Documente Academic
Documente Profesional
Documente Cultură
#: 43651
PAI120161
14 1/2"
BEAM "G" DETAIL BEAM "H" DETAIL
12" 12"
N3 L L C
7 1/2" (BAND "C")
6 1/2" (PLATE "H2") 78 1/4"
285° 75°
0"
J J A&B A&B
G (10) PLCS. H2
H H 38°
G C TYP.
F BAND "C" SHOWN AS A PLATE
FOR DETAIL PURPOSES ONLY. 1/2"
BEAM "J" DETAIL 120" X 161" NON-CODE
C 1"
DRAWING APPROVAL
SAFETY RELIEF DEVICES SHALL BE
328° 32° 6" 11"
THE RESPONSIBILITY OF THE END USER
20° B B
B C 20° PLEASE INDICATE APPROVAL FOR
0° SEAMS "S1" & "S3" LEAVE A GAP IN BAND "C" DRAWING & RETURN TO QUICK TANKS
345° 6 3/4" 3" AROUND SEAM "S3"
SEAM "S2" APPROVED AS DRAWN.
PROCEED WITH FABRICATION.
6 1/2" C 75°
NOTES: A SEAM "S3" APPROVED AS NOTED. PROCEED WITH
FABRICATION IN ACCORDANCE WITH NOTED
1. DIMENSIONS SHOWN IN ( ) ARE FOR REFERENCE ONLY. 1 1/4"
A
COPE TO FIT CHANGES. RESUBMIT CORRECTED DRAWING.
INSIDE BEAM "J"
2. NO LINING WARRANTY ABOVE 120 F. (SAME FOR BEAM "K") DISAPPROVED. DO NOT FABRICATE.
3. BOLT HOLES OF FLANGES TO STRADDLE MAJOR VESSEL DETAIL Z S3 BEAM "L" DETAIL RESUBMIT DRAWING FOR APPROVAL.
1 1/2"
CENTERLINES.
BY DATE
1" 3/4"
NON-CODE
QUICI
PAI120161
4. SEISMIC & WIND LOADING DESIGN PER IBC 2006 FOR REV. DESCRIPTION DATE APPROVED
INSTALLATION LOCATION. 2" 2" TANKS, Inc.
5" KENDALLVILLE, INDIANA USA
5. LEAVE A 5/16" GAP BETWEEN LIFT LUG REPADS. 4"
WELD CONTINUOUSLY AROUND EACH PART. ANCHOR PAD DETAIL DATE: 9/17/12 DRAWN BY: JM SIZE: B SCALE: NTS
THIS PRINT, IN ALL MEDIA FORMATS, IS THE SOLE PROPERTY OF QUICK TANKS, INC. REPRODUCTION OR DISSEMINATION IS STRICTLY PROHIBITED WITHOUT PRIOR WRITTEN CONSENT.
CUST: PURE AQUA, INC. SIZE: 24" PO #: 11046 W.O. #: 43651
DAVIT ASSY. FOR 24" WELDNECK
MOD. #: DAVIT ASSY. FOR 24" WELDNECK INT: PER VESSEL DRAWING QTY: 1
SHEET: 1 OF 1 WT: 259 LBS. EXT: PER VESSEL DRAWING DUE: 10/26/12
TT______ HT______ 50 PSI SN:
ITEM Part # Qty. Description
A 963004 1 COVER PLATE 3/4" X 32" DIA. SA-516-70
K B 337111 1 GASKET 24" FOR BLIND FLANGE
J C 380028 1 LIFT LUG 1/2" FORGED
D 119031 1 GUSSET 1/2" X 8-11/16" X 5-13/16"
E 157090 1 2-1/2" SCH. 40 PIPE X 10-1/4"
G F 157090 1 2-1/2" SCH. 40 PIPE X 1/2"
H G 157162 1 BENT PIPE 2" SCH 40. 10"R. CUT TO LENG.
