Water Infrastructure

Standard Details
Connections and Developer Services
Construction Requirements for Self-Lay Developments
December 2017 (Revision 03)

Document IW-CDS-5020-01
IW-CDS-5020-01

1 | Irish Water | [Type Document Title]


IW-CDS-5020-01 Rev. 03 December 2017

Revision Log
Date Details of Revision Revision Author Approver
April 2016 General revisions & 01 T’OC M’OD
drawing added
August 2016 General revisions 02 TO’C MO’D
December 2017 General revisions & 03 TO’C MO’D
drawing added
IW-CDS-5020-01 Rev. 03 December 2017

Background
Technical Documentation has been developed by Irish Water’s Connections and
Developer Services which outlines the requirements for water services infrastructure
within developments.

These standard details have been developed to outline to developers Irish Water’s
requirements for the provision of water infrastructure that is to be installed in
developments and that would be connected to Irish Water’s networks and subsequently
vested in Irish Water.

The aim is to provide details to developers for water infrastructure, which will outline
design and construction requirements to ensure consistency in the provision of
materials, equipment and workmanship, etc. The standard details will also provide the
basis for developers’ detailed design proposals for water infrastructure, leading to the
provision of infrastructure that is suitable for connection to Irish Water’s networks and
easy operation and maintenance of the new infrastructure.

The standard details are based on best practice within the water industry. They take
account of the experience of Local Authorities in the provision of these services to new
developments. They have been successfully used by Irish Water’s own internal
functions for a variety of projects and they are in line with water utility industry norms.

There are 40 No Standard Details dealing with water infrastructure covering all aspects
of such infrastructure.

These standard details are accompanied by a Design Risk Assessment (DRA)


(document number IW-CDS-5020-02), which outlines the residual health and safety
responsibilities of developers and their designers/contractors in the provision of such
infrastructure.

The use of the standard details is mandatory in all new Irish Water Connection
Agreement Offers issued after 1st June 2016.
IW-CDS-5020-01 Rev. 03 December 2017
Standard Details for Water Networks
Index Sheet
Drawing No. Drawing Title Rev.
STD-W-01 Water service connection responsibility 0
STD-W-02 Typical layout for water mains within developments 1
STD-W-03 Customer connection & boundary box 3
STD-W-04 General pipe connections (sheet 1 of 7) 3
STD-W-05 General pipe connections (sheet 2 of 7) 2
STD-W-06 General pipe connections (sheet 3 of 7) 2
STD-W-07 General pipe connections (sheet 4 of 7) 1
STD-W-08 General pipe connections (sheet 5 of 7) 1
STD-W-09 General pipe connections (sheet 6 of 7) 1
STD-W-10 General pipe connections (sheet 7 of 7) 1
STD-W-11 Typical service layout indicating separation distances 1
STD-W-12 Restrictions on water infrastructure works adjacent to existing trees 2
STD-W-12A Restrictions on new trees / shrubs planting adjacent to watermains 0
STD-W-13 Trench backfill & bedding 1
STD-W-14 Sluice valve for ductile iron (D.I.) pipe (<350mm dia.) (sheet 1 of 2) 3
STD-W-15 Sluice valve for polyethylene (P.E.) pipe (<350mm dia.) (sheet 2 of 2) 2
STD-W-16 On-line hydrant for ductile iron (D.I.) pipe (sheet 1 of 4) 2
STD-W-17 Off-line hydrant for ductile iron (D.I.) pipe (sheet 2 of 4) 3
STD-W-18 On-line hydrant for polyethylene (P.E.) pipe (sheet 3 of 4) 2
STD-W-19 Off-line hydrant for polyethylene (P.E.) pipe (sheet 4 of 4) 3
STD-W-20 On-line air valve for ductile iron (D.I.) pipe (sheet 1 of 4) 2
STD-W-21 Off-line air valve for ductile iron (D.I.) pipe (sheet 2 of 4) 3
STD-W-22 On-line air valve for polyethylene (P.E.) pipe (sheet 3 of 4) 2
STD-W-23 Off-line air valve for polyethylene (P.E.) pipe (sheet 4 of 4) 3
STD-W-24 Pressure reducing / sustaining valve (P.R.V. / P.S.V.) chamber 2
STD-W-25 Booster pump station arrangement 1
STD-W-26 Non Mech. Meter chamber (40 - 250mm dia.) 3
STD-W-26A Mech. Meter chamber (40 - 250mm dia.) 0
STD-W-27 Marker posts / plates 2
STD-W-28 Water main thrust & support blocks 1
STD-W-29 Duct chamber 2
STD-W-30 Scour chamber & head wall arrangements 3
STD-W-30A Washout hydrant 2
STD-W-31 Typical ditch / stream crossing for water main 1
STD-W-32 Typical bridge crossing for water main (sheet 1 of 2) 1
STD-W-33 Typical bridge crossing for water main (sheet 2 of 2) 1
STD-W-34 Security gate & fencing 2
STD-W-35 Pipe repair to existing mains 2
STD-W-36 Telemetry and wet kiosk 2
STD-W-37 Lamp bollard & lamp standard 1

These Standard Details show the acceptable typical details and outline on the minimum standards that are required by Irish Water for the
provision of water pipes and related infrastructure which are to be connected to the Irish Water Network. They shall be used in conjunction
with the associated Design Risk Assessments that have been developed which identify the risks that designers shall take into account in the
detailed design of the water and wastewater pipes and related infrastructure to be connected to the Irish Water Network. The pipes and
related infrastructure to be put in place within developments shall comply fully with these Standard Details. Ultimate responsibility (including,
but not limited to, any losses, costs, demands, damages, actions, expenses, negligence and claims) for the detailed design, construction
and provision of such pipes and related infrastructure shall rest entirely with the Developer, his/her Designer(s), Contractor(s) or other
connected party. Irish Water assumes no responsibility for and gives no guarantees, undertakings or warranties in relation to the pipes and
related infrastructure to be provided in accordance with these Standard Details.
No part of the Standard Details shall be reproduced or transmitted in any form or stored in any retrieval system of any nature without the
prior written permission of Irish Water as copyright holder, except as agreed for use.
These Standard Details shall be used in conjunction with current Irish Water Codes of Practice, which will take precedence over the
Standard Details.
These Standard Details may also be used for the installation of water & wastewater infrastructure for Asset Delivery Works & Capital Project
Works Programmes at the discretion of Irish Water.
DEC. 2017
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.

CUSTOMER PROPERTY

PROPERTY BOUNDARY

FOOTPATH
ROAD

BOUNDARY BOX
225mm
DISTRIBUTION SYSTEM
SERVICE PIPE

WATER MAIN

IRISH WATER PROPERTY OWNER

A B C

MAINTENANCE
RESPONSIBILITY

A - B SERVICE PIPE IRISH WATER

METER / BOUNDARY BOX IRISH WATER

B - C (DISTRIBUTION SYSTEM) PROPERTY OWNER

INTERNAL PLUMBING PROPERTY OWNER

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

WATER SERVICE CONNECTION


RESPONSIBILITY STD-W- 01 0
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. WATER MAIN LAYOUTS SHALL BE ARRANGED IN LOOPS OR RINGS SO AS TO AVOID ''DEAD ENDS'' OR TERMINAL POINTS. ALL MAINS SHALL TERMINATE IN A LOOP OR RING TO ACCOMMODATE ONE-DIRECTIONAL FLUSHING OF
THE NETWORK. LOOPS SHALL HAVE A MINIMUM OF 4 HOUSES AND 1 HYDRANT.

