From: anandkhanna [anandkhanna.s@beaconweir.co.in]


Sent: Monday, May 19, 2014 2:48 PM
To: Saini, Indra BIS
Subject: [External] FW: Issues related Beacon Weir Fire Pumps-NTPC Farakka,-Excssive power
consumption at Shut off

Categories: External, Orange Category

Fyi

Regards

S.Anand khanna

From: anandkhanna [mailto:anandkhanna.s@beaconweir.co.in]


Sent: Saturday, May 17, 2014 3:26 PM
To: 'Kamlakar.Ralkar@fs.utc.com'
Cc: 'mjm'; 'smk'
Subject: RE: Issues related Beacon Weir Fire Pumps-NTPC Farakka,-Excssive power consumption at Shut off

Dear Mr.Ralkar,

With reference to the below mentioned pump model, the power at shut off condition (62 kw) mentioned in our
technical data sheet seems to be a typographical error and the correct power at shut off condition is 96 kw. It is not
critical to check the power at shut off condition, but the pump should work satisfactorily at duty conditions.

Regards

S.Anand khanna

From: Saini, Indra BIS [mailto:Indra.Saini@fs.utc.com]


Sent: Friday, May 16, 2014 4:17 PM
To: tec@beaconweir.co.in
Cc: Langer, Nipun BIS; Deorukhkar, Vikas BIS; Nikumbh, Rakeshkumar BIS; Ralkar, Kamlakar BIS
Subject: RE: Issues related Beacon Weir Fire Pumps-NTPC Farakka,-Excssive power consumption at Shut off

Dear Mr. Anand,


As discussed yesterday, please send the letter of power 93KW so that we can process the same to NTPC.
Please treat on priority basis.
Regards,
Indra Saini Signature Not Digitally signed
Verified
by S K BASAK
Date: 2014.06.17
11:01:56 IST
From: Ralkar, Kamlakar BIS Reason: CAT II
Sent: Thursday, May 15, 2014 7:50 PM Location:
To: tec@beaconweir.co.in NTPCEOC
Cc: Saini, Indra BIS; Langer, Nipun BIS; Deorukhkar, Vikas BIS; Nikumbh, Rakeshkumar BIS
Subject: FW: Issues related Beacon Weir Fire Pumps-NTPC Farakka,-Excssive power consumption at Shut off

Dear Mr. Anand,

 This is further to tele communications we had today. Thanks for checking the data for pump SDD 200/200.
The shut off power is 96KW as against TDS number of 63KW.
 PL. mail the corrected data for the pump with corrected curve. Accordingly we will now take up with NTPC
for acceptance of this pump and keep you posted.

1
 WE now await your communication.

Regards-Ralkar-UTC Fire & Security

From: Ralkar, Kamlakar BIS


Sent: Thursday, May 15, 2014 12:49 PM
To: 'mjm@beaconweir.co.in'
Cc: 'tec@beaconweir.co.in'; Saini, Indra BIS; Langer, Nipun BIS; jagadish, Sangameswaran BIS; Nikumbh,
Rakeshkumar BIS
Subject: FW: Issues related Beacon Weir Fire Pumps-NTPC Farakka,-Excssive power consumption at Shut off

Dear M.Jeyaraj Manickam,

We are having issue of excessive -pump power consumption at Shut Off conditions. Details are
already forwarded to your design dept. Need possible reasons and solution. Customer is not
accepting pumps during PG tests.

Request log this complaint till resolution.


Earlier also this was communicated to you but not yet resolved.

Regards-Ralkar- UTC Fire & Security,Mumbai

Dear Anand- This is complaint call logged.PL. take necessary actions.-Regards-Ralkar

SL NO of one of the pump:- W0097908 ,Model No:- SDD 200/200

From: Ralkar, Kamlakar BIS


Sent: Wednesday, May 07, 2014 5:07 PM
To: 'tec@beconweir.co.in'
Subject: Problem of excessive power consumption at Shut off conditions-Becon Pumps

Dear Mr. Santosh,

This is further to our tele- communication today.

• WE have procured from Best & Crompton Engg Ltd, Pumps Division –Main pump -Pump
Model SDD 200/200 ( motor Driven)-410 m3/Hr-105M head-1470 RPM-and SDC 200/200( engine
Driven) & Jocky pump-CNW 100/315 -75M3/Hr @105M vide PO no.20090077 & 20100160
• Scanned copies of approved TDS and actual reading of power consumption during PG
tests is also attached.
• NTPC MDCC was issued by NTPC ROI-Chennai
• PL. check the power consumption TDS data -62 KW at Shut off- but actual recorded
data is 117.14KW/97.5KW after the necessary corrections. This is extremely high and as
such NTPC is not accepting these pumps
• Request your support urgently on what is the correct data of shut off power for
this model and what was the data at the time of factory tests. If TDS data needs
correction, then accordingly new need to approach customer with your letter.
• I will ring you tomorrow.

