Page 1 of 6 Bidding Document for 01WS01 Bulk Water Supply Improvement

ANNEXURE
SUMMARY OF PARAMETERS FOR ELECTRICAL SYSTEM DESIGN
(For Raw water and intake pump house)

1. Site Condition :

Design temperature : 45° C Ambient


Max. Relative humidity : 95% RH
Altitude : 150 m above MSL
Atmosphere : Tropical, saline & highly humid, dusty and
coastal climate.

2. Power Supply available

HV distribution voltage : 11kV/3.3kV AC


Expected fault level in : 350 MVA at 11kV, 250MVA at 3.3kV
MVA
DC supply for electrical HT : 110V DC
control circuit and
emergency lighting.
LV distribution voltage with : 415V AC ± 10 % , TPN & 240V AC ± 10 %
permissible variation SPN
Frequency : 50 HZ ± 5 %
Fault level : 36 MVA for 1.0 sec.
System neutral : Solidly earthed

3. HV switch board – :
Indoor/outdoor incomer

Rated voltage/highest : 11/12 kV


system voltage of switch
board
Type of construction : Sheet Steel enclosure panel
Degree of protection for : IP 67
enclosure

Material of bus bar : Copper


Short circuit withstand : 18.37KA for 1 sec. For 11 kV
capacity
Type of circuit breaker : Vacuum Circuit Breaker
Type of main protection : Over current and Earth Fault.
relays
Energy Meter : Electronic digital Load manager with Maximum
demand Indicator

Contractor Employer
Page 2 of 6 Bidding Document for 01WS01 Bulk Water Supply Improvement

4. HV switch board – :
Indoor/outdoor

Rated voltage/highest : 3.3/3.6 kV


system voltage of switch
board
Type of construction : Sheet Steel enclosure panel
Degree of protection for : IP 4X
enclosure
Material of bus bar : Copper
Short circuit withstand : 43.74 KA for 1 sec. For 3.3 kV
capacity
Type of circuit breaker : Vacuum Circuit Breaker
Type of main protection : Over current, Earth Fault, REF and Under
relays Voltage.
Energy Meter : Electronic digital Load manager.

5. FCMA Type Soft Starter :

Rated voltage : 3.3 kV


Type of construction : Sheet Steel enclosure panel
Degree of protection for : IP 41
enclosure
Material of bus bar : Copper
Short circuit withstand : 26.24 KA for 1 sec. For 3.3 kV
capacity
Isolator : On-load
Type of Contactor : Vacuum Contactor
Type of main protection : Motor Protection Relay, Surge suppressor.
relays

6. LV Switch Board :

Designation : PCC, MCC-1&2 APFC Panel


Rater voltage : 415V
Type of construction : Free standing, floor mounting sheet steel
compartmental design in single front
Type of execution : Draw out – Main incomer.
Material of bus bar : Aluminium
Type of outgoing feeder : MCCB Adjustable type
Min. Operating height : 300 mm
Type of cable entry : Bottom
Degree of protection of : IP 52 (min.)
enclosure

Contractor Employer
Page 3 of 6 Bidding Document for 01WS01 Bulk Water Supply Improvement

7. Lighting Distribution :
Board

Location of purposes : These LDB shall be located in pump house,


chemical house, Filter house, Storeroom,
laboratory, etc. All lighting fixtures shall be
controlled from these LDB
Voltage : 440V ± 10% , 50 Hz ± 3%, 3Ph, 4 wire system
fed from PCC
Incomer : 4 pole MCB –9 KA rating & 4 pole ELCB –
100mA.
Type : Wall mounting type with bus bar mounted
MCBs, IP 52.
Outgoing feeders : 9 KA rating MCB

8. Utilisation Voltage :

Motor rated above 0.18 kw : 415V ± 10% AC


& upto 160 kw 50 ± 3% Hz
Motor upto 0-18 kw & : 240V ± 10% AC
convenience outlet 50 ± 3% Hz
Control Voltage for starters : 240V, 1Ph, 50Hz, AC 2 wire
Voltage for Space Heaters : 240V, 1Ph, 50Hz, AC 2 wire

