04 · 2007
R-HG11-172.tif
Contents Page
Invalid:
Catalog HG 11.11 · 1999, Part 3 and
Catalog HG 11.12 · 2005, Part 3 Equipment Selection 11
Ordering data and configuration example
Selection of basic types, circuit-breakers
12
13
2
Selection of secondary equipment 15
Selection of additional equipment 22
Accessories and spare parts 23
Technical Data 27
Electrical data, dimensions and weights
Operating times, short-circuit protection
28
3
of motors, consumption data of releases 33
Circuit diagrams 34
Annex 37
Inquiry form
Configuration instructions
38
39 4
Configuration aid Foldout page
© Siemens AG 2007
R-HG11-173.tif
Contents Page
Description 5
General 6 1
Construction and mode of operation:
Switching medium 7
Pole assemblies 7
Operating mechanism box 7
Operating mechanism 7
Trip-free mechanism 7
Releases 8
Closing 8
Circuit-breaker tripping signal 8
Interlocking 8
R-HG11-174.tif
Standards 8
Ambient conditions 9
Industrial application: Refinery
Current carrying capacity 9
Dielectric strength 9
Product range overview 10
Basic equipment 10
1 and up to very high numbers of operating cycles. than 100 operating cycles a day.
3AH2 – makes a high number of operating cycles 3AH4 – the circuit-breaker for a maximum number
possible R-HG11-073a.eps of operating cycles
R-HG11-126.eps
In the voltage range up to 24 kV, up to 60,000 operating The vacuum circuit-breaker type 3AH4 up to 36 kV is
cycles are possible with 3AH2 circuit-breakers. designed for extremely high numbers of operating cycles:
Minimum maintenance work, such as greasing of operating It controls 120,000 operating cycles.
mechanisms after 10,000 operating cycles and replacement 3AH4 circuit-breakers master this extreme stress throughout
of vacuum interrupters after 30,000 operating cycles, their entire service life. Greasing of the operating mecha-
preserves the reliability of these circuit-breakers throughout nism is not required until 10,000 operating cycles have been
their entire service life – despite high mechanical stress. reached. And vacuum interrupters just have to be replaced
Note: Due to low quantities, the 3AH2 vacuum circuit- after 30,000 operating cycles.
breaker will be discontinued by December 31, 2007. As of
January 1, 2008, Siemens will offer this circuit-breaker type
for another 10 years for replacement purposes only.
HG11-2591 eps
Switching medium
The vacuum switching technology, proven and fully 4
developed for more than 30 years, serves as arc-quenching
principle by using vacuum interrupters.
Pole assemblies 5
Trip-free mechanism
3AH2/3AH4 vacuum circuit-breakers have a trip-free
mechanism according to IEC 62271-100. In the event of
an opening command being given after a closing operation
R-HG11-063a.eps
Ambient conditions
The vacuum circuit-breakers are designed for the normal
operating conditions defined in IEC 62271-100.
Condensation can occasionally occur under the ambient
conditions shown opposite. 3AH2/3AH4 vacuum circuit-
breakers are suitable for use in the following climatic classes
according to IEC 60721, Part 3-3:
40°C
1
Climatic ambient conditions: Class 3K4 1) max. 95% per day
Biological ambient conditions: Class 3B1 max. 90% per month
-5°C
Mechanical ambient conditions: Class 3M2
Chemically-active substances: Class 3C2 2)
HG11-2515a_en eps
Mechanically-active substances: Class 3S2 3)
1) Low temperature limit: – 5 °C
2) Without icing and wind-driven precipitation
3) Restriction: Clean insulation parts
HG11-2593a_en eps
1
The dielectric strength of air insulation decreases with 1000
increasing altitude due to low air density. According to
IEC 60694, the rated lightning impulse withstand voltage 600
10 20 30 40 50 60 °C 70
values specified in the chapter “Technical Data” apply to a Ambient temperature
site altitude of 1000 m above sea level. For an altitude
above 1000 m, the insulation level must be corrected
according to the opposite diagram.
