Solution

GROUND FLOOR

Heat gain from walls (ground floor)

For the north wall,

Q = Area x U x Eq.TD

Eq. TD = 8 (Table 3-42, Trane Air Conditioning Manual)

U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = 8 m x 2.7 m = 21.6 m2 x = 232.38144 ft2
1 𝑚2

So,

Q = (232.38144)(0.5)(8) = 929.52576 Btuh

For the east wall,

Q = Area x U x Eq.TD

Eq. TD = 16 (Table 3-42, Trane Air Conditioning Manual)

U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = (4 m x 2.7 m) – (1.2 m x 1.2 m) – (0.8 m x 2.1 m) = 7.68 m2 x = 82.62 ft2
1 𝑚2

So,

Q = (82.62)(0.5)(16) = 929.52576 Btuh

For the south wall,

Q = Area x U x Eq.TD
Eq. TD = 22 (Table 3-42, Trane Air Conditioning Manual)

U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = (4.3 m x 2.7 m) = 11.61 m2 x = 124.905024 ft2
1 𝑚2

So,

Q = (124.905024)(0.5)(16) = 1373.955264 Btuh

For the west wall,

Q = Area x U x Eq.TD

Eq. TD = 10 (Table 3-42, Trane Air Conditioning Manual)

U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = (1.950 m x 2.7 m) – (0.5 m x 1.2 m) – (0.9 m x 2.1 m) = 2.775 m2 x = 29.85456 ft2
1 𝑚2

So,

Q = (29.85456)(0.5)(10) = 149.2728 Btuh

Heat gain from glass (ground floor)

For the east window,

Q = Area {[Table 3-24][Table 3-31] + [Table 3-28][Table 3-32A]} (equation 3-11)

3.282 𝑓𝑡 2
Q = (1.2 x 1.2) m2 x [(16.8)(0.2) + (17.6)(1)] = 307.67302266 Btuh
1 𝑚2

For the west window,

Q = Area {[Table 3-24][Table 3-31] + [Table 3-28][Table 3-32A]} (equation 3-11)


3.282 𝑓𝑡 2
Q = (0.5 x 1.2) m2 x [(57.1)(0.2) + (17.5)(1)] = 186.6797568 Btu
1 𝑚2

Heat gain from partitions (ground floor)

For the south partition,

Temperature difference = 10 (Table 3-1, Trane Air Conditioning Manual)

U = 0.4 (Table 3-9, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Q = (3.7 x 2.7) m2 x (0.4)(10) = 429.92 Btuh
1 𝑚2

For the north partition,

Temperature difference = 10 (Table 3-1, Trane Air Conditioning Manual)

U = 0.4 (Table 3-9, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Q = (2.05 x 2.7) m2 x (0.4)(10) = 238.2 Btuh
1 𝑚2

Heat gain from people (ground floor)

Sensible heat gain from people,

Qs = (3)(220) = 660 Btuh

Latent heat gain from people,

QL = (3)(230) = 690 Btuh

Heat gain from lights (ground floor)

Heat gain from appliances (ground floor)


SECOND FLOOR

Heat gain from walls (second floor)

For the north wall,

Q = Area x U x Eq.TD

Eq. TD = 8 (Table 3-42, Trane Air Conditioning Manual)

U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = 8 m x 2.7 m = 21.6 m2 x = 232.38144 ft2
1 𝑚2

So,

Q = (232.38144)(0.5)(8) = 929.52576 Btuh

For the east wall,

Q = Area x U x Eq.TD

Eq. TD = 16 (Table 3-42, Trane Air Conditioning Manual)

U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = (4 m x 2.7 m) – (1.2 m x 1.2 m) – (0.8 m x 2.1 m) = 7.68 m2 x = 82.62 ft2
1 𝑚2

So,

Q = (82.62)(0.5)(16) = 929.52576 Btuh

For the south wall,

Q = Area x U x Eq.TD

Eq. TD = 22 (Table 3-42, Trane Air Conditioning Manual)


U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = (4.3 m x 2.7 m) = 11.61 m2 x = 124.905024 ft2
1 𝑚2

So,

Q = (124.905024)(0.5)(16) = 1373.955264 Btuh

For the west wall,

Q = Area x U x Eq.TD

Eq. TD = 10 (Table 3-42, Trane Air Conditioning Manual)

U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = (1.950 m x 2.7 m) – (0.5 m x 1.2 m) – (0.9 m x 2.1 m) = 2.775 m2 x = 29.85456 ft2
1 𝑚2

So,

Q = (29.85456)(0.5)(10) = 149.2728 Btuh

Heat gain from glass (second floor)

For the east window,

Q = Area {[Table 3-24][Table 3-31] + [Table 3-28][Table 3-32A]} (equation 3-11)

3.282 𝑓𝑡 2
Q = (1.2 x 1.2) m2 x [(16.8)(0.2) + (17.6)(1)] = 307.67302266 Btuh
1 𝑚2

For the west window,

Q = Area {[Table 3-24][Table 3-31] + [Table 3-28][Table 3-32A]} (equation 3-11)