H 380292 1 EYEBOLT 3/4"-10 X 11-15/16" OPEN - WELD SHUT
9/16" A J 380156 1 FLAT WASHER 3/4" SAE PLATED
LIFT LUG NOT
CENTERED ON L-P 1 3/16" K 380065 2 NUT 3/4"-10 HEX PLATED GR.5
COVER PLATE. F L 399999 20 BOLT 1-1/4"-7 X 5" LG. HHCS PLATED
C 23 1/8"
M 380077 40 FLAT WASHER 1-1/4" PLATED
C 3 1/8" N 380164 20 LOCK WASHER 1-1/4" PLATED
P 380076 20 HEX NUT 1-1/4"-7 PLATED
10 1/4"
D
CENTER ON
WELDNECK
FLANGE
21 3/4"
7/8" THRU
R2 1/8"
1 1/2"
2 15/16"
5 13/16"
R10"
3 5/16"
DAVIT ASSY. FOR 24" WELDNECK
NOTES: BY DATE
NON-CODE
1. DIMENSIONS SHOWN IN ( ) ARE FOR REFERENCE ONLY.
QUICI
REV. DESCRIPTION DATE APPROVED
THIS PRINT, IN ALL MEDIA FORMATS, IS THE SOLE PROPERTY OF QUICK TANKS, INC. REPRODUCTION OR DISSEMINATION IS STRICTLY PROHIBITED WITHOUT PRIOR WRITTEN CONSENT.
CUST: PURE AQUA, INC. SIZE: 24" PO #: 11046 W.O. #: 43650
DAVIT ASSY. FOR 24" SLIP-ON
MOD. #: DAVIT ASSY. FOR 24" SLIP-ON INT: PER VESSEL DRAWING QTY: 1
SHEET: 1 OF 1 WT: 262 LBS. EXT: PER VESSEL DRAWING DUE: 10/26/12
50 PSI TT______ HT______ SN:
ITEM Part # QTY. Description
A 963004 1 COVER PLATE 3/4" X 32" DIA. SA-516-70 NOTES:
B 150009 1 WEB 3/4" X 2-5/16" X 9-5/8" 1) WELD "D" TO "E" ONLY, NOT TO "C"
C 157090 1 2-1/2" SCH. 40 PIPE X 10-5/8" 2) CUT THE BOTTOM OFF OF "F" AND INSERT
D 157090 1 2-1/2" SCH. 40 PIPE X 1/2" THRU EYEBOLT BEFORE WELDING TO "A"
3) CENTER "B" AND "F" ON THE FACE
E 157162 1 BENT PIPE 2" SCH. 40 OF THEIR RESPECTIVE FLANGES.
F 380028 1 LIFT LUG 1/2" FORGED - CUT
G 380071 1 EYEBOLT 3/4"-10 X 6-15/16" OPEN
H 380156 1 FLAT WASHER 3/4" SAE PLATED 6"
J 380065 2 NUT 3/4"-10 HEX PLATED GR.5
K 156124 1 HANDLE 1/2" C.R. ROUND X 10-3/8"
L 399999 20 BOLT 1-1/4"-7 X 5" LG. HHCS PLATED 3" R1/2" TYP.
M 380077 40 FLAT WASHER 1-1/4" PLATED 1/2"
N 380164 20 LOCK WASHER 1-1/4" PLATED
ITEM "K"
P 380076 20 HEX NUT 1-1/4"-7 PLATED
Q 337111 1 GASKET 24" FOR BLIND FLANGE
21 13/16"
SLIP-ON FLANGE SHOWN FOR
REFERENCE ONLY & INCLUDED 10 5/8"
IN TANK BOM.
E
D 7/8" THRU
1 9/16"
R8 13/16"
A 1 9/16"
K 20 5/8"
29 9/16"
H J
E
23 1/16"
D
1/2"
12"
R16"
10 5/8"
2 5/16"
DAVIT ASSY. FOR 24" SLIP-ON
1/2"
B
WELDED C
TO
SLIP-ON 9 5/8" 24" DAVIT ASSY.