The characteristic shown applies to the rated short-duration
1.50
power-frequency withstand voltage and the rated lightning
impulse withstand voltage.
Altitude correction factor
1.40
To select the devices, the following applies:
U W U0 x Ka
1.30
U Rated withstand voltage under standard reference atmosphere
U0 Rated withstand voltage requested for the place of installation
Ka Altitude correction factor according to the opposite diagram
1.20
Example
HG11-2517c_en eps
Rated short-
1 kV
7.2
kA
31.5
40
210
o
o
275 350 210
o
o
275 350 210
o
o
275 350 210
o
12 31.5 o o o
40 o o o o
15 31.5 o o o
40 o o o o
17.5 31.5 o o o o
40 o o o o
24 25 o o o o o o
40 n
36 31.5 n n n
40 n
o 3AH21) n 3AH4
1) The 3AH2 vacuum circuit-breaker will be discontinued by December 31, 2007, and will then only be available as spare circuit-breaker
Basic equipment
Contents Page
Equipment Selection 11
Ordering data and configuration example 12
2 Position:
a: alphabetical
1 2
3 A H n
3 4 5
n
n: numerical
6
n
7
n
–
–
8
n
9
a
10 11 12 –
a n n –
13 14 15 16
n a a n –
Order codes
« n n n
Order No.:
Primary part
1st position Superior group
Switching devices
Secondary part
9th to 16th position Secondary equipment
Operating mechanism, releases, operating
voltages and further auxiliary equipment
Order codes
Group of 3 after the Order No.
Format: a n a
Special versions ( )«
Initiated with “-Z”
Group of 3 after the Order No.
Format: a n n
Configuration example
In order to simplify the selection of the correct order number
for the requested circuit-breaker type, you will find a con-
figuration example on each side of the chapter “Equipment
Selection”. For the selection of the secondary part, always the
last example of the primary part was taken over and continued, On the foldout page we offer a configuring aid.
so that at the end of the equipment selection (page 22) a Here you can fill in the order number you have deter-
completely configured circuit-breaker results as an example. mined for your circuit-breaker.
at 36 % DC component
Pole-center distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
power-frequency
breaking current
making current
Rated voltage
See page 15
See page 16
See page 17
See page 18
See page 19
See page 20
See page 21
See page 21
See page 22
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm A
7.2 60 20 31.5 80/82 210 1250 3 A H 2 0 5 5 – 2
2000 3 A H 2 0 5 5 – 4
2500 3 A H 2 0 5 5 – 6
40 100/104 210 1250 3 A H 2 0 5 6 – 2
2000 3 A H 2 0 5 6 – 4
2
2500 3 A H 2 0 5 6 – 6
3150 3 A H 2 0 5 6 – 7
12 kV
50/60 Hz
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm A
12 75 28 31.5 80/82 210 1250 3 A H 2 1 1 5 – 2
2000 3 A H 2 1 1 5 – 4
2500 3 A H 2 1 1 5 – 6
40 100/104 210 1250 3 A H 2 1 1 6 – 2
2000 3 A H 2 1 1 6 – 4
2500 3 A H 2 1 1 6 – 6
3150 3 A H 2 1 1 6 – 7
15 kV
50/60 Hz
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm A
15 95 36 31.5 80/82 210 1250 3 A H 2 1 6 5 – 2
2000 3 A H 2 1 6 5 – 4
2500 3 A H 2 1 6 5 – 6
40 100/104 210 1250 3 A H 2 1 6 6 – 2
2000 3 A H 2 1 6 6 – 4
2500 3 A H 2 1 6 6 – 6
3150 3 A H 2 1 6 6 – 7
Configuration example
Vacuum circuit-breaker 3 A H
Rated voltage Ur = 7.2 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 60 kV