3.282 𝑓𝑡 2
Q = (0.5 x 1.2) m2 x [(57.1)(0.2) + (17.5)(1)] = 186.6797568 Btu
1 𝑚2

Heat gain from partitions (seconnd floor)

For the south partition,

Temperature difference = 10 (Table 3-1, Trane Air Conditioning Manual)

U = 0.4 (Table 3-9, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Q = (3.7 x 2.7) m2 x (0.4)(10) = 429.92 Btuh
1 𝑚2

For the north partition,

Temperature difference = 10 (Table 3-1, Trane Air Conditioning Manual)

U = 0.4 (Table 3-9, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Q = (2.05 x 2.7) m2 x (0.4)(10) = 238.2 Btuh
1 𝑚2

Heat gain from people (second floor)

Sensible heat gain from people,

Qs = (3)(220) = 660 Btuh

Latent heat gain from people,

QL = (3)(230) = 690 Btuh

Heat gain from lights (second floor)

Heat gain from appliances (second floor)


THIRD FLOOR

Heat gain from walls (third floor)

For the north wall,

Q = Area x U x Eq.TD

Eq. TD = 8 (Table 3-42, Trane Air Conditioning Manual)

U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = 8 m x 2.7 m = 21.6 m2 x = 232.38144 ft2
1 𝑚2

So,

Q = (232.38144)(0.5)(8) = 929.52576 Btuh

For the east wall,

Q = Area x U x Eq.TD

Eq. TD = 16 (Table 3-42, Trane Air Conditioning Manual)

U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = (4 m x 2.7 m) – (1.2 m x 1.2 m) – (0.8 m x 2.1 m) = 7.68 m2 x = 82.62 ft2
1 𝑚2

So,

Q = (82.62)(0.5)(16) = 929.52576 Btuh

For the south wall,

Q = Area x U x Eq.TD

Eq. TD = 22 (Table 3-42, Trane Air Conditioning Manual)


U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = (4.3 m x 2.7 m) = 11.61 m2 x = 124.905024 ft2
1 𝑚2

So,

Q = (124.905024)(0.5)(16) = 1373.955264 Btuh

For the west wall,

Q = Area x U x Eq.TD

Eq. TD = 10 (Table 3-42, Trane Air Conditioning Manual)

U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = (1.950 m x 2.7 m) – (0.5 m x 1.2 m) – (0.9 m x 2.1 m) = 2.775 m2 x = 29.85456 ft2
1 𝑚2

So,

Q = (29.85456)(0.5)(10) = 149.2728 Btuh

Heat gain from glass (third floor)

For the east window,

Q = Area {[Table 3-24][Table 3-31] + [Table 3-28][Table 3-32A]} (equation 3-11)

3.282 𝑓𝑡 2
Q = (1.2 x 1.2) m2 x [(16.8)(0.2) + (17.6)(1)] = 307.67302266 Btuh
1 𝑚2

For the west window,

Q = Area {[Table 3-24][Table 3-31] + [Table 3-28][Table 3-32A]} (equation 3-11)


3.282 𝑓𝑡 2
Q = (0.5 x 1.2) m2 x [(57.1)(0.2) + (17.5)(1)] = 186.6797568 Btu
1 𝑚2

Heat gain from partitions (third floor)

For the south partition,

Temperature difference = 10 (Table 3-1, Trane Air Conditioning Manual)

U = 0.4 (Table 3-9, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Q = (3.7 x 2.7) m2 x (0.4)(10) = 429.92 Btuh
1 𝑚2

For the north partition,

Temperature difference = 10 (Table 3-1, Trane Air Conditioning Manual)

U = 0.4 (Table 3-9, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Q = (2.05 x 2.7) m2 x (0.4)(10) = 238.2 Btuh
1 𝑚2

Heat gain from people (third floor)

Sensible heat gain from people,

Qs = (3)(220) = 660 Btuh

Latent heat gain from people,

QL = (3)(230) = 690 Btuh

Heat gain from lights (third floor)

Heat gain from appliances (third floor)


FOURTH FLOOR

Heat gain from walls (fourth floor)

For the north wall,

Q = Area x U x Eq.TD

Eq. TD = 8 (Table 3-42, Trane Air Conditioning Manual)

U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = 8 m x 2.7 m = 21.6 m2 x = 232.38144 ft2
1 𝑚2

So,

Q = (232.38144)(0.5)(8) = 929.52576 Btuh

For the east wall,

Q = Area x U x Eq.TD

Eq. TD = 16 (Table 3-42, Trane Air Conditioning Manual)

U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = (4 m x 2.7 m) – (1.2 m x 1.2 m) – (0.8 m x 2.1 m) = 7.68 m2 x = 82.62 ft2
1 𝑚2

So,

Q = (82.62)(0.5)(16) = 929.52576 Btuh

For the south wall,

Q = Area x U x Eq.TD

Eq. TD = 22 (Table 3-42, Trane Air Conditioning Manual)


U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = (4.3 m x 2.7 m) = 11.61 m2 x = 124.905024 ft2
1 𝑚2