2. THE MINIMUM PIPE SIZE SHALL BE 100mm INTERNAL DIAMETER IN HOUSING DEVELOPMENTS OF 40 AND UP TO 100 HOUSES. DEVELOPMENTS OF 100 HOUSES AND ABOVE SHALL HAVE A MINIMUM PIPE SIZE OF 150mm INTERNAL
DIAMETER SPINE AND 100mm BRANCH MAINS. NOMINAL INTERNAL DIAMETERS OF 80mm AND LESS MAY BE ALLOWED IN SMALLER DEVELOPMENTS BUT NOT WHERE HYDRANTS ARE LOCATED AND ONLY AFTER PRIOR WRITTEN
AGREEMENT FROM IRISH WATER

3. THE MINIMUM PIPE SIZE SHALL BE 150mm IN INDUSTRIAL OR COMMERCIAL DEVELOPMENTS.

4. EVERY PREMISE SHOULD HAVE A SEPARATE SERVICE CONNECTION. THE USE OF COMMON SERVICE PIPES IS NOT ALLOWED. SERVICE CONNECTIONS SHALL BE AS SHORT AS REASONABLY POSSIBLE. LONG SERVICE
CONNECTIONS (IN EXCESS OF 15m) WILL NOT BE ALLOWED. A RIDER MAIN AT THE OPPOSITE SIDE OF THE ROAD TO THE MAIN WATER MAIN MAY BE REQUIRED SUBJECT TO APPROVAL FROM IRISH WATER. SERVICE
CONNECTIONS SHALL BE A MINIMUM PIPE SIZE OF 25mm OUTSIDE DIAMETER, 20mm INTERNAL DIAMETER.

5. WATER MAINS SHOULD BE LAID TO PROVIDE THE OPTIMUM CIRCULATION IN THE LOCAL WATER NETWORK. WATER MAINS MAY TERMINATE IN A DEAD END ONLY WITH IRISH WATER APPROVAL, IN WHICH CASE AN ON-LINE
WASHOUT HYDRANT SHALL BE PROVIDED AT THE DEAD END, LOCATED WITHIN A CHAMBER OR KIOSK.

6. VALVES SHALL BE ARRANGED IN SUCH A MANNER TO ALLOW THE NETWORK TO BE MANAGED TO ENSURE THAT NO MORE THAN 40 PROPERTIES LOSE WATER FROM A BURST ON THE SYSTEM, AT ANY ONE TIME.

7. NO DOMESTIC PROPERTY SHALL BE MORE THAN 46m FROM A HYDRANT. HYDRANT DETAILS AND LOCATIONS SHALL BE SUBJECT TO THE APPROVAL OF THE RELEVANT LOCAL AUTHORITY FIRE DEPARTMENT.

8. WATER SUPPLY MAINS SHALL BE LAID IN COMMON AREAS AND NOT THROUGH INDIVIDUAL PRIVATE GARDENS OR DRIVEWAYS ETC.

9. A THREE-WAY VALVE ARRANGEMENT SHALL BE PROVIDED AT ALL JUNCTIONS, AS A MINIMUM.

10. THE WATER MAIN PIPEWORK TO NEW DEVELOPMENTS SHOULD BE LOCATED AT THE RIGHT HAND SIDE OF THE ENTRANCE TO THE NEW DEVELOPMENT (FROM A VIEW FACING INTO THE DEVELOPMENT) IF POSSIBLE AND WHERE
THE PROPERTIES ARE EQUALLY AND REASONABLY DISTRIBUTED AT BOTH SIDES OF THE ESTATE ROADWAY.

11. AIR VALVES TO BE LOCATED AT POINTS WHERE AIR IS LIKELY TO BUILD UP.

12. THE DEVELOPER IS TO LIAISE WITH THE FIRE SERVICES AUTHORITY IN ORDER TO ENSURE FIRE FLOWS ARE AVAILABLE THROUGHOUT THE DEVELOPMENT.

13. BULK FLOW METERS SHALL BE FITTED IN ALL DEVELOPMENTS WITH A DEMAND IN EXCESS OF 20m³ PER DAY. BULK FLOW METERS SHALL HAVE A FACTORY FITTED AMR AND INSTALLED IN A SUITABLY SIZED CHAMBER.
DEVELOPMENTS WITH DEMAND LESS THAN 20m³ PER DAY SHALL BE PROVIDED WITH DEDICATED BYPASS PIPEWORK AND CHAMBER TO ACCOMMODATE LOCATION OF A TEMPORARY NIGHT FLOW METER.

14. WATERMAINS TO BE LOCATED IN GRASS VERGE . IF GRASS VERGE IS NOT AVAILABLE, WATERMAINS TO BE LOCATED UNDER FOOTPATH AWAY FROM KERB. REFER TO STD-W-11 FOR TYPICAL UTILITY LAYOUT.

TEMPORARY "DEAD END"


(FOR FUTURE EXTENSION).
REFER TO STD-W-05 FOR DETAIL.

S.V.
S.V. S.V.

H.
H.
H.

H.

A.V.

LEGEND

H. H. S.V. S.V. H. PROPOSED WATER MAIN


EXISTING WATER MAIN
S.V.
Me METER
H.
S.V. SLUICE VALVE

H. Sc.V. SCOUR VALVE


H. HYDRANT
A.V. AIR VALVE

S.V.
TELECOMMUNICATIONS

H. S.V. S.V.
STORM WATER
FOUL SEWER
WATER MAIN
ELECTRICITY
BOUNDARY

GAS MAIN
CABLE TV

H.
KERB

Sc.V.

H.

S.V. Me S.V.

S.V. S.V. S.V. S.V. H. S.V. S.V.


FOOTPATH

S.V.
GRASS VERGE BUILDING
ROAD

FOOTPATH S.V.

ROAD
SEE NOTE
1 ABOVE
H. BUILDING

JUNCTION ARRANGEMENT LAYOUT OF SERVICES IN FOOTPATH / ROAD


REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

TYPICAL LAYOUT
1 11/'17 JMC TOC Temp. "dead end" & note 1 ref. added MOD FOR WATER MAINS WITHIN DEVELOPMENTS STD-W- 02 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
GENERAL NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.


2. FOR CONNECTION TO AN EXISTING MAIN THE CONNECTION SHALL BE AS PER THE PIPE MANUFACTURER'S SPECIFICATION.
3. ELECTRO FUSION COUPLING TO BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
4. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
BOUNDARY BOX NOTES:

1. THE BOUNDARY BOX IS TO BE IN ACCORDANCE WITH THE IRISH WATER SPECIFICATION, INCORPORATING A G1.5
MANIFOLD, STOP-TAP, FROST PLUG & NON-RETURN VALVE.
2. THE BOUNDARY BOX SHALL BE POSITIONED IN PUBLIC SPACE & AS CLOSE AS POSSBILE TO THE PROPERTY BOUNDARY
BUT NO PART OR FITTING TO BE WITHIN 225mm OF THE PROPERTY LINE.
3. THE BOUNDARY BOX SHALL BE LOCATED WHERE IT IS SAFE TO OPEN THE COVER & ACCESS THE STOP TAP OR VISUALLY
READ THE METER, i.e. ON A FOOTPATH OR VERGE, & NOT IN A CARRIAGEWAY.
4. THE SURFACE BOX COVER ON THE BOUNDARY BOX SHOULD BE NOT LESS THAN GRADE C (BS 5834:2-2011); & THE
BOUNDARY BOX SHOULD BE LOCATED SUCH THAT HEAVIER GRADES OF COVER WOULD NOT BE REQUIRED.
5. THE SHAFT OF THE BOUNDARY BOX IS TO BE INSTALLED VERTICALLY, & THE SURFACE BOX/COVER INCLINED TO MATCH
THE SURFACE GRADIENT.
6. THE BOUNDARY BOX IS TO BE INSTALLED AT A MINIMUM DEPTH OF 600mm (+/- 25mm) TO THE CROWN OF THE INLET &
OUTLET FITTINGS ON THE OUTSIDE OF THE BOX.
7. THE SERVICE CONNECTION PIPE SHALL NOT BE WRAPPED AROUND THE SHAFT OF THE BOUNDARY BOX OR BENT IN ANY
RADIUS LESS THAN THAT APPROVED BY THE MANUFACTURER. CUSTOMER
8. THE PIPE FITTINGS TO THE BOUNDARY BOX SHALL BE APPROVED BY THE BOUNDARY BOX MANUFACTURER. PROPERTY
9. THE BOUNDARY BOX SHALL BE INSTALLED HYGIENICALLY & LEFT CLEAN & FREE OF CONSTRUCTION WASTE OR DIRT FOR
LATER METER INSTALLATION BY IRISH WATER. PROPERTY
10. BOX TO BE FOUNDED ON 100mm DEPTH OF C12/15 CONCRETE AND SURROUNDED WITH CLAUSE 808 GRANULAR MATERIAL. BOUNDARY
11. THE DESIRABLE MINIMUM COVER FROM THE FINISHED GROUND LEVEL TO THE EXTERNAL CROWN OF A SERVICE
CONNECTION SHALL BE 750mm WITH AN ABSOLUTE MINIMUM DEPTH OF 600mm FOR SHORT DISTANCES (SUBJECT TO IRISH
WATER AGREEMENT). THE DESIRABLE MAXIMUM COVER FOR A SERVICE CONNECTION PIPE SHOULD BE 1200mm, WHERE SEE NOTE
PRACTICABLE. 6 ABOVE 225mm
IRISH WATER
12. CUSTOMER'S DISTRIBUTION PIPEWORK WITHIN THE PREMISES SHOULD BE SUITABLY SIZED TO ACCOMMODATE FLOW APPROVED
FROM 20mm INTERNAL DIAMETER SERVICE PIPE. BOUNDARY BOX
MARKER TAPE