FLANGE
DRAWING APPROVAL
L-P SAFETY RELIEF DEVICES SHALL BE
THE RESPONSIBILITY OF THE END USER
BY DATE
CONFORMS TO ASME
REV. DESCRIPTION DATE APPROVED
QUICI TANKS, Inc.
KENDALLVILLE, INDIANA USA
REQUIREMENTS DATE: 9/13/12 DRAWN BY: JM SIZE: B SCALE: NTS
THIS PRINT, IN ALL MEDIA FORMATS, IS THE SOLE PROPERTY OF QUICK TANKS, INC. REPRODUCTION OR DISSEMINATION IS STRICTLY PROHIBITED WITHOUT PRIOR WRITTEN CONSENT.
www.hilti.us Profis Anchor 2.3.2
Company: Quick Tanks, Inc. Page: 1
Specifier: Phillip Perlich II Project: PAI120161 - Venezuela
Address: 545 N. Krueger St. Kendallville, IN, USA 46755 Sub-Project I Pos. No.:
Phone I Fax: (260) 347-3850 | Date: 9/20/2012
E-Mail: pperlich@quicktanks.com
Specifier's comments:
1 Input data
Anchor type and diameter: HDA-TR M16x190/40
Effective embedment depth: hef = 7.480 in., hnom = 7.992 in.
Material: 1.4401, 1.4404, 1.4571
Evaluation Service Report:: ESR 1546
Issued I Valid: 4/1/2012 | 3/1/2014
Proof: design method ACI 318 / AC193
Stand-off installation: eb = 0.000 in. (no stand-off); t = 1.000 in.
Anchor plate: lx x ly x t = 4.000 in. x 5.000 in. x 1.000 in.; (Recommended plate thickness: not calculated)
Profile: no profile
Base material: cracked concrete, , fc' = 3555 psi; h = 12.000 in.
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
Seismic loads (cat. C, D, E, or F) yes (D.3.3.5)
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.3.2
Company: Quick Tanks, Inc. Page: 2
Specifier: Phillip Perlich II Project: PAI120161 - Venezuela
Address: 545 N. Krueger St. Kendallville, IN, USA 46755 Sub-Project I Pos. No.:
Phone I Fax: (260) 347-3850 | Date: 9/20/2012
E-Mail: pperlich@quicktanks.com
Compression
3 Tension load
Load Nua [lb] Capacity fNn [lb] Utilization bN = Nua/fNn Status
Steel Strength* 6721 21141 32 OK
Pullout Strength* 6721 13069 52 OK
Concrete Breakout Strength** 6721 10253 66 OK
* anchor having the highest loading **anchor group (anchors in tension)
Variables
n Ase,N [in.2] futa [psi]
1 0.24 116000
Calculations
Nsa [lb]
28188
Results
Nsa [lb] fsteel f Nsa [lb] Nua [lb]
28188 0.750 21141 6721
√2500
'
fc
Npn,f'c = Np,2500 refer to ICC-ES ESR 1546
Variables
f'c [psi] Np,2500 [lb]
3555 22481
Calculations
√2500
'
f c
1.192
Results
Npn,f'c [lb] fconcrete fseismic fnonductile f Npn,f'c [lb] Nua [lb]
26808 0.650 0.750 1.000 13069 6721
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.3.2
Company: Quick Tanks, Inc. Page: 3
Specifier: Phillip Perlich II Project: PAI120161 - Venezuela
Address: 545 N. Krueger St. Kendallville, IN, USA 46755 Sub-Project I Pos. No.:
Phone I Fax: (260) 347-3850 | Date: 9/20/2012
E-Mail: pperlich@quicktanks.com
Ncb = (AA ) y
Nc
Nc0
ed,N yc,N ycp,N Nb ACI 318-08 Eq. (D-4)