Rated short-circuit breaking current Isc = 40 kA
Pole-center distance = 210 mm
Rated normal current Ir = 1250 A 2 0 5 6 – 2
at 36 % DC component
Pole-center distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
power-frequency
breaking current
making current
Rated voltage
See page 15
See page 16
See page 17
See page 18
See page 19
See page 20
See page 21
See page 21
See page 22
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm A
17.5 95 38 31.5 80/82 210 1250 3 A H 2 2 1 5 – 2
2000 3 A H 2 2 1 5 – 4
2500 3 A H 2 2 1 5 – 6
3150 3 A H 2 2 1 5 – 7
40 100/104 210 1250 3 A H 2 2 1 6 – 2
2
2000 3 A H 2 2 1 6 – 4
2500 3 A H 2 2 1 6 – 6
3150 3 A H 2 2 1 6 – 7
Special version (available for all 17.5 kV circuit-breakers)
Ud = 42 kV – Z E 1 3
24 kV
50/60 Hz
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm A
24 125 50 25 63/65 210 1250 3 A H 2 2 5 4 – 2
2000 3 A H 2 2 5 4 – 4
2500 3 A H 2 2 5 4 – 6
275 1250 3 A H 2 2 6 4 – 2
2000 3 A H 2 2 6 4 – 4
2500 3 A H 2 2 6 4 – 6
40 100/104 275 2500 3 A H 4 2 6 6 – 6
36 kV
50/60 Hz
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm A
36 170 70 31.5 80/82 350 1250 3 A H 4 3 0 5 – 2
2000 3 A H 4 3 0 5 – 4
2500 3 A H 4 3 0 5 – 6
40 100/104 350 2500 3 A H 4 3 0 6 – 6
Special versions (available for all 36 kV circuit-breakers)
Up = 185 kV (only possible together) – Z E 1 4
and Ud = 85 kV + E 1 5
Up = 195 kV (only possible together) – Z E 2 4
and Ud = 95 kV + E 2 5
Configuration example
Vacuum circuit-breaker 3 A H
Rated voltage Ur = 36 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 170 kV
Rated short-circuit breaking current Isc = 40 kA
Pole-center distance = 350 mm
Rated normal current Ir = 2500 A 4 3 0 6 – 6
Increase of rated lightning impulse withstand voltage Up = 195 kV – Z E 2 4
+ E 2 5
C.t.-operated release
C.t.-operated release
C.t.-operated release
with tripping pulse
ⱖ 0.1 Ws (10 c)
ⱖ 0.1 Ws (20 c)
Closing solenoid
See page 16
See page 17
See page 18
See page 19
See page 20
See page 21
See page 21
See page 22
0.5 A
1.0 A
n n M
n n n N
n n n n T
n n n n P
n n n n P – Z A 4 6
n n n R
n n n n S
n n n n S – Z A 4 6
n n n
n
n
n
n
n
n
n
n
n
U
U
V
V
–
–
Z
Z
A
A
4
4
6
5
2
Configuration example
Vacuum circuit-breaker 3 A H
(Ur = 36 kV, 50/60 Hz, Up = 195 kV, Isc = 40 kA, Ir = 2500 A,
pole-center distance = 350 mm) 4 3 0 6 – 6
Closing solenoid, 1st shunt release, 2nd shunt release and
c.t.-operated release with a rated normal current of 0.5 A P
See page 17
See page 18
See page 19
See page 20
See page 21
See page 21
See page 22
Standard voltages Special voltages
2 125 V DC
127 V DC
240 V DC
Z
Z
Z
With order code
With order code
With order code
K
K
K
1 D
1 E
1 F
120 V AC 50/60 Hz 1) Z With order code K 1 K
125 V AC 50/60 Hz 1) Z With order code K 1 L
240 V AC 50/60 Hz 1) Z With order code K 1 M
Manual electrical closing at the circuit-breaker
24 V DC M
48 V DC N
60 V DC P
110 V DC Q
220 V DC R
100 V AC 50/60 Hz 1) T
110 V AC 50/60 Hz 1) U
230 V AC 50/60 Hz 1) V
30 V DC Z With order code K 2 A
32 V DC Z With order code K 2 B
120 V DC Z With order code K 2 C
125 V DC Z With order code K 2 D
127 V DC Z With order code K 2 E