ROAD

350 mm
WELL

100 mm
COMPACTED
CLAUSE 808
GRANULAR
BACKFILL
REFER TO NOTE 3
STD-W-13
FOR BACKFILL DETAILS
THIS DETAIL APPLIES TO WHERE
THE FINISHED SURFACE IS EITHER
UNBOUND (GRASS VERGE), BRICK TO SUIT SURFACE FINISH OF CUSTOMER
PAVING OR MACADAM, & WHERE A SURROUNDING AREA DISTRIBUTION SYSTEM
CONCRETE PLINTH IS REQUIRED 475mm
TO SUPPORT THE TOP OF THE (APPROX.) 25mm (O.D.)
BOUNDARY BOX. FITTINGS TO BE APPROVED BY
PE PIPE BOUNDARY BOX MANUFACTURER

ELECTROFUSION SEE NOTE


TRANSITION COUPLER 10 ABOVE
(APPROX.)
475 mm

COVER
WATER MAIN
PRECAST CONCRETE
SURROUND
REFER TO NOTE 5
STD-W-13
FOR BEDDING DETAILS

PLAN SECTION
CONCRETE SURROUND
TO BOUNDARY BOX COVER
CUSTOMER
THE CONNECTION PIPE IS TO THE CONNECTION PIPE IS TO PROPERTY
BE LAID SLACK WITH NO KINKS BE LAID SLACK WITH NO KINKS
TO MANUFACTURER'S TO MANUFACTURER'S
SPECIFICATION. SPECIFICATION.

PLACE BOUNDARY BOX IN


FOOTPATH OR GRASS VERGE
AS CLOSE AS POSSIBLE TO
PROPERTY BOUNDARY
BUT NOT WITHIN 225mm 225mm
PROPOSED SADDLES
& FERRULES SHALL ELECTROFUSION
BE MADE FROM TRANSITION
NON-FERROUS COUPLER
MATERIAL IN
ACCORDANCE WITH
WIS 4-22-02 AND ELECTROFUSION
SHALL BE SUITABLE TAPPING TEE
FOR USE ON AC, CI, (25 mm OUTLET) - FOR CUSTOMER
HDPE, PVC & DI PE WATER MAIN ONLY
COUPLER DISTRIBUTION
PIPEWORK. SADDLE
SYSTEM
BOLTS SHALL BE
STAINLESS STEEL. POYLETHYLENE
(PE) WATER MAIN IRISH WATER
APPROVED
BOUNDARY BOX PROPERTY
BOUNDARY
25mm (O.D.) PE
PIPE

THE CONNECTION PIPE IS TO BE LAID SLACK WITH


NO KINKS TO MANUFACTURER'S SPECIFICATION.

PLAN
FOR D.I. FOR POLYETHYLENE ( PE )
WATER MAINS WATER MAIN ONLY
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
3 11/'17 JMC TOC Updated & added notes MOD TITLE DRAWING No. REV
2 08/'16 JMC TOC Revised D.I. service MOD CUSTOMER CONNECTION AND BOUNDARY BOX
tapping detail
1 04/'16 JMC TOC Added dimensions & notes MOD (25mm OD PIPE) STD-W- 03 3
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
REFER TO 1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED
NOTE 10 NEW FLANGED THRUST FLANGE (THRUST
STUB FLANGE OTHERWISE.
PLAIN ENDED BLOCK OMITTED FOR
( WITH BACKING RING )
DI PIPE CLARITY, SEE STD-W-28)
2. ALL BENDS, TEES, DEAD ENDS, ETC. OF PIPELINES TO BE
NEW PE PIPE ADEQUATELY RESTRAINED BY THRUST BLOCKS AS PER DRAWING
FLOW No. STD-W-28. THRUST BLOCKS NOT SHOWN FOR CLARITY.

3. BUTT FUSION WELDING AND ELECTRO FUSION JOINTING OF PIPES


SHALL ONLY BE CARRIED OUT BY TRAINED OPERATIVES IN
FUSION EXISTING AC / CI / uPVC PIPE POSSESSION OF A CURRENT TRAINING CERTIFICATE, USING
WELD SV DISMANTLING STEPPED OR FULLY AUTOMATIC APPROVED JOINTING MACHINE/RIGS IN
JOINT FLEXIBLE COUPLING ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. THE
IDENTITY OF THE PE PIPELINE MANUFACTURER SHALL BE MADE
NEW PE - EXISTING AC / CI / uPVC ( SAME SIZE AS NEW ) KNOWN TO IRISH WATER PRIOR TO COMMENCEMENT OF THE
INSTALLATION. CERTIFICATION AND TESTING (INCLUDING
INDEPENDENT THIRD PARTY CERTIFICATION) SHALL BE PROVIDED
REFER TO THRUST FLANGE (THRUST
STUB FLANGE CONCENTRIC TO CONFIRM QUALITY ASSURANCE COMPLIANCE. EACH JOINT
NOTE 10 NEW FLANGED BLOCK OMITTED FOR
( WITH BACKING RING ) TAPER SHALL BE CLEARLY MARKED WITH THE JOINT LOGGED
PLAIN ENDED CLARITY, SEE STD-W-28)
(IF REQUIRED) AUTOMATICALLY ON THE JOINTING MACHINE. A PRINTOUT OF THE
DI PIPE
NEW PE PIPE JOINT DETAILS, WITH A GPS LOCATION OF EACH JOINT, SHALL BE
EXISTING AC / CI / uPVC PIPE
PROVIDED AND RETAINED FOR QUALITY ASSURANCE PURPOSES.
FLOW
4. CONNECTING TO EXISTING MAINS IS TO BE CARRIED OUT BY IRISH
WATER OR AN APPROVED IRISH WATER AGENT.

