and operating instructions 13

Downloaded from www.Manualslib.com manuals search engine


4 Assembly and connection

EN CMC

I/O unit

RTT Adr.: 09 RTT Adr.: 11 RTT Adr.: 12 RTT Adr.: 19


Master Slave Slave Slave

X1 X1 X1 X1

X2 X3 X2 X3 X2 X3 X2 X3

St. X2 X3 Bu. St. X2 St. X2 St. X2

X2 X2 X2 X2 X2
Bu. St. Bu. St. Bu.
3

Fig. 19: Connection example: Master-slave operation


Legend
1 Serial interface (Model No. SK 3124.200) X2 Master-slave connection Sub-D, 9-pole
2 Serial interface cable X3 Serial interface Sub-D, 9-pole
3 Master-slave bus cable (Model No. SK 3124.100) St. Sub-D connector, 9-pole
RTT RITTAL TopTherm cooling units Bu. Sub-D jack, 9-pole
X1 Supply connection/door limit switch/alarms Adr. Address

X2 X2 X2 X2 X2 X2

Adr.: 06 Adr.: 11 Adr.: 12 Adr.: 13 Adr.: 14 Adr.: 15


1 2 2 2 2 2
L2 L2
X10 L1 N PE 1 2 3 4 5 X10 L1 L2 L3 PE 1 2 3 4 5 X10 L1 N PE 1 2 3 4 5 X10 L1 L2 L3 PE 1 2 3 4 5 X10 L1 L2 L3 PE 1 2 3 4 5 X10 L1 L2 L3 PE 1 2 3 4 5
X2

X10

NPE 1 2 3 4 5
L2
L1
Adr.: 16

1 2 3 4 5 6
3 4 4 3 2

Fig. 20: Connection example: Door limit switch and master-slave operation
Legend 4.6.3 Installing the power supply
1 Master cooling unit • Complete the electrical installation by following
2 Slave cooling units the wiring plan on the rear of the cooling unit
3 2-door enclosure with two door limit switches
(see Fig. 1 on page 5, for key see page 21).
4 Enclosure with door limit switch
• If you would like the system messages from the
cooling unit to be evaluated via the system
message relay, you should also connect a suitable
low-voltage cable to connection clamps 3 – 5.

14 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


4 Assembly and connection
SK 3302.100/.110, SK 3303.100/.110, SK 3302.200/.210, SK 3303.200/.210,
SK 3302.300/.310, SK 3361.100/.110, SK 3361.200/.210
EN

PE

21
5
Mains S1 A2

22
L1 L2 R1

L2
X1 L1 PE 1 2 3 4 5
N

1 2 3 1 2 3 2 1 2
NTC I red B1
L N 2
Power S1 NTC E blue B2
Kx
8
Term

A1
2
F2 1 P

M1 M2 M4
1 2 3 1 2 3 1 2 3 F2

C4

C1

S
R C2
M M
C F3 1~ 1~

M2 M4
M1

Fig. 21: Electrical wiring plan no. 1

SK 3303.500/.510, SK 3303.600/.610, SK 3361.500/.510, SK 3361.600/.610


21

Mains S1
22

PE
5 L2
X1 L1 N PE 1 2 3 4 5 X2 X3

3 8 A2

1 2 3 1 2 3 2 1 2
NTC I red B1
MS1 Serial
L N S1 K2 2
K1 NTC E blue B2
Power
Kx 2
NTC C white B3
PE 2
NTC A yellow B4
2
Level green B5

4
A1 Term

2
M1 M2 M4 F2 1 P F2
1 2 3 1 2 3 1 2 3

C4
PE

C1

S
R
C2
M M
C F3 1~ 1~

M2 M4
M1

Fig. 22: Electrical wiring plan no. 2

RITTAL cooling unit assembly and operating instructions 15

Downloaded from www.Manualslib.com manuals search engine


4 Assembly and connection

EN SK 3361.540/.640

L1 L2 PE

21
400 V S1
T1

22
230 V A2
PE
5 L2
X1 L1 N PE 1 2 3 4 5 X2 X3

3 8

1 2 3 2
1 2 3 2 1 B1
MS1 Serial NTC I red
K2 K1 2
L N S1 NTC E blue B2
Power Kx 2
NTC C white B3
PE 2
NTC A yellow B4
A1 2
Level green B5

4
Term

2
M1 M2 M4 F2 1 P
1 2 3 1 2 3 1 2 3

F2
C4
PE
C1

S R C2
M M
C F3 1~ 1~

M2 M4
M1

Fig. 23: Electrical wiring plan no. 3

SK 3304.100/.200
21

Mains S1
22

PE
5
L2
X1 L1 PE 1 2 3 4 5 R1
N L1 L2

F11 A2
L1 L2

T1 E1

L N

1 2 3 1 2 3 2 1 2
NTC I red B1
PE
L N 2
Power S1 NTC E blue B2
Kx 8
Term

A1
2
F2 1 P F2

M1 M2 M4
1 2 3 1 2 3 1 2 3

C1
C4

1
S R
M M
C2
F3 1~ 1~
3
C
M2 M4
M1

Fig. 24: Electrical wiring plan no. 4

16 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


4 Assembly and connection
SK 3305.100/.110, SK 3328.100/.110, SK 3329.100/.110, SK 3305.200/.210,
SK 3328.200/.210, SK 3329.200/.210, SK 3366.100/.110, SK 3377.100/.110,
EN
SK 3366.200/.210, SK 3377.200/.210

21
Mains S1

22
PE
5

L2
X1 L1 PE 1 2 3 4 5 R1
N L1 L2

F11
L1 L2 A2

T1 E1

L N

1 2 3 1 2 3 2 1 2
PE NTC I red B1
L N 2
Power S1 NTC E blue B2
Kx 8
Term

A1
2
F2 1 P F2

M1 M2 M4
1 2 3 1 2 3 1 2 3

A3 C4
A R
C 4
C12
1
P C11
2
5
M M
C2
1~ 1~
F3
M1 M2 M4

Fig. 25: Electrical wiring plan no. 5

SK 3304.140, SK 3304.142, SK 3305.140, SK 3305.142, SK 3328.140, SK 3329.140,


SK 3304.240, SK 3305.240, SK 3328.240, SK 3329.240, SK 3366.140/.240, SK 3377.140/.240
21

Mains S1
22

PE
5

X1 L1 L2 L3 PE 1 2 3 4 5

L1 L2 R1
F11 F12
A2
T1 E1

3 2 1 1 2 2 4 1 3 2
NTC I red B1
PE
R S T S1 2
Power NTC E blue B2
Kx 8
Term

A1

M1 F3 F2 M2 F4 M4 F5
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 1 2 3 1 2

F2

U V
M M

W F3
3~ 3~
M2 M4
M1

Fig. 26: Electrical wiring plan no. 6

RITTAL cooling unit assembly and operating instructions 17

Downloaded from www.Manualslib.com manuals search engine


4 Assembly and connection

EN SK 3304.700, SK 3328.700

21
Mains S1

22
PE
5 L1 L2
N
L1
X1 L1
L2
PE 1 2 3 4 5 A2
N
T1 R1
L1 L2
L1 L2/N F11

F11 F12 E1
E1

1 2 3

123 1 2 3 2 1 2
NTC I red B1
PE L N 2
Power S1 NTC E blue B2
Kx 8
Term

A1
2
F2 P F2
1
M1 M2 M4
1 2 3 1 2 3 1 2 3

A3
A R
C 4
C1.2
1
P C1.1
2
5
M M
1~ 1~
F3
M1 M2 M4

Fig. 27: Electrical wiring plan no. 7

SK 3304.800, SK 3328.800
21

L1 L2 Mains S1
PE
N A2
22

L1 X2 X3
5 T1 PE 6 PE
X1 L1 L2
N PE 1 2 3 4 5 3
L1 L2/N
F11 F12
E1 F11
E1
1 2 3

123 1 2 3 2 1 Serial NTC I red 2


B1
L N K2 K1
S1 2
Power NTC E blue B2
Kx 2
NTC C white B3
2
NTC A yellow B4
A1 2
Level green B5
4
Term
2
F2 P
M1 M2 M4 1
1 2 3 1 2 3 1 2 3
F2