240 V DC Z With order code K 2 F
120 V AC 50/60 Hz 1) Z With order code K 2 K
125 V AC 50/60 Hz 1) Z With order code K 2 L
240 V AC 50/60 Hz 1) Z With order code K 2 M
1) The AC frequency 50 or 60 Hz is selected at the 16th position of the
order number together with the language (see page 21)
Configuration example
Vacuum circuit-breaker 3 A H
(Ur = 36 kV, 50/60 Hz, Up = 195 kV, Isc = 40 kA, Ir = 2500 A,
pole-center distance = 350 mm) 4 3 0 6 – 6 P
Manual electrical closing at the circuit-breaker,
operating voltage of the closing solenoid 30 V DC Z K 2 A
See page 18
See page 19
See page 20
See page 21
See page 21
See page 22
Standard voltages Special voltages
24 V DC 1
48 V DC 2
60 V DC 3
110 V DC 4
220 V DC 5
100 V AC 50/60 Hz 1) 6
110 V AC 50/60 Hz 1) 7
230 V AC 50/60 Hz 1) 8
30 V DC 9 With order code L 1 A
32 V DC 9 With order code L 1 B
120 V DC 9 With order code L 1 C
125 V DC 9 With order code L 1 D
127 V DC
240 V DC
120 V AC 50/60 Hz 1)
9
9
9
With order code
With order code
With order code
L
L
L
1 E
1 F
1 K
2
125 V AC 50/60 Hz 1) 9 With order code L 1 L
240 V AC 50/60 Hz 1) 9 With order code L 1 M
Configuration example
Vacuum circuit-breaker 3 A H
(Ur = 36 kV, 50/60 Hz, Up = 195 kV, Isc = 40 kA, Ir = 2500 A,
pole-center distance = 350 mm) 4 3 0 6 – 6 P Z
Operating voltage of the 1st shunt release 48 V DC 2
See page 19
See page 20
See page 21
See page 21
See page 22
Standard voltages Special voltages
2 120 V DC
125 V DC
127 V DC
9
9
9
With order code
With order code
With order code
M
M
M
1 C
1 D
1 E
240 V DC 9 With order code M 1 F
120 V AC 50/60 Hz 1) 9 With order code M 1 K
125 V AC 50/60 Hz 1) 9 With order code M 1 L
240 V AC 50/60 Hz 1) 9 With order code M 1 M
Special versions
To operate the 2nd release as an undervoltage release on an
energy store type AN 1902- (for DC) or AN 1901-2 (for AC),
both make Bender, the operating voltage must be defined –
and whether the energy store will be provided by the customer
or included in the scope of supply.
Energy store
Type In the scope
of supply
60 V DC AN 1902- no 9 With order code M 2 D
110 V DC AN 1902- no 9 With order code M 2 E
220 V DC AN 1902- no 9 With order code M 2 F
100/110/230 V AC AN 1901-2 no 9 With order code M 2 G
60 V DC AN 1902- yes 9 With order code M 3 D
110 V DC AN 1902- yes 9 With order code M 3 E
220 V DC AN 1902- yes 9 With order code M 3 F
100/110/230 V AC AN 1901-2 yes 9 With order code M 3 G
Configuration example
Vacuum circuit-breaker 3 A H
(Ur = 36 kV, 50/60 Hz, Up = 195 kV, Isc = 40 kA, Ir = 2500 A,
pole-center distance = 350 mm) 4 3 0 6 – 6 P Z 2
2nd release as undervoltage release with operating voltage 32 V DC 9 M 1 B
See page 20
See page 21
See page 21
See page 22
Standard voltages Special voltages
Energy store
Type In the scope
of supply
60 V DC AN 1902- no 9 With order code N 2 D
110 V DC AN 1902- no 9 With order code N 2 E
220 V DC AN 1902- no 9 With order code N 2 F
100/110/230 V AC AN 1901-2 no 9 With order code N 2 G
60 V DC AN 1902- yes 9 With order code N 3 D
110 V DC AN 1902- yes 9 With order code N 3 E
220 V DC AN 1902- yes 9 With order code N 3 F
100/110/230 V AC AN 1901-2 yes 9 With order code N 3 G
Configuration example
