Fyi
Regards
S.Anand khanna
Dear Mr.Ralkar,
With reference to the below mentioned pump model, the power at shut off condition (62 kw) mentioned in our
technical data sheet seems to be a typographical error and the correct power at shut off condition is 96 kw. It is not
critical to check the power at shut off condition, but the pump should work satisfactorily at duty conditions.
Regards
S.Anand khanna
This is further to tele communications we had today. Thanks for checking the data for pump SDD 200/200.
The shut off power is 96KW as against TDS number of 63KW.
PL. mail the corrected data for the pump with corrected curve. Accordingly we will now take up with NTPC
for acceptance of this pump and keep you posted.
1
WE now await your communication.
We are having issue of excessive -pump power consumption at Shut Off conditions. Details are
already forwarded to your design dept. Need possible reasons and solution. Customer is not
accepting pumps during PG tests.
• WE have procured from Best & Crompton Engg Ltd, Pumps Division –Main pump -Pump
Model SDD 200/200 ( motor Driven)-410 m3/Hr-105M head-1470 RPM-and SDC 200/200( engine
Driven) & Jocky pump-CNW 100/315 -75M3/Hr @105M vide PO no.20090077 & 20100160
• Scanned copies of approved TDS and actual reading of power consumption during PG
tests is also attached.
• NTPC MDCC was issued by NTPC ROI-Chennai
• PL. check the power consumption TDS data -62 KW at Shut off- but actual recorded
data is 117.14KW/97.5KW after the necessary corrections. This is extremely high and as
such NTPC is not accepting these pumps
• Request your support urgently on what is the correct data of shut off power for
this model and what was the data at the time of factory tests. If TDS data needs
correction, then accordingly new need to approach customer with your letter.
• I will ring you tomorrow.
Regards-Ralkar
UTC Fire & Security India Ltd.SL NO :- W0097908 ,Model No:- SDD 200/200
2
3 Revised as per attached vandor mail 2/6/2014 IS IS IS NL
2 Revised to incorporate the correct Wear ring MOC, 6/2/2009 AP AP ANK NB
1 Revised to incorporate the correct data received from 15/1/2009 AP AP ANK NB
0 Sub mision for approval 8/4/2008 SG SG SCV AP
REV. Description Date Prepared Checked Approved PM
REVISION
NTPC LTD.
FARAKKA SUPER THERMAL POWER PROJECT
STAGE-III (1 X 500MW)
FIRE DETECTION & PROTECTION SYSTEM
NTPC DOC. NO. 4140-151 -PVM-Y-01 A 2
REV. 3
Page 4 of 4
C:\Documents and Settings\sachin.churi\Desktop\TDS-01A HYDRANT JOCKEY PUMPS R2
KIDDE INDIA LIMITED
: 146.56 36.
12. At rated duty point
: 167.49 40.
12. At run out condition 1
12. Max. power consumption throughout the entire : 167.49 40. 1
range of operation
: 167.49 N.A.
13. At 150% of rated capacity 1
: 1470 1500 2955 (Max)
13.0 Speed, RPM 1
14.0 Specific speed (in metric units) 25. 25. 13.
26.0a Flange Drilling Standard : BS4504 Table 25/11 ANSI B16.5 CL1 50 FF 1
26.0b Direction of rotation viewed
from prime mover's position : Clockwise
29.0 Vibration level (Peak to Peak) throughout the : As per HIS As per HIS As per HIS
operating range
39.0 Accessories provided with Pump. : Base Plate,coupling,Coupling Guard &Foundation Bolts.
Page 4 of 4
C:\Documents and Settings\sachin.churi\Desktop\TDS-01A HYDRANT JOCKEY PUMPS R2
not inline with shutoff power
requirement as mentioned in
Technical datasheet