A3
A R
C 4
C1.2
1
P C1.1
2
5
M M
1~ 1~
F3
M1 M2 M4

Fig. 28: Electrical wiring plan no. 8

18 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


4 Assembly and connection
SK 3304.500/.600 EN

21
Mains S1
PE

22
5 X2 X3
A2

X1 L2
L1 PE 1 2 3 4 5
N
3 6

L1 L2
F11
T1 E1
L N

2
1 2 3 1 2 3 2 1 NTC I red B1
PE MS1 Serial
L N S1 2
NTC E blue B2
Power
K2 K1 2
NTC C white B3
Kx
2
A1 NTC A yellow B4
2
Level green B5
4
Term
2
M1 M2 M4 F2
1 P
1 2 3 1 2 3 1 2 3

F2

C1
C4

1
S R
C2 M M
F3 1~ 1~
3
C
M2 M4
M1

Fig. 29: Electrical wiring plan no. 9

SK 3305.500/.510, SK 3328.500/.510, SK 3329.500/.510, SK 3305.600/.610, SK 3328.600/.610,


SK 3329.600/.610, SK 3366.500/.510, SK 3377.500/.510, SK 3366.600/.610, SK 3377.600/.610
21

PE A2
Mains X2 X3
S1
22

5
3 6
L2 L2
L1 X1 L1 PE 1 2 3 4 5
N N
F11
T1
E1

1 2 3 1 2 3 2 1 2
MS1 Serial NTC I red B1
L N K2 K1 2
Power S1 NTC E blue B2
Kx
2
NTC C white B3
2
NTC A yellow B4
A1
2
Level green B5
4
Term

2
M1 M2 M4 F2
1 P
1 2 3 1 2 3 1 2 3

F2

A3
A R
4 C4
C
C12
1
P C11
2
5
C2 M M
1~ 1~
F3
M1
M2 M4

Fig. 30: Electrical wiring plan no. 10

RITTAL cooling unit assembly and operating instructions 19

Downloaded from www.Manualslib.com manuals search engine


4 Assembly and connection

EN SK 3304.540, SK 3304.542, SK 3305.540, SK 3305.542, SK 3328.540, SK 3329.540, SK 3304.640,


SK 3305.640, SK 3328.640, SK 3329.640, SK 3366.540, SK 3377.540, SK 3366.640, SK 3377.640
Mains

22 S1
21

PE X1 L1 L2 L3 PE 1 2 3 4 5 X2 X3
5
F11 F12 3 8
A2
T1 E1

3 2 1 1 2 2
2 4 1 3 NTC I red B1
MS1 Serial
Power K2 2
K1 B2
S1 NTC E blue
2
Kx NTC C white B3
2
NTC A yellow B4
2
Level green B5

4
A1 Term

M1 F3 F2 M2 F4 M4 F5
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 1 2 3 1 2

F2

U V

M M

W F3
3~ 3~
M2 M4
M1

Fig. 31: Electrical wiring plan no. 11

SK 3332.140/.240
21

PE Mains S1
22

6 A2

L1 L2 R1

X1 L1 L2 L3 PE 1 2 3 4 5

F11 F12
T1 8
E1

3 2 1 1 2 2 4 1 3 2
Term NTC I red B1
R S T
S1 2
Power NTC E blue B2
Kx

A1

M1 F3 F2 M2 F4 M4 F5
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 1 2 3 1 2

F2
U V

M M
P
3~ 3~
W
M2 M4
M1

Fig. 32: Electrical wiring plan no. 12

20 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


4 Assembly and connection
SK 3332.540/.640 EN

21
S1
Mains

22
A2
PE
X2 X3
6 X1 L1 L2 L3 PE 1 2 3 4 5
3 8
F11 F12

T1 E1

3 2 1 1 2 2 4 1 3 2
NTC I red B1
MS1 Serial
R S T 2
K2 K1 NTC E blue B2
Power S1
2
Kx NTC C white B3
2
NTC A yellow B4
2
A1 Level green B5

4
Term

M1 F3 F2 M2 F4 M4 F5
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 1 2 3 1 2

U
V F2

M M
P
3~ 3~
W
M2 M4
M1

Fig. 33: Electrical wiring plan no. 13

Legend
A1 Power PCB Note:
A2 Basic or Comfort controller For technical data refer to the rating plate.
A3 Starter relay and RC element
B1 Temperature sensor, internal temperature
B2 Icing hazard temperature sensor AC DC
B3 Temperature sensor, external 1
cos f = 1 L/R = 20 ms
B4 Temperature sensor, external 2
B5 Condensate warning sensor (optional) I max. = 2 A I min. = 100 mA
C1 – C4 Running capacitors U max. = 250 V U max. = 200 V
E1 Condensate evaporator U min. = 18 V
F2 PSAH pressure-operated switch I max. = 2 A
(3302.1x0 has bridge instead of pressostat)
F3 Bimetal contact compressor Tab. 2: Contact data
F11/F12 Miniature fuses, condensate evaporator
K1 Relay collective fault 1
K2 Relay collective fault 2
L1 LED operational green
L2 LED alarm red
M1 Compressor
M2 Condenser fan
M4 Evaporator fan
R1 Potentiometer for setting the temperature
S1 Door limit switch
(without door limit switch: terminal 1, 2 open)
T1 Transformer (optional)
X1 Main terminal strip
X2 Master-slave connection
X3 Optional interface

RITTAL cooling unit assembly and operating instructions 21

Downloaded from www.Manualslib.com manuals search engine


5 Commissioning
4.7 Finalising assembly 4.7.3 Setting the filter mat monitor
(only with Comfort controller)
EN 4.7.1 Installing the filter media Function of the filter mat monitor:
The cooling unit condenser is finished all over with a Dirt on the filter mat is automatically detected by
dirt-repelling, easy-to-clean RiNano coating. In many measuring the temperature difference in the external
cases, therefore, the use of filter media is unneces- circuit of the cooling unit (see “6.2.5 Programming
sary, particularly in the case of dry dusts. overview”, page 28). As the level of filter mat soiling
For dry, coarse dust and lint in the ambient air, we rises, the temperature difference will increase. The
recommend installing an additional PU foam filter nominal value of the temperature difference in the
mat (available as an accessory) in the cooling unit. external circuit adapts automatically to the relevant
For air containing oil condensation, we recommend operating points in the performance diagrams.
the use of metal filters (also available as an accesso- Hence there is no need to readjust the nominal value
ry). When used in textile plants with heavy lint con- for different operating points of the cooling unit.
tamination, lint screens should be used (available as
an optional extra).
• Pull the louvred air inlet grille from the enclosure.
• Insert the filter mat into the louvred grille as shown 5 Commissioning
in Fig. 34 and push it back onto the enclosure.
Caution! Risk of damage!
The oil must collect in the compressor in
order to ensure effective lubrication and
cooling.
Do not operate the cooling unit for
at least 30 min. after assembling the
equipment.
• Once all the assembly and installation work is com-
plete, switch on the power supply to the cooling
unit.
Fig. 34: Installing the filter mat The cooling unit starts running:
– With Basic controller: The green operating LED
4.7.2 Fitting the cooling unit (“line”) is illuminated.
For partial and full internal mounting only. – With Comfort controller: The software version of the
• Connect the connector to the rear of the display. controller first appears for approx. 2 sec., then
• Place the louvred grille onto the unit at the front, the enclosure internal temperature appears in the
and press it down until you hear it snap into place. 7-segment display.
You can now make your individual settings on the
unit, e.g. set the temperature or (with Comfort con-
troller only) assign the network identifier, etc. (refer to
the “Operation” chapter).

