Common Control Front View 8 9

1. Display Screen
2. AC Overview Key
10
3. Engine Overview Key
4. Cursor Cluster
7 5. Enter Key
MAIN MENU
6. Escape Key
EVENT LOG
1 7. Alarm Acknowledge
ENGINE OVERVIEW
Silence

11 8. Alarm Lamp (Yellow)

RUN AUTO STOP 9. Shutdown Lamp (Red)


10. Lamp Test
6 11. Run, Auto and Stop
Keys and Indicators

2 3 4 5

Alarm Indicators
Red Shutdown Light
•A flashing red light indicates that there are unacknowledged active Yellow Warning Light
shutdown events. •A flashing yellow light indicates that there are unacknowledged active
•A solid red light indicates that there are acknowledged shutdown events warnings.
active. Shutdown events are acknowledged by pressing the Alarm •A solid yellow light indicates that there are acknowledged warnings
Acknowledge key. Any condition that has caused a shutdown event must be active. Warnings are acknowledged by pressing the Alarm
manually reset . Acknowledge key.
•No red light indicates that there are no active shutdown events •No yellow light indicates that there are no active warning
Main Menu MENUS LAYOUT
Event Log (Fig.1)
Engine Overview (Fig.2)
AC Overview (Fig.3)
Configuration (Fig.4) Security (Fig.4.1)
Setpoints (Fig.4.2) Control (Fig.4.2.1) Auto Stop / Start
AVR Desired voltage
Gov Desired Voltage
Eng Mon / Protect (Fig.4.2.2) Battery Volts Monitor
Crank Start Counter
Eng Coolant Tempt Monitor
Engine Oil Pressure Monitor
Engine Speed Monitor
Enhance Eng Monitor
Service Maint Interval
Events (Fig.4.2.3) Event Input Function
Event Output Function
Event Response Config
Event System
Gen Mon / Protect (Fig.4.2.4) Enhanced Gen Monitor
Gen AC Monitor
Gen AC PWR Monitor
Gen Overcurrent
Gen Over/Under Frequency
Gen Over/Under Volts
Gen Reverse Power
Inputs/Outputs (Fig.4.2.5) Digital Inputs
Digital Outputs
Relay Outputs
Spare Analogue I/P
Network (Fig.4.2.6) Data Link Scada
Other (Fig.4.2.7) Digital Selectors
Reduce PWR Mode
Time / Date (Fig.4.3)
I/O Status (Fig.5)
Control (Fig.6)
Preferences (Fig.7)
Fig.1 Event Logs

MAIN MENU Resetting Faults/Events


EVENT
EVENTLOGS
LOGS To reset faults carry out the following operations:
ENGINE OVERVIEW
1. Press Alarm Acknowledge key
AC OVERVIEW
2. Remove the condition which caused the
CONFIGURE Warning/Shutdown
I/O STATUS 3. Press the “STOP” key
CONTROL
PREFERENCES

ACTIVE EVENTS 2
GENSET CONTROL 2
2
SPN 168 FMI 17
Fig.1.1 Resetting Faults
PRESENT
NUM OCCURANCES
MAIN MENU
EVENT
EVENTLOGS
LOGS
LOW BATTERY VOLTAGE
WARNING 1/ 3 ENGINE OVERVIEW
SPN 168 FMI 17
PRESENT OCC 2 AC OVERVIEW
LAST HOURS 0.0
02/08/04 15:18:56 CONFIGURE
I/O STATUS
EMERGENCY STOP
CONTROL
ACTIVATED 2/ 3
ACTIVE OCC 4 SPN 168 FMI 17 PREFERENCES
FIRST HOURS 0.0
24/07/04 03:12:22

ENGINE OVERSPEED
SHUTDOWN 3/ 3
INACTIVE OCC 1 ACTIVE EVENTS 2
GENSET CONTROL 2
2
SPN 168 FMI 17
ACTIVE RESET
The event system uses the following terms to describe the status of NUM OCCURANCES
an Event
LOW BATTERY VOLTAGE
WARNING 1/ 3
PRESENT - The condition causing the event is present
ACTIVE OCC 2
. and affecting system behaviour.
ACTIVE - The Event was previously present but is no .

. longer present and is not affecting the .


