Sunteți pe pagina 1din 32

Installation

Operation
Maintenance

Air-Cooled Water Chiller


Air-Cooled Water Chiller
with Heat Pump Option
3~30 Tons

CGA-SVX01B-EN
TABLE OF CONTENTS

MODEL NOMENCLATURE 3

INSTALLATION 4
RIGGING
MOUNTING
WATER PIPING
FIGURE 1 : RECOMMENDED HOISTING ARRANGEMENT
FIGURE 2 : DIMENSION FOR MOUNTING
FIGURE 3 : SERVICE & MAINTENANCE CLEARANCE
ELECTRICAL WIRING
UNIT POWER SUPPLY
FIGURE 4 : TYPICAL PIPING ARRANGEMENT
FIGURE 5 : TYPICAL SYSTEM APPLICATION

ELECTRICAL DATA 11

FLOW SWITCH INTERLOCK 12


CIRCUIT DIAGRAM 1 : FOR CGAK 030~075
CIRCUIT DIAGRAM 2 : FOR CGAR 030~075
CIRCUIT DIAGRAM 3 : FOR CGAK 100~200
CIRCUIT DIAGRAM 4 : FOR CGAR 100~200
CIRCUIT DIAGRAM 5 : FOR CGAK 250~300
INSTALLATION CHECKLIST

PRE-START PROCEDURE 18
VOLTAGE UTILIZATION RANGE
VOLTAGE IMBALANCE
WATER FLOW RATE
UNIT WATER PRESSURE DROP
FIGURE 6 : HYDRAULIC CHARACTERISTIC
PRE-START CHECKLIST

OPERATION 23
START-UP PROCEDURE
EXTENDED UNIT SHUT-DOWN/WINTERIZATION
STANDARD AMBIENT OPERATION
OPTIONAL LOW AMBIENT OPERATION (CGAK)
OPTIONAL HEAT PUMP OPERATION (CGAR)
ELECTRICAL CONTROL & PROTECTION SYSTEM

MAINTENANCE 27

TROUBLE ANALYSIS 28
© American Standard Inc. 2004 2 CGA-SVX01B-EN
MODEL NOMENCLATURE

CGA K 050 5 D F R M R N A
1,2,3 4 5,6,7 8 9 10 11 12 13 14 15

DIGIT 1,2,3 DIGIT 9 - Development Sequence


CGA=Air-Cooled Water Chiller D=Fourth Design

DIGIT 4 - Model DIGIT 10 - Controls


K=Cooling Only F=Fixed Entering Water Temperature Control
R=Cooling With Heat Pump Option (Standard Option)
A=Microprocessor Controller
DIGIT 5,6,7 - Nominal Capacity (tons) (Adjustable Entering Water Temperature)
030 (For CGAK Models as Optional)
040 (For CGAR Models as Standard Option)
050
075 DIGIT 11- Water Pump
100 N = No Pump
125 R = Standard Pump
150 (Standard Option)
175
200 DIGIT 12 - Refrigerant Pressure Gauges
250 M = No
300 (Standard Option)
G = With High/Low Pressure Gauges
DIGIT 8 - Voltage
1=220V/60Hz/1Ph DIGIT 13 - Temperature Kit
(For model 030,040,050) R = Standard Ambient Temperature Kit
2=220V/60Hz/3Ph (Standard Option)
(For model 050,075,100,125,150,175,200,250,300) L = Low Ambient Temperature Kit
3=380V/60Hz/3Ph (For CGAK Models Only)
(For model 050,075,100,125,150,175,200,250,300)
4=460V/60Hz/3Ph DIGIT 14 - Other Options
(For model 050,075,100,125,150,175,200,250,300) M = Standard Fin + Standard Grille Cover
5=380V/50Hz/3Ph C = Blue Fin + Standard Grille Cover
(For model 050,075,100,125,150,175,200,250,300)
6=400V/50Hz/3Ph DIGIT 15 - Service Sequence
(For model 050,075,100,125,150,175,200,250,300) A = First
7=415V/50Hz/3Ph
(For model 050,075,100,125,150,175,200,250,300)

3 CGA-SVX01B-EN
INSTALLATION

Complete the “Installation Checklist” during MOUNTING Table 1 : Unit Shipping Weights
installation to verify completion of all Model Maximum Shipping Weight (Kg)
Mounting methods that will minimize sound
recommended procedures before unit and vibration problems are: 030 230
start-up.
040 250
1. Mount the unit directly on an isolated
concrete pad or on isolated concrete 050 260
RIGGING 075 320
footings at each unit mounting point.
Each unit is bolted to a shipping skid for
100 370
shipment to the job site. Move the unit using 2. Install the optional neoprene or spring
125 450
a forklift of suitable capacity. See Table 1 for isolators at each mounting location.
150 530
unit shipping weights.
Refer to Figure 2 for unit and base 175 550
Locate the unit near a large-capacity drain to
dimensions and Figure 3 for recommended 200 570
allow system drainage during unit shutdown
service clearance. 250 750
and repair. Rig the unit using canvas belt.
300 800
Fasten the belt to the unit over the unit’s
base as show in Figure 1. WATER PIPING
Thoroughly flush all water system piping
before making the final piping connections to
the unit.