Fig. 35: Connect the display and attach the louvred grille

22 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


6 Operation
6 Operation 6.1.1 Properties
– Three voltage variants are supported:
You can operate the cooling unit using the controller
on the front of the device (Fig. 1, no. 11, page 5). – 115 V
EN
Depending on the model, the unit is equipped with – 230 V
a Basic or Comfort controller. – 400/460 V, 3-phase
– Supports multiple voltages without rewiring
6.1 Control using the Basic controller – Integral start-up delay and door limit switch
For unit types SK xxxx.100/.110/.140 and function
SK xxxx.200/.210/.240/.300/.310. – Protective function to prevent icing
– Monitoring of all motors (compressor,
1
condenser fan, evaporator fan)
– Phase monitoring for three-phase units
– Visualisation of the operating status via LED
display:
– Voltage on, unit operational
– Door open (only if door limit switch installed)
– Warning of overtemperature
3 4
– High-pressure-operated switch has switched
– Switching hysteresis: 5 K
– Floating system message contact in case
of overtemperature
– Temperature setting
2 (setting range 30 – 55°C) via potentiometer
5 – Test function

The cooling unit operates automatically i.e. after


Fig. 36: Basic controller
switching on the power supply, the evaporator fan
Legend (see Fig. 2, page 5) will run continuously and perma-
1 Controller trim panel nently circulate the internal enclosure air. The built-in
2 Temperature setting
Basic controller ensures automatic normal shut-
3 LED green (“line”)
4 LED red (“alarm”)
down operation of the cooling unit by the value of the
5 Reset button fixed preset switching difference of 5 K.

RITTAL cooling unit assembly and operating instructions 23

Downloaded from www.Manualslib.com manuals search engine


6 Operation
6.1.2 Operating and error display
The Basic controller monitors and controls the cool-
EN ing unit. It indicates the operating and error status via
the green and red LEDs (Fig. 36, no. 3 and 4):

LED Status Cause Solution


Green Illuminated Voltage present, –
(line) unit operational
Flashing Only with door limit switch installed: In order to avoid condensation, close the
Enclosure door open enclosure door as quickly as possible.
Only with door limit switch installed: Check the position of the door limit switch.
Enclosure door closed
Red Alarm/error/warning Number of Flash interval
(alarm) flash intervals
for the red
LED
Implement Device reset (12) |_|_|_|_|_|_|_|_|_|_|_|*****|_|_|_|_|_|_|_|_|_|_|_|
a reset
High pressure alarm (0) |_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|
Sensors Potentiometer defective (3) |_|_|*****|_|_|*****|_|_|*****|_|_|*****|_|_|*****
or display error
Interior temperature (4) |_|_|_|*****|_|_|_|*****|_|_|_|*****|_|_|_|*****
sensor defective
Anti-icing sensor (5) |_|_|_|_|*****|_|_|_|_|*****|_|_|_|_|*****|_|_|_|_|
defective
Overload Compressor overloaded (6) |_|_|_|_|_|*****|_|_|_|_|_|*****|_|_|_|_|_|*****
Interior fan overloaded (7) |_|_|_|_|_|_|*****|_|_|_|_|_|_|*****|_|_|_|_|_|_|
Exterior fan overloaded (8) |_|_|_|_|_|_|_|*****|_|_|_|_|_|_|_|*****
Device Overload mode (9) |_|_|_|_|_|_|_|_|*****|_|_|_|_|_|_|_|_|*****
status/ (heat loss)
condition
Low load mode (11) |_|_|_|_|_|_|_|_|_|_|*****|_|_|_|_|_|_|_|_|_|_|
(heat loss)
Warning Anti-icing alarm (2) |_|*****|_|*****|_|*****|_|*****|_|*****|_|*****|_|
(ambient
Overtemperature (1) |*****|*****|*****|*****|*****|*****|*****|*****|*****|
conditions)
warning
Off No No power – Check power supply
display
Rotary current phase – Swap phases
monitoring:
“LED off” = Incorrect
phase connection
Tab. 3: Operating and error display of the Basic controller

Key to flash intervals


| = 500 ms (red LED on)
_ = 500 ms (red LED off)
***** = 3 s pause (red LED off)

24 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


6 Operation
The overtemperature message (red LED illuminated) The cooling unit will commence operation and the
may also be polled via an integral floating contact on green LED will flash (I_II_I_II_ . . .). Test mode is
the connection clamp of the cooling unit (system completed after approximately 5 minutes. The unit EN
message relay with changeover contact, see con- switches off and changes to normal operation.
nection diagrams under “4.6.3 Installing the power
supply”, page 14): Key
– Terminal 3: NC (normally closed) I = LED 500 ms on
– Terminal 4: C (connection of the supply voltage _ = LED 500 ms off
to the system message relay)
– Terminal 5: NO (normally open) In normal operation, the green LED is permanently
The NC and NO definitions refer to the de-energised illuminated.
state. As soon as power is applied to the cooling unit, • Next, rotate the potentiometer back to the required
the system message relay picks up, so that the relay setpoint.
contacts change status (contact 3 – 4 open; contact
4 – 5 closed). This is the normal operating state of the 6.1.4 Setting the temperature
cooling unit. As soon as an error message occurs or
the power supply is interrupted, the relay drops out Note:
and contact 3 – 4 is closed. With the Basic controller, the temperature
is preset at the factory to +35°C.
6.1.3 Test mode for the Basic controller In order to save energy, do not set the
The Basic controller is equipped with a test function temperature any lower than is actually
whereby the cooling unit commences cooling ope- necessary.
ration independently of the set temperature or door
limit switch function. To change the temperature setting:
First you must dismantle the trim panel of the control- • Dismantle the trim panel of the controller as
ler. described in “6.1.3 Test mode for the Basic
• Switch off the mains voltage. controller”, page 25.
• Remove the louvred grille or infill panel in which the • Set the required temperature on the temperature
controller is installed. setting device (Fig. 36, page 23).
• Release the display lock from behind and pull it • Carefully push the trim panel onto the display until
forwards slightly. you hear it snap into place.
• Push the display back into the infill panel or louvred
grille.
• Re-attach the louvred grille or infill panel to the
cooling unit.

6.1.5 Resetting the Basic controller


Following a high-pressure alarm in the cooling cycle,
and once the cause has been rectified, you will need
to manually reset the Basic controller:
• Dismantle the trim panel of the Basic controller
as described in “6.1.3 Test mode for the Basic
controller”, page 25.
• Press the reset button (Fig. 36, no. 5) for at least
3 sec.
Fig. 37: Loosen the trim panel of the Basic controller The red LED is extinguished.
• Carefully raise the trim panel, e.g. using your • Re-install the Basic controller.
thumb or a flat screwdriver, and remove it.
You can now start test mode.
• Rotate the potentiometer to the left-hand stop, then
hold the rubberised potentiometer display down
while you re-connect the mains voltage.

