Documente Academic
Documente Profesional
Documente Cultură
SUBMITTED BY,
BACHELOR OF TECHNOLOGY IN
POWER ENGINEERING UNDER M.A.K.A.U.T, W.B
ACKNOWLEDGEMENTS
In this era of extreme global development, we need a great balance between
the theoretical and practical knowledge. For this reason, the vocational
training is a great boon for the to-be engineers. It gives us a great chance to
come in line with the actual problems going on the industries and getting a
chance to work with engineers and learn how to tackle every situation.
First and foremost, I would like to express my sincere gratitude towards Mr.
P.K. Dubey for his guidance.
3. HISTORY OF ORGANISATION
A. TECHNICAL SPECIFICATIONS OF MTPS
4. COOLING TOWER
4.1 COMPONENTS
4.2 MATERIALS
4.4 PERFORMANCE
4.5 ASSESSMENT
5.2 SCALING
A. TYPES OF SCALING,
B. DEPOSIT CONTROL METHODS
I. OXIDIZING TOXICANTS,
II. NON OXIDIZING BIOCIDES
6. PERFORMANCE IMPROVEMENT
6.1 WATER USE
A. REDUCE WATER LOSE,
B. REDUCE BLOW DOWN,
C. USE ALTERNATIVE WATER SUPPLIES,
D. REUSE BLOW DOWN
7. RECOMMENDATION
8. CONCLUSION
9. REFERENCES
1. INTRODUCTION
India is the world’s fifth largest electricity generator with a total installed
capacity of 2,28,722 MW. Out of this, 90,062 MW is from state owned utilities,
72,927 MW is from privately owned utilities and 65,733 MW is from central
owned utilities. (as on Dec. 23 2013)
Most power plants in the word burn fossil fuels such as coal, oil, and natural
gas to generate electricity. Others use nuclear power, but there is an increasing
use of cleaner Renewable sources such as wind, solar, wave and hydroelectric.
1. Hydroelectric power
2. Solar energy
3. Wind energy
4. Marine energy
TYPES OF NON-RENEWABLE ENERGY SOURCES:
Installed capacity:-
Total number of Units: 4 X 210 MW (unit 1 to 4) with brush type
generators, 2X 250 MW (unit 5 to 6) with brushless type generators, and
2 X 500 MW (unit 7 to 8) generators.
Total Energy Generation: 2340 MW.
Source of water: Damodar river.
Sources of coal: B.C.C.L and E.C.L, also imported from Indonesia.
STATION
4. Cooling Tower
Cooling towers are a very important part of many chemical plants. The primary
task of a cooling tower is to reject heat into the atmosphere. They represent a
relatively inexpensive and dependable means of removing low-grade heat
from cooling water. The make-up water source is used to replenish water lost
to evaporation. Hot water from heat exchangers is sent to the cooling tower.
The water exits the cooling tower and is sent back to the exchangers or to
other units for further cooling. Cooling towers are able to lower the water
temperatures more than devices that use only air to reject heat, like the
radiator in a car, and are therefore more cost-effective and energy efficient.
4.1 Components
The basic components of a cooling tower include the frame and casing, fill,
cold-water basin, drift eliminators, air inlet, louvers, nozzles and fans. These
are described below.
a) Frame and casing: Most towers have structural frames that support the
exterior enclosures (casings), motors, fans, and other components. With some
smaller designs, such as some glass fibre units, the casing may essentially be
the frame.
b) Fill: Most towers employ fills (made of plastic or wood) to facilitate heat
transfer by maximizing water and air contact. There are two types of fill:
Splash fill: Waterfalls over successive layers of horizontal splash bars,
continuously breaking into smaller droplets, while also wetting the fill
surface. Plastic splash fills promote better heat transfer than wood
splash fills.
Film fill: consists of thin, closely spaced plastic surfaces over which the
water spreads, forming a thin film in contact with the air. These surfaces
may be flat, corrugated, honeycombed, or other patterns. The film type
of fill is the more efficient and provides same heat transfer in a smaller
volume than the splash fill.
d) Drift eliminators: These capture water droplets entrapped in the air stream
that otherwise would be lost to the atmosphere.
e) Air inlet: This is the point of entry for the air entering a tower. The inlet may
take up an entire side of a tower (cross-flow design) or be located low on the
side or the bottom of the tower (counter-flow design).
f) Louvers: Generally, cross-flow towers have inlet louvers. The purpose of
louvers is to equalize air flow into the fill and retain the water within the
tower. Many counter flow tower designs do not require louvers.
g) Nozzles: These spray water to wet the fill. Uniform water distribution at the
top of the fill is essential to achieve proper wetting of the entire fill surface.