© American Standard Inc. 2004 4 CGA-SVX01B-EN


Figure 1 :
Recommended Hoisting Arrangement
(CGAK-075 As Shown)

5 CGA-SVX01B-EN
Figure 2 :
Dimension for Mounting
(CGAK-075 As Shown)
Note: All Dimensions in Millimeter

© American Standard Inc. 2004 6 CGA-SVX01B-EN


Figure 3 :
Service and Maintenance Clearance
(CGAK-075 As Shown)

7 CGA-SVX01B-EN
CAUTION: If using an acidic commercial ELECTRICAL WIRING FLOW SWITCH INTERLOCK
flushing solution, construct a temporary To avoid possible evaporator freeze-up
bypass around the unit to prevent WARNING: To prevent injury or death,
resulting from reduced water flow, install a
damage to the evaporator. disconnect electrical power source
flow switch ( or other flow sensing device) in
before completing wiring connections to
CAUTION: To avoid possible equipment the evaporator outlet water line. This
the unit.
damage, do not use untreated or sensing device must be adjusted to stop
improperly treated water. CAUTION: Use only copper conductors compressor operation if water flow to the
for terminal connections to avoid evaporator drops below 70% of the system
For unit’s water connection sizes and
corrosion or over heating. design full-flow rate.
locations, please refer to Figure 2.
Figure 2 shows the location of the unit The installer must provide interconnecting
CAUTION: To prevent unit damage, do electrical access openings. Table 2 provides wiring between the unit control panel and
not reverse system piping connections to minimum circuit ampacities, recommended the water flow sensing switch in the
the unit; water entering the unit must fuse sizes, and motor electrical data. evaporator water line.
enter at the designated “Water In” and
leaving water must exit the unit through
UNIT POWER SUPPLY
the designated “Water Out” connection.
Refer to the unit wiring schematic fixed to
Figure 4 illustrates typical unit piping the control panel cover. The installer must
components. Components and layout will provide a power supply of proper voltage
vary slightly depending upon the locations and a fused disconnect switch to the unit.
of the connections and water source.
Run properly sized power wirings through
the electrical access opening on the side of
Figure 5 gives a schematic of a typical
system application for this unit. the unit, and connect it to the Voltage
Terminal Block (1TB1) in the unit control
Provide vents at high points in the piping to panel. Install a fused disconnect switch as
bleed air from the chilled water system. required by local codes. Provide proper
Install pressures gage(s) to monitor entering equipment grounds for the ground
and leaving chilled water pressure. connections in the unit control panel and at
CAUTION: To prevent damage to the the fused disconnect switch.
waterside components of unit, do not Refer to wiring diagrams from Page 12 to
allow evaporator pressure to exceed 100 Page 16 for reference of a typical unit
psig (i.e. maximum working pressure). installation. For actual wiring diagram, refer
Use an expansion tank to isolate this to the one fixed to the control panel cover.
pressure if water pressure exceeds this
value.

© American Standard Inc. 2004 8 CGA-SVX01B-EN


Figure 4 :
Typical Piping Arrangement
(CGAK-075 As Shown)

9 CGA-SVX01B-EN
Figure 5 :
Typical System Application
(CGAK-075 And Fans As Shown)

© American Standard Inc. 2004 10 CGA-SVX01B-EN


ELECTRICAL DATA

Table 2 : Electrical Data


60Hz
Electrical Water Comp Comp Fan Fan Unit Rec. Max
Model Power Pump 1 2 1 2 MCA Fuse Fuse
(V/Hz/Ph) FLA RLA RLA FLA FLA Size Size
030 220/60/1 4.4 14.4 - 2.8 - 25.2 28.8 39.6
040 220/60/1 4.4 19.4 - 2.8 - 31.5 36.3 50.9
050 220/60/1 4.4 24.4 - 2.8 - 37.7 43.8 62.1
100 220/60/1 6.5 24.4 24.4 4.3 - 65.7 71.8 90.1
050 220/60/3 2.7 15.3 - 3.0 - 24.8 28.7 40.1
050 380/60/3 1.6 8.8 - 1.7 - 14.3 16.5 23.1
075 220/60/3 4.2 23.0 - 3.0 - 36.0 41.7 59.0
075 380/60/3 2.4 13.3 - 1.7 - 20.7 24.1 34.0
100 220/60/3 4.2 15.3 15.3 4.5 - 43.1 47.0 58.4
100 380/60/3 2.4 8.8 8.8 2.6 - 24.8 27.0 33.6
125 220/60/3 5.4 17.4 17.4 4.5 - 49.1 53.4 66.5
125 380/60/3 3.1 10.1 10.1 2.6 - 28.4 31.0 38.5
150 220/60/3 5.4 23.0 23.0 3.0 3.0 63.2 68.9 86.2
150 380/60/3 3.1 13.2 13.2 1.7 1.7 36.2 39.5 49.4
175 220/60/3 6.0 26.0 26.0 4.5 4.5 73.5 80.0 99.5
175 380/60/3 3.5 15.0 15.0 2.6 2.6 42.5 46.2 57.5
200 220/60/3 9.1 32.4 32.4 4.5 4.5 91.0 99.1 123.4
200 380/60/3 5.3 18.7 18.7 2.6 2.6 52.6 57.3 71.3
250 220/60/3 9.1 35.0 51.0 4.5 4.5 116.9 129.6 167.9
250 380/60/3 5.3 20.0 29.0 2.6 2.6 66.8 74.0 95.8
300 220/60/3 11.3 51.0 51.0 4.5 4.5 135.1 147.8 186.1
300 380/60/3 6.5 29.0 29.0 2.6 2.6 77.0 84.2 106.0