RITTAL cooling unit assembly and operating instructions 25

Downloaded from www.Manualslib.com manuals search engine


6 Operation
6.2 Control using the Comfort controller The cooling unit operates automatically i.e. after
switching on the power supply, the evaporator fan
EN For unit types SK xxxx.500/.510/.540 and
SK xxxx.600/.610/.640. (see Fig. 2, page 5) will run continuously and per-
manently circulate the internal enclosure air. The
1 2 compressor and condenser fan are regulated by the
Comfort controller.
The Comfort controller has a 7-segment display
(Fig. 38, no. 4). After switching on the power supply,
the current software version is initially displayed for
approximately 2 sec., followed by a preset option
(e.g. t10) or the temperature.
In regular operation, the display shows both the tem-
perature (in degrees Celsius or Fahrenheit – users
may switch between the two) and any error messages.
4 3 The current enclosure internal temperature is usually
Fig. 38: Comfort controller displayed permanently. In the event of an error mes-
Legend
sage, this will alternate with the temperature display.
1 Programming button, also display of the set The unit is programmed using buttons 1 – 3 (Fig. 38).
temperature unit (degrees Celsius) The relevant parameters also appear in the display.
2 Set button
3 Programming button, also display of the set 6.2.2 Launching test mode
temperature unit (degrees Fahrenheit) The Comfort controller is equipped with a test func-
4 7-segment display tion whereby the cooling unit commences cooling
operation independently of the set temperature or
6.2.1 Properties door limit switch function.
– Three voltage variants are supported: • Simultaneously press buttons 1 and 2 (Fig. 38)
– 115 V for at least 5 sec.
– 230 V The cooling unit will commence operation.
– 400/460 V, 3-phase After approximately 5 minutes, test mode will end.
– Supports multiple voltages without rewiring The unit switches off and changes to normal oper-
– Integral start-up delay and door limit switch ation.
function
– Protective function to prevent icing 6.2.3 General programming information
– Monitoring of all motors (compressor, Using buttons 1, 2 and 3 (Fig. 38) you can change
condenser fan, evaporator fan) 24 parameters within the preset ranges (min. value –
– Phase monitoring for three-phase units max. value).
– Master-slave function with a maximum of ten units. Tables 4 and 5 show the parameters which can be
One device functions as a master unit. Once the altered. Fig. 39 of page 28 shows which buttons
set temperature is reached by one of the connect- must be pressed.
ed slave devices or in the event of the door limit
switch function, the affected slave unit will report Note on switching hysteresis:
to the master unit, which will switch all the other With a low hysteresis and short switching
cooling units on or off as required. cycles, there is a risk that cooling may not
– Switching hysteresis: Adjustable within the range be adequate or that only partial sections
2 – 10 K, preset to 5 K. of the enclosure are cooled.
– Visualisation of the current enclosure internal tem- Note on temperature settings:
perature and all error messages in the 7-segment
With the Comfort controller, the temperature
display.
is preset at the factory to +35°C.
– Using an interface card (Model No. SK 3124.100), In order to save energy, and due to the
the unit may be incorporated into higher-level risk of increased condensation, do not set
remote monitoring systems such as the RITTAL the temperature lower than that actually
Computer Multi Control CMC. necessary.

Note on useful cooling output:


Interactive performance diagrams for
calculating the useful cooling output may
be found at www.rittal.com.

26 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


6 Operation
In principle, the programming is identical for all You can now alter the parameter within the preset
editable parameters. limits.
To enter programming mode: • Press one of the programming buttons ▲ (°C) or EN
• Press button 2 (“Set”) for approx. 5 sec. ▼ (°F) until the required value appears.
The controller is now in programming mode. While in • Press button 2 (“Set”) to confirm the change.
programming mode, if you do not press any buttons You can now alter other parameters in the same way.
for approx. 30 sec., the display will first flash, then There is no need to re-enter the authorisation code
the controller will switch back to normal display “22”.
mode. The “Esc” display indicates that any made • To exit programming mode, press button 2 (“Set”)
changes have not been saved. again for approximately 5 sec.
• Press the programming buttons ▲ (°C) or ▼ (°F) “Acc” will appear in the display to indicate that the
to switch back and forth between the editable changes have been saved. The display will then
parameters (see tables 4 and 5). switch back to regular operation (enclosure internal
• Press button 2 (“Set”) to select the displayed temperature).
parameter for editing. You can also program the Comfort controller
The current value of this parameter is displayed. using a diagnosis software package (Model No.
• Press one of the programming buttons ▲ (°C) or SK 3159.100), the supply of which also includes
▼ (°F). a connection cable to the PC. The cable connector
The “Cod” display will appear. In order to be able to on the rear of the Comfort controller display serves
change a value, you must enter the authorisation as an interface.
code “22”.
• Keep the programming button ▲ (°C) held down
until “22” appears.
• Press button 2 (“Set”) to confirm the code.

6.2.4 Editable parameters


See also Fig. 39 on page 28.

Progr. Display Parameter Min. Max. Factory Description


level screen value value setting
1 St Internal enclosure 20 55 35 The setting of the enclosure internal temperature
temperature is preset at the factory to 35°C and may be altered
setpoint Ti within a range of 20 – 55°C.
2 Fi Filter mat 10 60 99 To activate filter mat monitoring, set the display to
monitoring (= off) at least 10 K above the temperature differential
displayed in programming mode “Fi”. Filter mat
monitoring is preset to “deactivated” in the factory
(99 = off).
3 Ad Master-slave 0 19 0 See “6.2.7 Setting the master-slave identifier”,
identifier page 30.
4 CF Temperature 0 1 0 The temperature display can be switched from
conversion °C (0) to °F (1). The corresponding LED displays
°C/°F the current unit of temperature.
5 H1 Setting for 2 10 5 The cooling unit is preset in the factory to a
switching switching hysteresis of 5 K. This parameter should
difference only be changed in consultation with us.
(hysteresis) Please contact us for advice.
6 H2 Differential for 3 15 5 If the internal enclosure temperature exceeds the
error message A2 set value by more than 5 K, then error message
A2 (enclosure internal temperature too high)
appears on the display terminal. If necessary,
the differential may be altered here within the
range of 3 – 15 K.
Tab. 4: Editable parameters

RITTAL cooling unit assembly and operating instructions 27

Downloaded from www.Manualslib.com manuals search engine


6 Operation
6.2.5 Programming overview

EN

= 5 sec.
= 5 sec.

Fig. 39: Programming overview

28 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


6 Operation
6.2.6 Defining system messages for evaluation A more detailed explanation of the system messages
System messages are shown on the display screen may be found in section “6.2.8 Evaluating system
of the Comfort controller via the displays A1 to A20 messages”, page 30. EN
and E0. See also Fig. 39 on page 28.

Progr. Display Min. Max. Factory Type or location of fault


level screen value value setting
7 A1 0 2 0 Enclosure door open
8 A2 0 2 0 Internal temperature of enclosure too high
9 A3 0 2 0 Filter monitoring
10 A4 0 2 0 Ambient temperature too high/too low
11 A5 0 2 0 Icing hazard
12 A6 0 2 1 PSAH pressure-operated switch
13 A7 0 2 2 Evaporator coil
14 A8 0 2 1 Condensate warning
15 A9 0 2 1 Condenser fan blocked or defective
16 A10 0 2 1 Evaporator fan blocked or defective
17 A11 0 2 2 Compressor
18 A12 0 2 1 Condenser
19 A13 0 2 1 Ambient temperature sensor
20 A14 0 2 1 Icing temperature sensor
21 A15 0 2 1 Condensate warning temperature sensor
22 A16 0 2 1 Internal temperature sensor
23 A17 0 2 1 Phase monitoring
24 A18 0 2 0 EPROM
25 A19 0 2 0 LAN/Master-Slave
Tab. 5: System messages which may be evaluated via relays

The system messages A1 – A19 may additionally be This is the normal operating state of the cooling unit.
evaluated via two floating system message relays. In As soon as a system message occurs or the power
this way, one of the two system message relays may supply is interrupted, the corresponding relay will
be allocated to each system message. drop out and open the contact.
System alarm relay with normally open contact: see
connection diagrams under “4.6.3 Installing the Program system messages with the value
power supply”, page 14: 0: System message is not sent to the system
– Terminal 3: NO (normally open, relay 2) message relay, but merely appears in the
– Terminal 4: C (connection of the supply voltage display
to the system message relay) 1: System message is evaluated by relay 1
– Terminal 5: NO (normally open, relay 1) 2: System message is evaluated by relay 2

The definition NO refers to the de-energised state.