Contractor Employer
Page 4 of 6 Bidding Document for 01WS01 Bulk Water Supply Improvement

Control supply for LT motor : 240V ± 10% (single phase)


starter
Fir alarm system : 240V ± 10% (single phase)

9. Fault Current At Various :


System Voltages

HV distribution system : 11KV– 18.37KA(3ecs), 3.3kV – 43.74kA(1sec)


LV distribution system : 415 V – 36 MVA

10. Short Circuit Withstand :


Time For Feeder Cables

11 KV incomer : 1 sec.
415V incomer : 1 sec.

11. Motor :
HV LV

Rated voltage 3.3 KV 415V ± 10%


Rated of frequency with 50 Hz ± 5%
permissible variation

Anti-condensation space For motor 37 KW & above


heaters shall be required
for motors

BTD & WTD shall be 161 KW & above (simplex – 3 wire type)
required for motor

Degree of protection of IP 55 & suitable for outdoor installation


enclosure IP 23 & suitable for indoor installation

Type of cooling SPDP TEFC


Regressing facility For motor rated 15 KW & above

Starting Soft starter FCMA type DOL/Star-Delta/ATS


:
12. Earthing : Earthing installation will be as IS:3043, Earthing
material will be MS/GI & Jumper to be GI Rope
(not exceeding 300 mm. for motor end.)

Contractor Employer
Page 5 of 6 Bidding Document for 01WS01 Bulk Water Supply Improvement

14. HT cabling : 11/3.3 kV Alu, conductor XLPE insulated


armoured overall PVC sheathed cables shall be
suitable sized for individual equipment motors,
transformers, etc.

15. LT cabling : Alu. / Cu. conductor PVC insulated armoured


overall PVC sheathed cables shall be suitably
sized for individual equipment PCC, LDB,
Lighting and motor load considering derating
factors and voltage drop.

16. Local Control Station for :


Motors

Material of Construction : MS
Push button / Ammeter / : Start, stop for with Ammeter for HT motors.
Lamps Start, Stop for LT motors(Ammeter if specified).
Degree of protection for : IP 55
enclosure
Mounting : Floor/ Structure
Location : These shall be provided near the motor as per
requirement

17. Cable Gland : Double compression type, nickel plated brass


cable gland shall be provided for all cable
termination.

18. Terminal Kit : For all 11/3.3 KV cable, heat shrinkable


Raychem / Similar make indoor type termination
kit shall be used.
19. Lighting Installation :

Illumination Level Level in Lux


: 150
a) Pump House Area

b) Offices : 250

c) Storeroom, Loading 150


:
d) Maintenance Room 100
:
e) Switchgear Room 200

f) Toilet : 100

g) Staircase : 100

h) Outdoor area, Road : 10

Contractor Employer
Page 6 of 6 Bidding Document for 01WS01 Bulk Water Supply Improvement

: 100
i) Substation –
Transformer area
: 100
j) Chemical house/Filter
house : 150

k) Laboratory : 300
l) Passage entrance 100
:

20. Type of fittings : LED/HPSV/Energy efficient fixtures for process


area, outdoor area and general outdoor areas etc.

Industrial vitreous enamelled reflector type


fluorescent light fitting with 2 nos. 28W
fluorescent tube.

21. Street light fitting : [For all open areas]

Light fitting : 43WLED/110W LED lamp street light fitting.

22. Battery & Battery :


Charger

Battery

Type of Battery : Lead acid ( Sealed maintenance free)

Battery Charger

Type of Battery Charger : Solid sate (thyristor control)


Designation of Charger : Float cum Boost
Operation of Battery : Float automatic , Boost manual
Charger (FCBC + FCBC) 2nos.of FCBC with load
sharing feature.

The details provided above are for guidance only subject to details given in tender documents