5. WHEN EXISTING AC WATERMAINS ARE PRESENT A SPECIFIC


FUSION
SV DISMANTLING STEPPED OR METHOD STATEMENT SHALL BE SUBMITTED TO IRISH WATER PRIOR
WELD
JOINT FLEXIBLE COUPLING TO WORKS TAKING PLACE AND SUBJECT TO WRITTEN APPROVAL,
DETAILING THE PROTECTION TO BE PUT IN PLACE TO EXISTING
NEW PE - EXISTING AC / CI / uPVC ( DIFFERENT SIZE TO NEW ) MAINS, METHOD OF REMOVAL OF EXISTING AC, METHOD OF
DISPOSAL OF EXISTING AC AND METHOD OF CONNECTION TO
EXISTING AC.
REFER TO THRUST FLANGE (THRUST
NOTE 10 NEW FLANGED 6. PIPE MATERIAL REFERENCES AS FOLLOWS:
BLOCK OMITTED FOR
STUB FLANGE PLAIN ENDED AC - ASBESTOS CEMENT
CLARITY, SEE STD-W-28)
( WITH BACKING RING ) DI PIPE DI - DUCTILE IRON
CI - CAST IRON
EXISTING DI PIPE
NEW PE PIPE PE - POLYETHYLENE
FLOW uPVC - UNPLASTICISED POLY VINYL CHLORIDE
ST - STEEL
OTHER - REFERS TO ALL EXISTING PIPE MATERIALS OTHER THAN PE
(TYPICALL AC, DI, CI, uPVC & ST).
FUSION
WELD DISMANTLING SV CONCENTRIC LONG BODY
JOINT TAPER (IF REQUIRED) FLEXIBLE 7. SLUICE VALVE CHAMBERS TO BE IN ACCORDANCE WITH STD-W-14
COUPLING PUDDLE FLANGE (THRUST (DI) AND STD-W-15 (PE). CHAMBERS NOT SHOWN FOR CLARITY.

NEW PE - EXISTING DI BLOCK OMITTED FOR


CLARITY, SEE STD-W-28)
8. ALL THRUST FLANGES TO BE ADEQUATELY RESTRAINED BY
THRUST BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS
NOT SHOWN FOR CLARITY.
REFER TO
NOTE 10 CONCENTRIC 9. A HIGH LEVEL OF HEALTH & SAFETY PROCEDURES IS REQUIRED
NEW FLANGED PLAIN TAPER (IF NEW FLANGED PLAIN WHEN WORKING ON AC MAINS, & THE OPERATION OF DISMANTLING/
ENDED DI PIPE REQUIRED) ENDED DI PIPE REMOVAL OF AC PIPES & JOINTS.
EXISTING AC / CI / uPVC PIPE
NEW DI PIPE 10. VALVES SHALL BE ARRANGED IN SUCH A MANNER TO ALLOW FOR
FLOW THE NETWORK TO BE MANAGED TO ENSURE THAT NO MORE THAN
40 PROPERTIES LOSE WATER FROM A BURST ON THE SYSTEM AT
ANY ONE TIME.

LONG BODY
FLEXIBLE COUPLING DISMANTLING SV
STEPPED OR
JOINT FLEXIBLE COUPLING
THRUST FLANGE (THRUST
BLOCK OMITTED FOR NEW DI - EXISTING AC / CI / uPVC
CLARITY, SEE STD-W-28)

REFER TO
NOTE 10
NEW FLANGED PLAIN NEW FLANGED PLAIN
ENDED DI PIPE ENDED DI PIPE
NEW DI PIPE
EXISTING DI PIPE
FLOW

SV LONG BODY
LONG BODY CONCENTRIC DISMANTLING
FLEXIBLE
FLEXIBLE TAPER JOINT
COUPLING
COUPLING (IF REQUIRED)
THRUST FLANGE (THRUST
NEW DI - EXISTING DI BLOCK OMITTED FOR
CLARITY, SEE STD-W-28)

REFER TO
STUB FLANGE CONCENTRIC NOTE 10 STUB FLANGE
(WITH BACKING RING) TAPER (WITH BACKING RING)
DISMANTLING
(IF REQUIRED)
JOINT
NEW PE PIPE
EXISTING PE PIPE

FUSION FUSION
SV WELD
WELD

NEW PE - EXISTING PE
REFER TO CONCENTRIC
NEW FLANGED PLAIN NOTE 10 TAPER STUB FLANGE
ENDED DI PIPE (IF REQUIRED) (WITH BACKING RING)

NEW DI PIPE

LONG BODY FUSION EXISTING PE PIPE


DISMANTLING SV WELD
FLEXIBLE
COUPLING JOINT
THRUST FLANGE (THRUST
BLOCK OMITTED FOR NEW DI - EXISTING PE
CLARITY, SEE STD-W-28)

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
Added 2 No. Extg. PE Details,
3 11/'17 JMC TOC MOD TITLE DRAWING No. REV
updated details & added notes
2 08/'16 JMC TOC Added Note 9 MOD GENERAL PIPE CONNECTIONS
1 04/'16 JMC TOC Added couplings (2 details) MOD (Sheet 1 of 7) STD-W- 04 3
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.

NEW PE PIPE
NEW DI PIPE
2. ALL BENDS, TEES, DEAD ENDS, ETC. OF PIPELINES TO BE ADEQUATELY
RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28.
THRUST BLOCKS NOT SHOWN FOR CLARITY.

3. BUTT FUSION WELDING AND ELECTRO FUSION JOINTING OF PIPES


FUSION WELD SHALL ONLY BE CARRIED OUT BY TRAINED OPERATIVES IN POSSESSION
LONG BODY STUB FLANGE OF A CURRENT TRAINING CERTIFICATE, USING FULLY AUTOMATIC
FLANGE ( WITH BACKING RING ) APPROVED JOINTING MACHINE/RIGS IN ACCORDANCE WITH THE
ADAPTOR MANUFACTURER'S INSTRUCTIONS. THE IDENTITY OF THE PE PIPELINE
MANUFACTURER SHALL BE MADE KNOWN TO IRISH WATER PRIOR TO
CONCENTRIC TAPER COMMENCEMENT OF THE INSTALLATION. CERTIFICATION AND TESTING
(IF REQUIRED) (INCLUDING INDEPENDENT THIRD PARTY CERTIFICATION) SHALL BE
PROVIDED TO CONFIRM QUALITY ASSURANCE COMPLIANCE. EACH
JOINT SHALL BE CLEARLY MARKED WITH THE JOINT LOGGED
SV AUTOMATICALLY ON THE JOINTING MACHINE. A PRINTOUT OF THE JOINT
DETAILS, WITH A GPS LOCATION OF EACH JOINT, SHALL BE PROVIDED
AND RETAINED FOR QUALITY ASSURANCE PURPOSES.
DISMANTLING
JOINT 4. CONNECTING TO EXISTING MAINS IS TO BE CARRIED OUT BY IRISH
WATER OR AN APPROVED IRISH WATER AGENT.
DOUBLE FLANGED
PIPE (TO SUIT VALVE NEW FLANGED PLAIN 5. WHEN EXISTING AC WATERMAINS ARE PRESENT A SPECIFIC METHOD
NEW FLANGED PLAIN CHAMBER STATEMENT SHALL BE SUBMITTED TO IRISH WATER PRIOR TO WORKS
EXISTING ENDED DI PIPE c/w
ENDED DI PIPE c/w ARRANGEMENT) EXISTING
AC / CI / THRUST FLANGE TAKING PLACE AND SUBJECT TO WRITTEN APPROVAL, DETAILING THE
THRUST FLANGE AC / CI /
uPVC PIPE PROTECTION TO BE PUT IN PLACE TO EXISTING MAINS, METHOD OF
uPVC PIPE
REMOVAL OF EXISTING AC, METHOD OF DISPOSAL OF EXISTING AC AND
METHOD OF CONNECTION TO EXISTING AC.

6. PIPE MATERIAL REFERENCES AS FOLLOWS:


ALL AC - ASBESTOS CEMENT
SV FLANGED SV DI - DUCTILE IRON
STEPPED OR DISMANTLING TEE DISMANTLING STEPPED OR
DOUBLE FLANGED DOUBLE FLANGED CI - CAST IRON
FLEXIBLE COUPLING JOINT JOINT FLEXIBLE COUPLING
SEPARATION PIPE SEPARATION PIPE PE - POLYETHYLENE
NEW PE / DI - EXISTING AC / CI / uPVC uPVC - UNPLASTICISED POLY VINYL CHLORIDE
ST - STEEL
OTHER - REFERS TO ALL EXISTING PIPE MATERIALS OTHER THAN PE
(TYPICALL AC, DI, CI, uPVC & ST).
NEW PE PIPE
NEW DI PIPE

7. VALVE CHAMBER TO BE IN ACCORDANCE WITH STD-W-14 (DI) AND


STD-W-15 (PE). CHAMBER NOT SHOWN FOR CLARITY.