As soon as power is applied to the cooling unit, both
system message relays (relay 1 and 2) energise.

RITTAL cooling unit assembly and operating instructions 29

Downloaded from www.Manualslib.com manuals search engine


6 Operation
6.2.7 Setting the master-slave identifier On the slave cooling unit (00 = factory setting),
When several cooling units are connected together set its own address:
EN (maximum ten), one of the cooling units must be 11: Slave cooling unit no. 1
defined as the “master” and the others as “slaves”. 12: Slave cooling unit no. 2
For this purpose, assign a corresponding identifier 13: Slave cooling unit no. 3
(address) to each cooling unit which will enable the 14: Slave cooling unit no. 4
cooling unit to be identified in the network. 15: Slave cooling unit no. 5
If one of the slave units reaches the set temperature 16: Slave cooling unit no. 6
or if the door limit switch function is activated, the 17: Slave cooling unit no. 7
affected slave unit will report to the master unit, 18: Slave cooling unit no. 8
which then deactivates all the other cooling units. 19: Slave cooling unit no. 9

Notes:
– Only one unit may be configured as Master Slave Slave
02 11 12
master, and its identifier must match the
number of slave units connected.
– The slave units must have different Fig. 40: Master-slave connection (example)
identifiers. For further connection examples, see “4.6.1 Bus
– The identifiers must be numbered in connection (only in conjunction with several units
ascending order without any gaps. with a Comfort controller)”, page 13.
For details of how to set the identifier, see “6.2.4
Editable parameters”, page 27 or “6.2.5 Program-
On the master cooling unit (00 = factory setting),
ming overview”, page 28, parameter “Ad”.
set the number of slave units present in the network:
01: Master with 1 slave cooling unit 6.2.8 Evaluating system messages
02: Master with 2 slave cooling units In the Comfort controller, system messages are indi-
03: Master with 3 slave cooling units cated by a number in the display.
04: Master with 4 slave cooling units Following the appearance of messages A03, A06
05: Master with 5 slave cooling units and A07 and after rectifying their cause, you will
06: Master with 6 slave cooling units need to reset the Comfort controller (see “6.2.9 Re-
07: Master with 7 slave cooling units setting the Comfort controller”, page 32).
08: Master with 8 slave cooling units
09: Master with 9 slave cooling units

30 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


6 Operation
Display System message Possible cause Measures to rectify the fault
screen
A01 Enclosure door open Door open or door limit switch Close door, position door limit switch correctly,
EN
incorrectly positioned check connection if necessary
A02 Internal temperature Cooling capacity inadequate/unit undersized. Check cooling capacity
of enclosure too high Error as a consequence of messages A03 to
A17.
A03 Filter monitoring Filter mat soiled Clean or replace;
reset the Comfort controller
A04 Ambient temperature Ambient temperature outside of admissible Raise or lower the ambient temperature
too high/too low operating range (+10°C to +60°C) (e.g. heat or ventilate the room)
A05 Icing hazard Operational display in case of icing hazard. Set the enclosure interior temperature to
Evaporator coil fan may be mechanically a higher value. Check the evaporator fan;
blocked, defective, or cold air outlet release or exchange if necessary.
obstructed.
A06 PSAH pressure-operated Ambient temperature too high Lower the ambient temperature;
switch reset the Comfort controller
Condenser soiled Clean the condenser;
reset the Comfort controller
Filter mat soiled Clean or replace;
reset the Comfort controller
Condenser fan defective Replace;
reset the Comfort controller
E-valve defective Have the sensor repaired by a refrigeration
engineer; reset the Comfort controller
PSAH pressure-operated switch defective Have the switch replaced by a refrigeration
engineer; reset the Comfort controller
A07 Evaporator coil Lack of coolant; sensor in front of or behind Have the sensor repaired by a refrigeration
condenser defective. engineer; reset the Comfort controller
A08 Condensate warning Condensate discharge kinked or blocked Check condensate discharge; repair any kinks
or blockages in the hose as necessary
Only in units with optional Check the evaporation unit,
condensate evaporation exchange if necessary
A09 Condenser fan Blocked or defective Clear the blockage; replace if necessary
A10 Evaporator fan Blocked or defective Clear the blockage; replace if necessary
A11 Compressor Compressor overloaded No action required;
(internal winding protection) unit switches back on automatically.
Defective Exchange by refrigeration engineer
(check by measuring the winding resistance)
A12 Condenser temperature Open or short-circuit Replace
sensor
A13 Ambient temperature Open or short-circuit Replace
sensor
A14 Icing temperature sensor Open or short-circuit Replace
A15 Condensate warning Open or short-circuit Replace
temperature sensor
A16 Internal temperature sensor Open or short-circuit Replace
A17 Phase monitoring For three-phase devices only: Exchange two phases
Incorrect rotary field/phase absent
A18 EPROM error New board obstructed Software update needed (only following board
installation with more recent software):
Enter the programming level with Code 22;
press button 1 and confirm with “Set” until
“Acc” appears. Next, disconnect the unit from
the mains and reconnect.
A19 LAN/Master-Slave Master and slave not connected Check setting and/or cable
A20 Voltage drop Error display not shown Event is stored in the log file
E0 Display message Connection problem between the display Reset: Switch power supply off, then switch
and the controller board on again after approx. 2 sec.
Cable defective; connection loose Exchange the boards
OL Overload Ambient parameters or heat loss outside of the applicable limits
LH Low heat Minimal heat loss inside the enclosure
rSt Reset Manual device reset required,
see “6.2.9 Resetting the Comfort controller”, page 32.
Tab. 6: Troubleshooting with the Comfort controller

RITTAL cooling unit assembly and operating instructions 31

Downloaded from www.Manualslib.com manuals search engine


7 Inspection and maintenance
6.2.9 Resetting the Comfort controller 7.1.1 Compressed air cleaning
After the occurrence of faults A03, A06 and A07, SK 3304.xxx, SK 3305.xxx
EN you will need to reset the Comfort controller.
• Press buttons 1 (▲) and 3 (▼) (Fig. 38) simul-
taneously for 5 sec.
The system messages will disappear and the tem-
perature display will be shown.

7 Inspection and maintenance

Risk of electric shock!


The unit is live.
Switch off the power supply before open-
Fig. 41: Disconnect the power cord
ing, and take suitable precautions against
it being accidentally switched back on.

7.1 General
The cooling circuit is designed in the form of a main-
tenance-free, hermetically sealed system. The cool-
ing unit is filled with the required quantity of refriger-
ant at the factory, checked for leaks, and subjected
to a functional test run.
The installed maintenance-free fans are mounted on
ball bearings, protected against moisture and dust,
and fitted with a temperature monitor. The life expec-
tancy is at least 30,000 operating hours. The cooling
unit is thus largely maintenance-free. All that may be
required from time to time is to clean the components
of the external air circuit using a vacuum cleaner or
compressed air if they become visibly dirty. Any
stubborn, oily stains may be removed using a non-
flammable detergent, such as degreaser.
Maintenance interval: 2000 operating hours. Depen-
ding on the level of contamination in the ambient air,
the maintenance interval may be reduced to suit the
air pollution intensity.

