[SmartStruxure Solution]

Information Technology System


Planning Guide

Commitment to IT-friendly and Identification and Authentication


secure solutions All human users are uniquely identified
Schneider Electric views the deployment, • Admin logon password management (SBO
monitoring, and security of the devices and v1.3)
software that comprise a Building Management
System as essential to the goal of achieving optimal Imported User Accounts are disabled by default
efficiency for a building. As a result, Schneider (SBO v1.7)
Electric is committed to providing an IT- friendly and
secure solution. Certificate functionality for - HTTPS connections

• Self-signed certificates
Scope
• Default certificates (SBO v1.4)
This guide is designed for IT professionals who
© 2017 Schneider Electric. All rights reserved.

need to review the system design and provide • Certificate Authority certificates (SBO v1.6)
support for the system installation.
Password policies can be enforced (SBO v1.6)

SmartStruxure Solution Cybersecurity • Days until password expires


Features • Minimum number of characters
The cybersecurity features in SmartStruxure
• Minimum number of lowercase characters
solution are constantly being enhanced. The
following list of cybersecurity features indicates the • Minimum number of numeric characters
version of StruxureWare Building Operation each
• Minimum number of special characters
feature was introduced in.

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017
[SmartStruxure Solution]
2

• Number of consecutive unique passwords Authorization


before reuse Custom logon banners can be enabled to
• No more than three repeating identical communicate usage policies to operators
characters
• Non-SSH connections (SBO v1.5)
SSH connection control (SBO v1.6)
• SSH connections (SBO v1.6)
• Disabled after failed logon attempts Role-based access control (permissions)
• Time-out for admin free connection re-enabling
• Object level security
• Rate limiting to protect against brute force
attacks Confidentiality
Encrypted transmission of data:
SSH device fingerprint authentication (SBO v1.9)
• HTTPS using TLS 1.0 (SBO v1.2)
Password policies are secure by default:
• HTTPS using TLS 1.1, TLS 1.2 (SBO v1.9)
• Factory settings (SBO v1.7):
• EWS Encrypted Logon (SBO v1.5)
– Days until password expires: Enabled: 90
• Disable use of MD5 configuration option (SBO
days
v1.6)
– Minimum number of characters: 8
• SNMPv3 support, SNMPv1 and v2 removed
– Minimum number of lowercase (SBO v1.5)
characters: 1
• SmartStruxure server device: SSHv2, SSHv1
– Minimum number of numeric characters: 1 removed (SBO v1.5)
– Minimum number of special characters: 1 • Redirect web clients to HTTPS configuration
option (SBO v1.6)
– Number of consecutive unique passwords
before reuse: 6 • SMTPS secure email notification support (SBO
v1.8)
– Do now allow more than three repeating
identical characters: Enabled Clickjacking protection options (SBO v1.9)
• Force Admin password change (SBO v1.7)
Password data is obscured from view
• Password blacklist (non editable) (SBO v1.7):
Passwords are stored and transmitted securely
– 123
– admin CA certificate central log storage (SBO v1.6)
– Admin
Basic secure key management
– admin1
– Admin1 Basic data at rest protection (SBO v1.4)

– Admin1! Integrity
– password Auto logoff (SBO v1.5)
© 2017 Schneider Electric. All rights reserved.

– Password Audit log with system-wide synchronized


– PaSsWoRd timestamps
– Password1! Activity logs provide non-repudiation
Active Directory/Windows Logon support is
available for Workstation only (SBO v1.2). SmartStruxure server device Boot Loader U-Boot
disabled (SBO v1.5)
Enterprise Server Run-As-Service selectable user
account (SBO v1.5). SmartStruxure server device Boot restricted to a
single boot location (SBO v1.5)

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017
[SmartStruxure Solution]
3

SHA2-256 Hash algorithm support (SBO v1.9) Web server access logging configuration option
(SBO v1.6)
WebStation: HTML5 Graphics and Trend viewing
support, removal of JAVA (SBO v1.7) Resource availability
System backup, recovery and reconstitution
Basic protection of audit information
Access to network and security configuration
Basic protection against program and data at rest settings
modification