50Hz
Electrical Water Comp Comp Fan Fan Unit Rec. Max
Model Power Pump 1 2 1 2 MCA Fuse Fuse
(V/Hz/Ph) FLA RLA RLA FLA FLA Size Size
050 380-415/50/3 1.1 7.4 - 1.5 - 11.9 13.7 19.3
075 380-415/50/3 1.4 11.6 - 1.5 - 17.4 20.3 29.0
100 380-415/50/3 1.4 7.4 7.4 2.2 - 20.3 22.1 27.7
125 380-415/50/3 1.7 8.7 8.7 2.2 - 23.5 25.7 32.2
150 380-415/50/3 1.7 11.6 11.6 1.5 1.5 30.8 33.7 42.4
175 380-415/50/3 2.0 13.0 13.0 2.2 2.2 36.5 39.8 49.5
200 380-415/50/3 2.8 15.1 15.1 2.2 2.2 41.2 45.0 56.3
250 380-415/50/3 2.8 15.0 25.0 2.2 2.2 53.5 59.7 78.5
300 380-415/50/3 5.9 25.0 25.0 2.2 2.2 66.6 72.8 91.6
Note:
• All voltages supply must fall within the utilization range of ±10 %
• Minimum Circuit Ampacity (MCA) = Largest Load x 1.25 + Sum of additional Loads. (Used for sizing wire)
• Recommended Fuse Size (REC) = Largest Load x 1.5 + Sum of additional Loads. (Select closest fuse size)
• Maximum Fuse Size (MFS) = Largest Load x 2.25 + Sum of additional Loads. (Select equal or next lower fuse size)

11 CGA-SVX01B-EN
FLOW SWITCH INTERLOCK

Circuit Diagram 1 :
For CGAK 030~075

© American Standard Inc. 2004 12 CGA-SVX01B-EN


Circuit Diagram 2 :
For CGAR 030~075

13 CGA-SVX01B-EN
Circuit Diagram 3 :
For CGAK 100~200

© American Standard Inc. 2004 14 CGA-SVX01B-EN


Circuit Diagram 4 :
For CGAR 100~200

15 CGA-SVX01B-EN
Circuit Diagram 5 :
For CGAK 250~300

© American Standard Inc. 2004 16 CGA-SVX01B-EN


INSTALLATION CHECKLIST EVAPORATOR PIPING ELECTRICAL WIRING
 Flush and clean all chilled water piping.
RECEIVING CAUTION: Use only copper conductors
 Verify that unit nameplate data CAUTION: If using an acidic commercial to prevent galvanic corrosion and
corresponds with sales order information. flushing solution, construct a temporary overheating at terminal connections.
 Inspect unit for shipping damages and bypass around the unit to prevent
 Connect unit power supply wiring (with
material shortages; report any damages damage to the evaporator.
fused disconnect) to appropriate
or shortages found to the carrier.
CAUTION: To avoid possible equipment terminals on terminal block (TB) in power
UNIT LOCATION AND MOUNTING damage, do not use untreated or section of unit control panel.
 Inspect unit installation location for improperly treated water.  In order to turn on/off the chiller from
adequate ventilation. indoors, connect wiring across reserved
 Make evaporator water connections.
 Provide drainage facilities for water terminals 2 & 3 in the unit control panel
 Vent the air from chilled water system at
accumulated from the base. from an indoor REMOTE OFF/ON switch.
high points.
 Remove and discard any shipping  Properly ground the unit, the chilled water
 Install pressure gauges, thermometers
materials (e.g. cartons, crates, etc.) pump motor, all disconnects, and other
and shutoff valves on water inlet and
 Inspect to determine that service access devices which require grounds.
outlet piping.
clearances are adequate.  Install wiring to connect flow switch to unit
 Install water strainer in evaporator supply
 Install optional unit neoprene-in-shear or control panel.
line.
spring isolators.
 Install balancing valve and flow switch on FOR NO-PUMP OPTION ONLY
Secure unit to mounting surface.
water outlet piping.  Connect chilled water pump power supply
Level the unit.
wiring (with fused disconnect) to the
proper terminals of the chilled water
pump.
 Install wiring to connect chilled water
pump switch to chilled water pump
starter.
 Connect auxiliary contacts of chilled
water pump starter to flow switch and unit
control panel.