Caution!
Risk of fire!
Never use flammabel liquids Fig. 42: Remove the upper louvred grille
for cleaning.

Sequence of maintenance measures:


– Check the level of dirt.
– Filter soiling? Replace the filter if necessary.
– Cooling membranes soiled? Clean if necessary.
– Activate test mode; cooling function OK?
– Check noise generation of compressor and fans.

32 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


7 Inspection and maintenance

EN

Fig. 43: Remove the lower louvred grille Fig. 45: Disconnect the connector from the display (1)

Fig. 46: Disconnect the connector from the display (2)

Fig. 44: Remove the infill panel

RITTAL cooling unit assembly and operating instructions 33

Downloaded from www.Manualslib.com manuals search engine


7 Inspection and maintenance

EN

Fig. 50: Disconnect the fan connectors

Fig. 47: Cooling unit without grille Fig. 51: Remove the cover (loosen the four screws)

Fig. 48: Remove the external circuit fan Fig. 52: Push back the display cable
(loosen the four screws)

Fig. 49: Remove the fan Fig. 53: Push the display cable through the cable gland

34 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


7 Inspection and maintenance

EN

Fig. 56: Loosen the earthing cable between the cover


and the chassis (1)

Fig. 54: Remove the cover (1)


Fig. 57: Loosen the earthing cable between the cover
and the chassis (2)

Fig. 55: Remove the cover (2)

Fig. 58: Clean out the heat exchanger coil and compressor
chamber using compressed air (1)

RITTAL cooling unit assembly and operating instructions 35

Downloaded from www.Manualslib.com manuals search engine


7 Inspection and maintenance

EN

Fig. 59: Clean out the heat exchanger coil and compressor Fig. 61: Remove the upper louvred grille (1)
chamber using compressed air (2)

7.1.2 Compressed air cleaning


SK 3328.xxx, SK 3329.xxx, SK 3332.xxx

Fig. 60: Disconnect the power cord

Fig. 62: Remove the upper louvred grille (2)

36 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


7 Inspection and maintenance

EN

Fig. 63: Remove the upper louvred grille (3) Fig. 65: Remove the lower louvred grille (2)

Fig. 64: Remove the lower louvred grille (1) Fig. 66: Remove the infill panel

RITTAL cooling unit assembly and operating instructions 37

Downloaded from www.Manualslib.com manuals search engine


7 Inspection and maintenance

EN

Fig. 67: Disconnect the display cable Fig. 71: Remove the external circuit fan

Fig. 68: Push back the display cable and press it through Fig. 72: Disconnect the fan connectors (1)
the cable gland (1)

Fig. 69: Push back the display cable and press it through Fig. 73: Disconnect the fan connectors (2)
the cable gland (2)

Fig. 70: Loosen the four screws of the external circuit fan Fig. 74: Disconnect the fan connectors (3)

38 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


7 Inspection and maintenance

EN

Fig. 75: Disconnect the fan earthing cable (1)

Fig. 76: Disconnect the fan earthing cable (2) Fig. 78: Remove the cover

Fig. 77: Loosen the four screws of the cover Fig. 79: Disconnect the earthing cable (1)

RITTAL cooling unit assembly and operating instructions 39

Downloaded from www.Manualslib.com manuals search engine


7 Inspection and maintenance

EN

Fig. 80: Disconnect the earthing cable (2) Fig. 82: Clean out the heat exchanger coil and compressor
chamber using compressed air (2)

Fig. 81: Clean out the heat exchanger coil and compressor Fig. 83: Clean out the heat exchanger coil and compressor
chamber using compressed air (1) chamber using compressed air (3)

40 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


8 Storage and disposal
8 Storage and disposal 9 Technical specifications
EN
Caution! Risk of damage!
The cooling unit must not be subjected
to temperatures above +70°C during
storage.
During storage, the cooling unit must stand upright.
The closed cooling circuit contains refrigerant and oil
which must be properly disposed of for the sake of
the environment. Disposal can be performed at the
RITTAL plant.
Please contact us for advice.

Fig. 84: Rating plate (technical specifications)

– Observe the mains connection data (voltage and


frequency) as per the rating plate.
– Observe the pre-fuse as per the specifications on
the rating plate.

RITTAL cooling unit assembly and operating instructions 41

Downloaded from www.Manualslib.com manuals search engine


9 Technical specifications
Unit Model No. SK
EN Basic controller,
– 3302.100 3302.110 3302.300 3302.310 3303.100 3303.110 3304.100 3304.110 3304.700
RAL 7035
Comfort controller,
– – – – – 3303.500 3303.510 3304.500 3304.510 3304.800
RAL 7035
Basic controller,
– 3302.200 3302.210 – – 3303.200 3303.210 3304.200 3304.210 –
stainless steel cover

Comfort controller,
– – – – – 3303.600 3303.610 3304.600 3304.610 –
stainless steel cover
V 230, 1~, 115, 1~, 230, 1~, 115, 1~, 230, 1~, 115, 1~, 230, 1~, 115, 1~, 230, 1~,
Rated voltage
Hz 50/60 60 50/60 60 50/60 60 50/60 50/60 50
Rated current A 1.6/1.7 3.3 1.6/1.7 4.0 2.6/2.6 5.7 5.4/5.0 10.6/11.1 3.0
Start-up current A 3.0/3.4 8.0 4.3/5.3 12.0 5.1/6.4 11.5 12.0/14.0 26.0/28.0 12.0
Pre-fuse T A 10.0 10.0 10.0 10.0 10.0 10.0 10.0 11.0 – 16.0 10.0
Motor circuit-breaker – – – – – – – – – –
Transformer circuit-breaker – – – – – – – –  –
Miniature circuit-breaker/fuse –        – 
.
Useful cooling output Qk L 35 L 35 W 300/320 300 300/320 300 500/610 500 1000/1060 1000/1060 1000
to DIN 3168 L 35 L 50 W 150/170 150 150/160 150 280/350 280 790/840 790/840 900
Power consumption Pel L 35 L 35 W 245/255 290 285/300 290 360/380 470 825/775 850/800 520
to DIN 3168 L 35 L 50 W 255/275 340 320/340 340 420/390 500 875/835 900/875 580
.
Refrigeration factor ε = Qk/Pel 1.2 1.2 1.1 1.1 1.4 1.4 1.2 1.2 1.9
Refrigerant
– Type – R134a R134a R134a R134a R134a R134a R134a
– Filling g 100 95 170 170 325 325 500
Admissible pressure bar 25 25 25 25 28 28 25 25 28
Temperature setting range1) °C +20 to +55 +20 to +45
Noise level dB (A) < 61 < 61 < 61 < 61 < 61 < 61 < 61 < 64 < 64
Protection category to EN 60 529
– Internal circuit – IP 54
– External circuit – IP 34
280 x 550 x
Dimensions (W x H x D) mm 280 x 550 x 140 525 x 340 x 153 400 x 950 x 260
200
Weight kg 13 13 13 17 17 17 39 44 40
1) Basic controller +30°C to +55°C

42 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


9 Technical specifications
Unit Model No. SK
Basic controller,
RAL 7035

3304.140
3304.142
3305.100 3305.110
3305.140
3305.142
3328.100 3328.110 3328.140 3329.100 3328.700 EN
Comfort controller, 3304.540 3305.540
– 3305.500 3305.510 3328.500 3328.510 3328.540 3329.500 3328.800
RAL 7035 3304.542 3305.542
Basic controller,
– 3304.240 3305.200 3305.210 3305.240 3328.200 3328.210 3328.240 3329.200 –
stainless steel cover