EMERGENCY STOP
. system behaviour
ACTIVATED 2/ 3
INACTIVE - The event was active at some time but is no. ACTIVE OCC 4
. longer active and is not effecting system .
. behaviour
ENGINE OVERSPEED
SHUTDOWN 3/ 3
INACTIVE OCC 1
Fig.2 Engine Overview 560 kPa 72° C 4.4V Fig.3 AC Overview
1500 rpm 0.2 hrs
RUNNING L-N V 240 240 240
MAIN MENU A 0 0 0
MAIN MENU
EVENT LOGS 50.0 Hz
EVENT LOGS
ENGINE OVERVIEW
ENGINE OVERVIEW OIL PRESSURE 560 kPa
COOLANT TEMP 72°C AC OVERVIEW
AC OVERVIEW ENGINE SPEED 1500 rpm KW 0 0 0
CONFIGURE
CONFIGURE KVA 0 0 0
I/O STATUS KV 0 0 0
I/O STATUS
CONTROL
CONTROL
BATT VOLTAGE 14.4 V
PREFERENCES
PREFERENCES LAST HRS 0.2
. KW 0 0 0
KVA 0 0 0
p.f. 0 0 0

SERV 500 HRS


OR 175 DAYS TOTAL KW 0 0%
RESET SERV INTVL 3 OR TOTAL KVA 0 0%
TOTAL KVAr 0 0%

OR
TOTAL CRANKS 6
T OTAL STARTS 6 KWh 0
RESET COUNTERS 3 KVArh 0
RESET ENERGY MTRS 3
AVG: 420 L-L 0A
50.0 Hz 1.00 LAGGING
TOTAL KW 0 0%
NO MORE INFORMATION
.AVAILABLE AVERAGE L-L 420 V
. FOR PREVIOUS SCREEN AVERAGE L-N 240 V
p.f. 1.0 LAGGING
L-L V 420 420 420
A 0 0 0
The Engine parameters may be viewed either by (a) going through the menus or by 50.0 Hz
(b) pressing the “Engine Overview” Key as shown in Fig.2. NO MORE INFORMATION
.AVAILABLE
. FOR PREVIOUS SCREEN
Similarly the AC parameters may be viewed either by (a) going through the menus
or by ( b) pressing the “AC Overview “ Key as shown in Fig.3.
Fig.4 Configure
4.1.4 Change Level 1 or 2 P/W
MAIN MENU
Fig.4.1.2 Level 1 or 2 Password Fig.4.1.3 Level 3 Password
EVENT LOGS
CURRENT LEVEL = 2
ENGINE OVERVIEW
CURRENT LEVEL = 2 CURRENT LEVEL = 2 DROP
DROP TO MIN
MIN LEVEL
LEVEL
AC OVERVIEW
DROP TO MIN LEVEL DROP TO MIN LEVEL ENTER LEVEL 1 OR 2
CONFIGURE
CONFIGURE
ENTER LEVEL 1 OR
ENTERLEVEL OR 22 ENTER LEVEL 1 OR 2 ENTER LEVEL 3
I/O STATUS
ENTER LEVEL 3 ENTER LEVEL 3 CHANGE LVL 1 PSWD
CONTROL
CHANGE LVL 1 PSWD CHANGE LVL 1 PSWD CHANGE LVL 2 PSWD
PREFERENCES
CHANGE LVL 2 PSWD CHANGE LVL 2 PSWD CHANGE SCADA PSWD
CHANGE SCADA PSWD CHANGE SCADA PSWD

Fig.4.1 Security
Ensure that the current level of
CONFIGURE
security is at least as high as
ENTER PASSWORD FOR the level of the password to be
SECURITY
SECURITY PHONE IN WITH changed
DESIRED LEVEL
SETPOINTS 5403895754824385
_______________0 CURRENT LEVEL = 2
TIME / DATE ENTER RESPONSE
DROP TO MIN LEVEL
ENTER LEVEL 1 OR 2
Press the UP or DOWN key to increment
Copy this number and call the ENTER LEVEL 3
or decrement the highlighted digit to the
factory to obtain a factory
Fig.4.1.1 Min Security Level desired number. CHANGE LVL 1 PSWD
provided response code to enter.
Press the RIGHT key to highlight the next CHANGE LVL 2 PSWD
CURRENT LEVEL = 2 character. When all digits entered press CHANGE SCADA PSWD
the ENTER key. ENTER RESPONSE
DROP
DROPTO
TOMIN
MINLEVEL
LEVEL
The Current Level of security is displayed _______________0
ENTER LEVEL 1 OR 2
and parameters can be set.
ENTER LEVEL 3
CHANGE LVL 1 PSWD CHANGE LEVEL 2
PASSWORD
CHANGE LVL 2 PSWD This places the controller into the lowest level of Enter new number obtained from the
______________0
CHANGE SCADA PSWD security authorised. This would be used when factory and press the ENTER key..
leaving the controller. The Current Level (LEVEL 3) of Enter new number and press the
If ‘DROP TO MIN LEVEL’ is not initiated it will security is displayed and parameters ENTER key.
automatically revert to minimum level after 10 can be set Note: To disable a security level, set
minutes. the password to a single zero.
Fig.4.2 Setpoints

