Sunteți pe pagina 1din 9

CHAPTER 10 Developments in Bench Testing Facilities

for Protective Gear


BYF. L. HAMILTON, AND N. S. ELLIS.

INTRODUCTION (4 Provision of facilities for close control of the


The testing of protective-gear systems and their con- test-conditions and parameters.
stituent components calls for test-equipment of a rather (4 Rapid rate of testing.
specialised nature. The requirements of modern
protective-gear systems have increased the complexity
and cost of such equipment and the amount of testing to General-purpose Test-bench for Protective-gear
be done has necessitated a speeding up in the procedure General
of tests.
An overall view of the test-bench is shown in fig. 1.
The tests which may be necessary on protective-gear
The main primary circuits for the test bench are supplied
equipment are somewhat varied but, in general, will fall
from the 440-volt 3-phase mains, with alternative
into one or more of the following categories.
arrangements for taking this supply from a three-phase
Investigatory variable-frequency machine when necessary. The max-
imum current which is taken by the primary circuits is of
These include those tests which may be essential on
the order of 120 amperes but, as tests at these currents
circuits and components during development projects.
are of a limited time-duration, the supply need not be
The scope of these test may be large, as they often
rated continuously at this current. When the primary
explore a variety of effects, design factors, parameter
currents are of the order of 10 amperes these may be
changes, etc. Tests of this type may also include investig-
used on a continuous basis.
ations into more fundamental problems, such as the
The main primary circuits are shown diagrammati-
transient response of current-transformers and the
cally in fig. 2, from which it can be seen that the three-
effect of this on various protective-systems.
phase supply is applied, by a “fault-making” switch, to
The information obtained from such investigations is
two sets of variable impedances per phase, one of which
often used to check the soundness of new ideas and
represents a generating source impedance and the other
provide practical design-data upon which new experi-
the impedance of a line. The current-transformers, of
mental equipment may be based or by which existing
which there may be up to four per phase, can be con-
designs may be modified to improve their performance.
nected in various combinations according to the particu-
lar fault distribution which it is required to reproduce.
Performance Testing The primary circuit has two ma’ln functions:
The overall performance of protective-systems, (0) To provide primary currents in various combina-
relays, and the like is an important aspect of protective- tions of current-transformers, with control of
gear testing. Tests of this type may be concerned with overall time constant, the point of wave at which
experimental and production prototypes or with the cer- the fault is applied, the type of fault, and the
tificiation and type-testing of new protective-gear duration of fault. This function is required when
equipment or relays. the bench is used for tests where only current is of
In the past, a large amount of the testing referred to significance.
above has required heavy-current rigs, which are costly (b) To provide variable current and voltage condi-
and limited in flexibility. Such heavy-current rigs require tions at a relaying point with control of time
extensive machine supplies, the demands upon which constant, duration of fault, point-of-wave, and
are so great that they often form a considerable limita- type of fault. This function is required when the
tion to the number of investigations which may be bench is used for the dynamic testing of relays
undertaken. and protective-systems which require both cur-
The protective-gear test-bench described in this arti- rent and voltage, e.g. distance protection.
cle was developed in order to replace the conventional The equipment required for the above basic functions
heavy-current and secondary-injection equipment in lends itself to many other test applications which require
many types of testing particularly those concerned with controlled current and/or voltage conditions. The vari-
investigatory work on experimental projects and pro- ous units which make up the complete test-bench are
totypes. The main requirements borne in mind in the described in more detail overleaf.
design of the equipment are as follows:
Source and Line Impedances
(a) Extreme flexibility of test circuit and conditions.
(b) Rapid setting up of equipment. One of the main requirements of test-equipment of
(c) Use of ac. mains as the source of power. this type is to obtain current and voltage transients of the