Vacuum circuit-breaker 3 A H
(Ur = 36 kV, 50/60 Hz, Up = 195 kV, Isc = 40 kA, Ir = 2500 A,
pole-center distance = 350 mm) 4 3 0 6 – 6 P Z 2 9 –
3rd release as c.t.-operated release 0
See page 21
See page 21
See page 22
Standard voltages Special voltages
24 V DC 2) B
48 V DC C
60 V DC D
110 V DC E
220 V DC F
100 V AC 50/60 Hz 1) H
110 V AC 50/60 Hz 1) J
230 V AC 50/60 Hz 1) K
30 V DC Z With order code P 1 A
32 V DC Z With order code P 1 B
120 V DC Z With order code P 1 C
125 V DC Z With order code P 1 D
2 127 V DC
240 V DC
120 V AC 50/60 Hz 1)
Z
Z
Z
With order code
With order code
With order code
P
P
P
1 E
1 F
1 K
125 V AC 50/60 Hz 1) Z With order code P 1 L
240 V AC 50/60 Hz 1) Z With order code P 1 M
Configuration example
Vacuum circuit-breaker 3 A H
(Ur = 36 kV, 50/60 Hz, Up = 195 kV, Isc = 40 kA, Ir = 2500 A,
pole-center distance = 350 mm) 4 3 0 6 – 6 P Z 2 9 – 0
Operating voltage of the operating mechanism 230 V AC, 50 Hz K
Auxiliary switch
terminal strip 2)
12 NO + 12 NC
64-pole plug 1)
24-pole plug
6 NO + 6 NC
See page 22
interlocking
Mechanical
24-pole
n n A
n n E
n n G
n n C
n n M
n n n B
n n n F
n n n H
n n n D
n n n N
Special versions gold-plated contacts and pins
Auxiliary switch 6 NO + 6 NC and 24-pole terminal strip (G or H)
Auxiliary switch 12 NO + 12 NC and 24-pole terminal strip (M or N)
–
–
Z
Z
A
A
1
1
7
8
2
Auxiliary switch 6 NO + 6 NC and 64-pole plug (A or B) – Z A 2 0
Auxiliary switch 12 NO + 12 NC and 64-pole plug (C or D) – Z A 2 1
16th position
AC frequency of operating voltages and
languages of operating instructions and rating plate
Language Frequency
German 50 Hz or DC 0
60 Hz 1
English 50 Hz or DC 2
60 Hz 3
French 50 Hz or DC 4
60 Hz 5
Spanish 50 Hz or DC 6
60 Hz 7
Other languages on request
Special versions
Additional information on the rating plate (only after consultation
with Dept. PTD M C S, Berlin). Information in clear text. – Z Y 1 2
Configuration example
Vacuum circuit-breaker 3 A H
(Ur = 36 kV, 50/60 Hz, Up = 195 kV, Isc = 40 kA, Ir = 2500 A,
pole-center distance = 350 mm) 4 3 0 6 – 6 P Z 2 9 – 0 K
Auxiliary switch 12 NO + 12 NC, 64-pole plug, without mechanical interlocking C
Frequency 50 Hz or DC, operating instructions and rating plate in English 2
Options
Configuration example
Vacuum circuit-breaker 3 A H
Rated voltage Ur = 36 kV (50/60 Hz)
Rated lightning impulse withstand voltage Up = 170 kV
Rated short-circuit breaking current Isc = 40 kA
Pole-center distance = 350 mm
Rated normal current Ir = 2500 A 4 3 0 6 – 6
Increase of rated lightning impulse withstand voltage Up = 195 kV – Z E 2 4
+ E 2 5
Closing solenoid, 1st shunt release, 2nd shunt release
and c.t.-operated release with a rated normal current of 0.5 A P
Manual electrical closing at the circuit-breaker, operating voltage
of the closing solenoid 30 V DC Z K 2 A
Operating voltage of the 1st release 48 V DC 2
2nd release as undervoltage release with operating voltage 32 V DC 9 – M 1 B
3rd release as c.t.-operated release 0
Operating voltage of the operating mechanism 230 V AC, 50 Hz K
Auxiliary switch 12 NO + 12 NC, 64-pole plug, without mechanical interlocking C
Frequency 50 Hz or DC, operating instructions and rating plate in English 2