FUSION WELD 8. ALL THRUST FLANGES TO BE ADEQUATELY RESTRAINED BY THRUST


BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN
LONG BODY STUB FLANGE FOR CLARITY.
FLANGE ( WITH BACKING RING )
ADAPTOR 9. DOUBLE FLANGED SEPARATION PIPE, UP TO 5m IN LENGTH, MAY BE
CONCENTRIC TAPER REQUIRED TO ALLOW SEPARATION DISTANCE BETWEEN VALVE
(IF REQUIRED) CHAMBERS.

10. A HIGH LEVEL OF HEALTH & SAFETY PROCEDURES IS REQUIRED WHEN


WORKING ON AC MAINS, & THE OPERATION OF DISMANTLING/ REMOVAL
SV OF AC PIPES & JOINTS.

11. VALVES SHALL BE ARRANGED IN SUCH A MANNER TO ALLOW FOR THE


DISMANTLING NETWORK TO BE MANAGED TO ENSURE THAT NO MORE THAN 40
JOINT PROPERTIES LOSE WATER FROM A BURST ON THE SYSTEM AT ANY ONE
DOUBLE FLANGED TIME.
PIPE (TO SUIT VALVE NEW FLANGED PLAIN
NEW FLANGED PLAIN CHAMBER ENDED DI PIPE c/w
ENDED DI PIPE c/w ARRANGEMENT)
EXISTING THRUST FLANGE
THRUST FLANGE EXISTING
DI PIPE DI PIPE

ALL
SV FLANGED SV
LONG BODY DISMANTLING TEE DISMANTLING LONG BODY
DOUBLE FLANGED DOUBLE FLANGED
FLEXIBLE JOINT JOINT FLEXIBLE
SEPARATION PIPE SEPARATION PIPE
COUPLING COUPLING
NEW PE / DI - EXISTING DI

DOUBLE FLANGED PE DOUBLE FLANGED


NEW PE SV SEPARATION PIPE A/F TEE SEPARATION PIPE
PIPE
NEW PE PIPE

DISMANTLING ON-LINE HYDRANT. BLANK FLANGE


JOINT REFER TO STD-W-16
FOR DETAILS.
FUSION WELD
STUB FLANGE
TEMPORARY "DEAD-END" DETAIL (FOR FUTURE EXTENSION) - PE
( WITH BACKING RING ) NEW FLANGED PLAIN DOUBLE FLANGED SEPARATION
ENDED DI PIPE c/w DOUBLE FLANGED PIPE c/w THRUST FLANGE
NEW THRUST FLANGE SV SEPARATION PIPE A/F TEE (THRUST BLOCK NOT SHOWN)
CONCENTRIC TAPER
DI PIPE
(IF REQUIRED)

SV
LONG BODY ON-LINE HYDRANT.
DISMANTLING BLANK FLANGE
FLEXIBLE REFER TO STD-W-16
JOINT
DISMANTLING COUPLING FOR DETAILS.
JOINT
DOUBLE FLANGED TEMPORARY "DEAD-END" DETAIL (FOR FUTURE EXTENSION) - DI
PIPE (TO SUIT VALVE
CHAMBER
STUB FLANGE STUB FLANGE
(WITH BACKING RING)
ARRANGEMENT) (WITH BACKING RING)
SV SV
EXISTING PE PIPE EXISTING PE PIPE

FUSION ALL FUSION


WELD FLANGED WELD
DISMANTLING TEE DISMANTLING
DOUBLE FLANGED DOUBLE FLANGED
JOINT JOINT
SEPARATION PIPE SEPARATION PIPE

NEW PE - EXISTING PE
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
Added new D.I. pipe to details, added
2 11/'17 JMC TOC
3 No. details & updated notes
MOD GENERAL PIPE CONNECTIONS
1 08/'16 JMC TOC Added Note 10 MOD (Sheet 2 of 7) STD-W- 05 2
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.

2. ALL BENDS, TEES, DEAD ENDS, ETC. OF PIPELINES TO BE ADEQUATELY


RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28.
THRUST BLOCKS NOT SHOWN FOR CLARITY.

3. BUTT FUSION WELDING AND ELECTRO FUSION JOINTING OF PIPES SHALL


ONLY BE CARRIED OUT BY TRAINED OPERATIVES IN POSSESSION OF A
CURRENT TRAINING CERTIFICATE, USING FULLY AUTOMATIC APPROVED
JOINTING MACHINE/RIGS IN ACCORDANCE WITH THE MANUFACTURER'S
INSTRUCTIONS. THE IDENTITY OF THE PE PIPELINE MANUFACTURER
SHALL BE MADE KNOWN TO IRISH WATER PRIOR TO COMMENCEMENT OF
THE INSTALLATION. CERTIFICATION AND TESTING (INCLUDING
INDEPENDENT THIRD PARTY CERTIFICATION) SHALL BE PROVIDED TO
CONFIRM QUALITY ASSURANCE COMPLIANCE. EACH JOINT SHALL BE
CLEARLY MARKED WITH THE JOINT LOGGED AUTOMATICALLY ON THE
JOINTING MACHINE. A PRINTOUT OF THE JOINT DETAILS, WITH A GPS
LOCATION OF EACH JOINT, SHALL BE PROVIDED AND RETAINED FOR
QUALITY ASSURANCE PURPOSES.

AC / CI / uPVC / DI PIPE
4. CONNECTING TO EXISTING MAINS IS TO BE CARRIED OUT BY IRISH
WATER OR AN APPROVED IRISH WATER AGENT.
EXISTING PE PIPE

5. WHEN EXISTING AC WATERMAINS ARE PRESENT A SPECIFIC METHOD


STATEMENT SHALL BE SUBMITTED TO IRISH WATER PRIOR TO WORKS
TAKING PLACE AND SUBJECT TO WRITTEN APPROVAL, DETAILING THE

EXISTING
PROTECTION TO BE PUT IN PLACE TO EXISTING MAINS, METHOD OF
REMOVAL OF EXISTING AC, METHOD OF DISPOSAL OF EXISTING AC AND
METHOD OF CONNECTION TO EXISTING AC.

STEPPED OR 6. PIPE MATERIAL REFERENCES AS FOLLOWS:


FLEXIBLE AC - ASBESTOS CEMENT
DI - DUCTILE IRON
NEW DI PIPE

COUPLING
CI - CAST IRON
PE - POLYETHYLENE
PE STUB FLANGE FUSION
uPVC - UNPLASTICISED POLY VINYL CHLORIDE
(WITH BACKING RING) WELD ST - STEEL
LONG BODY
OTHER - REFERS TO ALL EXISTING PIPE MATERIALS OTHER THAN PE
FLANGE
(TYPICALLY AC, DI, CI, uPVC & ST)
ADAPTOR
7. SLUICE VALVE CHAMBERS TO BE IN ACCORDANCE WITH STD-W-14 (DI)
CONCENTRIC TAPER AND STD-W-15 (PE). CHAMBERS NOT SHOWN FOR CLARITY.
(IF REQUIRED)
8. ALL THRUST FLANGES TO BE ADEQUATELY RESTRAINED BY THRUST
BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN
SV FOR CLARITY.

9. DOUBLE FLANGED SEPARATION PIPE, UP TO 5m IN LENGTH, MAY BE


DISMANTLING REQUIRED TO ALLOW SEPARATION DISTANCE BETWEEN VALVE
JOINT CHAMBERS.