17 CGA-SVX01B-EN
PRE-START PROCEDURES

VOLTAGE UTILIZATION VOLTAGE IMBALANCE The 2.2% imbalance that exists in the
example above exceeds maximum
RANGE Excessive voltage imbalance between
phases in all 3-phase system will cause allowable imbalance by 0.2 %. This much
Electrical power to the unit must meet imbalance between phases can equal as
stringent requirements for unit to operate motors to overheat and eventually fail.
Maximum allowable imbalance is 2 %. much as 20 % current imbalance with a
properly. Total voltage supply and voltage resulting increase in winding temperature
imbalance between phases should be within Voltage imbalance is defined as follows:
that will decrease compressor motor life.
the following tolerances. 100x Va-Vd
% Voltage Imbalance =
Va
Measure each leg supply voltage at all line WATER FLOW RATE
voltage disconnect switches. Readings must Where
Establish a balanced water flow through the
fall within the voltage utilization range shown Va = (V1 + V2 +V3) / 3(Average Voltage)
unit. Flow rates should fall between the
on the unit nameplate (±10%). If voltage on V1, V2, V3 = Line Voltages
minimum and maximum values indicated in
any leg does not fall within the tolerance, Vd = Maximum Line Voltage deviation from Va
TABLE 3. Evaporator water flow rates below
notify the power company to correct this Example: the minimum acceptable values will result in
situation before operating the unit. If the three voltages measured at the line 221 a stratified flow; this reduces heat transfer
Inadequate voltage to the unit will cause Volts, 230 Volts, and 227 Volts, the average and causes either loss of expansion valve
control components to malfunction and (Va) would be: control or repeated nuisance low pressure
shorten the life of electrical components and Va = (221 + 230 + 227)/3 = 226 Volts cutouts. Conversely, excessively high flow
compressor motors. then Vd = 221 Volts rate may cause erosion in the water system.
The percentage of imbalance is then:
100x 226-221
2.2%
226

© American Standard Inc. 2004 18 CGA-SVX01B-EN


Table 3 : Unit Water Flow Rate UNIT WATER PRESSURE
60Hz Units: LPM
DROP
Model Minimum Flow Rated Flow Maximum Flow
Measure the water pressure rise across the
030 18.5 27.7 38.8
standard unit (with built-in pump). The
040 22.9 34.3 48.0 Externally Available Head (E.A.H) should
050 30.2 45.3 63.4 approximate those indicated by the E.A.H.
075 44.9 67.3 94.2 curves, with the corresponding flow rates.
100 59.1 88.7 124.2 For units (without built-in pump) with field-
125 74.7 112.0 150.0 installed pump outside the unit, water
150 89.5 134.3 150.0 pressure drop across the unit should
approximate those indicated by the Internal
175 102.6 154.0 175.0
Pressure Loss (I.P.L.) curves, with the
200 120.0 180.0 240.0
corresponding flow rates.
250 147.3 221.0 290.0
300 175.3 263.0 350.0 For standard unit with built-in pump, refer to
the E.A.H. curve for the system hydraulic
design. For optional unit without a built-in
50Hz Units: LPM
pump, refer to the I.P.L. curves. (Refer to
Model Minimum Flow Rated Flow Maximum Flow
Figure 6 for hydraulic characteristics of all
050 25.1 37.7 56.6
models.)
075 37.3 56.0 84.0
100 49.1 73.7 110.6
125 62.1 93.3 140.0
150 74.4 111.7 150.0
175 85.5 128.3 160.0
200 98.3 149.0 190.0
250 124.6 187.0 240.0
300 148.6 223.0 300.0

19 CGA-SVX01B-EN
Figure 6 :
Hydraulic Characteristics - 60Hz

© American Standard Inc. 2004 20 CGA-SVX01B-EN


50Hz

21 CGA-SVX01B-EN
PRE-START CHECKLIST NOTE: With the water pump operating,
 Inspect all wiring connections; electrical
throttle the water flow to approximately
connections should be clean and tight. 50% of the full flow rate. Following the
 Check power supply voltage to the unit at
manufacturer’s instructions, adjust the
the main power fused disconnect switch. flow switch contacts to open at this
 Fill the chilled water circuit, leaving the
point. Use an ohmmeter to verify opening
system air vents open. Close vents after and closure of the flow switch contacts.
all air is out, and the system is completely  Stop the chilled water pump.
filled.  Open all fused disconnect switches.
 Remove jumper wire across terminals 1  Make electrical connection of flow switch
and 5 (in the control panel) for water to terminals 1 & 5 in the control panel.
system testing.
 Close the fused disconnect switch and
start the unit by turning the REMOTE/
OFF/ON switch to ON position. Pump
should start and with water circulating
through the chilled water system, inspect
all piping connections for leaks and make
any necessary repairs.
 Adjust the water flow rate through the
chilled water circuit, and check the
external available water pressure of the
unit (for standard unit) or the evaporator
water pressure drop for the no-pump
option unit.

© American Standard Inc. 2004 22 CGA-SVX01B-EN


OPERATION

START-UP PROCEDURE  Check compressor amp draw.  Measure system subcooling.