Condensation protection, heating for 230 V AC, 50 W – Z A 3 0
Routine test certificate enclosed – Z F 2 0
– Year of manufacture
R-HG11-198.tif
Contents Page
Technical Data 27
Electrical data, dimensions and weights:
Voltage level 7.2 kV 28
Voltage level 12 kV 28
Voltage level 15 kV 28
Voltage level 17.5 kV 30
Voltage level 24 kV 30
Voltage level 36 kV 30
Operating times 33
Short-circuit protection of motors 33
Consumption data of releases 33
Circuit diagrams 34
R-HG11-199.eps
3
R-HG11-200.tif
Control elements
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current
Pole-center distance
Minimum clearance,
Minimum clearance,
DC component in %
withstand voltage
(can be ordered)
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weights
Ir tk Isc Ima Up Ud
A mm s kA % kA kA kV kV mV mm mm mm mm kg
3 12 kV
50/60 Hz A
Ir
mm
tk
s
Isc
kA % kA
Ima
kA
Up
kV
Ud
kV mV mm mm mm mm kg
Ir tk Isc Ima Up Ud
15 kV
50/60 Hz A mm s kA % kA kA kV kV mV mm mm mm mm kg
n Standard according to IEC 62271-100 o Possible Rated operating sequence possible up to Isc = 31.5 kA
Operating cycles
Operating cycles
is shown as a function
10 000 of the breaking current 10 000
HG11-2598a_en eps
HG11-2597a_en eps
3
210 210 210 210
105
105
190 190
437
437
587
587
HG11-2595 eps
HG11-2596 eps
109
109
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current
Pole-center distance
Minimum clearance,
Minimum clearance,
DC component in %
withstand voltage
(can be ordered)
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weights
Ir tk Isc Ima Up Ud
A mm s kA % kA kA kV kV mV mm mm mm mm kg
3
Ir tk Isc Ima Up Ud
24 kV
50/60 Hz A mm s kA % kA kA kV kV mV mm mm mm mm kg
Ir tk Isc Ima Up Ud
36 kV
50/60 Hz A mm s kA % kA kA kV kV mV mm mm mm mm kg
n Standard according to IEC 62271-100 o Possible Rated operating sequence possible up to Isc = 31.5 kA
Operating cycles
is shown as a function
HG11-2600a_en eps
50
HG11-2599a_en eps
3
105
105
190 190
437
437
587
587
HG11-2595 eps
HG11-2596 eps
109
109
190 190
437
790
648
437
790
453
648
HG11-2602a eps
60
109
109
460 610
105
190 190
648
648
437
437
HG11-2604a eps
HG11-2603a eps
109
109
610
Dimension drawing 7
Dimension drawing 8
211
104
954
778
494
HG11-2605a eps
3
70
520
Dimension drawing 9
350 350
211
ca.104
1000
494
733
HG11-2606a eps
70
612
Dimension drawing 10
Operating times
3AH2 3AH4
Closing time – < 75 ms 1) < 80 ms 1)
Opening time 1st shunt release < 65 ms 1) < 65 ms 1)
2nd and 3rd release < 45 ms < 45 ms
Arcing time – < 15 ms < 15 ms
Opening time 1st shunt release < 80 ms < 80 ms
2nd and 3rd release < 60 ms < 60 ms
Dead time – 300 ms 300 ms
CLOSE/OPEN contact time 1st shunt release < 80 ms < 90 ms
2nd and 3rd release < 65 ms < 70 ms
Minimum command duration Closing solenoid 45 ms 45 ms
1st shunt release 40 ms 40 ms
2nd and 3rd release 20 ms 20 ms
Pulse time for circuit-breaker tripping signal 1st shunt release > 15 ms > 15 ms
2nd and 3rd release > 10 ms > 10 ms
Charging time for electrical operation – < 15 s < 15 s
Synchronism error between the poles – w 2 ms w 2 ms
Rated voltage Operating voltage Power consumption of the motor Smallest possible rated
of the motor current 2) of the m.c.b.