f Ncb ≥ Nua ACI 318-08 Eq. (D-1)
ANc see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b)
ANc0 = 9 h2ef ACI 318-08 Eq. (D-6)
( )
1
yec,N = 2 e'N ≤ 1.0 ACI 318-08 Eq. (D-9)
1+
3 hef
(
yed,N = 0.7 + 0.3 1.5h
ca,min
ef
)
≤ 1.0 ACI 318-08 Eq. (D-11)
(
ca,min 1.5hef
ycp,N = MAX c , c
ac ac
)
≤ 1.0 ACI 318-08 Eq. (D-13)
1.5
Nb = kc l √fc hef
'
ACI 318-08 Eq. (D-7)
Variables
hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.] yc,N
6.000 0.000 0.000 9.000 1.000
Calculations
ANc [in.2] ANc0 [in.2] yec1,N yec2,N yed,N ycp,N Nb [lb]
324.00 324.00 1.000 1.000 1.000 1.000 21032
Results
Ncb [lb] fconcrete fseismic fnonductile f Ncb [lb] Nua [lb]
21032 0.650 0.750 1.000 10253 6721
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.3.2
Company: Quick Tanks, Inc. Page: 4
Specifier: Phillip Perlich II Project: PAI120161 - Venezuela
Address: 545 N. Krueger St. Kendallville, IN, USA 46755 Sub-Project I Pos. No.:
Phone I Fax: (260) 347-3850 | Date: 9/20/2012
E-Mail: pperlich@quicktanks.com
4 Shear load
Load Vua [lb] Capacity fVn [lb] Utilization bV = Vua/fVn Status
Steel Strength* 2703 20898 13 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 2703 22084 13 OK
Concrete edge failure in direction y+** 2703 5350 51 OK
* anchor having the highest loading **anchor group (relevant anchors)
Variables
n Ase,V [in.2] futa [psi]
1 0.24 116000
Calculations
Vsa [lb]
32150
Results
Vsa [lb] fsteel f Vsa [lb] Vua [lb]
32150 0.650 20898 2703
( )
1
yec,N = 2 e'N ≤ 1.0 ACI 318-08 Eq. (D-9)
1+
3 hef
(
ca,min 1.5hef
ycp,N = MAX c , c
ac ac
≤ 1.0) ACI 318-08 Eq. (D-13)
1.5
Nb = kc l √fc hef
'
ACI 318-08 Eq. (D-7)
Variables
kcp hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.]
2 6.000 0.000 0.000 9.000
Calculations
ANc [in.2] ANc0 [in.2] yec1,N yec2,N yed,N ycp,N Nb [lb]
324.00 324.00 1.000 1.000 1.000 1.000 21032
Results
Vcp [lb] fconcrete fseismic fnonductile f Vcp [lb] Vua [lb]
42064 0.700 0.750 1.000 22084 2703
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.3.2
Company: Quick Tanks, Inc. Page: 5
Specifier: Phillip Perlich II Project: PAI120161 - Venezuela
Address: 545 N. Krueger St. Kendallville, IN, USA 46755 Sub-Project I Pos. No.:
Phone I Fax: (260) 347-3850 | Date: 9/20/2012
E-Mail: pperlich@quicktanks.com
Vcb = (AA ) y
Vc
Vc0
ed,V yc,V yh,V yparallel,V Vb ACI 318-08 Eq. (D-21)
f Vcb ≥ Vua ACI 318-08 Eq. (D-2)
AVc see ACI 318-08, Part D.6.2.1, Fig. RD.6.2.1(b)
AVc0 = 4.5 c2a1 ACI 318-08 Eq. (D-23)
( )
1
yec,V = 2e'v ≤ 1.0 ACI 318-08 Eq. (D-26)
1+
3ca1
yh,V = √
1.5ca1
ha
≥ 1.0 ACI 318-08 Eq. (D-29)
(( ) )
0.2
l 1.5
Vb = 7 e √da l √f'c ca1 ACI 318-08 Eq. (D-24)
da
Variables
ca1 [in.] ca2 [in.] ecV [in.] yc,V ha [in.]