Comfort controller,
– 3304.640 3305.600 3305.610 3350.640 3328.600 3328.610 3328.640 3329.600 –
stainless steel cover
400, 3~, 50/ 230, 1~, 115, 1~, 400, 3~, 50/ 230, 1~, 115, 1~, 400, 3~, 50/ 230, 1~, 230, 1~,
Rated voltage V, Hz
460, 3~, 60 50/60 50/60 460, 3~, 60 50/60 50/60 460, 3~, 60 50/60 50
Rated current A 2.8/2.9 6.0/6.5 12.1/13.6 2.6/2.9 7.5/9.1 14.7/17.3 2.8/3.3 8.6/10.6 4.5
Start-up current A 11.5/12.7 22.0/24.0 42.0/46.0 12.2/11.3 22.0/26.0 36.0/39.0 6.8/7.8 21.0/21.0 12.0
Pre-fuse T A 6.3 – 10.0 16.0 14.0 – 20.0 6.3 – 10.0 16.0 18.0 – 25.0 6.3 – 10.0 16.0 10.0
Motor circuit-breaker –  – –  – –  – –
Transformer circuit-breaker – – –  – –  – – –
Miniature circuit-breaker/fuse – –  – –  – –  
Useful cooling
.
output Qk L 35 L 35 W 1000/1060 1500/1510 1500/1510 1500/1510 2000/2350 2000/2350 2000/2350 2500/2750 2000
to DIN 3168 L 35 L 50 W 790/840 1230/1250 1230/1250 1230/1250 1450/1690 1450/1690 1450/1690 1600/1750 1630
Power
consumption Pel L 35 L 35 W 700/675 975/1125 1000/1175 925/1100 1025/1200 1085/1250 1050/1275 1450/1675 780
to DIN 3168 L 35 L 50 W 785/800 1125/1285 1165/1325 1085/1275 1250/1350 1300/1410 1275/1525 1625/2000 870
.
Refrigeration factor ε = Qk/Pel 1.4 1.5 1.5 1.6 2.0 1.8 1.9 1.7 2.6
Refrigerant
– Type – R134a R134a R134a R134a R134a R134a R134a R134a R134a
– Filling g 500 600 600 600 950 950 950 950 750
Admissible pressure bar 25 25 25 25 28 28 28 28 28
Temperature setting range1) °C +20 to +55 +20 to +45
Noise level dB (A) < 64 < 64 < 64 < 64 < 64 < 64 < 64 < 64 < 64
Protection category
to EN 60 529
– Internal circuit – IP 54
– External circuit – IP 34
Dimensions (W x H x D) mm 400 x 950 x 260 400 x 1580 x 290
Weight kg 40 41 46 42 66 73 67 69 66
1) Basic controller +30°C to +55°C

RITTAL cooling unit assembly and operating instructions 43

Downloaded from www.Manualslib.com manuals search engine


9 Technical specifications
Unit Model No. SK

EN Basic controller, RAL 7035


Comfort controller, RAL 7035


3329.110
3329.510
3329.140
3329.540
3332.140
3332.540
3361.100
3361.500
3361.110
3361.510
3361.140
3361.540
Basic controller,
– 3329.210 3329.240 3332.240 3361.200 3361.210 3361.240
stainless steel cover
Comfort controller,
– 3329.610 3329.640 3332.640 3361.600 3361.610 3361.640
stainless steel cover
115, 1~, 400, 3~, 50/ 400, 3~, 50/ 230, 1~, 115, 1~, 400, 2~,
Rated voltage V, Hz
50/60 460, 3~, 60 460, 3~, 60 50/60 60 50/60
Rated current A 17.0/22.0 3.7/3.8 4.2/4.2 2.3/2.4 5.3 1.2/1.4
Start-up current A 44.0/42.0 6.8/7.6 9.2/11.0 5.6/5.6 12.0 3.1/3.3
Pre-fuse T A 18.0 – 25.0 6.3 – 10.0 6.3 – 10.0 10.0 10.0 6.3 – 10.0
Motor circuit-breaker – –   – – –
Transformer circuit-breaker –  – – – – 
Miniature circuit-breaker/fuse – – – –   –
.
Useful cooling output Qk L 35 L 35 W 2500/2750 2500/2700 4000/4400 750/780 750 750/780
to DIN 3168 L 35 L 50 W 1600/1750 1900/1950 3070/3570 510/540 500 510/540
Power consumption Pel L 35 L 35 W 1500/1725 1425/1625 1850/2250 480/550 570 480/550
to DIN 3168 L 35 L 50 W 1675/2065 1675/1975 2120/2590 530/640 670 530/640
.
Refrigeration factor ε = Qk/Pel 1.7 1.8 2.1 1.5 1.5 1.5
Refrigerant
– Type – R134a R134a R134a R134a R134a R134a
– Filling g 950 950 3000 280 260 280
Admissible pressure bar 28 28 28 28 28 28
Temperature setting range1) °C +20 to +55 +20 to +52 +20 to +55
Noise level dB (A) < 64 < 64 < 64 < 64 < 64 < 64
Protection category to EN 60 529
– Internal circuit – IP 54
– External circuit – IP 34
Dimensions (W x H x D) mm 400 x 1580 x 290 500 x 1580 x 340 280 x 550 x 280
Weight kg 76 70 91 22 22 22

Unit Model No. SK


Basic controller, RAL 7035 – 3366.100 3366.110 3366.140 3377.100 3377.110 3377.140
Comfort controller, RAL 7035 – 3366.500 3366.510 3366.540 3377.500 3377.510 3377.540
Basic controller,
– 3366.200 3366.210 3366.240 3377.200 3377.210 3377.240
stainless steel cover
Comfort controller,
– 3366.600 3366.610 3366.640 3377.600 3377.610 3377.640
stainless steel cover
230, 1~, 115, 1~, 400, 3~, 50/ 230, 1~, 115, 1~, 400, 3~, 50/
Rated voltage V, Hz
50/60 50/60 460, 3~, 60 50/60 50/60 460, 3~, 60
Rated current A 7.1/7.3 14.3/14.7 3.0/3.1 7.1/7.3 14.3/14.7 3.3/3.4
Start-up current A 22.0/24.0 43.0/47.0 8.0/8.8 22.0/24.0 43.0/47.0 8.0/8.8
Pre-fuse T A 10.0 14.0 – 20.0 6.3 – 10.0 10.0 14.0 – 20.0 6.3 – 10.0
Motor circuit-breaker – – –  – – 
Transformer circuit-breaker – –  – –  –
Miniature circuit-breaker/fuse –  – –  – –
.
Useful cooling output Qk L 35 L 35 W 1500/1500 1500/1500 1500/1500 1500/1500 1500/1500 1500/1500
to DIN 3168 L 35 L 50 W 1050/1100 1050/1100 980/1080 1050/1100 1050/1100 980/1080
Power consumption Pel L 35 L 35 W 1045/1175 1075/1200 1090/1240 1045/1175 1075/1200 1090/1240
to DIN 3168 L 35 L 50 W 1220/1335 1265/1375 1260/1430 1220/1335 1265/1375 1260/1430
.
Refrigeration factor ε = Qk/Pel 1.4 1.4 1.3 1.4 1.4 1.3
Refrigerant
– Type – R134a R134a R134a R134a R134a R134a
– Filling g 700 700 700 700 700 700
Admissible pressure bar 28 28 28 28 28 28
Temperature setting range1) °C +20 to +55
Noise level dB (A) < 64 < 64 < 64 < 64 < 64 < 64
Protection category to EN 60 529
– Internal circuit – IP 54
– External circuit – IP 34
Dimensions (W x H x D) mm 450 x 1590 x 195 450 x 1590 x 165
Weight kg 45 50 46 45 50 46
1) Basic controller +30°C to +55°C