 Check electrical power supply.
 Close the fused disconnect switch and Normal subcooling for each circuit is 6.7°C
 Check the liquid line sight glasses.
turn REMOTE/OFF/ON switch to ON. to 12.2°C ARI conditions (12.2°C entering
Pump will start immediately. After 2 NOTE: Bubbles in the liquid line may water, 6.7°C leaving water, and 35°C
minutes, compressors1 will start. 1 indicate either a low refrigerant charge, ambient temperature). If subcooling for
minute later, compressor2 will start or excessive pressure drop in the liquid either circuit is normal but subcooling is not
(only in units with two refrigerant circuits). line. Such a restriction can often be in this range, check superheat for the circuit
 For CGAR models, turn REMOTE/OFF/ identified by a noticeable difference in and adjust, if required. If superheat is normal
ON switch to ON as described above, line temperature on either side of the but subcooling is not, contact a qualified
turn the already installed indoors cooling restricted area. (Frost often forms on the service technician.
and heating mode switch to cooling outside of the liquid line at the point of
 If operating pressure, sight glass,
mode, then the operation of the chiller restriction, as well). Bubbles are not
superheat and subcooling readings
would be similar to what is described necessarily a symptom of improper
indicate refrigerant shortage, find and
above. As for start-up with heating mode, system operation.
repair leaks and, gas-charge refrigerant
first turn REMOTE/OFF/ON switch to CAUTION: A clear sight glass does not into each circuit. Refrigerant shortage is
OFF. Then, turn the cooling and heating necessarily mean that the system is indicated if operating pressures are low
mode switch to heating. Finally, turn the sufficiently charged; be sure to consider and subcooling is also low.
REMOTE/OFF/ON switch to ON (see system superheat, subcooling, and unit
section on electrical wiring of the CAUTION: If suction and discharge
operating pressures and ambient
installation checklist). pressures are low, but subcooling is
temperatures.
normal, no refrigerant shortage exists.
Once the unit has operated for at least 30
Proper unit refrigerant charge-per circuit-is Adding refrigerant will result in
minutes and the system has stabilized,
indicated on the unit nameplate. overcharging.
complete the following checklist to ensure
proper unit operation.  Measure system superheat. Add refrigerant vapor with the unit running
by charging through the access port on the
 Re-check unit water flow and pressure Normal system superheat is 6.7°C to 8.3°C
suction line until operating pressures are
rise (for no built-in pump unit with field- for each circuit at ARI conditions (12.2°C
normal.
installed pump system). These readings entering water, 6.7°C leaving water, and
should be stable at proper levels. 35°C ambient temperature). If the superheat  If operating pressures indicate an
 Measure unit suction and discharge measured for either circuit does not fall overcharge, slowly (to minimize oil loss)
pressures by installing pressure gauges within this range, alter the setting of the recover refrigerant at the liquid line
on the discharge and suction line access superheat adjustment on the thermal service valve.
ports. Normal operation should render expansion valve to obtain the desired  Be sure that all remote sensing bulbs are
suction pressure in the range of 50-85 reading. Allow 15 to 30 minutes between properly installed in bulb wells with heat
psig and discharge pressure 200-310 adjustments for the expansion valve to transfer grease. Remote bulb capillary
psig. stabilize at each new setting. tubes must be secured (i.e. protected
from vibration and abrasion) and
undamaged.
 Inspect the unit. Remove any debris,
tools and hardware. Secure all exterior
panels, including the control and
compressor access panels. Replace and
tighten all retaining screws.

23 CGA-SVX01B-EN
EXTENDED UNIT SHUT-DOWN/ 3. Remove compressor delay on timer(s) STANDARD AMBIENT
(TR1, TR2). Record down the original
WINTERIZATION OPERATION
socket for the respective timer so that the
If the system is taken out of operation for correct timer(s) are replaced correctly Standard unit will operate in outdoor ambient
long periods of time for any reasons (e.g., temperature down to 15°C.
later.
seasonal shutdown), use this procedure to 4. Close the unit disconnect switch for power
prepare the system for shutdown. OPTIONAL LOW AMBIENT
supply.
1. Check the refrigerant piping for leaks, 5. Turn the REMOTE/OFF/ON switch to ON OPERATION (CGAK)
fixing any that exist. position. With water circulating through A factory installed Low Ambient Unit (LAU)
2. Service the chilled water pump and any the chilled water system, inspect all
option will enable units to operate at outdoor
air handling equipment according to the piping connections for leaks and make low ambient temperature (see Table 4).
manufacturers recommendtions. any necessary repairs.
3. Open both electrical disconnect switches 6. Adjust the water flow rate, using the
balancing valve, through the chilled water
OPTIONAL HEAT PUMP
for the unit and chilled water pump; lock
both disconnects in the open position. circuit, and check the water pressure rise OPERATION (CGAR)
(or drop) through the unit. A factory installed heat pump unit (CGAR)
WINTERIZATION: Close all evaporator
7. Adjust the flow switch (installed on the option will enable units to get either cooling
water supply valves and drain the
unit outlet piping) to provide proper and heating performance (not simultaneous).
evaporator by removing the drain plug
operation. When the unit is switched to heating mode,
and opening the vent on the entering
the four-valve is activated. Evaporator
water line just outside the unit. Re-install NOTE: With the unit operating, throttle
becomes the condenser while the condenser
the drain plug. Since the evaporator does the water flow to approximately 50% of
becomes the evaporator. There are two
not drain completely, add ethylene glycol the full flow rate. Following the
liquid lines in a CGAR unit. One is for cooling
antifreeze to the remaining water through manufacturer’s instructions, adjust the
mode while another is for heating mode.
the vent or evaporator drain hole, to keep flow switch contacts to open at this
the water from freezing. Protect system point. Use an ohmmeter to check for To carefully measure the high pressure,
to 5.5°C below the expected ambient contact opening and closure. there are two access ports in these two
temperature. liquid lines. If you operate this unit in cooling
8. Stop the unit by turning the REMOTE/
mode, connect high pressure gauge to the
SYSTEM RESTART AFTER EXTENDED OFF/ON switch to OFF position.
access port of the cooling liquid line. While
SHUTDOWN 9. Replace compressor delay on timer (TR1,
operating this unit in heating mode, must
1. Remove winterization antifreeze as it can TR2) back to their original sockets.
change the connection to the access port of
reduce system capacity.
This unit now is ready for normal operation. the heating liquid line.
2. Fill the chilled water circuit by opening the
gate valves at the returning and supply A timer override low pressure switch delays
water piping. Be sure to vent the system for 2 minutes to prevent nuisance trip-outs.
while filling it, and close the vents when
system is full.