140
order of those which may occur in practice. The source practice. The line impedances are designed with a max-
impedances are designed with maximum X/R values of imum X/R of about 10 which corresponds to that of a
the order of 30 and these produce current-transients typical 275-kV line. Resistance can be inserted to
which are large enough to be comparable to those reduced this X/R value to about 2,6 which corresponds
obtained with generator and transformer impedances in to that of a typical 132-kV line.
The reactors in both source and line impedances are
CONNECTION REACTANCE AT 50 C/S air-cored so that they are completely linear.
UNIT ‘A’ UNIT ‘6’ Two source-reactors are provided for each phase,
each having four sections. These two units are provided
3.0 6.0 with switches so that their sections can be connected in a
number of ways and the resulting impedances connected
singly, in series, or in parallel to give a total source-
impedance per phase, variable in relatively close steps
n 12.0 24.0 between 2 ohms and 144 ohms. This arrangement is
shown in fig. 3. The X/R values can be made constant
over this range of source-impedance. An earlier version
of the bench uses the simpler method of a tapped reactor
48-o 96.0
with manual plug-selection but this has the disadvantage
‘/R(O) FOR ALL CONNECTIONS z 35 of a varying value of X/R over the range of impedances.
Source-impedance is not normally included in the
(0)
neutral connection, but where tests require a higher
value of zero-sequence impedance in the source, the
source-impedance of one phase may be connected in the
neutral connection. This is permissible, since such tests
will invariably be concerned with single or double
phase-to-earth faults where one phase is not in use. A
- 0 3.0 12.0 48-O neutral link is provided so that resistance may be con-
nected to simulate systems which have a resistance-
earthed neutral.
=-iz% 6.0 9.0 160 54.0 Three line reactors are provided in each phase and in
the neutral. These represent, when all are in series, a line
of approximately 3.5 ohms, the sections being 0.5, 1.0,
24-O 27.0 36.0 72.0 and 2.0 ohms respectively (at 275 kV). By shorting out
various sections, the impedance between the relaying
point and the fault can be varied from O-3.5 ohms in
96.0 j 99.0 1 108.0 144-o steps of 0.5 ohm.
The neutral line impedances are half the value of the
phase line impedances, giving a typical value of ZO/Z1 =
(h) 2.5 for the line. The arrangement of the line reactors are
shown in fig. 4.

I-I ol”/ol OI Impedance ofllne


Phase
units:
0 10 3.5 ohm\ in O-5 ohm wzps \~~th phase-angles of
70 10 ns
Neutral 0 to l-75 ohms in 0.25 ohm step, with phase-angle5
0 2.0 4.0 5.34 of ho or 70

FIG. 4. ARRANGEMENTOFLINEIMPEDANCES

0 2.56 8.0 I b-0


“Make” Switch and Main Contactor
The function of the main contactor is to connect the
0 2.9 10.6 32.0
voltage-supply to the test-bench a short time (about f
sec.) before application of the fault and to interrupt the
I I I I I
fault-current after the required duration of the fault.
CC) With this arrangement, the main primary circuit is nor-
FIG. 3. SOURCEREACTORS,SHOWING(U) CONNECTIONS, mally dead and is only made alive for the minimum
(b) RANGEOFSOURCEIMPEDANCEWITHUNITSINSERIES, required time. The main contactor is of the heavy indus-
AND(C) RANGEOFSOURCEIMPEDANCEWITHUNITSIN trial type and is capable of interrupting repeatedly the
PARALLEL. maximum currents at very low power-factors.

142
The “make” switch is required to apply the fault at a also provides the facilities for interlinking the primary
particular “point-on-wave”, so that high speed and con- circuits of the current-transformers to form the various
sistency of operation are essential. Experience has arrangements required. A tapped section of 10 per cent
shown that telephone-type relays with heavy-duty con- of the secondary turns enables the ratio of some of the
tacts can perform this duty with comparative ease. The current-transformers to be controlled by t10 per cent in
arrangement adopted is shown in fig. 5. One telephone- steps of 2 per cent. The arrangement permits tests up to a
type relay with two parallel heavy-duy contacts is used current which is equivalent to 30 times the current-
per phase, and two auxiliary relays, energised in parallel transformer rating at fairly high values of X/R. The
with these, provide synchronised contacts for timing, amount of influence which the secondary burdening
interlocking, etc. The standard contacts have been mod- exerts on both the magnitude and time constant of the
ified by the addition of a momentum transfer-device primary current is relatively small with modern low-VA
with practically eliminates contact-bounce. Very consis- protection and the arrangement is a fairly close approx-
tent operation is thus obtained and wear on these con- imation to a current source over the whole range of
tacts is negligible. The relays are energised from the currents.
master control-unit as will be described later. Typical arrangements of the current-transformer cir-
cuits are shown in figs 6a, 6b, and 6c.
It should be noted that the reversing-switch in the
Current-transformers primary circuits of some current-transformers enables
Up to twelve current-transformers can be energised rapid change-over between a single-end-fed internal
from the primary circuit in various combinations. They fault, a double-end-fed internal fault, and a through-
are of typical bar-primary design having normal 300/l fault, when balanced-current systems of protection are
and 3001.5 secondaries. Four primary windings are pro- being tested.
vided to enable the overall transformation-ratio (and The provision of both l-ampere and 5-ampere secon-
thus secondary current level) to be varied over a wide daries on the current-transformers enables relays and
range in close steps. These windings are in the propor- protection for either rating to be tested. Alternatively,
tion 1 : 3 : 9 : 27 giving primary turns by addition or one secondary can be used as a search coil while the
subtraction of 2-80 in steps of two. Selection of the other is in use, or can be used for the injection of d.c. or
primary turns is by means of a manual plug board which a.c. ampere-turns into the current-transformer to simu-
late certain conditions.