Basic protection for input validation


IT Overview
Best practice LAN architecture
Basic protection for secure and effective error Servers should be protected against cybersecurity
messages threats by using standard IT hardening methods,
such as a firewall and port filtering. The servers in
Restricted data flow SmartStruxure solution have several internal
Basic capabilities for network segmentation cybersecurity features. However, a defense-in-
depth approach is recommended, particularly when
Basic options for enabling/disabling ports Internet connectivity is required. Direct Internet
connectivity is not supported.
• Disable HTTP (HTTPS only) configuration
option (SBO v1.5) The figure below shows the best practice
architecture for the implementation of a Building
World-writable programs or scripts removed (SBO Management System LAN connected to a
v1.6) Corporate LAN. The primary feature is the presence
of the segregation firewall that effectively decouples
Timely response to events the two networks.
Audit log access

SIEM Support: Remote system logging option


(SBO v1.6)

© 2017 Schneider Electric. All rights reserved.

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017
[SmartStruxure Solution]
4

© 2017 Schneider Electric. All rights reserved.

Figure: IT architecture implementation example

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017
[SmartStruxure Solution]
5

On the Corporate LAN side, there may be many EcoStruxure Web Services is a Schneider
StruxureWare Building Operation WorkStations. Electric web services standard used for
They are used to program and manage the Building integration between systems. In certain
Management System equipment. scenarios, the EcoStruxure Web Services
traffic remains on the Building Management
Mobile and wireless devices are becoming as System LAN, and in other scenarios, the traffic
prevalent in the Building Management System could traverse public networks. As such, the
world as they are in the corporate world. Building firewall needs to be configured according to
management professionals require secure and easy each use case.
access to the Building Management System. The IT
• SSH: This protocol is used for StruxureWare
professional should plan on providing a pathway
Building Operation upgrade operations. The
from the wireless system to the Building
need to have this port open depends on
Management System firewall.
network use policy.
On the Building Management System side, a wide • SNMPv3: This protocol is used to monitor
range of IP devices are operational 24/7/365: servers within a SmartStruxure solution using
standard SNMP Managers supporting SNMP
• StruxureWare Building Operation WorkStations version 3 authentication.
• StruxureWare Building Operation servers • SMTPS: This protocol is used to send secure
(Enterprise Server, License Server, and email messages.
Reports Server) Open port on segregation firewall
• SmartStruxure server devices (Automation The active communication paths should first be
Server and AS-P): These servers use TCP/IP identified between network segments. Refer to the
for their main communications and additionally Communication Paths table and figure to determine
support a wide array of open and proprietary the paths that will be active to support the targeted
serial bus protocols. system design. Then refer to the Network Ports
During normal operation, only a very limited amount table to identify the network ports each path will
of well-defined data needs to pass through the require. All of the required ports should be
firewall, which ensures a simplified configuration of configured for both inbound and outbound
the segregation firewall. communication.

Types of traffic
In general, communication passing through the
segregation firewall is associated with the following
functions:

• HTTPS: This protocol is used for Building


Management System engineering and
monitoring, reports, web services, and
EcoStruxure Web Services.
Table: Communication paths
Communi- Function A-Side B-Side Internet
cation Path Access
© 2017 Schneider Electric. All rights reserved.

A Server to server Enterprise Server, Enterprise Server, Not


communications SmartStruxure SmartStruxure recommended
server device server device

B Administrative Device SmartStruxure No


tool to server Administrator server device
communications

B Administrative License Server License Optional


tool to server Administrator,
communications Enterprise Server

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017
[SmartStruxure Solution]
6