CONFIGURE Fig.4.2.1.b AVR Desired Voltage


SECURITY
SETPOINTS
SETPOINTS MAXIMUM NUMBER OF CONTROL
CRANK CYCLES AUTOMATIC STOP/START
TIME / DATE
3
AVR
AVR DESIRED VOLTAGE
DESIRED VOLTAGE
GOV DESIRED ENG SPD
Fig.4.2.1 Control COOLANT DURATION
0 minutes
SETPOINTS .
CONTROL MAXIMUM GEN OUTPUT
VOLTAGE BIAS PERCENT
ENG MON / PROTECT
5%
EVENTS START AID ACTIVATION
TIME
GEN MON / PROTECT 0 seconds
I/O
GENERATOR NOMINAL
NETWORK OUTPUT VOLTAGE
OTHER CRANK ALERT 100 V
ACTIVATION TIME
0 seconds

Fig.4.2.1.a Auto/Stop/Start
CRANK TERMINATION
RPM 400 RPM
CONTROL
. 3
AUTOMATIC STOP/START Fig.4.2.1.c Gov Desired Eng SPD

AVR DESIRED VOLTAGE


GOV DESIRED ENG SPD CONTROL
ENGINE FUEL TYPE
CONFIGURATION AUTOMATIC STOP/START
DIESEL 3 AVR DESIRED VOLTAGE
GOV DESIRED
GOV DESIRED ENG
ENG SPD
SPD
ENGINE START FAULT
PROTECTION DELAY TIME FUEL SHUTOFF
30 seconds SOLENOID TYPE CONFIG
ENERGISE TO RUN

CRANK DURATION MAXIMUM ENGINE


. SPEED BIAS
ENGINE TYPE 100 rpm
. 7 seconds
CONFIGURATION
MECHANICAL

CRANK CYCLE REST GEN NOMINAL OUTPUT


INTERVAL FREQUENCY
7 seconds ENGINE CONTROLLER 50.0 Hz
J1939 SUPPORT CONFIG
NO DATA LINK

ENGINE PURGE CYCLE


TIME
0 seconds .. ENGINE COOL DOWN
SPEED CONFIGURATION
RATED SPEED
Note:
Factory defaults values are used for all of the
setpoints values in these examples.
Fig.4.2.2 Engine Mon / Protect Fig.4.2.2b Crank / Starter Counter Fig.4.2.2c Eng Cool Tempt Mon

SETPOINTS ENG MON / PROTECT ENG MON / PROTECT

CONTROL BATT VOLTS MONITOR BATT VOLTS MONITOR


ENG
ENGMON
MON//PROTECT
PROTECT CRANK / START
CRANK START COUNTER
COUNTER CRANK / START COUNTER

EVENTS ENG COOL TEMP MONITOR ENG


ENGCOOL
COOLTEMP
TEMPMONITOR
MONITOR
GEN MON / PROTECT ENGINE OIL PRESS MONITOR ENGINE OIL PRESS MONITOR

I/O ENGINE SPEED MONITOR ENGINE SPEED MONITOR

NETWORK ENHANCED ENG MONITOR ENHANCED ENG MONITOR

OTHER SERV MAINT INTERVAL SERV MAINT INTERVAL

PSWD LEVEL TO RESET


CRANK / START COUNTERS
2 2 ENGINE COOLANT TEMPT
SENSOR CONFIGURATION
I/O PIN 2
Fig.4.2.2a Batt Volts Monitor