Nozzles can either be fixed and spray in a round or square patterns, or they can
be part of a rotating assembly as found in some circular cross-section towers.
h) Fans: Both axial (propeller type) and centrifugal fans are used in towers.
Generally, propeller fans are used in induced draft towers and both propeller
and centrifugal fans are found in forced draft towers. Depending upon their
size, the type of propeller fans used is either fixed or variable pitch. A fan with
non-automatic adjustable pitch blades can be used over a wide kW range
because the fan can be adjusted to deliver the desired air flow at the lowest
power consumption. Automatic variable pitch blades can vary air flow in
response to changing load conditions.
4.2 Materials:
Originally, cooling towers were constructed primarily with wood, including the
frame, casing, louvers, fill and cold-water basin. Sometimes the cold-water
basin was made of concrete. Today, manufacturers use a variety of materials
to construct cooling towers.
a) Frame and casing: Wooden towers are still available, but many components
are made of different materials, such as the casing around the wooden
framework of glass fibre, the inlet air louvers of glass fibre, the fill of plastic
and the cold-water basin of steel. Many towers (casings and basins) are
constructed of galvanized steel or, where a corrosive atmosphere is a problem,
the tower and/or the basis are made of stainless steel. Larger towers
sometimes are made of concrete. Glass fibre is also widely used for cooling
tower casings and basins, because they extend the life of the cooling tower
and provide protection against harmful chemicals.
b) Fill: Plastics are widely used for fill, including PVC, polypropylene, and other
polymers. When water conditions require the use of splash fill, treated wood
splash fill is still used in wooden towers, but plastic splash fill is also widely
used. Because of greater heat transfer efficiency, film fill is chosen for
applications where the circulating water is generally free of debris that could
block the fill passageways .
c) Nozzles: Plastics are also widely used for nozzles. Many nozzles are made of
PVC, ABS, polypropylene, and glass-filled nylon.
d) Fans: Aluminium, glass fibre and hot-dipped galvanized steel are commonly
used fan materials. Centrifugal fans are often fabricated from galvanized steel.
Propeller fans are made from galvanized steel, aluminium, or moulded glass
fibre reinforced plastic.
The natural draft or hyperbolic cooling tower makes use of the difference in
temperature between the ambient air and the hotter air inside the tower. As
hot air moves upwards through the tower (because hot air rises), fresh cool air
is drawn into the tower through an air inlet at the bottom. Due to the layout of
the tower, no fan is required and there is almost no circulation of hot air that
could affect the performance. Concrete is used for the tower shell with a
height of up to 200 m. These cooling towers are mostly only for large heat
duties because large concrete structures are expensive. There are two main
types of natural draft towers:
Cross flow tower: air is drawn across the falling water and the fill is
located outside the tower.
Counter flow tower: air is drawn up through the falling water and the
fill is therefore located inside the tower, although design depends on
specific site conditions.
D. Hybrid Towers:
Hybrid towers are closed towers which can operate either in the sensible heat
transfer mode only (without evaporation) or a combination of sensible and
latent heat transfer (with evaporation). During periods of low load and/or low
ambient temperature, the spray of water is stopped and heat is sensibly
transferred to the flow of air across the fins of the coils containing the cooling
fluid. During periods when this is not enough, a latent heat transfer system is
activated by switching on an evaporative cooler or water is sprayed across the
dry coils to allow for increased heat transfer through evaporation. These
processes offer substantial savings in water.
Forced draft:
Air is blown through the Suited for high air Recirculation due to
tower by a fan located in the resistance due to high air-entry and
air inlet. centrifugal blower low air-exit
fans velocities, which can
Fans are relatively be solved by locating
quiet. towers in plant
rooms combined
with discharge ducts.
These measured parameters and then used to determine the cooling tower
performance in several ways.
a) Range: This is the difference between the cooling tower water inlet and
outlet temperature. A high CT Range means that the cooling tower has been
able to reduce the water temperature effectively, and is thus performing well.
The formula is:
Equation 1: CT Range:
b) Approach: This is the difference between the cooling tower outlet coldwater
temperature and ambient wet bulb temperature. The lower the approach the
better the cooling tower performance; although, both range and approach
should be monitored, the `Approach’ is a better indicator of cooling tower
performance.
Equation 2: CT Approach:
c) Effectiveness.: This is the ratio between the range and the ideal range (in
percentage), i.e. difference between cooling water inlet temperature and
ambient wet bulb temperature, or in other words it is = Range / (Range +
Approach). The higher this ratio, the higher the cooling tower effectiveness.