Continued
Communi- Function A-Side B-Side Internet
cation Path Access

B Administrative Software Enterprise Server No


tool to server Administrator
communications

C Server to BMS Enterprise Server, BACnet Device Not


open protocol SmartStruxure recommended
device server device

D Server to BMS Enterprise Server, LON Device No


open protocol SmartStruxure
device server device

E Server to BMS Enterprise Server, Modbus Device No


open protocol SmartStruxure
device server device

F Server to BMS Enterprise Server I/NET System No


proprietary running INET IO
system interface Service

G Server to BMS Enterprise Server MicroNet System No


proprietary
system interface

H Client to server WorkStation, Enterprise Server, Optional


communications Reports Server SmartStruxure
server device

I Client to server WebStation Enterprise Server, Optional


communications SmartStruxure
server device

J Mobile client to Technician Tool Enterprise Server, Not


server Mobile App, SmartStruxure recommended
communications AdaptiApps server device

K System to system Enterprise Server, EcoStruxure Web Optionala


web service SmartStruxure Services based
communications server device client or server

L System to system Enterprise Server, Generic web Optionala


web service SmartStruxure service based
communications server device server

M System to License Server License Activation Required if


Schneider Electric Server Network licenses
cloud service are used. Local
licenses do not
© 2017 Schneider Electric. All rights reserved.

require Internet.

N System to Connect Agent S2 Connect Required for


Schneider Electric Registration online registration
cloud service server from Workstation

O Client to Server WorkStation License Server Optionala


communications

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017
[SmartStruxure Solution]
7

Continued
Communi- Function A-Side B-Side Internet
cation Path Access

P Mobile app to SmartXKiosk, Software Required for


software SmartX AD-Link activation servers mobile app
activation servers activation, one-
time
communication

Q Mobile app to Technician Tool App Store, Optional for


software Mobile App, Google Play, mobile app
download servers AdaptiApps Shell AdaptiApps portal upgrade
App

R Mobile app to AdaptiApps Shell AdaptiApps Required when


software App deployment deployment is
deployment server done from the
server cloud.
Deployment on
premises is
available as an
option.

S Network Service DHCP Server Enterprise Server, Optional


SmartStruxure
server device

T Network Service DNS Server Enterprise Server, Optional


SmartStruxure
server device

U Network Service SNMP Manager Enterprise Server, Not


SmartStruxure recommended
server device

V Network Service SMTP Server Enterprise Server, Optional


SmartStruxure
server device

X Network Service NTP Server Enterprise Server, Optional


SmartStruxure
server device

a) Not recommended over insecure channel.

© 2017 Schneider Electric. All rights reserved.

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017
[SmartStruxure Solution]
8

© 2017 Schneider Electric. All rights reserved.

Figure: Communication paths

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017
[SmartStruxure Solution]
9

Table: Network ports


Function Protocol Default Port Configurable Communi- Optional
(Default State) (TCP/UDP) Port cation Paths Settings

IT HTTP 80 Yes Aa, Ha, I, J, Oa Redirect all


Communication (Disabled) (TCP) WebStation
Protocols connections to
HTTPS

HTTP 80 Yes K, L –
(Unconfigured) (TCP)

HTTPS 443 Yes Aa, Ha, I, J, K, L, For SBO: Disable


(Enabled) (TCP) M, Oa, P, Q MD5 hash
algorithm

SSH 22 – B, M, N –
(Enabled) (TCP)

MQTT 1883 – R –
(Enabled) (TCP)

Proprietary CSP 4444 – Aa, Ha, I, Oa –


Communications (Enabled) (TCP)

FLEXnet Random (TCP)b Yes Oa –


Publisher
Licensing
(Enabled)

License Server 27000-27009 – B, Oa –


(Enabled) (TCP)

License 8888c – B –
Administrator (TCP)
(Enabled)

BMS Open BACnet/IP 47808/33487 Yes C –


Protocol Device (Unconfigured) (UDP)
Interface

LonWorks IP 1628 – D –
(Unconfigured) (UDP)

Modbus TCP 502 – E –


(Unconfigured) (TCP)

I/NET User set from – F –


(Unconfigured) 49152 to 65535.
© 2017 Schneider Electric. All rights reserved.