DOUBLE FLANGED PIPE STUB FLANGE 10. A HIGH LEVEL OF HEALTH & SAFETY PROCEDURES IS REQUIRED WHEN
STUB FLANGE (TO SUIT VALVE CHAMBER ( WITH BACKING WORKING ON AC MAINS, & THE OPERATION OF DISMANTLING/ REMOVAL
( WITH BACKING ARRANGEMENT) RING ) OF AC PIPES & JOINTS.
RING )
11. VALVES SHALL BE ARRANGED IN SUCH A MANNER TO ALLOW FOR
NEW PE PIPE NEW PE PIPE
NETWORK TO BE MANAGED TO ENSURE THAT NO MORE THAN 40
PROPERTIES LOSE WATER FROM A BURST ON THE SYSTEM AT ANY ONE
TIME.
ALL
FUSION FUSION
SV FLANGED SV
WELD DISMANTLING WELD
DISMANTLING DOUBLE FLANGED TEE DOUBLE FLANGED
JOINT SEPARATION PIPE SEPARATION PIPE JOINT

NEW PE - EXISTING AC / CI / uPVC / DI / PE


AC / CI / uPVC
EXISTING

EXISTING

/ DI PIPE
PE PIPE

STEPPED OR
FLEXIBLE
COUPLING
NEW DI PIPE

PE STUB FLANGE FUSION


(WITH BACKING RING) WELD LONG BODY
FLANGE
ADAPTOR

CONCENTRIC TAPER
(IF REQUIRED)

SV

DISMANTLING
JOINT DOUBLE
FLANGED PIPE
(TO SUIT VALVE
NEW FLANGED PLAIN NEW FLANGED PLAIN
CHAMBER
ENDED DI PIPE c/w ENDED DI PIPE c/w
ARRANGEMENT)
THRUST FLANGE THRUST FLANGE
NEW DI PIPE NEW DI PIPE

ALL
FLANGED
LONG BODY DISMANTLING SV SV DISMANTLING LONG BODY
DOUBLE FLANGED TEE DOUBLE FLANGED
FLEXIBLE JOINT JOINT FLEXIBLE
COUPLING SEPARATION PIPE SEPARATION PIPE COUPLING

NEW DI - EXISTING AC / CI / uPVC / DI / PE

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
Added extg. PE pipe to details
2 11/'17 JMC TOC
& updated notes
MOD GENERAL PIPE CONNECTIONS
1 08/'16 JMC TOC Added Note 10 MOD (Sheet 3 of 7) STD-W- 06 2
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.

2. ALL BENDS, TEES, DEAD ENDS, ETC. OF PIPELINES TO BE ADEQUATELY


RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28.
THRUST BLOCKS NOT SHOWN FOR CLARITY.

3. BUTT FUSION WELDING AND ELECTRO FUSION JOINTING OF PIPES SHALL


ONLY BE CARRIED OUT BY TRAINED OPERATIVES IN POSSESSION OF A
CURRENT TRAINING CERTIFICATE, USING FULLY AUTOMATIC APPROVED
JOINTING MACHINE/RIGS IN ACCORDANCE WITH THE MANUFACTURER'S
INSTRUCTIONS. THE IDENTITY OF THE PE PIPELINE MANUFACTURER
SHALL BE MADE KNOWN TO IRISH WATER PRIOR TO COMMENCEMENT OF
THE INSTALLATION. CERTIFICATION AND TESTING (INCLUDING
INDEPENDENT THIRD PARTY CERTIFICATION) SHALL BE PROVIDED TO
CONFIRM QUALITY ASSURANCE COMPLIANCE. EACH JOINT SHALL BE
CLEARLY MARKED WITH THE JOINT LOGGED AUTOMATICALLY ON THE
JOINTING MACHINE. A PRINTOUT OF THE JOINT DETAILS, WITH A GPS
LOCATION OF EACH JOINT, SHALL BE PROVIDED AND RETAINED FOR
QUALITY ASSURANCE PURPOSES.

4. CONNECTING TO EXISTING MAINS IS TO BE CARRIED OUT BY IRISH WATER


OR AN APPROVED IRISH WATER AGENT.

NEW PE PIPE
5. WHEN EXISTING AC WATERMAINS ARE PRESENT A SPECIFIC METHOD
STATEMENT SHALL BE SUBMITTED TO IRISH WATER PRIOR TO WORKS
TAKING PLACE AND SUBJECT TO WRITTEN APPROVAL, DETAILING THE
PROTECTION TO BE PUT IN PLACE TO EXISTING MAINS, METHOD OF
REMOVAL OF EXISTING AC, METHOD OF DISPOSAL OF EXISTING AC AND
METHOD OF CONNECTION TO EXISTING AC.

6. PIPE MATERIAL REFERENCES AS FOLLOWS:


AC - ASBESTOS CEMENT
DI - DUCTILE IRON
CI - CAST IRON
FUSION WELD PE - POLYETHYLENE
STUB FLANGE uPVC - UNPLASTICISED POLY VINYL CHLORIDE
( WITH BACKING RING ) ST - STEEL
OTHER - REFERS TO ALL EXISTING PIPE MATERIALS OTHER THAN PE
(TYPICALLY AC, DI, CI, uPVC & ST)
CONCENTRIC TAPER
(IF REQUIRED)
7. SLUICE VALVE CHAMBERS TO BE IN ACCORDANCE WITH STD-W-14 (DI) AND
STD-W-15 (PE). CHAMBERS NOT SHOWN FOR CLARITY.

SV 8. ALL THRUST FLANGES TO BE ADEQUATELY RESTRAINED BY THRUST


BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN
FOR CLARITY.
DISMANTLING
JOINT 9. DOUBLE FLANGED SEPARATION PIPE, UP TO 5m IN LENGTH, MAY BE
REQUIRED TO ALLOW SEPARATION DISTANCE BETWEEN VALVE
DOUBLE FLANGED PIPE CHAMBERS.
(TO SUIT VALVE CHAMBER
ARRANGEMENT) 10. VALVES SHALL BE ARRANGED IN SUCH A MANNER TO ALLOW FOR
FUSION FUSION NETWORK TO BE MANAGED TO ENSURE THAT NO MORE THAN 40
WELD WELD PROPERTIES LOSE WATER FROM A BURST ON THE SYSTEM AT ANY ONE
TIME.

NEW PE PIPE ALL NEW PE PIPE


SV FLANGED SV
DISMANTLING DOUBLE FLANGED TEE DOUBLE FLANGED DISMANTLING
JOINT SEPARATION PIPE SEPARATION PIPE JOINT

STUB FLANGE STUB FLANGE


( WITH BACKING ( WITH BACKING
RING ) NEW PE - NEW PE RING )
NEW DI PIPE

LONG BODY
FLANGE ADAPTOR

CONCENTRIC TAPER
(IF REQUIRED)

SV

DISMANTLING
JOINT
DOUBLE
FLANGED PIPE
(TO SUIT VALVE
FLANGED PLAIN CHAMBER FLANGED PLAIN
ENDED DI PIPE c/w ARRANGEMENT) ENDED DI PIPE c/w
THRUST FLANGE THRUST FLANGE
NEW DI PIPE NEW DI PIPE

ALL
FLANGED
LONG BODY DISMANTLING SV SV DISMANTLING LONG BODY
DOUBLE FLANGED TEE DOUBLE FLANGED
FLEXIBLE JOINT JOINT FLEXIBLE
COUPLING SEPARATION PIPE SEPARATION PIPE COUPLING

NEW DI - NEW DI

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

GENERAL PIPE CONNECTIONS


1 11/'17 JMC TOC Notes added & updated. MOD (Sheet 4 of 7) STD-W- 07 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.

2. ALL BENDS, TEES, DEAD ENDS, ETC. OF PIPELINES TO BE ADEQUATELY RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN FOR CLARITY.

3. BUTT FUSION WELDING AND ELECTRO FUSION JOINTING OF PIPES SHALL ONLY BE CARRIED OUT BY TRAINED OPERATIVES IN POSSESSION OF A CURRENT TRAINING CERTIFICATE, USING FULLY AUTOMATIC APPROVED JOINTING MACHINE/RIGS IN
ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. THE IDENTITY OF THE PE PIPELINE MANUFACTURER SHALL BE MADE KNOWN TO IRISH WATER PRIOR TO COMMENCEMENT OF THE INSTALLATION. CERTIFICATION AND TESTING (INCLUDING
INDEPENDENT THIRD PARTY CERTIFICATION) SHALL BE PROVIDED TO CONFIRM QUALITY ASSURANCE COMPLIANCE. EACH JOINT SHALL BE CLEARLY MARKED WITH THE JOINT LOGGED AUTOMATICALLY ON THE JOINTING MACHINE. A PRINTOUT OF THE
JOINT DETAILS, WITH A GPS LOCATION OF EACH JOINT, SHALL BE PROVIDED AND RETAINED FOR QUALITY ASSURANCE PURPOSES.