(miniature circuit-breaker)
with C-characteristic
V
24 DC
48 DC
max. V
26
53
min. V
20
41
W (at DC)
350/500 3)
350/500 3)
VA (at AC)
–
–
A
8/16 3)
6/8 3)
3
60 DC 66 51 350/500 3) – 4/6 3)
110 DC 121 93 350/500 3) – 2/3 3)
220 DC 242 187 350/500 3) – 1.6
110 AC 121 93 – 400/650 2) 2/3 3)
230 AC 244 187 – 400/650 2) 1.6
2) The current inrush in the drive motor can be neglected due to its very short presence
3) Values are valid for 3AH2/3AH4
Operation at
4) Consumption at pickup current (90 % of the rated normal current) and open armature
Basic equipment
HE
-M1 M P 11 13 21 23 31 33 41 43 51 53 61 63
-S1
12 14 22 24 32 34 42 44 52 54 62 64
-S7 -S6
HG11-2575_en eps
OPEN release
HG11-2579a eps
HA
-Y1
-X0
Manual closing – manual opening with auxiliary switch 6 NO + 6 NC Contacts available for customer with basic circuit-
breaker equipment and auxiliary switch 6 NO + 6 NC
32
OPEN release
3
14 A1 A1
HG11-2580a eps
HA 1
-S15 -Y9 u 2 -K1
13 A2 A2
-Y1
-X0
Motor operating mechanism with manual electrical closing Manual Closing and
electrical closing anti-pumping
33 43
-S1 -S1
34 44
D1
-Y7 U<
D2
A1 A1 A1 1
-Y2 -Y4 -Y6 -R1
A2 A2 A2 2
HG11-2583 eps
HG11-2584 eps
HG11-2585 eps
HG11-2586 eps
The circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring
-X0 -X0
21
-S21 23
22
11 22 22 -S1
22 -S3 24
-S1 -S7
-S10 12 21 21
21
A1 21 13
-K1
-M1 1M= u 2 22 14
21
14 -S41 13 -S42
31
D2 -S6
21 -K1 13 14 22
32
-S11 22 A1 A1 A1
HG11-2578b eps
1
HG11-2577a eps
1
22 -Y9 u 2 -K1 -Y1 u 2
A2 A2 A2
-S22
21
-X0 -X0
Motor operating mechanism with manual mechanical closing Cicuit-breaker Signal “closing 1st shunt
tripping signal spring charged” release
-X0 -X0
21
-S21
22
A1
11 13 21 23 31 33 41 43 51 53 61 63 71 73 81 83 91 93 101 103 111 113 121 123
-M1 1M= u 2
-S1
12 14 22 24 32 34 42 44 52 54 62 64 72 74 82 84 92 94 102 104 112 114 122 124
D2
22
3
HG11-2581a eps
-S22
HG11-2582a eps
21
-X0 -X0
Motor operating Contacts available for customer with basic circuit-breaker equipment
mechanism
Auxiliary switch –S1 (12 NO + 12 NC) instead of auxiliary switch 6 NO + 6 NC
Legend
HA Manual opening S14, Anti-pumping S41, Position switches Y1 1st shunt release
HE Manual closing S15 S42 (to indicate the charging state) Y2 2nd shunt release
K1 Contactor (anti-pumping) S21, Position switches S6 Circuit-breaker tripping signal Y4 Current-transformer
M1 Motor operating mechanism S22 (to de-energize the motor S7 Cutout switch for circuit- operated release
P Energy store operating mechanism breaker tripping signal Y6 Low-energy current-
R1 Resistance after charging) X0 Lower part of plug/ transformer operated release
S1 Auxiliary switch S3 Position switch terminal strip Y7 Undervoltage release
S10, Anti-pumping for (opens when closing spring Y9 Closing solenoid
S11 manual closing is charged)
The circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring
R-HG11-181.tif
Contents Page
Annex 37
Inquiry form 38
Configuration instructions 39
Configuration aid Foldout page
R-HG11-180.eps
Inquiry concerning
Technical Data Other values
4
terminal strip
Street
Postal code/city
Fax
1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16
3 A H n n n n – n n n n n – n n n n – Z
Instruction for configuration of the 3AH2 and 3AH4 vacuum circuit-breakers
1st step: Definition of the primary part (see pages 13 and 14)
See page 13