HIGH ENG COOL TEMPT


ENG MON / PROTECT WARNING THRESHOLD
BATT VOLTS MONITOR 102°C 2
CRANK / START COUNTER
ENG COOL TEMP MONITOR
ENG OIL PRESS MONITOR HIGH ENG COOL TEMPT
WARNING DELAY TIME
ENGINE SPEED MONITOR
15 seconds 2
ENHANCED ENG MONITOR HIGH BATTERY VOLTAGE
SHUTDOWN DELAY TIME
SERV MAINT INTERVAL
30 seconds
HIGH ENG COOL TEMPT
SHUTDOWN THRESHOL
120°C 2
LOW BATTERY VOLTAGE
WARNING THRESHOLD
HIGH BATTERY VOLTAGE 23.4 VDC
WARNING THRESHOLD
29.4 VDC HIGH ENG COOL TEMPT
SHUTDOWN DELAY TIME
LOW BATTERY VOLTAGE 15 seconds 2
WARNING DELAY TIME
HIGH BATTERY VOLTAGE 30 seconds
WARNING DELAY TIME
30 seconds
LOW ENG COOL TEMPT
WARNING THRESHOLD
LOW BATT CHARGER SYS
VOLT WARN THRESHOLD 6°C 2
HIGH BATTERY VOLTAGE 26.0 VDC
SHUTDOWN THRESHOLD
30.0 VDC
LOW ENG COOL TEMPT
LOW BATT CHARGER SYS WARNING DELAY TIME
VOLT WARN DELAY TIME 10 seconds 2
30 seconds
Fig.4.2.2d Eng Oil Press Mon Fig.4.2.2e Eng Speed Monitor Fig.4.2.2f Enhanced Eng Monitor

ENG MON / PROTECT


ENG MON / PROTECT ENG MON / PROTECT BATT VOLTS MONITOR
BATT VOLTS MONITOR BATT VOLTS MONITOR CRANK / START COUNTER
CRANK / START COUNTER CRANK / START COUNTER ENG COOL TEMP MONITOR
ENG COOL TEMP MONITOR ENG COOL TEMP MONITOR ENGINE OIL PRESS MONITOR
ENGINE OILPRESS
ENGINE OIL PRESSMONITOR
MONITOR ENGINE OIL PRESS MONITOR ENGINE SPEED MONITOR
ENGINE SPEED MONITOR ENGINESPEED
ENGINE SPEEDMONITOR
MONITOR ENHANCED
ENHANCEDENG
ENGMONITOR
MONITOR
ENHANCED ENG MONITOR ENHANCED ENG MONITOR SERV MAINT INTERVAL
SERV MAINT INTERVAL SERV MAINT INTERVAL

ENG CYL TEMP SENSOR


INSTALL STATUS
NOT INSTALLED 2
FLYWHEEL TEETH
ENGINE OIL PRESSURE
.
SENSOR CONFIGURATION
I/O PIN 2 126 3
NUMBER OF ENGINE
CYLINDERS
1 2
LOW ENGINE OIL PRES ENGINE OVER SPEED
WARNING THRESHOLD SHUTDOWN THRESHOLD
276 KPa 2 1800 rpm 3

Fig.4.2.2g Service Maint Interval


ENGINE UNDER SPEED
• OIL
LOW IDLE ENGINE WARNING THRESHOLD
PRES WARNING THRESH ENG MON / PROTECT
1330 rpm 3
138 KPa 2
BATT VOLTS MONITOR
CRANK / START COUNTER
ENGINE UNDER SPEED
LOW ENGINE OIL PRES ENG COOL TEMP MONITOR
WARNING DELAY TIME
WARNING DELAY TIME 1.0 seconds 2 ENGINE OIL PRESS MONITOR
10 seconds 2
ENGINE SPEED MONITOR
ENHANCED ENG MONITOR
ENGINE UNDER SPEED SERVMAINT
MAINTINTERVAL
INTERVAL
LOW ENGINE OIL PRES SHUTDOWN THRESHOLD SERV
SHUTDOWN THRESHOLD 1300 rpm 3
36 KPa 2

ENGINE UNDER SPEED


LOW IDLE ENGINE OIL SHUTDOWN DELAY TIME SERVICE MAINTENANCE
PRES S/D THRESHOLD 2.0 seconds 2 INTERVAL – HOURS
68 KPa 2 500 HOURS

LOW ENGINE OIL PRES SERVICE MAINTENANCE


SHUTDOWN DELAY TIME INTERVAL – DAYS
10 seconds 2 180 DAYS

LOW ENGINE OIL PRES PSWD LEVEL TO RESET


STEP SPEED SERVICE MAINT INTVAL
1350 rpm 2 3 3
Fig.4.2.3 Events Fig.4.2.3b Event O/P Function Fig.4.2.3d Event System