© American Standard Inc. 2004 24 CGA-SVX01B-EN


ELECTRICAL CONTROL & during normal unit operation, the leaving For Single Refrigeration Circuit Operation
chilled water temperature falls to the trip For units with only one refrigerant circuit, the
PROTECTION SYSTEM point, the FU will open to interrupt compres- operation of water pump, fan and compres-
Low Pressure Cutouts (LP1, LP2) sor operation. sor is exactly the same. The only difference
These units are protected by low pressure is the unit will operate the single compressor
When leaving chilled water temperature falls
cutouts that open and stop compressor from any temperature over 14.0 °C and 10.
down, the suction temperature also falls
operation if the operating pressure drops 0°C when the compressor will stop.
down. For further protection to avoid freeze
below 25 ± 4 psig . The cutout automatically damage, another freezestat ( FS1 , FS2 ) in Heating Mode
resets when the pressure reaches 50 ± 4 contact with the suction line. If suction Water Temperature Thermostat
psig. The LP is a SPDT device and if it temperature falls to the trip point , the FS1 Operation (TS3, TS4) for cooling mode
opens at low ambient start-up, there will be (FS2) will open to interrupt compressor
a 2 minute override to prevent nuisance For Double Refrigeration Circuit Operation
operation.
trip-outs ( for LAU only). At start-up, pump will come on immediately.
Motor Overloads Two minutes after the pump is on and EWT
High Pressure Cutouts (HP1, HP2) These units have internal compressor and (entering water temperature)is below 38.
These units have high pressure cutouts that condenser fan motor overloads to protect 0°C, compressor 1 will start. One minute
open and stop compressor operation if the the motors from overcurrent and overheat- later, if EWT is below 39.0 °C, compressor
discharge pressure reaches 400 ± 7 psig. ing conditions and automatically reset as 2 will start.
The cutout automatically resets when soon as they cool sufficiently. Pump motor
pressure drops to 300 ± 20 psig. When heating demand is met and EWT
has thermal overload installed at the load
rises to 42.0 °C, compressor 1 will stop, if
Reset Relays (CR1,CR2) contactor. Pump overload needs manual
EWT continues to rise to 43.0 °C,compres-
If the unit is shut down by safety devices reset.
sor 2 will stop. Subsequently,when load
(LP, HP, FS, FU, KF etc.) the reset relay Cooling Mode builds up and EWT drops to 39.0 °C,
locks out the compressor contactor (MC1, Water Temperature Thermostat compressor 2 comes on, and if EWT
MC2). This prevents the system from Operation (TS1, TS2) for cooling mode drops further to 38.0 °C, compressor 1
recycling until the condition that caused the comes on. Pump remains on unless the unit
safety devices to trip is determined and For Double Refrigeration Circuit Operation
is turned off.
corrected. At Start-up, the pump will come on
immediately. Two minutes after the pump is For Single Refrigeration Circuit Operation
CAUTION: To prevent unit damage, do on and EWT(entering water temperature)is For units with only one refrigerant circuit, the
not reset the control circuit until the above 14.0 °C, compressor 1 will start. operation of water pump, fan and compres-
cause of the safety lockout is identified One minute later, if the EWT is above 13. sor is exactly the same. The only difference
and corrected. 5°C, compressor 2 will start. is the unit will operate the single compressor
To reset CR1 and CR2, open and reclose from any temperature below 38.0 °C and 42.
When cooling demand is met and EWT
the unit REMOTE/OFF/ON switch. 0 °C when the compressor will stop.
drops to 10.0 °C. Compressor 1 will stop,if
Anti-freeze Cutout (FS1, FS2, FU) EWT continues to fall to 9.5 °C,compressor
The FS and FU are designed to protect the  2 will stop. Subsequently,when load
evaporator from freeze damage in the event builds up and EWT rises to 13.5 °C com-
of a water temperature thermostat (WTT) pressor 2 comes on, and if EWT rises
malfunction or restricted water flow. The further to 14.0°C, compressor 1 comes on.
FU’s remote sensing bulb is mounted at the Pump remains on unless the unit is turned
outlet end of the evaporator, where it off.
monitors leaving water temperature. If