See page 15
See page 16
See page 17
See page 18
See page 19
See page 20
See page 21
See page 21
See page 22
page 14
Please specify the following ratings: Possible options:
and
Rated voltage (Ur) Ur: 7.2 kV to 36 kV
Rated lightning impulse withstand voltage (Up) Up: 60 kV to 195 kV
Rated short-duration power-frequency withstand voltage (Ud) Ud: 20 kV to 95 kV
Rated short-circuit breaking current (Isc) Isc: 25 kA to 40 kA 3 A H – –
Rated normal current (Ir) Ir: 1250 A to 3150 A
Pole-center distance 210 mm to 350 mm + + + +
3 A H – –
+ + + +
2nd step: Definition of the secondary equipment (see pages 15 to 21)
+ + + +
+ + + +
Release combination Shunt release, current-transformer operated release
(position 9) and undervoltage release
Closing solenoid Operating voltages from 24 V DC to 240 V AC + + + +
(position 10)
Operating voltage of the releases Operating voltages from 24 V DC to 240 V AC 3 A H – –
(positions 11/12)
Type of local closing Mechanical closing, + + + +
(position 10) manual electrical closing
Operating voltage of the motor Motor operating stored-energy mechanism
(position 14) with operating voltages from 24 V DC to 240 V AC + + + +
Number of auxiliary contacts 6 NO + 6 NC, 12 NO + 12 NC
(position 15) 3 A H – –
Design of the secondary connection 24-pole terminal strip, 24-pole plug connector,
(position 15) 64-pole plug connector
+ + + +
Language of the documentation English, German, French, Spanish
(position 16)
Frequency of the operating voltage of the 50 Hz/60 Hz + + + +
secondary equipment at AC (position 16)
3 A H – –
These equipment features define the positions 9 to 16 of the order number.
+ + + +
+ + + +
3rd step: Do you have any further requirements concerning the equipment? (Please refer to page 22)
3 A H – –
Should you still need more options than the possible special equipment like halogen-free and
flame-retardant or silicone-free version, condensate protection or an additional rating plate, etc., + + + +
please contact your responsible sales partner.
+ + + +
3 A H – –
+ + + +
+ + + +
3 A H – –
+ + + +
+ + + +
Siemens HG 11.04 · 2007 39
If not stated otherwise on the individual pages of this catalog, Siemens AG For questions concerning Subject to change without notice
we reserve the right to include modifications, especially regarding Power Transmission and Distribution Power Transmission and Distribution: Order No. E50001-K1511-A041-A1-7600
Printed in Germany
the stated values, dimensions and weights. Medium Voltage Division You can contact our Customer Support
Dispo 31601
Drawings are not binding. All product designations used are Nonnendammallee 104 Center 24 hours a day, 365 days a year. KG 04.07 5.0 36 En
trademarks or product names of Siemens AG or other suppliers. 13623 Berlin Tel.: +49 180/524 70 00 102413 6101/C6154
If not stated otherwise, all dimensions in this catalog are given Germany Fax: +49 180/524 24 71
in mm. (Calls charged: e.g. 12 Ct/min)
www.siemens.com/energy E-Mail: support.energy@siemens.com
www.siemens.com/energy-support
Responsible for
Technical contents: General editing:
Siemens AG, Dept. PTD M C PPM Siemens AG, Dept. PTD CC M The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases.
Berlin Erlangen The required features should therefore be specified in each individual case at the time of closing the contract.