Equation 3: CT Effectiveness:
d) Cooling capacity. This is the heat rejected in kCal/hr or TR, given as product
of mass flow rate of water, specific heat and temperature difference.
e) Evaporation loss. This is the water quantity evaporated for cooling duty.
Theoretically the evaporation quantity works out to 1.8 m3 for every 1,000,000
kCal heat rejected. The following formula can be used.
h) Liquid/Gas (L/G) ratio: The L/G ratio of a cooling tower is the ratio between
the water and the air mass flow rates. Cooling towers have certain design
values, but seasonal variations require adjustment and tuning of water and air
flow rates to get the best cooling tower effectiveness. Adjustments can be
made by water box loading changes or blade angle adjustments.
Thermodynamic rules also dictate that the heat removed from the water must
be equal to the heat absorbed by the surrounding air. Therefore the following
formulae can be used:
𝐿 (𝑻𝟏−𝑻 𝟐) = 𝑮 (𝒉𝟐−𝒉𝟏)
𝑳/𝑮=(𝒉𝟐−𝒉𝟏)/(𝑻𝟏−𝑻 𝟐)
Where: L/G = liquid to gas mass flow ratio (kg/kg);
T1 = hot water temperature (°C);
T2 = cold-water temperature (°C);
h2 = enthalpy of air-water vapour mixture at exhaust wet-bulb temperature;
h1 = enthalpy of air-water vapour mixture at inlet wet-bulb temperature.
4.5 Assessment
A. Design:
Capacity :
Heat dissipation (in kCal/hour) and circulated flow rate (m3/hr) are not
sufficient to understand cooling tower performance. Other factors, which we
will see, must be stated along with flow rate m3/hr. For example, a cooling
tower sized to cool 4540 m3/hr through a 13.9°C range might be larger than a
cooling tower to cool 4540 m3/hr through 19.5°C range.
Range :
Range is determined not by the cooling tower, but by the process it is
serving. The range at the exchanger is determined entirely by the heat load
and the water circulation rate through the exchanger and on to the cooling
water.
Equation 7: CT Range:
Thus, Range is a function of the heat load and the flow circulated through the
system.
Cooling towers are usually specified to cool a certain flow rate from one
temperature to another temperature at a certain wet bulb temperature. For
example, the cooling tower might be specified to cool 48000 m3/hr from 44°C
to 34°C at 26.7°C wet bulb temperature.
As a generalization, the closer the approach to the wet bulb, the more
expensive the cooling tower due to increased size. Usually a 2.8°C approach to
the design wet bulb is the coldest water temperature that cooling tower
manufacturers will guarantee. If flow rate, range, approach and wet bulb had
to be ranked in the order of their importance in sizing a tower, approach would
be first with flow rate closely following the range and wet bulb would be of
lesser importance.
The range increases when the quantity of circulated water and heat
load increase. This means that increasing the range as a result of added
heat load requires a larger tower. There are two possible causes for the
increased range:
The inlet water temperature is increased (and the cold-water
temperature at the exit remains the same). In this case it is economical
to invest in removing the additional heat.
The exit water temperature is decreased (and the hot water
temperature at the inlet remains the same). In this case the tower size
would have to be increased considerably because the approach is also
reduced, and this is not always economical.
Heat Load :
The heat load imposed on a cooling tower is determined by the process
being served. The degree of cooling required is controlled by the desired
operating temperature level of the process. In most cases, a low operating
temperature is desirable to increase process efficiency or to improve the
quality or quantity of the product. In some applications (e.g. internal
combustion engines), however, high operating temperatures are desirable. The
size and cost of the cooling tower is proportional to the heat load. If heat load
calculations are low undersized equipment will be purchased. If the calculated
load is high, oversize and more costly, equipment will result.
Process heat loads may vary considerably depending upon the process
involved. Determination of accurate process heat loads can become very
complex but proper consideration can produce satisfactory results. On the
other hand, air conditioning and refrigeration heat loads can be determined
with greater accuracy.
Initial selection of towers with respect to design wet bulb temperature must be
made on the basis of conditions existing at the tower site. The temperature
selected is generally close to the average maximum wet bulb for the summer
months. An important aspect of wet bulb selection is whether it is specified as
ambient or inlet. The ambient wet bulb is the temperature, which exists
generally in the cooling tower area, whereas inlet wet bulb is the wet bulb
temperature of the air entering the tower. The later can be, and often is,
affected by discharge vapours being re-circulated into the tower. Recirculation
raises the effective wet bulb temperature of the air entering the tower with
corresponding increase in the cold water temperature. Since there is no initial
knowledge or control over the recirculation factor, the ambient wet bulb
should be specified. The cooling tower supplier is required to furnish a tower
of sufficient capability to absorb the effects of the increased wet bulb
temperature peculiar to his own equipment.
Tower Size:
b) Tower size varies inversely with wet bulb temperature. When heat load,
range, and approach values are fixed, reducing the design wet-bulb
temperature increases the size of the tower. This is because most of the heat
transfer in a cooling tower occurs by virtue of evaporation (which extracts
approximately 1000 Btu’s for every pound of water evaporated), and air’s
ability to absorb moisture reduces with temperature.
d) Tower size varies inversely with range. Two primary factors account for this.
First; increasing the range—also increases the ITD (driving force) between the
incoming hot water temperature and the entering wet-bulb temperature.
Second, increasing the range (at a constant heat load) requires that the water
flow rate be decreased—which reduces the static pressure opposing the flow
of air.
Electricity is used for pumping above the fill and for fans that create the
air draft. An efficiently designed fill media with appropriate water
distribution, drift eliminator, fan, gearbox and motor with therefore lead
to lower electricity consumption.
Heat exchange between air and water is influenced by surface area of
heat exchange, duration of heat exchange (interaction) and turbulence
in water effecting thoroughness of intermixing. The fill media
determines all of these and therefore influences the heat exchange. The
greater the heat exchange, the more effective the cooling tower
becomes.
C. Water Distribution:
Fans :
The fan efficiency in turn is greatly dependent on the profile of the blade.
Blades include:
5.1 Corrosion
Corrosion is an electrochemical or chemical process that leads to the
destruction of the system metallurgy. Figure illustrates the nature of a
corrosion cell that may be encountered throughout the cooling system
metallurgy. Metal is lost at the anode and deposited at the cathode. The
process is enhanced by elevated dissolved mineral content in the water and
the presence of oxygen, both of which are typical of most cooling tower
systems.
A. Corrosion Control:
Cathodic Polarization :
Anodic Polarization :
Passivation:
B. Corrosion Inhibitors :
Anodic inhibitors build a thin protective film along the anode increasing the
potential at the anode and slowing the corrosion reaction, the film is initiated
at the anode although it may eventually cover the entire metal surface.
Because this film is not visible to the naked eye so the appearance of the metal
will be left unchanged.
Cathodic inhibitors are generally less effective than the anodic type. But they
often form a visible film along the cathode surface, which polarizes the metal
by restricting the access of dissolved oxygen to the metal substrate. The film
also acts to block hydrogen evolution sites and prevent the resultant
depolarizing effect.
Examples include:
Chromates
Orthophosphates
Zinc
Polyphosphates
Synergic Blends like:
o zinc-chromates
o chromate-polyphosphates
o chromate-orthophosphate
C. Inhibitor Selection:
Design parameters
Water composition
Metals in the system
Stress conditions
Treatment level required
pH
Dissolved oxygen content
Salts and SS composition
5.2 Scaling
Scaling is the precipitation of dissolved minerals components that have
become saturated in solution. Factors that contribute to scaling tendencies
include water quality, pH, and temperature. Scale formation reduces the
heat exchange ability of the system because of the insulating properties of
scale, making the entire system work harder to meet the cooling demand.
Deposits typically consist of mineral scales (i.e.CaCO3. CaSO4, Ca3(PO4)2,
CaF2, etc), corrosion products (i.e. Fe2O3, Fe3O4, CuO etc), particular matter
(i.e. clay, slit), and microbiological mass.
A. Types of Scaling:
Waterborne salts:
Precipitated salts of calcium and magnesium often form dense scales and
sludge’s which are usually quite adherent and therefore difficult to remove. In
addition they are effective heat insulators, which reduce process efficiency.
Calcium carbonate, calcium sulphate, calcium and magnesium silicates and
calcium phosphate are some of the more prevalent compounds found in
cooling water systems.
Waterborne foulants:
Airborne foulants :
The air in contact with open cooling water systems contains many of the
same suspended materials found in the makeup water. Sand, slit, clay, dirt,
bacteria etc. entering with the air add to the overall fouling of the system.
Airborne contamination by gases also helps in deposition. Oxygen and carbon
dioxide accelerate corrosion, leading to deposition and further corrosion by
the under-deposit mechanism. Since pick up of both gases occur continuously,
near saturation levels of these dissolved gasses are present in the water.
Gaseous contaminants such as sulphur dioxide, hydrogen sulphide and
ammonia may also be absorbed from the air. The first two reduce oxidizing
corrosion inhibitors (e.g. chromates) to insoluble foulants. Hydrogen sulphide
is very corrosive and quickly forms iron sulphide deposits, which lead to further
corrosion. Ammonia selectively corrodes copper and its alloys leading to the
deposition of copper corrosion products.
Conventional treatments:
Scale Inhibitors:
Dispersants:
“The principal role of a dispersant is to reduce the tendency for small particles
to agglomerate”.
Flocculants:
Deposit Problems:
Chlorination:
The most commonly used oxidizing micro biocide is Chlorine. It is the most
effective of all halogens. Chlorine is an excellent algaecide and sporicide. It is
also an excellent bactericide in most circumstances. Free residual chlorine at
levels of 0.5 ppm and slightly above are usually enough to control most
microbial growth. A number of factors determine the amount of chlorine
required in an open cooling water system. These include chlorine demand,
contact time, pH, and temperature of the water.
The PH of the cooling water is directly responsible for the extent of ionization
of hypochlorous acid. The acid state is favoured by low pH .At pH 7.5 there will
be approximately equal amounts of acid and hypochlorite ion. Chlorine
becomes ineffective as a micro biocide at pH 9.5 or greater as a result of total
ionization. A, pH range of 6.5~7 is considered practical for chlorine based
microbial control programme.
Bromination:
6. Performance Improvement
Reducing water losses reduces the quantity of make-up water required for
the system. Potential opportunities to reduce water loss include:
• Fixing leaks
• Reducing splash
• Optimising overflow
• Eliminating drift – drift losses should be maintained at less than 0.002% of
cooling water circulation rate. Repair or install new systems to achieve best
practice.
Increasing the number of C.O.C. will reduce the volume of blow down
and consequently the volume of make-up water required by the tower. The
maximum C.O.C. for a tower will depend on the quality of the make-up water
and the corrosion resistance of the tower’s basin and condenser. C.O.C. over 5
is considered to be efficient but this is not always achievable. Scale forming
ions such as calcium and magnesium can often be precipitated out (by water
softeners) or kept in solution (by acids) through effective water treatment
enabling the tower to operate at higher cycles of concentration. According to
the Queensland Water Commission, a cooling tower is considered inefficient if:
• The system is operating at less than 5 COC or 1850 mg/L TDS/2750 μs/cm
conductivity (allowed only in documented instances of high-TDS make-up
water); and/or
• System losses are greater than 8% of the make-up water.
Sulphuric acid can be used in cooling tower water to help control scale
build-up. When properly applied, sulphuric acid will lower the water’s pH and
help convert the calcium bicarbonate scale to a more soluble calcium sulphate
form. In central North Carolina, most plants will be able to operate six to 10
cycles of concentration without acid feed. Along our coasts, acid can be used
to increase cycles as water tends to be harder and higher in alkalinity. The
same can be said if hard alkaline well water is used as tower make-up.
Important precautions need to be taken when using sulphuric acid treatment.
Because sulphuric acid is an aggressive acid that will corrode metal, it must be
carefully dosed into the system and must be used in conjunction with an
appropriate corrosion inhibitor. Workers handling sulphuric acid must exercise
caution to prevent contact with eyes or skin. All personnel should receive
training on proper handling, management and accident response for sulphuric
acid used at the facility.
In cooling towers that use make-up water with high suspended solids, or in
cases where airborne contaminants such as dust can enter cooling tower
water, side stream filtration can be used to reduce solids build up in the
system. Typically, five to 20 per-cent of the circulating flow can be filtered
using a rapid sand filter or a cartridge filter system.
Rapid sand filters can remove solids as small as 15 microns in diameter while
cartridges are effective to remove solids to 10 microns or less. High efficiency
filters can remove particles down to 0.5 microns. Neither of these filters are
effective at removing dissolved solids, but can remove mobile mineral scale
precipitants and other solid contaminants in the water. The advantages of side
stream filtration systems are reduced particle loading on the tower. This
ensures heat transfer efficiency and may reduce biocide or dispersant
demands.
C. Ozone:
D. Magnets:
E. Sonication:
G. Activated carbon:
J. Radio frequencies:
The training at MTPS was altogether an exotic experience, since work, culture
and mutual cooperation was excellent here. Moreover, fruitful result of
adherence to quality control awareness of safety and employees were fare
which is much evident here.
THE END