Regards-Ralkar

UTC Fire & Security India Ltd.SL NO :- W0097908 ,Model No:- SDD 200/200

2
3 Revised as per attached vandor mail 2/6/2014 IS IS IS NL
2 Revised to incorporate the correct Wear ring MOC, 6/2/2009 AP AP ANK NB
1 Revised to incorporate the correct data received from 15/1/2009 AP AP ANK NB
0 Sub mision for approval 8/4/2008 SG SG SCV AP
REV. Description Date Prepared Checked Approved PM
REVISION
NTPC LTD.
FARAKKA SUPER THERMAL POWER PROJECT
STAGE-III (1 X 500MW)
FIRE DETECTION & PROTECTION SYSTEM
NTPC DOC. NO. 4140-151 -PVM-Y-01 A 2
REV. 3

KIDDE INDIA LIMITED O/C NO.


EL-205, TTC INDUSTRIAL AREA,
MAHAPE, NAVI MUMBAI - 400 710 200791204
INDIA
TITLE
TECHNICAL DATA SHEET FOR HYDRANT & JOCKEY Pump REV. 3
SHEET(S) 1
KIDDE DOC. NO. TDS-1A
PAGE 1 OF 13
MArk the revision no. at every changes
mentioned in the document.

KIDDE INDIA LIMITED


NTPC Doc. No.- 4140-151-PVM-Y-01A Date: 02/06/2014

Kidde Doc. No.- TDS - 01A Rev. 3


TECHNICAL DATA SHEET FOR HYDRANT & JOCKEY FIRE WATER
Title PUMPS O/C No 200791204

Client :NTPC Ltd.


Project: Farakka Super Thermal Power Stage-III (1 X 500MW) REV.
ItemNo. :1 2 3

Service : Main Hydrant Standby Hydrant Jockey Pump

1.0 Liquid Handled/Temp./Sp.Gr


: Clarified Water / 50 Deg. C / 1.0

2.0 Pump to be driven by : Electric Motor Diesel Engine

3.0 No.of Pumps : Two One Two


4.0 Manufacturer : Best & Crompton Engg. Ltd. 2

5.0 Model No. : SDD 200/200 CNW 100/315


6.0 Type of Pump
: Horizontal Split Casing Type End Suction Back Pull Out

7.0 Number of Stages : Two Stage Single Stage


3
8.0 Capacity M /Hr
8. At rated duty point : 410 Cu.M / hr 75 Cu M/hr
8. Min. capacity at which pump may run
continuosly : 40 Cu.M / hr 12 Cu M/hr

8. Max. capacity at which pump can operate : 1


continuosly 615 Cu.M / hr 90 Cu M/hr

9.0 Total dynamic head, MWC :

9. At rated capacity (indicated against 8.01 : 105


above)
9.2a At max. capacity (indicated against 8.03 : 75 1
above) 100

9.2b At 150% of rated capacity : 75


N.A

9.3Shuttoffhead,MWC : 121 114


10.0a Efficiency at rated duty point (- 2.5% tol.) : 60%
80%
10.0b At max. capacity (indicated against 8.03 : 61% 1
above) 75%

1 0.0c At 150% of rated capacity : 75% N.A. 1


11.0 NPSH required (Mtrs.)
11. At rated duty point (As per clause no. : 3.5 3. changed wrt ot
8.01 & 9.01 above) last revsiion,but no
revision no.
11. At max. capacity conditions (As per : 4.5 3 1 marked.
clause no. 8.03& 9.02a above)

11. At 150% of rated capacity : 4.5 N.A 1

Page 4 of 4
C:\Documents and Settings\sachin.churi\Desktop\TDS-01A HYDRANT JOCKEY PUMPS R2
KIDDE INDIA LIMITED

NTPC Doc. No.- 4140-151-PVM-Y-01A Date: 02/06/2014

Kidde Doc. No.- TDS - 01A Rev. 3

TECHNICAL DATA SHEET FOR HYDRANT & JOCKEY FIRE WATER


Title PUMPS O/C No 200791204

Client :NTPC Ltd.

Project: Farakka Super Thermal Power Stage-III (1 X 500MW) REV.