Default to 50069
for unencrypted
communication
and to 49152 for
encrypted
(UDP)

MicroNet 7001 – G –
(Unconfigured) (TCP)

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017
[SmartStruxure Solution]
10

Continued
Function Protocol Default Port Configurable Communi- Optional
(Default State) (TCP/UDP) Port cation Paths Settings

DHCP 68 – S –
(Enabled) (UDP)

DNS 53 – T –
(Enabled) (TCP/UDP)

SNMPv3 161/162 – U –
(Enabled) (UDP)

SMTP 25 – V –
(Enabled) (TCP)

SMTPS 587 Yes V TLS (Default) or


(Enabled) (TCP) SSL

NTP 123 – X –
(Enabled) (UDP)

a) This communication path uses dynamic port assignment. The port assignment is controlled by the operating system (Windows or
Linux). The allowable range for the port assignment is configurable only from Windows. The default dynamic port range depends
on the operating system. For SmartStruxure server devices (Linux), the default port range is 32768 to 61000. For the Building
Operation supported Windows versions, the default port range is 49152 to 65535.
b) Flexera does not specify a port for the vendor daemon. If the port has not been specified, the port will be chosen at random by the
operating system at runtime. It is completely random and depends upon what (non-restricted) ports are available at the time the
operating system assigns it. This port may be configured manually to align with local policies and standard network management
practices.
c) This is the port that a network scanner picks up when the Admin page starts up.

Table: Software Activation Servers


Americas China Asia, Africa, Europe and all
other regions

gslb.secb2b.com china-gslb.secb2b.com.cn gslb.secb2b.com

us-prod-klm.secb2b.com china-klm.secb2b.com.cn eu-prod-klm.secb2b.com

us-elm.secb2b.com china-elm.secb2b.com.cn eu-elm.secb2b.com

Table: Windows Services


Application Windows Service Startup Type Recovery Log On As Default
© 2017 Schneider Electric. All rights reserved.

Enterprise Server Building Operation x.y Automatic Run a Program Local System
Enterprise Server

Enterprise Servera Building Operation x.y Automatic Restart the service Local System
Connect Agent

License Building Operation x.y Automatic Restart the service Local System
Administratorb License Server

Project Configuration Project Configuration Automatic Restart the service Local System
Tool Tool Modules Service

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017
[SmartStruxure Solution]
11

Continued
Application Windows Service Startup Type Recovery Log On As Default

WebReports Building Operation x.y Automatic Restart the service Local System
WebReports Agent

a) The Enterprise Server installation file includes the Connect Agent.


b) The License Administrator installation file includes two components: License Administrator and License Server. You can select to
install both components or one of them. Only the License Server has a Windows service.

Bandwidth requirements SmartStruxure solution LAN


As in all instances of planning, more is generally descriptions
better. Although the current SmartStruxure server
devices are limited to 100 Mbps, a single SmartStruxure server devices and Enterprise Server
installation may contain many SmartStruxure server The SmartStruxure server devices
devices each with a significant number of field are hardware devices with embedded Linux
devices resulting in substantial data traffic. operating systems and the Enterprise Server is a
Insufficient bandwidth may affect the overall software application that is installed on a PC. These
performance of the building. SmartStruxure servers are multi-function IP
addressable devices that can provide the following
functions:

Table: Server functions


Function SmartStruxure server devices Enterprise Server

Server (for data exchange) – a server Yes Yes


for open and proprietary protocols

Server (for clients) – a web server Yes Yes


and server for application-based user
interfaces

Table: Router functions


Function SmartStruxure server devices Enterprise Server

IP Networks – a router for LON Yes Yes


IP, BACnet/IP, Modbus TCP, Web
Services, Proprietary networks

Private RS-485 Networks – Yes No


a router for BACnet MS/TP,
LON, Modbus RTU, Proprietary
networks

Private FT-10a Networks – Yes Yesa


© 2017 Schneider Electric. All rights reserved.

a router for LON TP networks

a) With optional adaptor

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017
[SmartStruxure Solution]
12

