Documente Academic
Documente Profesional
Documente Cultură
Gas-insulated substations
Figure 2: Layout of gas-insulated substation
Figure 2a shows the structure of a functio- a) Sectional view 1. voltage transformer
nal unit of the substation: there is one 2. three-position disconnector 3. vacuum cir-
three-position disconnector provided for each cuit breaker 4. toroidal transformer Panel
width 600 m m b) single line diagram
unit - for the function "disconnect" and
117
“earthing - ready“ and one vacuum circuit
breaker. The connection to earth of an - Large frame, 6 0 cm diameter, up to 30 MHz
cable unit is put into effect by a three- - Small aerial, 15 cm diameter, > 100 MHz
position disconnector and a vacuum circuit
breaker. The enclosure of the substation is A digital oscilloscope with a scanning
made up of aluminum alloy: SF6 is used as frequency of 100 MHz was used to record the
insulating gas. The current is measured by time characteristics. Uncomplicated treat-
means of toroidal transformers encompassing ment - integration and / or frequency ana-
each switch cover. lysis - was guaranteed by this method of di-
Figure 2b shows the single line diagram of rect digitalization. Together with the
the investigated substation. The two busbar small aerial it became possible to present
sections are connected by a synthetic cable processes accurately up into the 30 MHz area;
5 m in length. Switching operations were accuracy was still sufficient to allow an
carried out by the circuit breaker in unit estimation up to approx. 50 MHz.
J02. All the remaining units were connec-
ted to the underground cables. During the In order to show even more rapid processes,
switching operation of the three-position an oscilloscope with scanner digitalization
disconnector in the coupler panel JOla, the was installed as a support.
circuit breaker of the coupler unit (JO1) was The applicability of this principle, howe-
open. ver, proved to be only limited since supe-
rimposed radiation of curve shapes lying
The transient interference voltage of the next to each other was so strong that the
24-kV current transformers was - in both scanner was no longer able to distinguish
substations - measured at the secondary the different parts of the curve. Voltage
terminals under the condition of normally shapes obtained in this way can give an im-
loaded windings in the control cubicle, pression of the frequencies to be expected,
which was installed in a separate relay room the voltage itself however, cannot be eva-
next to the substation room. luated.
4. Principles and equipment used for measu- 5. Survey of the experiments made and of the
rement numerical evaluation
118
t-
t :: la
B(PT)..
'i--
B ~ T )
t(us)-10
t
B (UT)
$7t (JlS)-+10
119
operating condition. The voltage appearing at the secondary
Energizing of the bus coupling (unit 25). windings of current transformers ranges
During these experiments, a busbar approx at approx. 100 V in both types of substa-
18 m in length was energized. tions (cf. Table 1). These values however,
largely depend on the local conditions rela-
Gas-insulated substation ted to the geometrical distance to the acti-
ve parts of the substation, the installa-
1. Field measurements with the small ae- tion of secondary circuits as well as on the
rial, aligned vertically, in front of type of transformer used.
functional unit 502, center point approx. 80 The absolute values of the magnetic induc-
cm above the ground, distance to the next tion in the area of the normally accessible
enclosure approx. 50 cm (Figure 2). Measure- operating aisle ranges at approx. 3 0 p T in
ments at the secondary terminals of the cur- both types of substations. In contrast to
rent transformer in operating condition Ener- this, essential differences could be obser-
gizing of an underground cable line ap- ved in the maximum change of the field
prox. 800 m in length with an open end.Limit strength in relation to time. The voltage Ui
frequency of the oscilloscope: 50 MHz induced by the magnetic field in the conduc-
2. Field measurements with the small aerial tor loop is however, determined by dB /at.
as described in experiment 1 in front of Considering the fact that the values are
the functional unit JOla (Figure 2) (circuit nearly 10 times the interference voltage to
breaker in the coupler open). be expected in secondary installations of
Inserting and opening the earthing discon- gas-insulated substations, the difficulties
nector JOla (Figure 2a). In these experiments arising when putting into operation this
the short line between the two busbar sec- type of substation become quite obvious.
tions was energized.
Experiments B,,, Characteristic
frequencies
1
): I V / d (pTI (UHz)
The results obtained from the experi-
ments concerning conventional and gas- I. c a b l e line - 10 17 0.04 : 0.33
1000 m
insulated substations are shown in Table 1.
2. c a b l e line
The values (dB/dt),, and B mO,x 3300 m
a ) 30-MHz frames - 5 46 0.012: 0.08; 0.5
were calculated from -
11 1
b ) small aerial 4 36 0.012; 0.08; 0.5
the measured values with the aid of 3. S w i t c h truck - 13 0.07 40; 1 0 0 $1)
equation(2) and (3). 4. switch bus
coup11ng
a) f i e l d
6 . Comparison of the two types of substations measurement - 2: 1;41 2.5; 25: 40
b ) at t r a n s -
former 120 4; 17: 25; 50
1; I “1
1. c a b l e line
ried out, was to compare conventional sub- 800 m
a) f x e l d
stations with gas-insulated substations. b ) at trans-
measurement :11 0.2; 2.4; 25: 60
In addition to Table 1, Figures 3 - 5 farmer 0.2: 2.2; 4.5; 22
When energizing a longer busbar section in MV-substations definitely have a higher sha-
the conventional substation (experiment K4a), re of high-energy frequency, owing to
the voltage at the aerial includes fre- their substantially smaller size as compared
quencies ranging from 2 MHz to approx. 40 to HV-substations: nevertheless, it can
MHz. Similar frequencies can be observed also be observed - although to a lesser
when evaluating all switching operations in degree - in conventionally built substa-
the gas-insulated substation: in both ca- tions. Since the prevention of interference
ses, transient waves within the respective fields would not be reasonable technically
substation or busbar are probably responsi- and economically, special attention must be
ble for this phenomenon. Still higher fre- paid to the immunity to interference of se-
quencies, exceeding 100 MHz, must be expec- condary equipment and its cable connec-
tions, which are increasingly installed
ted from the oscillograms (unfortunately in-
in the close proximity of the interference
complete) when inserting extremely short
sources.
busbar sections. This applies to both types
of substations.
120