ItemNo. :1 2 3

Service : Main Hydrant Standby Hydrant Jockey Pump

12.0 Power consumed by pump in Kw at the following


conditions

: 146.56 36.
12. At rated duty point

12. At shut off condition(Appo)


92 24 3

: 167.49 40.
12. At run out condition 1
12. Max. power consumption throughout the entire : 167.49 40. 1
range of operation

: 167.49 N.A.
13. At 150% of rated capacity 1
: 1470 1500 2955 (Max)
13.0 Speed, RPM 1
14.0 Specific speed (in metric units) 25. 25. 13.

15.0 Material of Construction


changed
: Bronze IS 318 Gr LTB2
15. Impeller

15. Shaft : ASTMA276 Type SS 316


15. Shaft Sleeve : ASTM A 276 Type SS 410
15. Casing : CI, IS:210 GR. FG.260 (2.5%Ni)
16. Casing wearing rings : Bronze IS 318 Gr LTB5 2

16. Stuffing box packing : TIWA

15.7a Base Plate : M.S. (IS:2062) (Epoxy Coated)


15.7b Foundation Bolts : M.S.
15.7c Coupling Guard : Aluminium.
15.80 Pump Bearings : Steel
16.0 Pump Bearing
a) Type : Roller Bearing Roller Bearing 1
b)Nos. :1
c) Location : DE
17.0 Thrust Bearing
a) Type : Ball Bearing Ball Bearing 1
b)Nos. :1
c) Location : NDE
18.0 Shaft sealing arrangement : Gland Packing
19.0 Detailsofpumplubrication : Grease Oil 2
20.0 Coupling
20. Type : Flexible Pin Bush type Flexible (will be supplied by Lovejoy - Spacer type
Engine Manufacturer)

20. Manufacturer : BIPL Graves Lovejoy


20. Coupling Guard Provided : Yes
21.0 Air release valve on pump discharge casing : Yes Page Yes
4 of 4
C:\Documents and Settings\sachin.churi\Desktop\TDS-01A HYDRANT JOCKEY PUMPS R2
provided?

22.0 Base plates, lifting lugs & eye bolts, foundation :


anchor bolts supplied? Yes
clause no. 23.o is missing

KIDDE INDIA LIMITED

NTPC Doc. No.- 4140-151-PVM-Y-01A Date: 02/06/2014

Kidde Doc. No.- TDS - 01A Rev. 3

TECHNICAL DATA SHEET FOR HYDRANT & JOCKEY FIRE WATER


Title PUMPS O/C No 200791204

Client :NTPC Ltd.

Project: Farakka Super Thermal Power Stage-III (1 X 500MW) REV.


ItemNo. :1 2 3

Service : Main Hydrant Standby Hydrant Jockey Pump

24.0 Weight (Approx. in Kg)

24. Weightof pump : 950 160

24. Weight of primer mover : 1500 1200 379 1


24. Weight of heaviest piece to be handled

a) During Erection : 1500 1200 379 1


b) During Maitenance : 1500 1200 379 1
25.0 Size of pump suction/delivery (mm) : 200 /200 100 /80

26.0a Flange Drilling Standard : BS4504 Table 25/11 ANSI B16.5 CL1 50 FF 1
26.0b Direction of rotation viewed
from prime mover's position : Clockwise

27.0 Impeller Dia. (mm) Approx.

a)Rated : 410 410 278

b)Minimum : 340 340 243

c)Maximum 440 440 314


28.0 Noise level (Peak to Peak) throughout the operating : 85 dBA 85 dBA (Only for Pumps) 85 dBA
range

29.0 Vibration level (Peak to Peak) throughout the : As per HIS As per HIS As per HIS
operating range

30.0 Acceptance : TAC Accepted N.A.


31.0 Inspection & Testing : As perApproved QAP/HIS
32.0 Manufacturer's GA Drawing : GA-UG-E086141 GA-UG-E086151 GA-CW-E086471 2
33.0 Manufacturer's Cross Section : CS-UG-E086140 CS-UG-E0861 50 CS-CW-E086470 2
34.0 Drwing : PC-UG-E086141 PC-UG-E086151 PC-CW-E086471 2
Manufacturer's Performance Curve
Drawing
35.0 Static Load (Kgs.) : 2795 2440 697 1

36.0 Dynamic Load (Kgs.) : 3494 3050 871 1

37.0 Prime Mover Rating : 200KW 253BHP 45KW 1

38.0 Painting : As per Technical Specification 1

39.0 Accessories provided with Pump. : Base Plate,coupling,Coupling Guard &Foundation Bolts.

Page 4 of 4
C:\Documents and Settings\sachin.churi\Desktop\TDS-01A HYDRANT JOCKEY PUMPS R2
not inline with shutoff power
requirement as mentioned in
Technical datasheet