Item package package

Brief description of work Unit Total Qty SIFANG Queries


No. 3 4

4 Control & Relay panels (220 kV)


4.1.0 220 KV Line C & R panel with necessary relay:-

1. Against Main-1 & Main-2 protections, please


confirm whether Distance protection relay is
required or Line Current Differential protection
relay is required?

2. Please confirm the panel type requirement i.e.


whether Simplex or Duplex type.

3. Clause "8.49(vi) 220kV Protection" mentioned


in Page 138 of 386 and Clause "8.67
4.1.1 Line distance CRP  Nos  5 2 7 Relay/Protection Panel Equipment for Different
voltage class" mentioned in Page 150 of 386
has mentioned the requirement for "Line CVT
operated two stages Over Voltage protection"
and "Line CVT operated Under Voltage relay"
respectively. Please note the above protection
features are available as inbuilt in our offered
Distance protection relays, kindly confirm
whether the above protection features will be
accepted as inbuilt functionality in our offered
Distance protection relays or not.

1. Please confirm the panel type requirement i.e.


whether Simplex or Duplex type.

2. Please confirm the Vector Group, HV(primary),


MV(secondary) and LV(tertiary) voltages for
each of the transformers.
4.1.2 Transformer CRP Nos  2 4 6
3. We presume that Control & Protection panel is
required only for HV side of the Transformers
and Control & Protection panel is not required
for Transformer's MV & LV sides. Please confirm
whether our understanding is correct or not.

1. Please confirm the panel type requirement i.e.


whether Simplex or Duplex type.

2. Clause 8.56 "220kV Bus Coupler Protection"


mentioned in page 140 of 386 has specified the
requirement of "Over Current & earth Fault
4.1.3 Bus Coupler Nos  2 1 3
Protection with Check-Sync facility, Bus bar
protection and Local breaker backup protection".
We presume that the requirement of "Bus bar
protection" as mentioned above is a
typographical error. Please confirm whether our
understading is correct or not.

4.1.4 Transfer Bus Coupler Nos  0 0 0


4.1.5 Bus Bar CRP Nos  0 0 0
Control & Relay panels (132 kV)
4.2.0 132 KV Line C & R panel with necessary relay:-

Page 1 of 3
1. Against "Main protection", please confirm
whether Distance protection relay is required or
Line Current Differential protection relay is
required?

2. Please confirm the panel type requirement i.e.


whether Simplex or Duplex type.

3. Clause "8.67 Relay/Protection Panel


4.2.1 Line outgoing CRP  Nos  18 17 35
Equipment for Different voltage class"
mentioned in Page 150 of 386 has mentioned
the requirement for "Line CVT operated Under
Voltage relay". Please note the above protection
feature is available as inbuilt in our offered
Distance protection relay, kindly confirm
whether the above protection feature will be
accepted as inbuilt functionality in our offered
Distance protection relay or not.

1. Please confirm the panel type requirement i.e.


whether Simplex or Duplex type.

2. Please confirm the Vector Group, HV(Primary),


MV(secondary) and LV(tertiary) voltages for
each of the transformers.
4.2.1 Transformer  CRP  Nos  11 11 22
3. We presume that Control & Protection panel is
required only for HV side of the Transformers
and Control & Protection panel is not required
for Transformer's MV & LV sides. Please confirm
whether our understanding is correct or not.

4.2.3 Bus Bar CRP Nos  0 0 0

1. Please confirm the panel type requirement i.e.


whether Simplex or Duplex type.

2. We presume that the present requirement is


for supply of Bus Coupler CRP and not Transfer
Bus Coupler CRP. Please confirm whether our
4.2.4 Bus coupler CRP Nos  4 4 8 understanding is correct or not.

3. As the specification for 132kV Bus Coupler


CRP is not available, we presume that only
"Over Current & earth Fault Protection with
Check-Sync facility" is required for 132kV Bus
coupler protection purpose. Please confirm
whether our understanding is correct or not.

Control & Relay panels (33 kV)


4.3.0 33 KV Line C & R panel with necessary relay
4.3.1 Feeder Panel Nos  25 9 34

1. Please confirm the Vector Group, HV(Primary),


MV(secondary) and LV(tertiary) voltages for
each of the transformers.

2. We presume that Control & Protection panel is


4.3.2 Transformer  CRP  Nos  10 8 18 required only for HV side of the Transformers
and Control & Protection panel is not required
for Transformer's MV & LV sides. Please confirm
whether our understanding is correct or not.

Page 2 of 3
1. We presume that the present requirement is
for supply of Bus Coupler CRP and not Transfer
Bus Coupler CRP. Please confirm whether our
understanding is correct or not.

4.3.3 Bus coupler CRP Nos  6 2 8 2. As the specification for 33kV Bus Coupler CRP
is not available, we presume that only "Over
Current & earth Fault Protection with Check-Sync
facility" is required for 132kV Bus coupler
protection purpose. Please confirm whether our
understanding is correct or not.

5 Other Protection & Control System  Equipment


Replacement of Existing Electromechanical & static
5.1
relays
5.2 Numerical Back up Relay Nos  11 25 36
5.3 Numerical Distance Protection Relay Nos  0 7 7
5.4 Numerical Transformer Differential Relay Nos  3 4 7
5.5 Master Trip Relay Nos  3 6 9
5.6 Auxiliary Relay Nos  3 6 9
5.7 Numerical Bus Bar diff Relay  Nos  0 0 0
5.8 Numerical  LBB relay Nos  0 0 0
Annunciation Scheme
24 windows - Microprocessor based with replaceable
5.9 windows,Rated 85V to 270V AC/DC, Stand by - 12V DC +/- 10%, Nos  0 0 0
Fault Input contact - Selectable NO/NC type.
16 windows -  Microprocessor based with replaceable
5.1 windows,Rated 85V to 270V AC/DC, Stand by - 12V DC +/- 10%, Nos  0 0 0
Fault Input contact - Selectable NO/NC type.
10 Synchronizing panel/trolley Nos  3 2 5

GENERAL Queries
Clause 8.33.1 mentioned in Page 124 of 386
Please note this requirement(i.e. supply of PC) is
1 "The supply of relay should be inclusive of necessary software not mentioned in your given BOQ. Therefore, we
and hardware for interfacing with a PC. to be supplied by the presume this is not applicable. Please confirm.
bidder."

We presume Bay Control Units(BCU) is not


applicable for this project as your given Bill of
Clause 8.17 e) mentioned in Page 116 of 386
materials under Clause "8.65 Control Panel
Equipment for Different Voltage Class"
2 "At bay level, Bay Control IEDs shall provide all bay level
mentioned in Pages
functions regarding control and monitoring, inputs for status
144,145,146,147,148,149,150,151,152,153 &
indication and outputs for commands."
154 of 386 has not specified the same
requirement. Please confirm.

Page 3 of 3