Table: Gateway functions


Function SmartStruxure server devices Enterprise Server

Gateway – a gateway for open and Yes Yes


proprietary building automation
protocols

Clients Project Configuration Tool


The SmartStruxure server devices and the Project Configuration Tool is an off-site engineering
Enterprise Server support the following clients: platform for SmartStruxure solutions. The Project
Configuration Tool simulates all functions of the
• WorkStation: An application-based Microsoft Enterprise Server and SmartStruxure server devices
Windows client. virtually before deployment.
• WebStation: A browser-based client.
Project Configuration Tool is a suite of three
• Technician Tool Mobile App: A mobile software programs: server, client, and WorkStation.
application client. The Project Configuration Tool sever provides an
environment within which all virtual SmartStruxure
• AdaptiApps: A mobile application design
servers of the project can run while being
environment that creates custom applications
engineered. The Project Configuration Tool client
for iPad, Android tablet, Microsoft Windows,
provides an intuitive user interface for project
and Mac OS Platforms.
management. WorkStation is a full-featured user
AD interface for configuration of SmartStruxure servers.
AD is a touch screen device on which you can run
the AdaptiApps or the preinstalled Technician Tool StruxureWare Building Operation Software OS user
Mobile App. The preinstalled SmartXKiosk app requirements
prevents the user from closing AdaptiApps or To install and use the StruxureWare Building
Technician Tool Mobile App, or switching to Operation software, users must have the following
another application. AD is connected to the credentials:
SmartStruxure system using either the wireless
network or the USB ports on AD and a • All software requires the installing user to have
SmartStruxure server device. The preinstalled administrative privileges on the PC onto which
SmartX AD-Link app enables IP communication the installation is to take place.
over USB.
• Enterprise Server and License Server are
installed as services and require a user with
Reports Server
administrative privileges to start and stop the
The Reports Server is used to gather data from the services.
Building Management System and generate
reports. The Reports Server requires the following • The PC running the Enterprise Server service
Microsoft applications: or License Server service needs to be running
under an administrative user’s account.
• ASP.NET • Use of the Software Administrator or License
• Internet Information Services (IIS) Administrator requires that the user have
© 2017 Schneider Electric. All rights reserved.

administrative privileges.
• SQL Server
• Operation of WorkStation, Device
• SQL Server Reporting Services Administrator, and WebReports requires
For more information on supported versions, see normal user privileges.
StruxureWare Building Operation requirements.
StruxureWare Building Operation
requirements
WorkStation includes Graphics Editor, Script Editor,
Function Block Editor, and WorkPlace Tech Editor.

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017
[SmartStruxure Solution]
13

Table: WorkStation
Hardware and software requirements Supported versions
Processor Minimum: Intel Core i5 @ 2.0 GHz or equivalent
Recommended: Intel Core i5 @ 3.0 GHz or better
Memory Minimum: 4 GB
Recommended: 8 GB or higher
Hard disk space Minimum: 20 GB
Operating systems Microsoft Windows 7 (32-bit)
Microsoft Windows 7 (64-bit)
Microsoft Windows 8.1 (32-bit)
Microsoft Windows 8.1 (64-bit)
Microsoft Windows 10 (64-bit)
Microsoft Windows Server 2008 R2 (64-bit)
Microsoft Windows Server 2012 (64-bit)
Microsoft Windows Server 2012 R2 (64-bit)
Visio versions (WorkPlace Tech Editor) Microsoft Office Visio 2016 (32-bit)
Microsoft Office Visio 2013 (32-bit)
Microsoft Office Visio 2010 SP1 (32-bit)
Required additional software Microsoft .NET Framework 4.5 or 4.6
Microsoft .NET Framework 3.5 SP1 (WorkPlace Tech
Editor)

The following Microsoft Windows 7 editions are The following Microsoft Windows Server 2008 R2
supported: Professional, Enterprise, and Ultimate. editions are supported: Standard, Web, Enterprise,
Datacenter, and Itanium.
The following Microsoft Windows 8.1 editions are
supported: Pro, Pro N, Enterprise, and Enterprise The following Microsoft Windows Server 2012 and
N. Microsoft Windows Server 2012 R2 editions are
supported: Datacenter, Standard, Essentials, and
The following Microsoft Windows 10 editions are Foundation.
supported: Pro and Enterprise.
Table: WebStation
Software requirements Supported versions

Web browsers Microsoft Internet Explorer 11


© 2017 Schneider Electric. All rights reserved.