4. CONNECTING TO EXISTING MAINS IS TO BE CARRIED OUT BY IRISH WATER OR AN APPROVED IRISH WATER AGENT.

5. WHEN EXISTING AC WATERMAINS ARE PRESENT A SPECIFIC METHOD STATEMENT SHALL BE SUBMITTED TO IRISH WATER PRIOR TO WORKS TAKING PLACE AND SUBJECT TO WRITTEN APPROVAL, DETAILING THE PROTECTION TO BE PUT IN PLACE TO
EXISTING MAINS, METHOD OF REMOVAL OF EXISTING AC, METHOD OF DISPOSAL OF EXISTING AC AND METHOD OF CONNECTION TO EXISTING AC.

6. PIPE MATERIAL REFERENCES AS FOLLOWS:


AC - ASBESTOS CEMENT
DI - DUCTILE IRON
CI - CAST IRON
PE - POLYETHYLENE
uPVC - UNPLASTICISED POLY VINYL CHLORIDE
ST - STEEL
OTHER - REFERS TO ALL EXISTING PIPE MATERIALS OTHER THAN PE (TYPICALLY AC, DI, CI, uPVC & ST)

7. SLUICE VALVE CHAMBERS TO BE IN ACCORDANCE WITH STD-W-14 (DI) AND STD-W-15 (PE). CHAMBERS NOT SHOWN FOR CLARITY.

8. ALL THRUST FLANGES TO BE ADEQUATELY RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN FOR CLARITY.

9. DOUBLE FLANGED SEPARATION PIPE, UP TO 5m IN LENGTH, MAY BE REQUIRED TO ALLOW SEPARATION DISTANCE BETWEEN VALVE CHAMBERS.

STUB FLANGE STUB FLANGE STUB FLANGE STUB FLANGE


(WITH BACKING (WITH BACKING (WITH BACKING (WITH BACKING
RING) DOUBLE FLANGED DOUBLE FLANGED RING) RING) DOUBLE FLANGED DOUBLE FLANGED RING)
DISMANTLING SEPARATION PIPE SEPARATION PIPE DISMANTLING DISMANTLING SEPARATION PIPE SEPARATION PIPE DISMANTLING
NEW PE JOINT (SEE NOTE 9) (SEE NOTE 9) JOINT NEW PE NEW PE JOINT (SEE NOTE 9) (SEE NOTE 9) JOINT NEW PE
PIPE PIPE PIPE PIPE

FUSION ALL FUSION FUSION ALL FUSION


WELD SV FLANGED SV WELD WELD SV FLANGED SV WELD
TEE TEE
DOUBLE FLANGED PIPE DOUBLE FLANGED PIPE
(TO SUIT VALVE CHAMBER ARRANGEMENT) (TO SUIT VALVE CHAMBER ARRANGEMENT)

DISMANTLING DISMANTLING
JOINT JOINT

SV SV

CONCENTRIC CONCENTRIC
TAPER (IF REQUIRED) TAPER (IF REQUIRED)

LONG BODY LONG BODY


FLANGE FLANGE EXISTING
STUB PIPE MATERIAL
ADAPTOR ADAPTOR
FLANGE EXISTING OTHER THAN PE
STUB ( WITH PIPE MATERIAL
FLANGE NEW FLANGE BACKING OTHER THAN PE NEW FLANGE
( WITH PLAIN ENDED PIPE RING ) PLAIN ENDED PIPE
BACKING (CUT TO SUIT) NEW FLANGED (CUT TO SUIT) NEW FLANGED
RING ) PLAIN ENDED DI PLAIN ENDED DI
ALL ALL
PIPE c/w THRUST PIPE c/w THRUST
SV FLANGED SV SV FLANGED SV
EXISTING EXISTING FLANGE FLANGE
TEE TEE
PE PIPE PE PIPE

FUSION DOUBLE FLANGED DOUBLE FLANGED


FUSION STEPPED STEPPED OR
DISMANTLING DISMANTLING WELD DISMANTLING DOUBLE FLANGED DOUBLE FLANGED DISMANTLING
WELD SEPARATION PIPE SEPARATION PIPE OR FLEXIBLE FLEXIBLE
SEPARATION PIPE SEPARATION PIPE
JOINT (SEE NOTE 9) (SEE NOTE 9) JOINT JOINT JOINT
COUPLING (SEE NOTE 9) (SEE NOTE 9) COUPLING

NEW PE - EXISTING PE NEW PE - EXISTING OTHER MATERIAL


DISMANTLING DISMANTLING DISMANTLING DISMANTLING
JOINT JOINT JOINT JOINT
LONG BODY DOUBLE FLANGED DOUBLE FLANGED LONG BODY LONG BODY DOUBLE FLANGED DOUBLE FLANGED LONG BODY
FLEXIBLE SEPARATION PIPE SEPARATION PIPE FLEXIBLE FLEXIBLE SEPARATION PIPE SEPARATION PIPE FLEXIBLE
COUPLING (SEE NOTE 9) (SEE NOTE 9) COUPLING COUPLING (SEE NOTE 9) (SEE NOTE 9) COUPLING

ALL ALL
NEW SV FLANGED SV NEW FLANGED PLAIN SV FLANGED SV FLANGED PLAIN
FLANGED DOUBLE FLANGED FLANGED DOUBLE FLANGED
TEE ENDED DI PIPE TEE ENDED DI PIPE
PLAIN ENDED PIPE (TO SUIT PLAIN ENDED PIPE (TO SUIT
DI PIPE DI PIPE c/w THRUST c/w THRUST
VALVE CHAMBER FLANGE VALVE CHAMBER FLANGE
DISMANTLING ARRANGEMENT) DISMANTLING ARRANGEMENT)
NEW DI PIPE JOINT NEW DI PIPE NEW DI JOINT NEW DI
PIPE PIPE

SV SV

CONCENTRIC CONCENTRIC
TAPER (IF REQUIRED) TAPER (IF REQUIRED)
LONG BODY LONG BODY
FLANGE FLANGE EXISTING
ADAPTOR STUB PIPE MATERIAL
ADAPTOR
FLANGE OTHER THAN PE
EXISTING
STUB ( WITH
PIPE MATERIAL
FLANGE NEW FLANGE BACKING NEW FLANGE
OTHER THAN PE
( WITH PLAIN ENDED PIPE RING ) PLAIN ENDED PIPE
BACKING (CUT TO SUIT) NEW FLANGED (CUT TO SUIT) NEW FLANGED
RING ) ALL PLAIN ENDED DI ALL PLAIN ENDED DI
FLANGED PIPE c/w THRUST FLANGED PIPE c/w THRUST
EXISTING SV SV EXISTING FLANGE SV SV FLANGE
TEE TEE
PE PIPE PE PIPE

FUSION FUSION
DOUBLE FLANGED DOUBLE FLANGED STEPPED OR DISMANTLING DOUBLE FLANGED DOUBLE FLANGED DISMANTLING STEPPED OR
WELD DISMANTLING SEPARATION PIPE SEPARATION PIPE
DISMANTLING WELD
SEPARATION PIPE SEPARATION PIPE
JOINT JOINT FLEXIBLE JOINT JOINT FLEXIBLE
(SEE NOTE 9) (SEE NOTE 9) (SEE NOTE 9) (SEE NOTE 9)
COUPLING COUPLING

NEW DI - EXISTING PE NEW DI - EXISTING OTHER MATERIAL


REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

GENERAL PIPE CONNECTIONS


1 11/'17 JMC TOC Notes added & updated. MOD (Sheet 5 of 7) STD-W- 08 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.