25 CGA-SVX01B-EN
Table 4 : Range of Operating Ambient
Model Standard Unit Low Ambient Unit (If LAU option is added)
All Models Cooling Mode 15˚C-46˚C 7°C-46°C
All Models Heating Mode Above 10˚C Above -4˚C

Table 5 : Control Settings and Time Delays


Control Description Electrical Designation Contacts Open Contacts Close (Reset)
High Pressure Cutoff HP1, HP2 4007 psig 30020 psig
Low Pressure Cutoff LP1, LP2 254 psig 504 psig
Antifreeze Cutout (Refrigerant Side) FS1, FS2 -3˚C2.0˚C 3˚C2.0˚C
Antifreeze Cutout (Water Side) FU 1.8˚C1.5˚C 7˚C1.5˚C
1st compressor On Delay TR1 Normally Open, Time Closed 2 Minutes
2nd compressor On Delay TR2 Normally Open, Time Closed 3 Minutes
Low Suction Pressure Override Delay (CGAR) TR3, TR4 Normally Closed, Time Open 2 Minutes

© American Standard Inc. 2004 26 CGA-SVX01B-EN


Maintenance

Once the unit has been operating for about Monthly Annually
30 minutes and the system has stabilized,  Check suction and discharge pressures  Perform all monthly maintenance
check operating conditions and complete the for normal operating pressures. procedure.
checkout procedure described below:  Check the liquid line sight glass indicator  Have a qualified service technician check
for normal operating conditions. the setting and function of each control
If operating pressures and sight glass and inspect the condition of all contactors
conditions indicate a refrigerant shortage, and replace as necessary.
measure system superheat and  Drain water from unit. Inspect piping for
subcooling. damage. Clean out the built-in water
 If operating conditions indicate an strainer and any other in-line water
overcharge, slowly (to minimize oil loss) strainer.
recover refrigerant from the schraeder  Clean and repaint any corroded surfaces.
valve.  Clean condenser coil with soft brush and
 Open the unit disconnect switch; then water spray.
manually rotate the condenser fan(s) to  Inspect the expansion valve(s) sensing
ensure proper orifice clearance. bulbs for cleanliness; clean if required.
 Inspect the fan mounting bolts for These bulbs must make good contact
tightness. with the suction lines and must be
 Check fan set screws for tightness. properly insulated.
 Please clean up internal and pipe’s  Clean condenser fan.
strainer once the unit first starts running
and monthly after use.

27 CGA-SVX01B-EN
TROUBLE ANALYSIS

A. Compressor Neither Starts Nor Hums


Probable Cause Recommended Action
(1) No power to unit Check for followings:
a. Disconnect switch open
b. Fuse(s) blown
(2) No call for cooling Check for followings:
a. Defective thermostat
b. Broken or improper control wiring
c. Blown control power fuse
(3) Compressor start delay (TR1,TR2) timer has not timed out time out Wait at least 2 minutes for the timer to time out
(4) Unit locked out by reset relay (CR) Check for the followings:
a. Excessive discharge pressure
b. Defective high pressure control
c. Low charge; Low pressure cut-out
d. Gate/water valve not open causing flow switch or anti-freeze
cutoff to trip
e. Fan motor internal temperature switch open
f . Defective reset relay contact
(5) Compressor contactor will not close Check for the followings:
a. Defective compressor contactor
b. Improper wiring
c. Reset relay (CR) open
d. Low pressure cut-out open
(6) Compressor winding stat open Check compressor amp draw

B. Compressor Hums, But Will Not Start


Probable Cause Recommended Action
(1) Low voltage at compressor Check for the followings:
a. Single blown fuse
b. Low line voltage
c. Defective compressor contactor
d. Loose wiring connections
(2) Defective compressor Check for the followings:
a. Open motor winding
b. Excessive amp draw on all phases
(3) Insufficient starting voltage (Single-Phase Units Only) Check for the followings:
a. Defective start capacitor
b. Defective start relay

© American Standard Inc. 2004 28 CGA-SVX01B-EN


C. 2nd Stage Compressor Fails To Start
Probable Cause Recommended Action
(1) Time delay contacts fail to close Replace time delay relay
(2) No call for cooling Check for the followings:
a. Defective thermostat
b. Broken or improper control winding
(3) Unit locked out by reset relay (CR) See (A) item (4)
(4) Compressor contactor will not close See (A) item (5)

D. Compressor Short Cycles


Probable Cause Recommended Action
(1) Intermittent contact in control circuit Check for the followings:
a. Defective relay contacts
b. Loose wiring connections

E. Compressor Runs Continuously


Probable Cause Recommended Action
(1) Unit undersized for load (cannot maintain water temperature) Check for cause of excessive load
(2) Thermostat setpoint too low Readjust thermostat
(3) Defective thermostat or control wiring Replace thermostat
Replace or repair control wiring
(4) Welded contacts on compressor contactor Repair or replace contactor
(5) Leaky valves in compressor (indicated by abnormally low Replace compressor
discharge and high suction pressures)
(6) Shortage of refrigerant (indicated by reduced capacity, high Find and repair refrigerant leak
superheat, low subcooling, and low suction pressure) Recharge system