So,

Q = (124.905024)(0.5)(16) = 1373.955264 Btuh

For the west wall,

Q = Area x U x Eq.TD

Eq. TD = 10 (Table 3-42, Trane Air Conditioning Manual)

U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = (1.950 m x 2.7 m) – (0.5 m x 1.2 m) – (0.9 m x 2.1 m) = 2.775 m2 x = 29.85456 ft2
1 𝑚2

So,

Q = (29.85456)(0.5)(10) = 149.2728 Btuh

Heat gain from glass (fourth floor)

For the east window,

Q = Area {[Table 3-24][Table 3-31] + [Table 3-28][Table 3-32A]} (equation 3-11)

3.282 𝑓𝑡 2
Q = (1.2 x 1.2) m2 x [(16.8)(0.2) + (17.6)(1)] = 307.67302266 Btuh
1 𝑚2

For the west window,

Q = Area {[Table 3-24][Table 3-31] + [Table 3-28][Table 3-32A]} (equation 3-11)


3.282 𝑓𝑡 2
Q = (0.5 x 1.2) m2 x [(57.1)(0.2) + (17.5)(1)] = 186.6797568 Btu
1 𝑚2

Heat gain from partitions (fourth floor)

For the south partition,

Temperature difference = 10 (Table 3-1, Trane Air Conditioning Manual)

U = 0.4 (Table 3-9, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Q = (3.7 x 2.7) m2 x (0.4)(10) = 429.92 Btuh
1 𝑚2

For the north partition,

Temperature difference = 10 (Table 3-1, Trane Air Conditioning Manual)

U = 0.4 (Table 3-9, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Q = (2.05 x 2.7) m2 x (0.4)(10) = 238.2 Btuh
1 𝑚2

Heat gain from people (fourth floor)

Sensible heat gain from people,

Qs = (3)(220) = 660 Btuh

Latent heat gain from people,

QL = (3)(230) = 690 Btuh

Heat gain from lights (fourth floor)

Heat gain from appliances (fourth floor)


FIFTH FLOOR

Heat gain from walls (fifth floor)

For the north wall,

Q = Area x U x Eq.TD

Eq. TD = 8 (Table 3-42, Trane Air Conditioning Manual)

U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = 8 m x 2.7 m = 21.6 m2 x = 232.38144 ft2
1 𝑚2

So,

Q = (232.38144)(0.5)(8) = 929.52576 Btuh

For the east wall,

Q = Area x U x Eq.TD

Eq. TD = 16 (Table 3-42, Trane Air Conditioning Manual)

U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = (4 m x 2.7 m) – (1.2 m x 1.2 m) – (0.8 m x 2.1 m) = 7.68 m2 x = 82.62 ft2
1 𝑚2

So,

Q = (82.62)(0.5)(16) = 929.52576 Btuh

For the south wall,

Q = Area x U x Eq.TD

Eq. TD = 22 (Table 3-42, Trane Air Conditioning Manual)


U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = (4.3 m x 2.7 m) = 11.61 m2 x = 124.905024 ft2
1 𝑚2

So,

Q = (124.905024)(0.5)(16) = 1373.955264 Btuh

For the west wall,

Q = Area x U x Eq.TD

Eq. TD = 10 (Table 3-42, Trane Air Conditioning Manual)

U = 0.50 (Table 3-6, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Area = (1.950 m x 2.7 m) – (0.5 m x 1.2 m) – (0.9 m x 2.1 m) = 2.775 m2 x = 29.85456 ft2
1 𝑚2

So,

Q = (29.85456)(0.5)(10) = 149.2728 Btuh

Heat gain from glass (fifth floor)

For the east window,

Q = Area {[Table 3-24][Table 3-31] + [Table 3-28][Table 3-32A]} (equation 3-11)

3.282 𝑓𝑡 2
Q = (1.2 x 1.2) m2 x [(16.8)(0.2) + (17.6)(1)] = 307.67302266 Btuh
1 𝑚2

For the west window,

Q = Area {[Table 3-24][Table 3-31] + [Table 3-28][Table 3-32A]} (equation 3-11)


3.282 𝑓𝑡 2
Q = (0.5 x 1.2) m2 x [(57.1)(0.2) + (17.5)(1)] = 186.6797568 Btu
1 𝑚2

Heat gain from partitions (fifth floor)

For the south partition,

Temperature difference = 10 (Table 3-1, Trane Air Conditioning Manual)

U = 0.4 (Table 3-9, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Q = (3.7 x 2.7) m2 x (0.4)(10) = 429.92 Btuh
1 𝑚2

For the north partition,

Temperature difference = 10 (Table 3-1, Trane Air Conditioning Manual)

U = 0.4 (Table 3-9, Trane Air Conditioning Manual)

3.282 𝑓𝑡 2
Q = (2.05 x 2.7) m2 x (0.4)(10) = 238.2 Btuh
1 𝑚2

Heat gain from people (fifth floor)

Sensible heat gain from people,

Qs = (3)(220) = 660 Btuh

Latent heat gain from people,

QL = (3)(230) = 690 Btuh

Heat gain from lights (fifth floor)

Heat gain from appliances (fifth floor)