Voltage-transformers
These are provided so that the voltage windings of
relays may be connected to the relaying point, i.e. bet-
ween the source and line impedances. They are of nor-
mal accuracy, suitable for burdens up to 75 VA, and are
of ratio 440/l 10 volts, open-delta windings being pro-
vided for relays requiring residual voltage connection.
The primary windings of these voltage-transformers
may be connected via a selector-switch to a number of
positions as follows:
(1) Continuous 440-volt supply. This is of use during
those tests and adjustments where a continuous
voltage-supply is necessary.
(2) The source side of the “make” switch, so that the
relays are energised at normal voltage prior to the appli-
cation of the fault-current. This represents the condi-
tion, in practice, of a fault occurring on a line which is in
service.
(3) The line side of the “make” switch, so that the relays
are energised by the fault-voltage simultaneously with
application of the fault-current. This represents the con-
dition, in practice, of a faulted line being switched into
service.
The general arrangements of the voltage-transformer
connections is shown in fig. 7. It can be seen from this
that the current taken by the voltage-transformers is fed
through the current-transformers. This is not completely
desirable, but with the normal voltage-transformer bur-
FIG. 5. “MAKE" SWITCH ASS~MBLI dens used in practice the reflected impedance of the

143
voltage-circuits is so large compared with the line impe-
dance that the resulting errors are negligible. This con-
nection is preferable to that in which the current-
PLUG CONNECTIONS transformers are on the line side of the voltage-
transformers, since in this case the small voltage-drop
across the current-transformers is imposed on the
voltage-circuits. This voltage-drop becomes significant
when testing with terminal faults close to the relaying
point with heavy currents.

REVERSING I AMP
SWITCH MAIN ‘MAKE’
CONTACTOR SWJTCH

REVERSING
IL /SWITCH

VOLTAGE z jjjc-
TRANSFORMER c

FIG. 7. SELECTIONOFVOLTAGE-TRANSFORMER
CONNECTION.

MP
Master Control-unit
The master control-unit provides the following fea-
MP tures:
(1) A safety time-lag of about f second between closing
of the main contactor and operation of the “make”
switch. Interlocking contacts on the contactor and
“make” switch ensure that the circuit is always broken
by the contactor.
(2) 360” control through a “selsyn” and thyratron cir-
cuit for selecting the point-on-wave at which the “make”
switch closes its contacts. This is accurate and consistent
within about 1” or 2”.
(3) A timing circuit which controls the duration of the
Eault-current. Extreme accuracy of interruption of the
circuit is not possible but the duration of fault may be
adjusted from short faults of the order of 3 loops up to
long faults of the order of seconds.
(4) A variable pulse which can be used for triggering an
oscilloscope at any point in the fault-sequence. This
means that the whole of the fault may be observed on a
slow time base or that any part of the fault or associated
phenomena may be recorded in an expanded form by
using a fast time base. This feature is extremely valuable,
espeically when used with an oscilloscope equipped with
a long persistence tube. Full advantage may be taken of
the rapid testing-rate as photographic records may be
kept down to a minimum.
The genera1 arrangement of the lastest type of
control-unit which has been developed is shown in block
form in fig. 8. The unit is shown withdrawn from the
pane1 in fig. 9 which also shows the unit construction of
the Dekatron counter stages. These are made withdraw-
able so that units can be easily replaced or interchanged.
The selsyn unit provides a variable-phase supply to an
FIG. 6. CURRENT-TRANSFORMERSSHOWING (a) ARRANGE- electronic squaring circuit from which a pulse-forming
MENTOFTYPE-A UNIT,(b) ARRANGEMENT OFTYPE-B UNIT, circuit is energised. The 51-cycle oscillator may be used
AND(c) A VIEWOFTYPE A AND B UNIT. as an alternative to the phase-shifter and this provides