SETPOINTS EVENTS EVENTS


CONTROL EVENT I/P FUNCTION EVENT I/P FUNCTION
ENG MON / PROTECT EVENT
EVENTO/P
O/PFUNCTION
FUNCTION EVENT O/P FUNCTION
EVENTS
EVENTS
EVENTS EVENT RESPONSE CONFIG EVENT RESPONSE CONFIG
GEN MON / PROTECT EVENT SYSTEM EVENTSYSTEM
EVENT SYSTEM
I/O
NETWORK
OTHERS

EVENT O/P FUNCTIONS EVENT O/P FUNCTIONS


EVENT INSTANCE ##11
EVENT INSTANCE EVENT INSTANCE ##11
EVENT INSTANCE
EVENT INSTANCE # 2 EVENT INSTANCE # 2
Fig.4.2.3a Event I/P Function

EVENTS
EVENT I/PFUNCTION
EVENT I/P FUNCTION

EVENT O/P FUNCTION WARNING EVENT


EVENT RESPONSE CONFIG EVENT OUTPUT FUNCTION AUTO RESET ENABLE
# 1 TRIGGER CONDITION AUTO RESET
EVENT SYSTEM CAUSE NOT KNOWN 2

AUDIBLE ALARM EVENT


EVENT OUTPUT FUNCTION AUTO RESET ENABLE
# 1 SUSPECT PAR NUM NO AUTO RESET
EVENT I/P FUNCTIONS UNEXPECTED ENG S/D

EVENT INSTANCE
EVENT INSTANCE ##11
EVENT INSTANCE # 2 LOSS OF UTIL EVENT
The same procedure is used for setting AUTO RESET ENABLE
EVENT INSTANCE # 3 up Event Output Functions # 2 AUTO RESET
EVENT INSTANCE # 4
EVENT INSTANCE # 5
EVENT INSTANCE # 6 BREAKER #1 TRIP EVENT
AUTO RESET ENABLE
AUTO RESET

BREAKER #2 TRIP EVENT


AUTO RESET ENABLE
EVENT INPUT FUNCTION EVENT INPUT FUNCTION AUTO RESET
# 1 ACTIVE STATE CFG # 1 SUSPECT PAR NUM
ACTIVE HIGH 2 ENG COOLANT TEMP 2

EVENT INPUT FUNCTION EVENT INPUT FUNCTION


# 1 EVENT DELAY TIME # 1 FAILURE MODE I/D
10 seconds 2 HIGH SHUTDOWN 2

The same procedure is used for setting


up Event Input Functions # 2 to # 6
Fig.4.2.3c Event Response Config Fig.4.2.3c (ii) Engine, Gen and Other
. Protect Configs
.

EVENTS EVENT RESPONSE CONFIG


EVENT I/P FUNCTION DIAGNOSTICS CONFIG
EVENT O/P FUNCTION ENGINE PROTECTCONFIG
ENGINE PROTECT CONFIG
EVENT RESPONSE
EVENT RESPONSECONFIG
CONFIG GEN PROTECT CONFIG
EVENT SYSTEM OTHER SYSEM CONFIG

The same procedure used in Diagnostics


Fig.4.2.3c (i) Diagnostics Config Config is used to configure the desired
response in:

EVENT RESPONSE CONFIG


DIAGNOSTICS CONFIG
DIAGNOSTICS CONFIG • ENGINE PROTECT CONFIG

ENGINE PROTECT CONFIG • GEN PROTECT CONFIG

GEN PROTECT CONFIG • OTHER SYSEM CONFIG

OTHER SYSEM CONFIG

Below is the list of all the available options


DIAGNOSTICS CONFIG • Warning
PRESSURES
PRESSURES • Audible Alert
TEMPERATURES • Soft Shutdown
LEVELS • Hard Shutdown
OTHERS • Loss Of Utility
• Breaker #1 Trip
• Breaker #2 Trip
• FPT
AIR FILTER DIFF PRESS
• Active Only
SENSOR DIAG CONFIG
. VIEW EDIT

ENGINE OIL PRESSURE


SENSOR DIAG CONFIG
. VIEW EDIT

The “Diagnostics Configuration” block is


used to configure the desired response for any
diagnostic generated by the genset control.