F. Compressor Motor Winding Stat Open


Probable Cause Recommended Action
(1) Excessive load on evaporator (indicated by high supply water Check for the followings:
temperature) a. Excessive water flow
b. High return water temperature
(2) Lack of motor cooling (indicated by excessive superheat) Check for the followings:
a. Improper expansion valve setting
b. Faulty expansion valve
c. Restriction in liquid line
(3) Improper voltage at compressor Check for the followings:
a. Low or imbalanced line voltage
b. Loose power wiring
c. Defective compressor contactor
(4) Internal parts of compressor damaged Replace compressor

29 CGA-SVX01B-EN
G. Compressor is Noisy
Probable Cause Recommended Action
(1) Internal parts of compressor damaged or broken (compressor Replace compressor
knocks)
(2) Liquid floodback (indicated by abnormally cold suction line and Check and adjust superheat
low superheat)
(3) Liquid refrigerant in compressor at start-up (indicated by Check for refrigerant overcharge
abnormally cold compressor shell)

H. System Short of Capacity


Probable Cause Recommended Action
(1) Low refrigerant charge (indicated by high superheat and low Add refrigerant
subcooling)
(2) Clogged filter drier (indicated by temperature change in Replace filter drier or filter drier core
refrigerant line through drier)
(3) Incorrect expansion valve setting Readjust expansion valve
(4) Expansion valve stuck or obstructed(i.e., high superheat and Repair or replace expansion valve
high water temperature)
(5) Low evaporator water flow Check strainers. Adjust water flow
(6) Noncondensibles in system Evacuate and recharge system
(7) Leaky valves in compressor (i.e., operation at abnormally high Replace compressor
suction and low discharge pressures)

I. Suction Pressure Too Low


Probable Cause Recommended Action
(1) Shortage of refrigerant (i.e., high superheat, low subcooling) Find and repair leak; recharge system
(2) Thermostat set too low (i.e., low discharge pressure, low leaving Readjust thermostat
water temperature)
(3) Low water flow Check for clogged strainers and ncorrect balancing valve settings
(4) Clogged filter drier Check for frost on filter drier. Replace if needed
(5) Expansion valve power assembly has lost charge Repair or replace expansion valve power head assembly
(6) Obstructed expansion valve (i.e., high superheat) Clean or replace valve

J. Suction Pressure Too High


Probable Cause Recommended Action
(1) Excessive cooling load (i.e., high supply water temperatures) See (E) above
(2) Expansion valve overfeeding (i.e.,superheat too low, liquid Adjust superheat setting; verify that remote bulb is properly attached
flooding to compressor) to suction line
(3) Suction valves broken (i.e. noisy compressor) Replace compressor

© American Standard Inc. 2004 30 CGA-SVX01B-EN


K. Discharge Pressure Too Low
Probable Cause Recommended Action
(1) Shortage of refrigerant (i.e., low subcooling, high superheat, Find and repair leak; recharge system
bubbles in sight glass)
(2) Broken or leaky compressor discharge valves Replace compressor
(3) Defective low pressure switch Replace defective control
(4) Unit running below minimum operating ambient Provide adequate head pressure controls, or an ambient lockout
switch

L. Discharge Pressure Too High


Probable Cause Recommended Action
(1) Too little or too warm condenser air; airflow restricted Clean coil; Check fans and motors for proper function
(2) Air or non-condensable gas in system (i.e., exceptionally hot Evacuate and recharge system
condenser)
(3) Refrigerant overcharge (i.e., high subcooling, low superheat, Recover excess refrigerant
high suction pressure)
(4) Excessive system load Reduced load
(5) Defective condenser fan or fan pressure control (i.e., 1 fan off, Repair or replace switch
high condenser pressure)

M. System Cannot Heating Mode (CGAR Model Only)


Probable Cause Recommended Action
(1) Broken or improper control wiring Check control wiring
(2) Defective four-way valve Replace four-way valve

N. Suction Pressure Too Low - Heating Mode (CGAR Model Only)


Probable Cause Recommended Action
(1) Low refrigerant charge Add refrigerant
(2) Too little or too cold evaporator air; airflow restricted Clean coil; Check fans and motors for proper function
(3) Unit running below minimum operating ambient Provide an ambient lockout switch
(4) Expansion valve power assembly has lost charge Repair or replace expansion valve power head assembly

O. Discharge Pressure Too High - Heating Mode (CGAR Model Only)


Probable Cause Recommended Action
(1) Low water flow Check for clogged strainers and incorrect balancing valve settings
(2) Defective heating thermostat switch a. Verify that sense bulb is properly inserted bulbwell of
heat-exchanger
b. Replace heating thermostat switch

31 CGA-SVX01B-EN
FM38631
ISO 9001 Qualified factory - Trane Taiwan

North American Group Literature Order Number CGA-SVX01B-EN-0404


The Trane Company
File Number CGA-IOM-7
3600 Pammel Creek Road
La Crosse, Wl 54601-7599 Supersedes CGA-SVX01A-EN-0701

http : // www.trane.com Stocking location Taipei, Taiwan

Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design and
An American-Standard Company specifications without notice.

S-ar putea să vă placă și