144
SELECTOR

AUXILIARY CIRCUITS

cR0. TRIGGER

FIG. 8. BLOCK DIAGRAM OF CONIXOL-UNIT.

the facilities for random point-on-wave switching which the main contactor. The duration of fault may therefore
is sometimes required. The pulse-forming circuit be controlled in IO-millisecond steps from about 2-3
develops a train of pulses at 10 ms intervals which, when loops up to 9Q seconds. Facilities are also provided for
taken from the phase-shifter, are locked to a selected stopping the sequence, i.e. tripping the main contactor,
point-on-wave of the main supply-voltage. The pulse from a protection relay under test.
train actuates a 3-decade “dekatron” counter unit which The whole test-sequence is automatically controlled
gives a maximum overall time of 10 seconds. The from on2 push-button. the equipment automatically
counter system is arranged to start always on a pulse resetting when this button is released.
corresponding to the negative going half-cycle of voltage
out of the phase-shifter. Thus the firing unit for the make
switch, which is selected to a fixed 500-millisecond point
on the second decade. always fires at the correct point-
on-wave which is indicated by the phase-shifter. The
firing unit of the make switch contains a thyratron which
is triggered at the correct point, discharging a condenser
through the “make” switch coil. Fast consistent opcra-
tion of the “make” switch is thus obtained.
The trigger control for the oscilloscope can be selected
to any point in the pulse train thus enabling it to be up to
1 second in advance or 9; seconds later than the firing
point of the make switch. This enables the beginning of
the fault to be observed or any point after to be
expanded on a fast time base. For complete convenience
in this respect. a variable IO&20 milliseconds delay is
fitted to the trigger circuit to enable triggering to be
effected at points between the pulses of the main pulse
train.
The internal stop selector is also capable of being
selected to any pulse in the train and this is used to trip FIG c). Vlt:U 01. (‘ON I‘KOL:UNIT
Ancillary Equipment
Apart from the facilities offered by the main primary
circuit, current-transformers, voltage-transformers,
control-unit etc., certain auxiliary equipment has been SECONDARV

included in the bench in order to extend its use and


provide greater flexibility. The main items are described
below:

Phase-shifters
A variable-phase supply is a frequent necessity in both
protective-systems and relay-testing and this facility has I I
440V MAINS
been incorporated in the test-bench. The normal rotary INPUT
phase-shifters have limitations which make them unsuit-
able for such use and a special static phase-shifting trans-
former has been built. The arrangement is as shown in
fig. 10a and is basically a tapped three-phase trans-
former energised from the same power-supply as the
main primary circuits. The taps are so arranged that the
manual plug-selection of the output circuits on the
phase-shifter panel provides a 240-volt supply adjust-
able in 10” steps through 360”. The plug-selection pro-
vides a visual indication of the phase-angle selected. The
turns on the various secondary taps are so arranged that
output-voltage remains constant independent of its
phase-angle. Variac transformers can be inserted in the
output to give control of the output-voltage. Two plug-
250 v
selector systems are provided so that two variable-phase OUTPUT
supplies may be obtained. The phase-shifter is capable (h)
of delivering currents of the order of 10 amperes without
FIG. 10. PHASE-SHIFTINGTRANSFORMER,SHOWINC (a)
significant phase-shift so that there is no zero-correction
ARRANGEMENTFORlo'STEPS,AND (b) THEATTACHMENT
necessary and the selected phase-angle may be referred
FOR 1" STEPS.
to the main supply-voltage. Practice has shown that con-
trol in 10” steps is adequate for most tests. Where closer
control of phase-angle is necessary an external auto- Auxiliary A.C. and D.C. Supplies
transformer unit has been designed, as shown in fig. lob,
In view of the large number of electronic instruments
which gives control between the 10” positions in steps of
1”. in use which require mains supplies, a number of mains
sockets are provided on the bench. These can also be
used for auxiliary voltage supplies of fixed phase-angle.
Voltage Simulators A 1 lo-volt d.c. supply which can be used for repeat-
It is sometimes advantageous to use the main current contactors is provided on the bench. A repeat-contactor
circuits of the bench to energise the current circuits of a with seal-in contacts and lamp-indication is a built-in
relay, but to use voltages which change in a predeter- feature for relays with no repeat-contactor incorpo-
mined way (independent of the bench circuits) on appli- rated.
cation of the fault-current. A voltage-simulator unit has
been designed for this purpose. Potentiometers in each
phase-to-neutral voltage enable the voltages on each Timing
phase to be adjusted to a particular value to which they A portable electronic timer is normally used in con-
will fall from normal voltage when the current is applied. junction with the bench. The provision of contacts sync-
hronised with those on the “make” switch ensure easy
measurement of overall operating-times of relays and
Primary Shunts and Meters
protection. Auxiliary contacts on the main contactor
The primary circuits are provided with current-shunts provide similar facilities for measuring the release times
so that the primary current-transient may be observed of relays on de-energisation.
by oscilloscope. A multi-range ammeter is provided
together with current-transformers so that the steady-
state current in any phase or the neutral may be meas- Oscillographic Work
ured. The facilities for triggering oscilloscopes on single-
An operations-counter is provided so that the number stroke operation enable transient phenomena to be
of operations may be logged. This is useful both from the readily investigated on the bench. The ability to repeat
test and maintenance aspects. shots under controlled test-conditions in conjunction