U WARNING The options available for each setpoint can be


viewed or edited as shown. A U indicates
. U AUDIBLE ALERT
.. SOFT SHUTDOWN which options are selected. The user may
STARTING AIR PRESS . HARD SHUTDOWN select or remove U by using the left cursor
SENSOR DIAG CONFIG . BRK 1 TRIP key.
. VIEW EDIT . BRK 2 TRIP
The same procedure is used to view or edit
TEMPERATURES, LEVELS and OTHERS.
Fig.4.2.4 Gen Mon / Protect Fig 4.2.4b Gen AC Monitor Fig 4.2.4c Gen AC PWR Monitor

GEN MON
GEN MON
SETPOINTS ENHANCED GEN MONITOR
ENHANCED GEN MONITOR
CONTROL GEN AC
AC MONITOR
MONITOR GEN AC MONITOR
GEN
GEN AC
GEN AC PWR
PWRMONITOR
MONITOR
ENG MON / PROTECT GEN AC PWR MONITOR
EVENTS GEN OVERCURRENT
GEN OVERCURRENT
GEN
GEN MON
MON // PROTECT
PROTECT GEN OVER/UNDER FREQ
GEN OVER/UNDER FREQ
I/O GEN OVER/UNDER VOLT
GEN OVER/UNDER VOLT
NETWORK GEN REVERSE POWER
GEN REVERSE POWER
OTHER

PSWD LEVEL TO RESET


GEN CONNECTION GEN ENERGY METERS
Fig 4.2.4a Enhanced Gen Monitor CONFIGURATION 3 3
STAR/WYE 3

GEN MON GEN PT PRIMARY


ENHANCEDGEN
ENHANCED GENMONITOR
MONITOR WINDING RATING Fig 4.2.4d Gen Overcurrent
1V 3
GEN AC MONITOR
GEN MON
GEN AC PWR MONITOR
ENHANCED GEN MONITOR
GEN OVERCURRENT GEN PT SECONDARY
WINDING RATING GEN AC MONITOR
GEN OVER/UNDER FREQ
1V 3 GEN AC PWR MONITOR
GEN OVER/UNDER VOLT
GEN OVERCURRENT
GEN OVERCURRENT
GEN REVERSE POWER
GEN OVER/UNDER FREQ
GEN CT PRIMARY
WINDING RATING GEN OVER/UNDER VOLT
150A 3 GEN REVERSE POWER

GEN WINDING TEMP


SNSR INSTALL STATUS
NOT INSTALLED 2 GEN CT SECONDARY
WINDING RATING
5A 3 GEN DEF TIME OVER
CUR WARNING % THRESH
NUM OF GEN BEARING 100 %
TEMP SENSORS
NOT INSTALLED 2 NUMBER OF GENERATOR
POLES
4 GEN INV TIME OVER
CUR S/D TIME MULTPLR
0.27 seconds
GENERATOR RATED
FREQUENCY
GENERATOR RATED 50 HZ 3 GEN DEF TIME OVER
POWER CUR S/D % THRESHOLD
36 kW 3 125 %
GENERATOR RATED
VOLTAGE
400 V 3 GEN DEF TIME OVER
GENERATOR RATED
APPARENT POWER CUR S/D DELAY TIME
45 kVA 3 0.1 seconds
Fig 4.2.4e Gen Over/Under Freq Fig 4.2.4f Gen Over/Under Freq Fig 4.2.4g Gen Reverse Power

GEN MON GEN MON GEN MON

ENHANCED GEN MONITOR ENHANCED GEN MONITOR ENHANCED GEN MONITOR

GEN AC MONITOR GEN AC MONITOR GEN AC MONITOR

GEN AC PWR MONITOR GEN AC PWR MONITOR GEN AC PWR MONITOR

GEN OVERCURRENT GEN OVERCURRENT GEN OVERCURRENT

GEN OVER/UNDER
GEN OVER/UNDERFREQ
FREQ GEN OVER/UNDER FREQ GEN OVER/UNDER FREQ

GEN OVER/UNDER VOLT GEN OVER/UNDER


GEN OVER/UNDERVOLT
VOLT GEN OVER/UNDER VOLT
GEN REVERSE
GEN REVERSEPOWER
POWER
GEN REVERSE POWER GEN REVERSE POWER

GEN OVER VOLTAGE


GEN OVER FREQUENCY GEN OVER VOLTAGE WARNING % THRESHOLD
WARNING % THRESHOLD WARNING % THRESHOLD 105.0 %
105.0 % 105.0 %

GEN OVER VOLTAGE


GEN OVER FREQUENCY GEN OVER VOLTAGE WARNING DELAY TIME
WARNING DELAY TIME WARNING DELAY TIME 10 seconds
3 seconds 10 seconds