Mozilla Firefox
Google Chrome

Table: Enterprise Server


Hardware and software requirements Supported versions
Processor Minimum: Intel Core i5 @ 2.0 GHz or equivalent
Recommended: Intel Core i5 @ 3.0 GHz or better

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017
[SmartStruxure Solution]
14

Continued
Hardware and software requirements Supported versions
Memory Minimum: 4 GB
Recommended: 8 GB or higher
Hard disk space Minimum: 100 GB
Operating systems Microsoft Windows 7 (32-bit)
Microsoft Windows 7 (64-bit)
Microsoft Windows 8.1 (32-bit)
Microsoft Windows 8.1 (64-bit)
Microsoft Windows 10 (64-bit)
Microsoft Windows Server 2008 R2 (64-bit)
Microsoft Windows Server 2012 (64-bit)
Microsoft Windows Server 2012 R2 (64-bit)
Required additional software Microsoft .NET Framework 4.5 or 4.6

Processor power, memory, and hard disk space The following Microsoft Windows 10 editions are
should be scaled upwards to accommodate supported: Pro and Enterprise.
targeted system size as impacted by the total
quantity of SmartStruxure server devices and The following Microsoft Windows Server 2008 R2
expected historical archiving. The Enterprise Server editions are supported: Standard, Web, Enterprise,
is tested on a machine with an 8-core 3.6 GHz Datacenter, and Itanium.
processor, 32 GB of memory, and a hard drive of 3
TB. The following Microsoft Windows Server 2012 and
Microsoft Windows Server 2012 R2 editions are
The following Microsoft Windows 7 editions are supported: Datacenter, Standard, Essentials, and
supported: Professional, Enterprise, and Ultimate. Foundation.

The following Microsoft Windows 8.1 editions are


supported: Pro, Pro N, Enterprise, and Enterprise
N.
Table: Project Configuration Tool
Hardware and software requirements Supported versions
Processor Standalone solution:
Minimum: Intel Core i5-3340M @ 2.70 GHz
Recommended: Intel Core i7-4800MQ @ 2.70 GHz or
higher
Server:
© 2017 Schneider Electric. All rights reserved.

Minimum: Intel Core i7-4800MQ @ 2.70 GHz


Recommended: Intel Core i7-3930K @ 3.20 GHz or
higher
Client:
Minimum: Intel Core i5-3340M @ 2.70 GHz
Recommended: Intel Core i7-4800MQ @ 2.70 GHz or
higher

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017
[SmartStruxure Solution]
15

Continued
Hardware and software requirements Supported versions
Memory Standalone solution:
Minimum: 8 GB
Recommended: 16 GB or higher
Server:
Minimum: 32 GB
Recommended: 64 GB or higher
Client:
Minimum: 4 GB
Recommended: 8 GB or higher
Hard disk space Standalone solution:
Minimum: 50 GB
Server:
Minimum: 200 GB
Recommended: 1 TB or higher
Client:
Minimum: 1 GB
Required BIOS configuration Standalone solution and Server:
Intel VT-x or AMD-V virtualization support enabled
Operating systems Microsoft Windows 7 (64-bit)
Microsoft Windows 8.1 (64-bit)
Microsoft Windows 10 (64-bit)
Microsoft Windows Server 2008 R2 (64-bit)
Microsoft Windows Server 2012 R2 (64-bit)
Required additional software Microsoft .NET Framework 4.5 or 4.6

Processor power, memory, and hard disk space The following Microsoft Windows 10 editions are
should be scaled upwards to accommodate supported: Pro and Enterprise.
targeted system size as impacted by the total
quantity of SmartStruxure solution projects. The The following Microsoft Windows Server 2008 R2
Project Configuration Tool is tested on a machine editions are supported: Standard, Web, Enterprise,
with an 8-core 3.6 GHz processor, 32 GB of Datacenter, and Itanium.
memory, and a hard drive of 1 TB.
The following Microsoft Windows Server 2012 R2
The following Microsoft Windows 7 editions are editions are supported: Datacenter, Standard,
© 2017 Schneider Electric. All rights reserved.

supported: Professional, Enterprise, and Ultimate. Essentials, and Foundation.