146
with long persistence tubes reduces photography to a the overall time of operation for faults within the zone
minimum. It is usually only necessary to photograph may be determined for various source conditions and for
traces when permanent records of a particular trace are varying degrees of transients.
required. With suitable interconnections it has been possible to
explore the effect of reversal of current-flow when a
Typical Application switch opens under fault. The effect of the zero-
Some of the applications for which the test-bench has sequence impedance of transformers and the efficacy of
been used are described below. earth-fault compensation has also been investigated.

Differential Protection Relays

Most of the protective-systems based on current- Tests on individual types of relays may be made with
balance of current-transformers can be explored. or without the effects of current-transformers. Some
Protective-systems with up to four terminals can be examples are as follows:
tested on a three-phase basis, and those with up to (a) The dynamic characteristics of instantaneous-
twelve terminals on a single-phase basis. The steady- relays with off-set current-inputs.
state and transient balance of current-transformers are (b) Timing characteristics of overcurrent relays and
readily checked by the equipment. The examples of overshoot measurements. The effect of current-
oscillograms shown in fig. 11 illustrate how clearly the transformer saturation on time of operation of
problems of transient balance of current-transformers overcurrent-relays.
may be demonstrated. These records also show the con- (c) Dynamic tests on directional-relays.
siderable time constants obtainable and the consistency
of point-on-wave switching. CONCLUSION
The illustrations in this article apply to a new design of
Distance Protection test-bench just nearing completion. A previous pro-
lndividual distance-relays or complete distance- totype design has been in use for three years and has
protection schemes may be tested in a very realistic proved invaluable. It is of interest to note that nore than
manner with extreme rapidity. The provision of line and 100,000 operations have been done on the earlier test-
source impedances affords a realistic relaying point for bench with practically no maintenance.
distance-protection, the source-impedance being varied The principles developed in these test-benches have
to simulate the system plant conditions and the line been applied to the testing of production-equipment,
impedance varied to simulate the fault-position. Fine and a bench of similar type is being supplied to the
control of the impedance relay setting is effected by C.E.A. It is also of interest to note that the equipment
means of primary and secondary adjustments on the developed and the methods used are finding application
current-transformers, thus enabling the accuracy of the to University research. For example, a bench of this type
relays to be determined under switched conditions in is being constructed at Manchester College of Technol-
addition to ordinary static bench-test. The effects of the ogy for use in post-graduate research and as demonstra-
primary transients on accuracy is important with high- tion equipment, the major items being supplied by
speed systems and this may be readily explored. Also, Reyrolle.

147
Primary current adding to rcmanence
i

IP

IP

IP

IP

IP

FIG. 11. ZERO-SEQUENCETESTSONBALANCEDEARTH


FAULTPROTECTIONWITHLOW-IMPEDANCERELAY.

148

S-ar putea să vă placă și