Sunteți pe pagina 1din 3

Water

Temperature

10 g/kg

12 g/kg

14 g/kg

16 g/kg

18 g/kg

20 g/kg
0 g/kg

2 g/kg

4 g/kg

6 g/kg

8 g/kg
5% 10% 15% 20% 30%

40 ° 0.88 kg/m3
40%

35 ° 50%
0.90 kg/m3

3 60%
30 °
70%
0.92 kg/m3
80%
25 °
90%

100%
4

Rel. Humidity
20 ° 8

5 ASHRAE DESHUMIDIFICACIÓN

0.9
4
15 °

kg

y
alp
/m

th
3

En
7
0.9
6

10 ° 6
kg
/m
3

2
0.9


8
kg

ESTADO HIPOTETICO: PEOR HUMEDAD ABSOLUTA PARA


/m

1
40

CONDICIONES DE DISEÑO PARA HUMIDIFICACIÓN Y PEOR


3

kJ

CONDICIÓN PARA CALENTAMIENTO


/k
g
1.0


0
kg
/m
3
1.0

-5 °
2
kg

20
/m

DIAGRAMA DE MOLLIER
kJ
3

/k
g

Número: 2 de 2
1.0

-10 °
4

Titulo: Procesos
kg
/m

Laboratorios Química Son's S.A de C.V


3

-15 ° Elaborado por: IQ. Hector Pedraza Romero

Mollier-h-x-Diagram for air humid - Pressure 0.790 bar


1) Point

Air

Temperature °C 4.400
Rel. Humidity % 48.300
Abs. Humidity g/kg 3.203
Density humid kg/m³ 0.989
Enthalpy humid kJ/kg 12.461
Volumeflow humid m³/h 0.000
Massflow dry kg/h 0.000

2) Heating

Capacity kW 28.218

Air In Air Out


Temperature °C 4.400 32.000
Rel. Humidity % 48.300 8.538
Abs. Humidity g/kg 3.203 3.203
Density humid kg/m³ 0.989 0.900
Enthalpy humid kJ/kg 12.461 40.410
Volumeflow humid m³/h 3685.199 4051.649
Massflow dry kg/h 3634.702 3634.702

3) Moistening of air with water

Capacity kW 0.347
Moistening flow kg/h 15.040
Moistening temperature °C 20.000
Moistening enthalpy kJ/kg 83.065

Air In Air Out

Temperature °C 32.000 21.959


Rel. Humidity % 8.530 35.000
Abs. Humidity g/kg 3.200 7.338
Density humid kg/m³ 0.900 0.928
Enthalpy humid kJ/kg 40.402 40.746
Volumeflow humid m³/h 4051.479 3944.245
Massflow dry kg/h 3634.702 3634.702

4) Cooling of air - Partition of fins (2.5 - 3.5 mm)

Capacity kW 2.292
Mean temp.diff. K 20.856
Coefficient kW/K 0.110

Coolant In °C 0.000
Coolant Out °C 0.000

Air In Air Out


Temperature °C 21.959 19.790
Rel. Humidity % 35.000 39.863
Abs. Humidity g/kg 7.338 7.316
Density humid kg/m³ 0.928 0.935
Enthalpy humid kJ/kg 40.746 38.477
Volumeflow humid m³/h 3944.246 3915.113
Massflow dry kg/h 3634.702 3634.702
Condensed water kg/h 0.080
Surface temperature °C 5.145

5) Point

Air

Temperature °C 17.800
Rel. Humidity % 80.480
Abs. Humidity g/kg 13.168
Density humid kg/m³ 0.938
Enthalpy humid kJ/kg 51.272
Volumeflow humid m³/h 3924.664
Massflow dry kg/h 3634.702
6) Cooling of air - Partition of fins (2.5 - 3.5 mm)

Capacity kW 14.567
Mean temp.diff. K 5.390
Coefficient kW/K 2.703

Coolant In °C 6.000
Coolant Out °C 12.000

Air In Air Out


Temperature °C 17.800 11.000
Rel. Humidity % 80.480 97.351
Abs. Humidity g/kg 13.168 10.225
Density humid kg/m³ 0.938 0.962
Enthalpy humid kJ/kg 51.272 36.844
Volumeflow humid m³/h 3924.664 3815.188
Massflow dry kg/h 3634.702 3634.702
Condensed water kg/h 10.697
Surface temperature °C 7.300

7) Heating

Capacity kW 7.247

Air In Air Out


Temperature °C 11.000 18.000
Rel. Humidity % 97.351 62.001
Abs. Humidity g/kg 10.225 10.225
Density humid kg/m³ 0.962 0.939
Enthalpy humid kJ/kg 36.844 44.021
Volumeflow humid m³/h 3815.188 3909.173
Massflow dry kg/h 3634.702 3634.702

8) Heating

Capacity kW 1.967

Air In Air Out


Temperature °C 18.000 19.900
Rel. Humidity % 62.001 55.084
Abs. Humidity g/kg 10.225 10.225
Density humid kg/m³ 0.939 0.933
Enthalpy humid kJ/kg 44.021 45.970
Volumeflow humid m³/h 3909.173 3934.684
Massflow dry kg/h 3634.702 3634.702

S-ar putea să vă placă și