The following Microsoft Windows 8.1 editions are


supported: Pro, Pro N, Enterprise, and Enterprise
N.

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017
[SmartStruxure Solution]
16

Table: Reports Server


Hardware and software requirements Supported versions
Processor Minimum: Intel Core i5 @ 2.0 GHz or equivalent
Recommended: Intel Core i5 @ 3.0 GHz or better
Memory Minimum: 4 GB
Recommended: 8 GB or higher
Hard disk space Minimum: 20 GB
Operating systems Microsoft Windows 7 (32-bit)
Microsoft Windows 7 (64-bit)
Microsoft Windows 8.1 (32-bit)
Microsoft Windows 8.1 (64-bit)
Microsoft Windows 10 (64-bit)
Microsoft Windows Server 2008 R2 (64-bit)
Microsoft Windows Server 2012 (64-bit)
Microsoft Windows Server 2012 R2 (64-bit)
SQL versions Microsoft SQL Server 2008 R2 (64-bit) SP2 or SP3
Microsoft SQL Server 2012 (64 bit)*
Required additional software Microsoft .NET Framework 4.5 or 4.6

* Microsoft SQL Server 2012 SP1, SP2 or SP3 is The following Microsoft Windows Server 2012 R2
required if the operating system Windows Server editions are supported: Datacenter and Standard.
2012 R2 is used
The following Microsoft SQL Server 2008 R2 and
The following Microsoft Windows 7 edition is Microsoft SQL Server 2012 editions are supported:
supported: Professional. Standard and Express with Advanced Services.

The following Microsoft Windows 8.1 editions are For more information on software requirements for
supported: Pro and Enterprise. installing SQL Server 2008 R2, see
https://msdn.microsoft.com/en-
The following Microsoft Windows 10 editions are us/library/ms143506(v=sql.105).
supported: Pro and Enterprise.
For more information on software requirements for
The following Microsoft Windows Server 2008 R2 installing SQL Server 2012, see
editions are supported: Standard, Web, Enterprise, https://msdn.microsoft.com/en-
Datacenter, and Itanium. us/library/ms143506(v=sql.110).aspx/html.
© 2017 Schneider Electric. All rights reserved.

The following Microsoft Windows Server 2012


edition is supported: Standard.

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017
[SmartStruxure Solution]
17

Table: WebReports
Software requirements Supported versions

Web browsers Microsoft Internet Explorer 9 (32-bit)


Microsoft Internet Explorer 11
Mozilla Firefox
Google Chrome

Table: Technician Tool Mobile App


Hardware and software requirements Supported versions
Hardware Minimum: iPad 2
Minimum: iPhone 4
Android Phones
Android Tablets
Operating systems iOS 7.1 to 10.x
Android 4.4 to 4.4.4 (KitKat)
Android 4.4W to 4.4W.2 (KitKat)
Android 5.0 to 5.1 (Lollipop)
Android 6.0 (Marshmallow)
SmartStruxure servers Minimum: 1.6.1
Minimum: 1.7.1 for graphics and SmartX AD-Link support

Table: AdaptiApps
Hardware and software requirements Supported versions
Hardware iPads
iPhones
Android Phones
Android Tablets

© 2017 Schneider Electric. All rights reserved.

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017
[SmartStruxure Solution]
18

Continued
Hardware and software requirements Supported versions
Operating systems iOS 7.x to 10.x
Android 4.4 to 4.4.4 (KitKat)
Android 4.4W to 4.4W.2 (KitKat)
Android 5.0 to 5.1 (Lollipop)
Android 6.0 (Marshmallow)
Microsoft Windows 7.x, Windows 8.x, or Windows 10
Mac OS 10.x
SmartStruxure servers Minimum: 1.6.1
Minimum: 1.7.1 for SmartX AD-Link support

© 2017 Schneider Electric. All rights reserved.

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
04-19013-03-en April 2017