44 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


10 List of spare parts
10 List of spare parts
75 EN
SK 3302.xxx
40 10

71

25
45

100
55 71
90
15

Fig. 85: Spare parts for SK 3302.xxx

SK 3302.3xx
10

90
71 71 20

25

100
45
40

5 1

15

55

Fig. 86: Spare parts for SK 3302.3xx

RITTAL cooling unit assembly and operating instructions 45

Downloaded from www.Manualslib.com manuals search engine


10 List of spare parts

EN SK 3303.xxx
SK 3361.xxx 10

40

71

30

75
25

45

15
55
100

90
5
71 71

20
71

Fig. 87: Spare parts for SK 3303.xxx, SK 3361.xxx

SK 3304.xxx
10
SK 3305.xxx 40

71

30

102
75

1
45

25
100

71
50
80 15

20
55
90
5
45
71

71

101

Fig. 88: Spare parts for SK 3304.xxx, SK 3305.xxx

46 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


10 List of spare parts
75
SK 3328.xxx
SK 3329.xxx 46
40
10
EN
71

30

102
45

71
20
50

1
55

100

45

46
90 80
5

71
71 15
101

Fig. 89: Spare parts for SK 3328.xxx, SK 3329.xxx

SK 3332.xxx 75
10
46
40
71

102
45
25
100

50

55
1

45

71
90
46
71
71
20 15
5

30

101

Fig. 90: Spare parts for SK 3332.xxx


RITTAL cooling unit assembly and operating instructions 47

Downloaded from www.Manualslib.com manuals search engine


10 List of spare parts

EN SK 3366.xxx
SK 3377.xxx
75 100 75
40 10
46
71

102
45

20

90
50 71 30

55

25
45

101

46
80
5

15

Fig. 91: Spare parts for SK 3366.xxx, SK 3377.xxx

Legend
1 Compressor Note:
5 Condenser fan As well as the spare part number, when
10 Evaporator fan ordering spare parts the following informa-
15 Dispatch bag tion must be provided:
20 Expansion valve – Unit model
25 Filter dryer – Fabrication number
30 PSAH pressure-operated switch
– Date of manufacture
40 Controller board
45 Louvred grille 1 This information may be found
46 Louvred grille 2 on the rating plate.
50 Infill panel
55 Display
71 Temperature sensor
75 Enclosure tray
80 Transformer
90 Evaporator coil
100 Condenser
101 Condensate evaporator
102 Miniature fuse, condensate evaporator
(T4A; 6.3 x 32 mm)

48 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


11 Appendix: Cut-out and hole sizes
11 Appendix:
354
Cut-out and hole sizes 345
EN

78.5

55
11.1 Dimensions for external mounting

240
353
326
280

360
251 140
354

360
354

49

260
353
Ø8
155
(10x)
550

165.5
501

354

85.5
Fig. 95: SK 3366.xxx, SK 3377.xxx external mounting

400

Fig. 92: SK 3302.xxx external mounting

34.5
250 260

(except SK 3302.3xx)

280
255
350

525
471 153
6

Ø 9.5 (8x)

255
950

385
350
340
281

350

15
25

Fig. 96: SK 3304.xxx, SK 3305.xxx external mounting

Fig. 93: SK 3302.3xx external mounting


400
280 290
35

280
262 200
15.5

310

380

350

266
480

532
550

550
1580

Ø 13 (10x)
Ø 8 (4x)
325
260

320

Fig. 94: SK 3303.xxx, SK 3361.xxx external mounting


340

275
25

Fig. 97: SK 3328.xxx, SK 3329.xxx external mounting

RITTAL cooling unit assembly and operating instructions 49

Downloaded from www.Manualslib.com manuals search engine


11 Appendix: Cut-out and hole sizes
400
500

EN 380 340
370

45
320 145 145

330

380
440 R9.5 (2x)

500
1580

Ø 13 (10x)

1558

1580
1540
1554
375

440 376
164
360

275
25

Ø 13 (4x)

Fig. 98: SK 3332.xxx external mounting R9.5 (2x)

11.2 Dimensions for partial internal 320

mounting
Fig. 101: SK 3328.xxx, SK 3329.xxx partial internal mounting

280
254 100 100
20

500
362 145 195

25
550
497
523
524

266

Ø 8 (4x)
1550

1580
1530

474
18 x 45°
(230)

Fig. 99: SK 3303.xxx, SK 3361.xxx partial internal mounting


Ø 13 (4x)
400
370
330 105 155

Fig. 102: SK 3332.xxx partial internal mounting


25 x 45
950
920

920

380

Ø 9.5 (4x)

Fig. 100: SK 3304.xxx, SK 3305.xxx partial internal mounting

50 RITTAL cooling unit assembly and operating instructions

Downloaded from www.Manualslib.com manuals search engine


11 Appendix: Cut-out and hole sizes
11.3 Dimensions for full internal mounting
280
254
98
42
400
210
EN
370
200 R6 (4x) 25

25
50

25 x 45
Ø 15 (2x)

550
518
492
524

266

950

920
920
380
Ø 8 (4x)

18 x 45°
(230) Ø 9.5 (4x)

Fig. 103: SK 3302.1xx full internal mounting

98 55 Fig. 106: SK 3304.xxx, SK 3305.xxx full internal mounting


525
510 400
20

370
320 240 50

R9.5 (2x)
340

325
314

20 x 45°

Ø 7.5 (4x)

499
1558

1580
1540
1554

376
Fig. 104: SK 3302.3xx full internal mounting

42
280 158
254
200
25

Ø 13 (4x)

R9.5 (2x)
Ø 19 (2x)

320
550
518
492
524

266
Fig. 107: SK 3328.xxx, SK 3329.xxx full internal mounting

Ø 8 (4x)
45

400

18 x 45°
(230)

Fig. 105: SK 3303.xxx, SK 3361.xxx full internal mounting


1500
1510

45

Fig. 108: SK 3366.xxx, SK 3377.xxx full internal mounting

RITTAL cooling unit assembly and operating instructions 51

Downloaded from www.Manualslib.com manuals search engine


Schaltschrank-Systeme
Industrial Enclosures
Coffrets et armoires électriques
Kastsystemen
Apparatskåpssystem
Armadi per quadri di comando
Sistemas de armarios

Stromverteilung
Power Distribution
Distribution de courant
Stroomverdeling
Strömfördelning
Distribuzione di corrente
Distribución de corriente

Elektronik-Aufbau-Systeme
Electronic Packaging
Electronique
Electronic Packaging Systems
Electronic Packaging
Contenitori per elettronica
Sistemas para la electrónica

System-Klimatisierung
System Climate Control
Climatisation
Systeemklimatisering
Systemklimatisering
Soluzioni di climatizzazione
Climatización de sistemas

IT-Solutions
IT Solutions
Solutions IT
IT-Solutions
IT-lösningar
Soluzioni per IT
Soluciones TI

Communication Systems
Communication Systems
Armoires outdoor
Outdoor-behuizingen
Communication Systems
Soluzioni outdoor
Sistemas de comunicación 318 635

Rittal GmbH & Co. KG · Postfach 1662 · D-35726 Herborn R

Telephone: +49(0)2772 505-0 · Telefax: +49(0)2772 505-2319 · eMail: info@rittal.de · www.rittal.com

Switch to perfection
(04/07)
edition
12/09
3rd

Downloaded from www.Manualslib.com manuals search engine

S-ar putea să vă placă și