8.000 9.000 0.000 1.000 12.000
Calculations
AVc [in.2] AVc0 [in.2] yec,V yed,V yh,V Vb [lb]
216.00 288.00 1.000 0.925 1.000 14689
Results
Vcb [lb] fconcrete fseismic fnonductile f Vcb [lb] Vua [lb]
10191 0.700 0.750 1.000 5350 2703
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.3.2
Company: Quick Tanks, Inc. Page: 6
Specifier: Phillip Perlich II Project: PAI120161 - Venezuela
Address: 545 N. Krueger St. Kendallville, IN, USA 46755 Sub-Project I Pos. No.:
Phone I Fax: (260) 347-3850 | Date: 9/20/2012
E-Mail: pperlich@quicktanks.com
6 Warnings
• To avoid failure of the anchor plate the required thickness can be calculated in PROFIS Anchor. Load re-distributions on the anchors due to
elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be sufficiently stiff, in order not to be deformed when
subjected to the loading!
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout Strength
and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout Strength. Refer to
ACI 318, Part D.4.4(c).
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI318 or the relevant standard!
• An anchor design approach for structures assigned to Seismic Design Category C, D, E or F is given in ACI 318-08 Appendix D, Part D.3.3.4 this
requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the case, Part D.3.3.5
requires that the attachment that the anchor is connecting to the structure shall be designed so that the attachment will undergo ductile yielding at
a load level corresponding to anchor forces no greater than the controlling design strength. In lieu of D.3.3.4 and D.3.3.5, the minimum design
strength of the anchors shall be multiplied by a reduction factor per D.3.3.6.
An alternative anchor design approach to ACI 318-08, Part D.3.3 is given in IBC 2009, Section 1908.1.9. This approach contains "Exceptions"
that may be applied in lieu of D.3.3 for applications involving "non-structural components" as defined in ASCE 7, Section 13.4.2.
An alternative anchor design approach to ACI 318-08, Part D.3.3 is given in IBC 2009, Section 1908.1.9. This approach contains "Exceptions"
that may be applied in lieu of D.3.3 for applications involving "wall out-of-plane forces" as defined in ASCE 7, Equation 12.11-1 or Equation
12.14-10.
• It is the responsibility of the user when inputting values for brittle reduction factors (fnonductile) different than those noted in ACI 318-08, Part
D.3.3.6 to determine if they are consistent with the design provisions of ACI 318-08, ASCE 7 and the governing building code.
Selection of fnonductile = 1.0 as a means of satisfying ACI 318-08, Part D.3.3.5 assumes the user has designed the attachment that the anchor is
connecting to undergo ductile yielding at a force level <= the design strengths calculated per ACI 318-08, Part D.3.3.3.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.3.2
Company: Quick Tanks, Inc. Page: 7
Specifier: Phillip Perlich II Project: PAI120161 - Venezuela
Address: 545 N. Krueger St. Kendallville, IN, USA 46755 Sub-Project I Pos. No.:
Phone I Fax: (260) 347-3850 | Date: 9/20/2012
E-Mail: pperlich@quicktanks.com
7 Installation data
Anchor plate, steel: - Anchor type and diameter: HDA-TR, M16x190/40
Profile: no profile; 0.000 x 0.000 x 0.000 in. Installation torque: 1062.089 in.lb
Hole diameter in the fixture: df = 1.260 in. Hole diameter in the base material: 1.181 in.
Plate thickness (input): 1.000 in. Hole depth in the base material: 7.992 in.
Recommended plate thickness: not calculated Minimum thickness of the base material: 11.200 in.
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.
y
2.000 2.000
2.500
3.000
x
1
2.500
2.000
2.000 2.000
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.3.2
Company: Quick Tanks, Inc. Page: 8
Specifier: Phillip Perlich II Project: PAI120161 - Venezuela
Address: 545 N. Krueger St. Kendallville, IN, USA 46755 Sub-Project I Pos. No.:
Phone I Fax: (260) 347-3850 | Date: 9/20/2012
E-Mail: pperlich@quicktanks.com
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan