SF & HF
200V class 0.2–7.5kW
400V class 0.4–7.5kW
Cat . No.
POWER TRANSMISSION & CONTROLS GROUP
D1001E-1
Features
High-function" to "High Functionality and easy operation The method of operation remains unchanged!
• Front cover protects programming keys to comply • The two models share external dimensions, basic
with PL Law. functions, and basic operation so you can focus
• External signals permit use for various applications. your selection based on load characteristics.
• Easily switch operation between panel and external • The HF Series eliminate complicated setup for
signal. achieving starting torque.
RUN
Compact size
yet complete
Program the terminals for the functions required by functionality.
Fine adjustment meets the need in the age of Flexible Manufacturing System (FMS).
A75 F01
A75
P
Operation A72
command I
Use PID function to simplify + - A73 +
+
+
Frequency setting
process control. D
A74
Analog
Feedback input setting A75 Monitor
A11–A14 d04
1
Global applications
Features
The overseas specification series are also available.
Type
None: standard specifications
W: CE, UL, Standard specifications
(Single phase series is only available for W type.)
A: Southeast asian Specifications
(Carrier Frequency Default Setting is
lower.)
Series name
S: SF-320 Series Applicable motor capacity
Voltage class
H: HF-320 Series A20: 0.2kW 2A2: 2.2kW
2: 200V class A40: 0.4kW 3A7: 3.7kW
4: 400V class A75: 0.75kW 5A5: 5.5kW
1A5: 1.5kW 7A5: 7.5kW
SF-320
● Apply V/f control method in multi-motor application* and in PID function for industrial
pumps and fans.
✽Operation of more than one motor with one inverter
HF-320
● The sensorless vector control method provides 200% starting torque ! Furthermore, the
maximum torque during operation exceeds 150%.
● The auto tuning function permits high-performance operation.
● This inverter is suitable for machines that need high torque during start-up, slow-speed
operation or regular operation. It is ideal for applications such as extruders, high-viscosity
pumps, cart drivers, elevators, and special agitators, as well as for applications that need
regenerative braking.
High starting torque of 200% or more High starting at wide speed range of 1 : 60
Torque Torque
(kgf m)
●
(kgf m)
●
200% 1Hz
Torque 3Hz
6Hz
150%
Torque
100%
Torque
2
Common
List of Functions
Monitor Mode/Basic Setting Mode
List of Functions
A20
3: 15Hz
Multispeed frequency setting Setting range: 0.0–360Hz 4: 20Hz
● ● |
(speed 0–speed 15) Arbitrary setting is possible 5: 30Hz
6: 40Hz
A35 7: 50Hz
8: 60Hz
Other: 0Hz
● ● A38 Jogging frequency setting 0.00–9.99Hz 1.0Hz
00: Free run stop
● ● A39 Jogging stop operation selection 01: Decelerate stop 00
02: DC braking
00: Manual
characteristics
3
Common
List of Functions
HF SF Code Function Monitor/setting Range Initial setting
00: Invalid
● ●
DC Braking
Easily operate the SF-320 and HF-320 series with the standard equipped digital operator panel.
Method of operation
1. Setting (Setting the maximum frequency)
or the previously monitored value is displayed. Function code appears appears appears
Turn
on
the
power Press the key Display Using the Press the key
up and down keys
appears The previous set value is displayed. The set value is updated. The setting is complete ( appears)
Display Press the key Change the set value using the Press the key
Using the up and down keys to enter the value.
up and down keys Return to the monitor mode or basic
setting mode before operation.
Turn
on
the
power
Press the key and Press the key
to stop the monitor.
rotate the potentiometer. Operating frequency monitor
Turn
on
the
power Display using the
Press the key Press the key
up and down keys.
5
Common
Explanation of Functions
Explanation of Functions
Monitor Setting the acceleration/deceleration time
Output frequency monitor Acceleration time 1 setting
Output current monitor Acceleration time 1 setting
Operation direction monitor · is the acceleration time from 0Hz to
PID feedback value monitor (maximum frequency). is the deceleration time
Input terminal status monitor from (maximum frequency) to 0Hz.
Output terminal status monitor Frequency
Output frequency equivalent monitor
Trip monitor
Trip history monitor
Time
• The output frequency and current value can also be monitored. Acceleration time Deceleration time
F02 F03
• displays the contents of the latest error. In addition Base frequency setting
to the error code, the output frequency, output current, and Maximum frequency setting
DC voltage between P and N at time of trip can be viewed. • The base frequency and maximum frequency can be set
• shows the error codes of the last two trips prior to within the 50-360 Hz range (1 Hz).
the latest one.(Refer to p.13)
V
Setting the output frequency
Output frequency setting 100%
Output voltage
6
Common
Explanation of Functions
Explanation of Functions
5
speed A25 OFF ON OFF ON Multispeed 0 can only be
6
speed A26 OFF ON ON OFF activated when A01 is
7
A27 OFF ON ON ON programmed to 02.
A12 speed
8 ∗ Additionally, A20 through A35
speed A28 ON OFF OFF OFF
can be programmed using F01
9
speed A29 ON OFF OFF ON when each corresponding
10
speed A30 ON OFF ON OFF speed is activated.
11
speed A31 ON OFF ON ON ∗ Setting during operation is
A11
12
speed A32 ON ON OFF OFF possible.
13
Analog speed A33 ON ON OFF ON
14
input speed A34 ON ON ON OFF
15
A13 A14 speed A35 ON ON ON ON
0 10V
4 20mA Jogging operation setting
: The scaling start frequency is set. Jogging frequency setting
: The scaling end frequency is set. Jogging stop mode selection
: The analog input level for the scaling start • Use motor jogging operation for simple positioning. Assign
jogging to any of the input terminals FR through RST.
frequency is set.
• The operation after jogging can
: The analog input level for the scaling end frequency be selected from among "Free- FR COM
is set. run stop," "Deceleration stop,"
• sets the frequency output start method. and "DC braking stop." FR SWJ
[Operation timing]
Output frequency
Output frequency
SWJ
A12 A12
FR
Selection from among
"Free-run stop,"
"Deceleration stop,"
Motor rotation and "DC braking stop"
A11 A11
Analog Analog
input input
Set value 1 8
A42
Response Quick Slow (Codes 0-99)
(Set the range within Base frequency
Stability (Filter effect) Small Large 0-50% of the base A43 (100%)
frequency)
7
Common
Explanation of Functions
Explanation of Functions
V/F characteristic setting Jump frequency setting
V/F characteristics setting , , Jump frequency setting
Output voltage gain setting , , Jump frequency width setting
• permits selection of constant torque or reduced * Used to avoid resonance frequencies on the applied
torque of the V/F characteristic by means of a load. HF-320
machinery. Deceleration
permits selection of sensorless control as well. Output frequency
Jump width
• The output voltage at the base frequency can be set within A maximum of three
Jump frequency 1
50-100% of the range by . jump frequencies Jump frequency 2
Use this to operate a motor with rated voltage lower than the can be set. Acceleration
Jump frequency 3
inverter supply voltage under optimum condition.
Frequency command
PID function
Output voltage
Output voltage
100% 100%
A45 A45
PID control selection
P gain setting
I gain setting
Base frequency Base frequency
D gain setting
·Constant torque characteristic ·Reduced torque characteristic
PID scale setting
Feedback input method setting
DC braking
Use PID operation to control processes with a feedback
DC braking function selection signal. PID control the motor speed to drive the error
DC braking frequency setting between the target value and feedback value to zero.
It is effective for controlling processes such as temperature,
DC braking output wait time setting
pressure, flow rate, and air capacity.
DC braking force setting
DC braking time setting 〈P: Proportional control〉
• Use DC braking during deceleration and stopping for In this control, the operation quantity is proportional to
position and to adjust stopping accuracy. the deviation of the target value and feedback value.
• When the DC braking output wait time is set, the operation
P gain setting KP KP Large Small
during that time will be in the free-run state.
Response Quick Slow
(Note 1) Disable DC braking for applications with frequent starts and • The response of the
stops. operation quantity with Stability Unstable Stable
(Note 2) Excessively strong braking force may cause tripping. respect to deviation is adjusted.
DC braking output small when the deviation is small; therefore correction may
Output
Braking
force A54
Time I gain setting KI KI Small Large
• Integral time is set. Response Quick Slow
When the integral time Stability Unstable Stable
Upper/lower limiter is short (I/K I ), the
response is quick.
Frequency upper limiter setting
Frequency lower limiter setting 〈D: Differential operation〉
Differential operation uses the rate of change of the deviation
• The upper and lower limits of the output frequency can be
to adjust the operation quantity. It is used for correction of P
controlled.
(proportional) and I (integral) control.
Output frequency
D gain setting KD KD Large Small
Response Quick Slow
Upper limiter Stability Unstable Stable
8
Common
Explanation of Functions
Explanation of Functions
Output frequency
corrected and maintained at a constant value according S-curve S-curve
acceleration deceleration
to the motor voltage. (However, output voltage
exceeding the input voltage of the inverter is not Linear Linear
possible.) acceleration deceleration
• The AVR function can be turned OFF during Time
deceleration.
Setting the restart (mode)
2nd deceleration function
Restart mode
2nd Acceleration time setting Allowable undervoltage time setting
2nd Deceleration time setting Retry waiting time setting
2nd accel/decel change method • Retry or restart is possible after undervoltage,
Acceleration time crosseover frequency overcurrent, and overvoltage protection functions. (If
Deceleration time crossover frequency the fault conditions still persists after the decided
retrials, the drive will stop.)
• The acceleration and deceleration time can be changed 〈Set value of 〉
during operation. Use the 2nd acceleration and 2nd
deceleration times when load inertia changes during Set value Function
operation. 00 Alarm output after tripped
• Change the acceleration and deceleration time with input
01 0 Hz restart
terminals or with the crossover frequency setting.
02 Frequency matching restart
〈Change by terminal〉 03 Deceleration stop after frequency matching restart
Example
frequency
*
Allowable undervoltage stop time b02 *Operation stops
Output
(Hz)
Free-run state
Motor
speed (rpm)
〈Change by crossover frequency〉
frequency
Electronic thermal
Output
(Hz)
9
Common
Explanation of Functions
Explanation of Functions
〈Electronic thermal level〉
Starting frequency adjustment
50 120
Starting frequency adjustment
Time (sec)
100
Output
80
60 Reduced torque characteristics 100%
Output voltage
Output frequency
5 20 60 120 (Hz)
(Note) Contact the technical staff at our factory when the electronic
thermal level is to be set below 50%.
f
b82 Starting frequency Output frequency
Overload restriction Adjustment range
0.5-9.9Hz
• When set data should not be changed, use this software Data/trip history initialization
lock function.
• The software lock function is enabled by code setting or by Initialization mode selection
a control terminal. Initialization data selection
Set value Function • Data on all the functions can be returned to the initial set
[When software lock terminal is ON] Change of any function values. In addition, the trip history can be cleared.
00* other than software lock is impossible.
[When software lock terminal is ON] Change of any function
01* other than software lock and frequency setting is impossible.
[Whether software lock terminal is ON or OFF] Change of
Setting the frequency conversion scale display func-
02 any function other than software lock is impossible. tion
[Whether software lock terminal is ON or OFF] Change of any function
03 other than software lock and frequency setting is impossible. Frequency conversion value setting
* When the control terminal is used • The monitor permits monitoring of the frequency after
scale conversion. The line speed and speed of rotation can
No-load reactive current setting be displayed.
Displayed value = Output frequency ×
Reactive current setting
• The no-load (reactive) current of the motor is set. (Example) When the line speed is 6 m/min at 60 Hz
Note: is only for SF-320. 0.1 is set to .
〈Display〉
Analog meter adjustment At 20 Hz: (2 m/min)
At 40 Hz: (4 m/min)
Analog meter adjustment
• The scale of an analog frequency counter and ammeter
connected to the inverter can be adjusted.
10
Common
Explanation of Functions
Explanation of Functions
Motor speed
Output frequency
Output frequency
〈FR〉 ON
11
Common
Explanation of Functions
Explanation of Functions
Input method Terminal assignment Terminal ON/OFF • Frequency match signal and frequency detect signal
These functions for the multifunction output terminals enable
Current (4-20 mA) ON
Assigned output signals either when output frequency matches
Voltage (0-10 V) OFF
command frequency or when output frequency exceeds
Current + Voltage Not assigned – detect frequencies. The detect frequencies are assigned with
(Note) When no terminal is assinged, the frequency equivalent to the
current command value plus voltage command value is output. and separately for acceleration and
• Reset deceleration.
This digital input removes the trip condition from the drive
Frequency
and cancels the fault signal.
Frequency
(Note) When this function is turned on during operation, the output is cut off.
12
Common
Protective Functions
Protective Functions
Remote
Digital panel/
Name Description operator
Digital operator ERR1****
Constant speed OC.Drive
When output of an inverter is short circuited, the motor is
Overcurrent locked or drive sees sudden heavy load, the inverter output Deceleration OC.Decel
protection current exceeds a certain level, and the inverter output is cut Acceleration OC.Accel
off.
Others Over.c
When a motor overload is detected by the electronic thermal function,
Overload protection (Note 1) the output of the inverter is cut off. Over.L
With USP function enabled through the intelligent terminal, a run command
USP error when power comes on causes this fault.
USP
At power up, the inverter looks for ground fault at the motor output terminals.
Ground fault protection This protection is provided for the inverter and not for operator safety.
GND.Fit
When the input voltage is higher than the specified value, inverter responds to this
Input overvoltage protection 100 seconds after power up by faulting and by cutting off the output. The detection OV.SRC
level is approximately 258V for 200V Class and 516V for 400V Class.
When thermal sensor in the inverter detects high temperature in the power
Thermal protection module, the inverter trips and shuts output off.
OH FIN
The drive shuts output and waits when input voltage drops below a specific
Undervoltage wait condition value.
UV.WAIT
(Note 1) Press the reset key 10 seconds after the alarm has occurred.
(Note 2) If an EEPROM error occurs, be sure to comfirm the seting value again.
Trip cause (Note 3) (Note 4) Trip frequency Trip current Trip P–N voltage
FUNC
FUNC FUNC
13
SF-320
Standard
Standard
200 V class 400 V class
Model SF3202- SF3202- SF3202- SF3202- SF3202- SF3202- SF3202- SF3202- SF3204- SF3204- SF3204- SF3204- SF3204- SF3204- SF3204
A20 A40 A75 1A5 2A2 3A7 5A5 7A5 A40 A75 1A5 2A2 3A7 5A5 7A5
Applicable motor (kW) (Note 1) 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 0.4 0.75 1.5 2.2 3.7 5.5 7.5
Rated capacity (kVA) 0.6 1.0 1.5 2.7 3.8 6.1 9.1 12.2 1.1 1.9 2.9 4.2 6.6 9.9 12.2
Output
Rated output current 1.6 2.6 4.0 7.1 10 15.9 24.0 32.0 1.5 2.5 3.8 5.5 8.6 13.0 16.0
Rated output voltage (Note 2) 3-phase 200–230 V (corresponding to input voltage) 3-phase 380–460 V (corresponding to input voltage)
Overload current rating 150%, 60 seconds
Power
Frequency monitor Analog output frequency monitor, analog output current monitor or digital output frequency monitor.
Alarm output contact ON for the inverter alarm (IC contact output) (Possible to change to OFF for the alarm)
AVR function, upper/lower limiter, PID control, carrier frequency, jump frequency, electronic
Other functions thermal level, gain/bias adjustment, retry function, automatic torque boost, trip monitoring
etc.
Overcurrent, overvoltage, undervoltage, overload, high temperature, CPU error, EEPROM
Protective function
error, ground fault detection at startup, internal communication error etc.
Location Indoor (Corrosion, toxicity, inflammable gas, dust, or oil mist not allowed.)
Ambient temperature -10–50˚C (Note 6)
ervironment
Operating
14
SF-320
Terminal Functions
Terminal Functions
RR external trip, jogging, analog input selection, software lock, reset. Operation by SW Close. (Changeable to operation by SW Open.) (Note 2)
FR Minimum ON time: 12 ms or more
Alarm output Output signal Frequency command (Note 1)
AL2 Alarm output terminals (IC contact (relay) output) Contact rating
〈Initial setting〉 AC250V 2.5A (resistive load)
AL0 AL1 AL2 0.2A (cos =0.4)
AL1 When normal, power OFF: AL0-AL2 Close DC30V 3.0A (resistive load)
0.7A (cos =0.4)
When alarm: AL0-AL2 Open (Min.) AC100V 10mA
AL0 (Switchable to AL0-AL1 Close when normal.) DC 5V 100mA
(Note 1) The maximum frequency command is 9.8 V when the voltage input is 0-10 VDC, and 19.6 mA when the current input is 4-20 mA.
(Note 2) The reset terminal cannot be changed to [Operation with (SW) Open].
15
SF-320
Basic Connection Diagram
Inverter
(Note 1) Option SF-320
MCB MC ACL TH (Note 7)
R U
Power
3-phase 200–230V 50/60Hz S V IM
3-phase 380–460V 50/60Hz T W
DC24V PCS P1 DCL
(In case of supplying (DC reactor) (option)
external DC power) FR
L
P
RR
L
2DF
L AL1
AL2 Alarm output contact
3DF AL0
L
RST UPF
L RY1
+ FRQ
COM
DRV
RY2
+V DC10V DC24V
OM
Frequency setting device VRF
1k–2kΩ
IRF
Current input
COM
4–20mA
(Note 2)
Ground
(Note 1) Do not start and stop the motor with only the MC
swithch.
(Note 2) Be sure to ground the inverter chassis and motor.
(Note 3) The common of each terminals differ.
Terminal FR, RR, 2DF, 3DF, RST, FRQ +V, VRF, IRF UPF, DRV
[Turn on the main power at the timing shown below.]
Common COM COM OM
(Note 4) Refer to the figure at right for the power ON and Main circuit power
t>2.0 second (Note 4)
Run command ON timing. Even if the main circuit
power and operation command are turned ON Run command
simultaneously, the control power will not be turned
ON for 2.0 seconds and not permit operation.
(Note 5) When the contactor is to be opened and closed for Output frequency
each operation, be sure to insert an ACL on the primary
side of the contactor to reduce the inrush current. Motor rpm
(Note 6) When a DC reactor is used, remove the shorting
bar between terminals P and P1.
(Note 7) Provide external thermal overload protection for each
when operating frequency is below 30 Hz or when
multiple motors are used.
16
SF-320
Applied Connection Diagram
✽Refer to p.24 for circuits using PID.
Applied Connection Diagram
MCB TH (Note 1)
U X P P1
R U
Power V Y V IM Frequency setting by external signal
S
W Z W
T
Frequency Multi-stage Multi-stage Multi-stage Multi-stage
speed speed speed speed
setting 1 2 3 4
SF-320 A20 × × × ×
A21 × × ×
A22 × × ×
A23 × ×
Forward rotation FR Parameter setting
A02=01 A24 × × ×
Multi-stage speed 1 RR
Multi-stage speed 1 C02=02
A25 × ×
Multi-stage speed 2 2DF
Multi-stage speed 2 C03=03
Multi-stage speed 3 3DF A26 × ×
Multi-stage speed 3 C04=04
Multi-stage speed 4 RST A27 ×
Multi-stage speed 4 C05=05
COM A28 × × ×
A29 × ×
A30 × ×
A31 ×
A32 × ×
A33 ×
: Twisted wire
A34 ×
: Shielded wire
A35
(× . . . Open, . . . Closed)
Standard
200 V class 400 V class
Model HF3202- HF3202- HF3202- HF3202- HF3202- HF3202- HF3202- HF3202- HF3204- HF3204- HF3204- HF3204- HF3204- HF3204- HF3204
A20 A40 A75 1A5 2A2 3A7 5A5 7A5 A40 A75 1A5 2A2 3A7 5A5 7A5
Applicable motor (kW) (Note 1) 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 0.4 0.75 1.5 2.2 3.7 5.5 7.5
Rated capacity (kVA) 0.6 1.0 1.5 3.0 4.2 6.7 9.1 12.2 1.1 1.9 2.9 4.2 6.6 9.9 12.2
Output
Rated output current 1.6 3.0 5.0 8.0 11 17.5 24.0 32.0 1.5 2.5 3.8 5.5 8.6 13.0 16.0
Rated output voltage (Note 2) 3-phase 200–230 V (corresponding to input voltage) 3-phase 380–460 V (corresponding to input voltage)
Overload current rating 150%, 60 seconds
Power
Frequency monitor Analog output frequency monitor, analog output current monitor or digital output frequency monitor.
Alarm output contact ON for the inverter alarm (IC contact output) (Possible to change to OFF for the alarm)
AVR function, S-curve acceleration/deceleration, upper and lower limiters, 16-stage speed,
fine adjustment of start frequency, carrier frequency, jump frequency, gain and bias setting,
Other functions
jogging run, electronic thermal level adjustment, retry function, trip history monitor, 2nd
setting selection, auto tuning.
Overcurrent, overvoltage, undervoltage, overload, high temperature, CPU error, EEPROM
Protective function
error, ground fault detection at startup, internal communication error etc.
Location Indoor (Corrosion, toxicity, inflammable gas, dust, or oil mist not allowed.)
Ambient temperature -10–50˚C (Note 6)
ervironment
Operating
18
HF-320
Explosion-proof motor series with
protection type "frameproof (d2G4)".
Explosion-proof motor series
200V•400V class
NEW
Features
Specifications
Specifications
Motor
Protection type Constant Scope of
kW✕P frame Output base Starting
Insulation Characteristics Indoor Outdoor power manufacture
No. frequency torque
JP44 JPW44 range
0.2✕4 T-71S Totally-enclosed 1. Available
self-cooled • Direct coupling
0.4✕4 T-80M 1:20 with CYCLO
Constant Dedicated 200% –120Hz
0.75✕4 T-90L Class • Outdoor
torque to or • JEM flange
1.5✕4 T-100L B Totally-enclosed • Foot mounted
Continuous 60 Hz more
2.2✕4 fan-cooled 2. Unavailable
T-112M rating –110Hz
• With PG
3.7✕4 T-132MS –100Hz • With brake
200 V class 0.2 kW model alone is available.
The output base frequency is 60 Hz only. Any other base frequency setting may cause fire. Be sure to set the base frequency at
60 Hz.
The explosion-proof (d2G4) motor is used only with HF-320 Series, and it cannot be used with SF-320 Series. Set the inverter to
"Sensorless vector control."
Option
Operator station specifications for Exd2
Model No. EGFCT3203
Ordering type OS1-Exd2- - OS2-Exd2- - OS3-Exd2- - OS4-Exd2- -
Frequency counter Scale: 0-100% (Special scale is also available.)
Volume RA30YN-2W 1kΩ
Pilot lamp – Power indication Power indication Power indication
ON-OFF Reverse-Stop-Normal Normal-Reverse ON-OFF
Operation switch
selector switch selector switch selector switch pushbutton switch
(Products are made according to customer's specifications.)
19
HF-320
Terminal Functions
Terminal Functions
[Main circuit terminals] [Control circuit terminals]
AL2 Alarm output terminals (IC contact (relay) output) Contact rating
〈Initial setting〉 AC250V 2.5A (resistive load)
AL0 AL1 AL2 0.2A (cos =0.4)
AL1 When normal, power OFF: AL0-AL2 Close DC30V 3.0A (resistive load)
0.7A (cos =0.4)
When alarm: AL0-AL2 Open (Min.) AC100V 10mA
AL0 (Switchable to AL0-AL1 Close when normal.) DC 5V 100mA
(Note 1) The maximum frequency command is 9.8 V when the voltage input is 0-10 VDC, and 19.6 mA when the current input is 4-20 mA.
(Note 2) The reset terminal cannot be changed to [Operation with (SW) Open].
20
HF-320
Connection Diagram
Connection Diagram
Inverter
(Note 5)
(Note 1) (option) HF-320
MCB MC ACL
R U
Main power supply
3-phase 200–230V S V IM
3-phase 380–460V T W
DC24V PCS PR
(In case of supplying
external DC power) FR Regenerative braking resistor
L (option)
P Note: Refer to p.23.
RR TH
L DCL (Note 6)
P1 (DC reactor) (option)
DFH
L AL0
AL1 Alarm output contact
DFM AL2
L
DFL UPF
L RY1
RST
L DRV
- + FRQ RY2
COM DC24V
OM
+V DC10V
Ground
(Note 1) Do not start and stop the motor with only the MC
switch.
Refer to p.23 for the reference circuit for MC.
(Note 2) Be sure to ground the inverter chassis and motor. [Turn on the main power at the timing shown below.]
(Note 3) The common of each terminals differ.
Terminal FR, RR, DFH, DFM, DFL, RST, FRQ +V, VRF, IRF UPF, DRV
Main circuit power
Common COM COM OM t > 2.0 second (Note 4)
(Note 4) Refer to the figure at right for the power ON and Run command
Run command ON timing. Even if the main circuit
power and operation command are turned ON
simultaneously, the control power will not be turned Output frequency
ON for 2.0 seconds and not permit operation.
(Note 5) When the contactor is to be opened and closed for Motor rpm
each operation, be sure to insert an ACL on the primary
side of the contactor to reduce the inrush current.
(Note 6) When a DC reactor is used, remove the shorting
bar between terminals P and P1.
21
HF-320
Applied Connection Diagram
MCB ACL P P1
U X
R U
V Y
Power S V IM
W Z
T W
Tx
FU (Note 4)
: Shielded wire
Current signal + IRF
DC4–20mA -
MCB
U X P P1
R U Frequency setting by external signal
Power V Y V IM
S
W Z
T W Frequency Multi-stage Multi-stage Multi-stage Multi-stage
speed speed speed speed
setting 1 2 3 4
A20 × × × ×
HF-320
A21 × × ×
A22 × × ×
22
HF-320
Reference Circuit
Reference Circuit
(Note 1)
Br
MCB MC ACL
U X P P1
R U
V Y
Power S V IM
W Z Normal Brake
T W
rotation
Tx
Note 2 Reverse
FU AL2 rotation Brake
(Note 4)
ON AL0
Preparation OFF
MC Operation pattern
for operation MC
Normal HF-320
MC Stop rotation
R
F
F
Reverse FX
rotation
F
R
R
F
RX
R
(Note 1) When using a DC reactor,
BX
DRV FRQ + remove the shorting bar between
Frequency
BR FM counter and P1 and connect them.
_ 10V F.S.
COM (Note 2) When the power supply is a 400
FX V class, install a step-down
FR +V transformer.
RX Speed setter
VRF 1kΩ
RR (Note 3) Set parameter C03 to 11.
COM
BX (Note 3) (Note 4) Set parameter C33 to 00.
DFL
Reset
Twisted wire RST
Shielded wire DRV DRV
COM
DC24V
OM
Br
MCB ACL
U X P P1
R U
V Y
Power S V IM
W Z
T W LS1
Tx
(Note 3)
FU Normal LS2
ON rotation
Preparation OFF THR
MC AL2 LS1, LS3 Normal
for operation MC rotation
Normal (Note 6) The limit switch is a LS4
rotation AL0 holding type.
MC Stop LS2 R
F
HF-320 THR Braking resistor LS3
F
P Operation pattern
Reverse FX
rotation
LS4 F (Note 1)
R PR
R
(Note 1) Use inflammable cable for
RX
F LS1 braking resistor wiring.
DF (Note 2) Parameter A21 is for slow-speed
R LS3
frequency setting and A20 is for
BX
F UPF high-speed setting.
BR (Note 3) When the power supply is a 400
R
V class, install a step-down
UPF FX transformer.
FR
RX (Note 4) Set parameter C21 to 02 and
RR adjust the braking timing by C42
DF
Twisted wire DFL (Note 2) and C43. Parameters C42 and
BX UPF UPF
DFM (Note 5) C43 should be set at approx. 2
Shielded wire DC24V
Hz usually.
COM OM
(Note 5) Set parameter C03 to 11.
(Note 6) Set parameter C33 to 00.
23
Common
Reference Circuit
Reference Circuit
PID circuit
DCL(Option)
Option
MCB Noise
ACL filter P P1
R U
Power S V IM
T W
E
HF-320
SF-320 (Note 1) Command source parameters
Parameter
Purpose No.
Set value
Inputting target signal to VRF terminal. A01 01
Using FR terminal for normal rotation command. A02 01
PID control is set. A71 01
AL1 Feedback input destination: IRF terminal A76 00 (Initial value)
(Note 1) RUN
Foward run FR AL2
(Note 2) PID adjusting parameters
COM AL0
Details of adjustment Parameter No.
[Target value setting]
(Note 2) P (proportional) gain A72
Frequency setter +V I (integral) gain A73
1kΩ VRF D (differential) gain A74
PI DC
COM 24V Level matching of target value and feedback value A75
[Feedback signal] DRV
(Note 3) (Note 3) Parameters setting for PID deviation signal
IRF
4-20mA OM
COM
Parameter
Purpose No.
Set value
DRV terminal function setting C22 04
PID deviation signal detection level setting C44 0–100%
24
Common
Dimensional Drawings
Dimensional Drawings
POWER POWER
RUN Hz RUN Hz
PRG PRG A
A
STOP
118±1
STOP RUN
RUN RESET
RESET
130
MIN MAX
MIN MAX
120
110
10
2.5
5 5 5 2.5
110 4 7 129
80 4 7 D
Model D
3202-A20
107
3202-A40
3202-A75 130
(SF or HF)
POWER
RUN Hz
PRG A
168±1
POWER
118±1
STOP
RUN RUN Hz
180
RESET
130
STOP
RUN
RESET
MIN MAX
5 5
110 4 6 5 128±1 5
7 156 6
7 164
FAN FAN
257
7 7
7
Model FAN
3202-5A5
170
3204-5A5 1
3204-7A5
3202-7A5 2
(SF or HF) (Note) Overseas specification models have different
dimensions. Contact our company for details.
6
25
Common
Applicable Wiring for Accessories and Options
When using an earth leakage breaker (ELB), select the breaker's trip current from the table below
based on the total wire distance (R) by summing the distance from the breaker to the inverter and the
LC filter inverter to the motor.
Radio noise R Trip current (mA) Notes: 1. When CV wiring is used in metal conduit, the
filter leakage current is approximately 30mA/km.
100m or less 30 2. Leakage current will increase eightfold with IV type
DC 300m or less 100 cable due to higher dielectric constant. In this
reactor 200 case, use ELB with the next higher trip rating.
R S T P1 600m or less
P Name Function
Input AC reactor for This is useful in suppressing harmonics induced on the power supply
harmonic suppression/power lines, or when the main power voltage imbalance exceeds 3%, (and
Inverter smoothing/powerfactor power source capacity is more than 500kVA), or to smooth out line
(Note 1)
PR improvement fluctuations. It also improves the power factor.
Radio noise filter Electrical noise interference may occur on nearby equipment such
as a radio receiver. This magnetic choke filter helps reduce radiated
U V W Zero-phase reactor noise.
Input noise filter for This filter reduces the conducted noise in the power supply wiring
between the inverter and the power distribution system. Connect it
LC inverter LC filter to the inverter primary (input side).
filter
Input radio noise filter This capacitive filter reduces radiated noise from the main power
Zero-phase (XY filter) wires in the inverter input side.
reactor
DC reactor The inductor or choke filter suppresses harmonics generated by the inverter.
Regenerative braking resistor The regenerative braking resistor is useful for increasing the
AC
inverter's control torque for high duty-cycle (on-off) applications, and
HF-320 only improving the decelerating capacity.
reactor
Output noise filter This filter reduces radiated noise emitted on the inverter output cable
that may interfere with radio or television reception and test
LC filter equipment and sensor operation.
Motor Radio noise filter Electrical noise interference may occur on nearby equipment such
IM as a radio receiver. This magnetic choke filter helps reduce radiated
Zero-phase reactor noise.
(Note 1) SF-320 Series are not equipped with a PR terminal. Use HF-320 when regenerative braking is required.
26
Common
Operation
Operation
H2
A DC reactor is available for improvement of the
power factor of the inverter, ensuring power line
H1
impedance, and control of higher harmonics.
H
P1 P
W1 4-dia.G D1
W D
(Note) Models below 200 V class 3.7 kW of SF-320 and HF-320 are subject to the "Guideline for the Suppression of Harmonics in Household and General-Use Equipment"
issued by the Ministry of International Trade and Industry in September 1994. Therefore, it is necessary to install a reactor for inverters to be installed from January 1,
1997 onward to conform to the standards described in these guidelines.
Applicable Specification Part No.
capacity W W1 D D1 D2 D3 H H1 H2 G Connection Weight Insulation
(kW) Current(A) L(mH) Y220DA terminal (kg)
0.2 1.0 29.7 032 52 35 40 32 20 22 65 - 300 dia.4 M4 0.3 B
0.4 2.0 14.8 033 52 35 40 32 20 22 75 - 300 dia.4 M4 0.4 B
0.75 3.75 9.72 034 52 35 50 42 25 27 85 - 300 dia.4 M4 0.6 B
200V 1.5 7.5 4.83 035 74 50 45 37 - - 120 145 - dia.5 M5 1.0 B
Series 2.2 11.0 3.41 036 74 50 45 37 - - 120 145 - dia.5 M5 1.1 B
3.7 18.5 2.13 037 90 60 62 52 - - 140 170 - dia.5 M8 2.0 B
5.5 28.0 1.47 038 90 60 62 52 - - 140 170 - dia.5 M5 2.4 B
7.5 38.0 1.11 039 100 80 95 80 - - 140 170 - 5.5✕7 M5 3.5 B
0.4 1.0 59.3 003 52 35 40 32 20 22 75 - 300 dia.4 M4 0.4 B
0.75 1.88 38.9 004 52 35 50 42 25 27 85 - 300 dia.4 M4 0.6 B
1.5 3.75 19.3 005 59 40 60 47 30 35 100 - 300 dia.4 M4 0.9 B
400V
2.2 5.5 13.7 006 74 50 45 37 - - 120 140 - dia.5 M5 1.1 B
Series
3.7 9.25 8.52 007 74 50 70 62 - - 120 145 - dia.5 M5 1.8 B
5.5 14.0 5.87 008 90 60 62 52 - - 140 165 - dia.5 M5 1.5 B
7.5 19.0 4.46 009 100 80 95 80 - - 140 165 - 5.5✕7 M5 3.5 B
T D1 D2
AC reactor for power factor improvement and higher harmonics control
L
(Note) Models below 200 V class 3.7 kW of SF-320 and HF-320 are subject to the "Guideline for the Suppression of Harmonics in Household and General-Use Equipment"
issued by the Ministry of International Trade and Industry in September 1994. Therefore, it is necessary to install a reactor for inverters to be installed from January 1,
1997 onward to conform to the standards described in these guidelines.
Applicable Specification Part No. Weight
capacity W DI D2 H1 H2 A B G L T Insulation
(kW) Current(A) L(mH) Y220CA (kg)
–0.4 2.1 5.8 053 90 35 30 100 - 50 38 4 300 M4 1.0 B
0.75 4.0 3.1 054 90 35 30 100 - 50 38 4 300 M4 1.1 B
1.5 8.0 1.6 055 90 40 35 100 120 55 48 4 - M4 1.6 B
200V
2.2 11 1.2 056 115 42 37 120 145 55 43 4 - M4 2.1 B
Series
3.7 17 0.7 057 115 42 37 120 145 55 43 4 - M5 2.4 B
5.5 24 0.5 058 155 45 40 150 180 80 50 5 - M5 3.9 F
7.5 33 0.4 059 155 45 40 150 185 80 50 5 - M6 4.4 F
0.4 1.2 22 080 90 35 30 100 - 50 38 4 300 M4 1.0 B
0.75 2.1 12 081 90 35 30 100 - 50 38 4 300 M4 1.1 B
1.5 4.0 6.5 082 90 40 35 100 - 55 48 4 300 M4 1.7 B
400V
2.2 5.5 4.6 083 115 42 37 120 - 55 43 4 300 M4 2.5 B
Series
3.7 9.0 2.9 084 115 42 37 120 145 55 43 4 - M4 2.8 B
5.5 13 2.0 085 155 45 40 150 175 80 50 5 - M4 4.2 B
7.5 17 1.5 086 155 45 40 150 175 80 50 5 - M5 4.4 B
27
Common
Noise filter
Noise filter
1. Zero-phase reactor (inductive filter) Method of connection
(1) It can be used on both input (power supply) side and
Common to 200 V and 400 V classes, as well output (motor) side of the inverter.
as input and output sides (2) Wind the cables of the three phases respectively on the
• 3.7 kW or less • 5.5 kW or more input or output side more than three times (4 turns) in the
Part No. X480AC188 Part No. X480AC192 same direction. If cables are too thick to wind more than
three times (4 turns), arrange two or more zero-phase
Type RC5078 Type RC9129 reactors to reduce the number of winding turns.
(3) Make the gap between the cable and the inside of the
core as small as possible.
Zero-phase reactor Zero-phase reactor Winding More than 3 times (4T)
RC5078 RC9129 turns
180–2
160–1
dia.7
Qty used 1 pc
31.5
85
130
85
64
14 dia.7
23
7
83–2
35
80
R3.5 130
150
2. Capacitive filter
Common to all capacities
Common to 200 V and 400 V classes MCB
Part No. X480AC185 R
Type 3XYHB-105104 Power S
Inverter
Method of connection T
(1) Connect directly to the input (power) terminal of the
inverter. Make the connection cable as short as Shortest possible wiring E
possible.
(2) Correctly ground the equipment. (Grounding
Black
Black
Black
Yellow/
Green
22
12 dia.4.3
Leakage current
11.0
200V: 3.9mA
400V: 7.8mA
5.5
31.0 –1.0
Soldering
UL-1015AWG18
Black and yellow/green
10 –2
300mm
47.0 –1.0
4.5
55.0 –1.0
28
Common
Noise filter
Noise filter
3. LC filter
200V class (1) Connect the input-side filter between the power supply
and inverter input terminal, and the output-side filter
Power Applicable Input side Output side
supply motor between the inverter output terminal and motor. Make
(kW) Type Part No. Type Part No.
0.2–0.4 CC3005C-P X480AC163 the connection cable as short as possible.
0.75–1.5 NF3010A-VZ X480AC289 CC3010C-P X480AC164 (2) Use grounding cable as thick as possible. Correctly
3-phase 2.2 CC3015C-P X480AC165
200V NFf3020A-VZ X480AC290 ground the equipment.
3.7 CC3020C-P X480AC166
class 5.5 NF3030A-VZ X480AC291 CC3030C-P X480AC167 (3) The input and output cables of the filter should be
7.5 NF3040A-VZ X480AC292 CC3045C-P X480AC168 sufficiently separated.
(4) Do not connect the input-side filter to the inverter output
400V class (motor) side.
Power Applicable Input side Output side
supply motor Input-side Output-side
(kW) Type Part No. Type Part No. LC filter LC filter
0.4–1.5 CC3005C-P X480AC163 Inverter
3-phase 2.2–3.7 NF3010C-VZ X480AC296 CC3010C-P X480AC164 1 4 R U 1 4
400V 5.5 CC3015C-P X480AC165
Power 2 5 S V 2 5 M
class NFf3020C-VZ X480AC297 3 6 T W 3 6
7.5 CC3020C-P X480AC166 E
E
Input-side LC filter
D±1.5
E±1.0
H C±1.5 J
B±1.5
A±1.5
F±1.5
G
Model Type A B C D E F G H J K L
X480AC289 NF3010A-VZ
X480AC290 NF3020A-VZ 128 118 108 63 43 42 1.0 M4
X480AC291 NF3030A-VZ 145 135 125 70 50
X480AC292 NF3040A-VZ 179 167 155 90 70 54 1.6 4.5✕6 dia.4.5 M5 M4
X480AC296 NF3010C-VZ
X480AC297 NF3020C-VZ 128 118 108 63 43 42 1.0 M4
D±1.3 J
C±1
B±1.5 H±1.5
A±7.5
29
Common
Example of noise filter use
Power R U
supply S V IM
Power R U
T W supply S V IM
Inverter T InverterW
Metal conduit or
Metal tube or shielded lower the carrier shielded cable Lower the carier
frequency. grounded at Capacitive filter frequency as much Metal conduit or
cable grounded at one shielded cable
point one point as possible.
E grounded at
E one point
Use 4-wire cable
as a motor power
line, and ground Use 4-wire cable
one of the wires. as a motor power line,
and ground one of the
wires.
Control panel or machine frame Note: The above measures may be
insufficient in places where the Control panel or machine frame
broadcast reception is weak.
Corrective measures
Corrective measures qLower the carrier trequency as much as possible. Up to approx. 10 kHz
qLower the carrier frequency as much as possible. Up to approx. 10 kHz when low-noise operaton is necessary.
when low-noise operation is necessary. wInstall a zero-phase reactor on the output side of the inverter.
wInstall a zero-phase reactor on the output side of the inverter. (Type: RC5078, RC9129)
(Type: RC9129) eInstall a zero-phase reactor on the input side the inverter.
eInstall an LC filter on the input side of the inverter. (Type: RC5078, RC9129)
( -FS) rInstall a capacitive filter on the input side of the inverter.
rConnect the inverter and motor with a metal conduit or shielded cable. (Type: 3XYHB-105104)
tUse 4-wire cable as a motor power line, and ground one of the wires. tConnect the inverter and motor with a metal conduit or shielded cable.
yConnect the inverter and power with a metal conduit or shielded cable. yUse 4-wire cable as a motor power line, and ground one of the wires.
uInstall a drive isolation or noise reduction transtormer for the power
supply. Connection of we zero-phase reactor and r capacitive
differs according to the inverter capacity and voltage. filter
Connection of w zero-phase reactor and e LC filter Zero-phase reactor Make the cable as Zero-phase reactor
RC5078 shortas possible. RC5078
LC filter (Note)
NF3 –CD Zero-phase reactor
RC5078 R U
HF3 –FS Power Inverter V
supply S Power
1 4 R U supply
T W
Power S Inverter V
supply 2 5
Motor
E
3 6 T W
Make the cable as short
as possible.
Green
Black
Black
Black
Blue/
E
Capacitive
Make the cable as filter 3XYHB Make the cable as short as possible.
short as possible. -105104
Control panel or machine frame
Note: Turn wires the same number of times for all phases of the zero-phase
Note: Turn wires the same number of times for all phases of the zero-phase reactor. 3 times (4 T) or more Increase the number of zero-phase reactor
reactor. 3 times (4 T) or more Increase the number of zero-phase reactor when the cable is too thick to wind correctly.
when the cable is too thick to wind correctly.
Ground this part via a 0.01-0.1 µF Avoid direct grounding Connection of ty reactors and u capacitive filter
capacitor instead of direct grounding
Zero-phase reactor Zero-phase reactor
RC5078 RC5078
Corrective measures RC9129
Make the cable as
short as possible. RC9129 (Note) Note: Turn wires the same
qUse twisted pair/shielded wire as a sensor signal line, and connect the number of times for
R U all phases of the
shielded wire to common. Power
supply S
Inverter
V zero-phase reactior.
Motor
wSeparate the inverter and power line from the sensor circuit as much as T W 3 times (4 T) or
more. Increase the
possible. (More than 10 cm desirable) E number of zero-
eRemove the grounding wire when the power supply for the sensor is Make the cable as phase reactors when
short as possible. the cable is too thick
grounded.
Yellow/
Black
Black
Black
Green
30
Common
Peripheral equipment
Peripheral equipment
15 24
12.5 31.5 11±1 120±1.5 Panel cut
0.5 10 50±0.5 50±0.5 50±0.5 50±0.5
50 dia.3
40 60
30 70
35±0.5 45±0.5
45±0.5
dia.25
12
dia.30
50
20 80 .8
dia
100±1
10 90 dia.9.5 M4 (M5)
dia.85
35±0.5
0 100
Terminal screw
Panel cut thread
AC ammeter: ACF-12N
The CT directly detects the current of the secondary side of the inverter.
12.5 31.5 11±1 120±1.5 Panel cut
0.5 10 50±0.5 50±0.5 50±0.5 50±0.5
45±0.5
7
35±0.5 45±0.5
.8
dia
100±1
M4 (M5)
dia.85
35±0.5
140
Terminal thread
ACF-12N
75 60
M5 thread M5 thread
M6 thread
E
110
Rating plate
101
Rating plate
96
.72
dia
65±2
60±1
84±1 8 84±1 8
1.6
10
100 42 100 42
COMA-15 COM-15-26
31
Common
Peripheral equipment
Peripheral equipment
Remote operator
13 8
Remote operator 80 26.5
OS-41
2
18
POWER
R
ALARM PRG RUN
POWE N
RU
PRG
ALARM
18
COPY COPY
READ R
ST
REMT N 3
FU 2
MO N ET
1 STOP/RES
0 N
REV RU
L
N
COPY
103
103
FWD RU
123
REMT READ COPY
Inverter 0 1 2 3
2ーdia.4
FWD RUN REV RUN STOP/RESET
6.5
Model Cable length: L (m)
ICS–1 1
ICS–3 3
Electromagnetic When using an electromagnetic contactor between the inverter and motor, do not turn the contactor ON or
contactor OFF during inverter operation.
Install a thermal relay that matches the motor in the following cases:
Wiring * Install a thermal relay for each motor when operating more than one motor with one inverter.
between * Set the current of the thermal relay at the rated motor current x 1.1. When the wiring length is long (more
inverter and than 10 m), the thermal relay may be activated too quickly. Install an AC reactor or current sensor on the
Thermal
motor output side.
relay
* When motors are to be operated with the rated current exceeding the adjustable level of the built-in
electronic thermal relay.
〈SF-320〉
* When operation continues at frequencies beyond the 30-60 Hz range.
Install an earth leakage breaker on the input side for protection of the inverter wiring and operators.
Conventional earth leakage breakers may malfunction because of high harmonics from the inverter;
Earth leakage breaker
therefore use an earth leakage breaker that is applicable to the inverter. The leakage current differs
according to the cable length. Refer to p.26.
The wiring distance between the inverter and operation panel should be less than 20 m. If it exceeds 20 m,
use a current/voltage converter, etc. Use shielded cable for wiring.
When the wiring distance between the motor and inverter is long, the leakage current from high harmonics
Wiring distance
may cause the protective function of the inverter and peripheral equipment to be activated. The situation will
be improved by an AC reactor installed on the output side of the inverter.
Select appropriate cable to prevent voltage drop. (Large voltage drop lowers the torque.)
32
Common
Notes to inverter users
Notes to inverter users
HF-320 Output torque characteristics when general-purpose motors are operated under sensorless vector control
150 150
Torque (%)
Torque (%)
Continuous operation torque Continuous operation torque
100 100
80 80
50 50
40 40
0 6 20 40 60 120 0 6 20 40 60 120
Frequency (Hz) Frequency (Hz)
0.2–0.4 kW 0.75–3.7 kW
●Combination ... The output torque is 100% when the motor rating is 60 Hz.
Use an AF motor when constant torque is necessary for motors 5.5 kW or more.
33
Common
Warranty
1. Warranty policy on inverter
Warranty
Warranty
The warranty shall be 18 months from date of shipment or 12 months after intial operation, whichever is shorter.
period
In the event that any problem or damage to the Product arises during the "Warranty Period" from defects in the Product
whenever the Product is properly installed and combined with the Buyer's equipment or machines maintained as specified in the
maintenance manual, and properly operated under the conditions described in the catalog or as otherwise agreed upon in
writing between the Seller and the Buyer or its customers; the Seller will provide, at its sole discretion, appropriate repair or
Warranty
replacement of the Product without charge at a designated facility, except as stipulated in the "Warranty Exclusions" as
condition
described below.
However, if the Product is installed or integrated into the Buyer's equipment or machines, the Seller shall not reimburse the cost
of: removal or re-installation of the Product or other incidental costs related thereto, any lost opportunity, any profit loss or other
incidental or consequential losses or damages incurred by the Buyer or its customers.
Not withstanding the above warranty, the warranty as set forth herein shall not apply to any problem or damage to the Product
that is caused by:
1. Installation, connection, combination or integration of the Product in or to the other equipment or machine that rendered by
any person or entity other than the Seller;
2. Insufficient maintenance or improper operation by the Buyer or its customers such that the Product is not maintained in
accordance with the maintenance manual provided or designated by the Seller;
3. Improper use or operation of the Product by the Buyer or its customers that is not informed to the Seller, including, without
Warranty limitation, the Buyer's or its customers' operation of the Product not in conformity with the specifications;
exclusion 4. Any problem or damage on any equipment or machine to which the Product is installed, connected or combined or any
specifications particular to the Buyer or its customers;
5. Any changes, modifications, improvements or alterations to the Product or those functions that are rendered on the Product
by any person or entity other than the Seller;
6. Any parts in the Product that are supplied or designated by the Buyer or its customers;
7. Earthquake, fire, flood, salt air, gas, lightning, acts of God or any other reasons beyond the control of the Seller;
8. Normal wear and tear, or deterioration of the Product's parts, such as the cooling fan bearings;
9. Any other troubles, problems or damage to the Product that are not attributable to the Seller.
The Seller will not be responsibility for the installation and removal of the inverter. Any inverter transportation cost shall be born
Others
by both Seller and Buyer.
Warranty Warranty on repaired Product will apply only on the replacement parts used in the repair done or authorized by the Seller. All
condition other aspects conform to the Warranty Conditions described in item 1.
Warranty
Please refer to Warranty Exclusions described in item 1.
exclusion
34
SAFETY PRECAUTIONS
● Before use, be sure to read the Instruction Manual thoroughly to insure proper use of the inverter.
● Note that the inverter requires electrical wiring; a specialist should carry out the wiring.
● The inverter in this catalog is designed for general industrial applications. For special applications in fields such as
aircraft, aerospace, nuclear power, electrical power, transportation, medical equipment, and submarine relay
equipment, please consult with us in advance.
● For application in a facility where human safety is involved or serious losses may occur, make sure to provide adequate
safety devices to avoid a serious accident.
● The inverter is intended for use with a three-phase AC motor. For use with a load other than this, please consult with
us.
W18