GEN OVER VOLTAGE


GEN OVER FREQUENCY GEN OVER VOLTAGE SHUTDOWN % THRESH
SHUTDOWN % THRESH SHUTDOWN % THRESH 110.0 %
110.0 % 110.0 %

GEN OVER VOLTAGE


GEN OVER FREQUENCY GEN OVER VOLTAGE SHUTDOWN DELAY TIME
SHUTDOWN DELAY TIME SHUTDOWN DELAY TIME 2 seconds
5 seconds 2 seconds

GEN UNDER FREQUENCY GEN UNDER VOLTAGE


WARNING % THRESHOLD WARNING % THRESHOLD
95.0 % 95.0 %

GEN UNDER FREQUENCY GEN UNDER VOLTAGE


WARNING DELAY TIME WARNING DELAY TIME
3 seconds 10 seconds

GEN UNDER FREQUENCY GEN UNDER VOLTAGE


SHUTDOWN % THRESH SHUTDOWN % THRESH
90.0 % 90.0 %

GEN UNDER FREQUENCY GEN UNDER VOLTAGE


SHUTDOWN DELAY TIME SHUTDOWN DELAY TIME
5 seconds 4 seconds
Fig.4.2.5 Inputs / Outputs Fig.4.2.5d Spare Analog Inputs Fig.4.2.5b Digital Outputs

SETPOINTS I/O I/O


CONTROL DIGITAL INPUTS DIGITAL INPUTS
ENG MON / PROTECT DIGITAL OUTPUTS DIGITAL OUTPUTS
DIGITAL OUTPUTS
EVENTS RELAY OUTPUTS RELAY OUTPUTS
GEN MON / PROTECT SPARE
SPARE ANALOG
ANALOG INPUT
INPUT SPARE ANALOG INPUT
I/O

NETWORK
OTHER
SPARE ANALOG INPUT
ENABLE STATUS DIGITAL OUTPUTS
DISABLED
OUTPUT
OUTPUT 11
Fig.4.2.5a Digital Inputs
OUTPUT 2
I/O SPARE ANALOG INPUT
DIGITAL INPUTS
DIGITAL INPUTS TYPE CONFIGURATION
TEMPERATURE
DIGITAL OUTPUTS
RELAY OUTPUTS DIGITAL OUTPUT #1
ACTIVE STATE CONFIG
SPARE ANALOG INPUT SPARE ANALOG INPUT HIGH
SUSPECT PARM NUM
ENGINE OIL TEMP
Repeat for setting Digital Output 2

DIGITAL INPUTS
SPARE ANALOG INPUT
Fig.4.2.5c Relay Outputs
INPUT
INPUT 11 HIGH TEMP WARN THRESH
INPUT 2 100 ° C
I/O
INPUT 3 DIGITAL INPUTS
INPUT 4 DIGITAL OUTPUTS
SPARE ANALOG INPUT
INPUT 5 RELAY OUTPUTS
RELAY OUTPUTS
HIGH WARN DELAY TIME
INPUT 6 10 seconds SPARE ANALOG INPUT
INPUT 7
INPUT 8
SPARE ANALOG INPUT
HIGH TEMP S/D THRESH
120 ° C Relay Outputs

DIGITAL INPUT #1 OUTPUT


OUTPUT 11
ACTIVE STATE CONFIG OUTPUT 2
LOW
SPARE ANALOG INPUT OUTPUT 3
HIGH S/D DELAY TIME
Repeat for setting Digital Inputs 2 to 8 10 seconds OUTPUT 4
OUTPUT 5
OUTPUT 6
SPARE ANALOG INPUT OUTPUT 7
LOW TEMP WARN THRESH
20 ° C OUTPUT 8
SPARE ANALOG INPUT
LOW TEMP S/D THRESH
10 ° C
SPARE ANALOG INPUT
LOW WARN DELAY TIME RELAY OUTPUT #1
10 seconds ACTIVE STATE CONFIG
SPARE ANALOG INPUT ACTIVE HIGH
LOW S/D DELAY TIME
10 seconds
Repeat for setting Relay Outputs 2 to 8