Sunteți pe pagina 1din 2

Brand & Grade of

Maximum size of

Slump Observed
Optimum Slump
Aggregate (mm)
Mode of Placing

After 1 Hr.(mm)
Required (mm)
Mix Proportions in Kg/m³ of Concrete Compressive Strength N/mm²

W/C Ratio
Concrete
Grade of

Cement
Usage
S.No.

Admixture

Admixture
in Kg. by

in (%) by

strength
28 Days
Content
Cement

7 Days
10 mm

20 mm
Water

target
wt. of

wt. of
Sand
1 M-15 PCC Chute 20 0.5 25 50 290 145 744 479 716 2.61 0.9 21.33 25.69 21.60

2 M-15 PCC PUMP 20 0.5 80-100 100 290 145 744 479 716 2.9 1 20.5 24.25 21.60

3 M-20 RCC Chute 20 0.44 50-75 65 330 145.2 722 465 695 3.3 1 21.62 29.62 26.60

4 M-20 RCC Chute 20 0.44 100-120 115 330 145.2 722 465 695 3.63 1.1 20.96 28.49 26.60

PPC JAYPEE CEMENT


5 M-25 RCC Chute 20 0.42 50-75 65 360 151.2 706 455 680 3.96 1.1 28.36 35.54 33.25

6 M-25 RCC Pump 20 0.42 100-120 120 360 151.2 706 455 680 4.68 1.3 27.93 34.82 33.25

7 M-30 RCC Chute 20 0.40 50-75 60 410 164 683 440 658 4.51 1.1 31.38 38.46 38.25

8 M-30 RCC Pump 20 0.40 100-120 115 410 164 771 528 610 5.33 1.3 29.44 37.92 38.25

9 M-35 RCC Chute 20 0.38 50-75 75 450 171 666 429 642 4.5 1 39.85 48.4 43.25

10 M-35 RCC Pump 20 0.38 100-120 120 450 171 666 429 642 5.4 1.2 37.39 45.19 43.25

11 M40 RCC Chute 20 0.37 50-75 75 480 177.6 628 404 604 5.28 1.1 45.39 50.10 48.25

12 M40 RCC Pump 20 0.37 100-120 115 480 177.6 628 404 604 6.72 1.4 43.91 48.73 48.25

Admixture Used:- Super Plasticizer (retarder & water reducing)(Any Branded Company etc.. FOSROC)

W/C VS CEMENT CONTENT


600

CEMENT CONTENT
500

400

300

200

/
200

100

0
0.53 0.52 0.51 0.5 0.49 0.48 0.47 0.46 0.45 0.44 0.43 0.42 0.41 0.4 0.39 0.38 0.37 0.36 0.35 0.34 0.33 0.32 0.31 0.3 0.29

W/C