2. ALL BENDS, TEES, DEAD ENDS, ETC. OF PIPELINES TO BE ADEQUATELY RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN FOR CLARITY.

3. BUTT FUSION WELDING AND ELECTRO FUSION JOINTING OF PIPES SHALL ONLY BE CARRIED OUT BY TRAINED OPERATIVES IN POSSESSION OF A CURRENT TRAINING CERTIFICATE, USING FULLY AUTOMATIC APPROVED JOINTING MACHINE/RIGS IN
ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. THE IDENTITY OF THE PE PIPELINE MANUFACTURER SHALL BE MADE KNOWN TO IRISH WATER PRIOR TO COMMENCEMENT OF THE INSTALLATION. CERTIFICATION AND TESTING (INCLUDING
INDEPENDENT THIRD PARTY CERTIFICATION) SHALL BE PROVIDED TO CONFIRM QUALITY ASSURANCE COMPLIANCE. EACH JOINT SHALL BE CLEARLY MARKED WITH THE JOINT LOGGED AUTOMATICALLY ON THE JOINTING MACHINE. A PRINTOUT OF THE
JOINT DETAILS, WITH A GPS LOCATION OF EACH JOINT, SHALL BE PROVIDED AND RETAINED FOR QUALITY ASSURANCE PURPOSES.

4. CONNECTING TO EXISTING MAINS IS TO BE CARRIED OUT BY IRISH WATER OR AN APPROVED IRISH WATER AGENT.

5. WHEN EXISTING AC WATERMAINS ARE PRESENT A SPECIFIC METHOD STATEMENT SHALL BE SUBMITTED TO IRISH WATER PRIOR TO WORKS TAKING PLACE AND SUBJECT TO WRITTEN APPROVAL, DETAILING THE PROTECTION TO BE PUT IN PLACE TO
EXISTING MAINS, METHOD OF REMOVAL OF EXISTING AC, METHOD OF DISPOSAL OF EXISTING AC AND METHOD OF CONNECTION TO EXISTING AC.

6. PIPE MATERIAL REFERENCES AS FOLLOWS:


AC - ASBESTOS CEMENT
DI - DUCTILE IRON
CI - CAST IRON
PE - POLYETHYLENE
uPVC - UNPLASTICISED POLY VINYL CHLORIDE
ST - STEEL
OTHER - REFERS TO ALL EXISTING PIPE MATERIALS OTHER THAN PE (TYPICALLY AC, DI, CI, uPVC & ST)

7. SLUICE VALVE CHAMBERS TO BE IN ACCORDANCE WITH STD-W-14 (DI) AND STD-W-15 (PE). CHAMBERS NOT SHOWN FOR CLARITY.

8. ALL THRUST FLANGES TO BE ADEQUATELY RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN FOR CLARITY.

9. DOUBLE FLANGED SEPARATION PIPE, UP TO 5m IN LENGTH, MAY BE REQUIRED TO ALLOW SEPARATION DISTANCE BETWEEN VALVE CHAMBERS.

STUB FLANGE STUB FLANGE


( WITH BACKING RING ) ( WITH BACKING RING )

DOUBLE DOUBLE
FLANGED FLANGED
SEPARATION SEPARATION
NEW PE PIPE (SEE PIPE (SEE
NEW PE
PIPE SV NOTE 9) ALL FLANGED NOTE 9) SV
TEE PIPE

FUSION FUSION
WELD DISMANTLING DISMANTLING WELD
JOINT CONCENTRIC JOINT
TAPER (IF REQUIRED)

STUB FLANGE( WITH BACKING RING ) DOUBLE DOUBLE


EXISTING PE FLANGED FLANGED
PIPE FUSION WELD SEPARATION SEPARATION
NEW PE PIPE PIPE
(SEE NOTE 9) (SEE NOTE 9)
PIPE
STEPPED OR STEPPED OR
PE BEND EXISTING FLEXIBLE DISMANTLING ALL DISMANTLING FLEXIBLE
(IF REQUIRED) PIPE MATERIAL COUPLING JOINT FLANGED JOINT COUPLING
FUSION WELD
OTHER THAN PE TEE
STUB FLANGE ( WITH BACKING RING )
NEW PE
DISMANTLING PIPE
JOINT
PE BEND
NEW FLANGED SV SV NEW FLANGED
DOUBLE FLANGED PIPE (IF REQUIRED)
SV PLAIN ENDED DI PLAIN ENDED DI
DOUBLE (TO SUIT VALVE CHAMBER PIPE c/w THRUST PIPE c/w THRUST
FLANGED ARRANGEMENT) FLANGE FLANGE
SEPARATION NEW PE PIPE
STUB FLANGE( WITH BACKING RING )
PIPE (SEE
NOTE 9) SV NEW NEW PE FUSION WELD EXISTING
PE PIPE PIPE PIPE MATERIAL
ALL NEW PE
OTHER THAN PE
FLANGED PIPE
90° PE
TEE BEND PE BEND
DOUBLE FUSION (IF REQUIRED)
DISMANTLING STUB FLANGE
FLANGED WELD (WITH BACKING RING)
JOINT
SEPARATION NEW PE
FUSION DISMANTLING
PIPE (SEE PIPE
WELD JOINT
NOTE 9)
PE BEND
SV STUB FLANGE
SV (IF REQUIRED)
( WITH BACKING RING ) DOUBLE FLANGED PIPE
DISMANTLING DOUBLE (TO SUIT VALVE CHAMBER
JOINT FLANGED ARRANGEMENT)
STUB FLANGE SEPARATION NEW PE
( WITH BACKING RING ) PIPE (SEE PIPE
FUSION NOTE 9) SV NEW
WELD PE PIPE
ALL
EXISTING PE FLANGED 90° PE
PIPE TEE BEND
DOUBLE DISMANTLING
FLANGED JOINT
SEPARATION FUSION
NEW PE - EXISTING PE PIPE (SEE
NOTE 9)
WELD
SV STUB FLANGE
( WITH BACKING RING )
DISMANTLING
JOINT
STUB FLANGE
(WITH BACKING RING)
FUSION
WELD

NEW PE
PIPE

NEW PE - EXISTING OTHER MATERIAL

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

GENERAL PIPE CONNECTIONS


1 11/'17 JMC TOC Notes added & updated MOD (Sheet 6 of 7) STD-W- 09 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.

2. ALL BENDS, TEES, DEAD ENDS, ETC. OF PIPELINES TO BE ADEQUATELY RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN FOR CLARITY.

3. BUTT FUSION WELDING AND ELECTRO FUSION JOINTING OF PIPES SHALL ONLY BE CARRIED OUT BY TRAINED OPERATIVES IN POSSESSION OF A CURRENT TRAINING CERTIFICATE, USING FULLY AUTOMATIC APPROVED JOINTING MACHINE/RIGS IN
ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. THE IDENTITY OF THE PE PIPELINE MANUFACTURER SHALL BE MADE KNOWN TO IRISH WATER PRIOR TO COMMENCEMENT OF THE INSTALLATION. CERTIFICATION AND TESTING (INCLUDING
INDEPENDENT THIRD PARTY CERTIFICATION) SHALL BE PROVIDED TO CONFIRM QUALITY ASSURANCE COMPLIANCE. EACH JOINT SHALL BE CLEARLY MARKED WITH THE JOINT LOGGED AUTOMATICALLY ON THE JOINTING MACHINE. A PRINTOUT OF THE
JOINT DETAILS, WITH A GPS LOCATION OF EACH JOINT, SHALL BE PROVIDED AND RETAINED FOR QUALITY ASSURANCE PURPOSES.

4. CONNECTING TO EXISTING MAINS IS TO BE CARRIED OUT BY IRISH WATER OR AN APPROVED IRISH WATER AGENT.

5. WHEN EXISTING AC WATERMAINS ARE PRESENT A SPECIFIC METHOD STATEMENT SHALL BE SUBMITTED TO IRISH WATER PRIOR TO WORKS TAKING PLACE AND SUBJECT TO WRITTEN APPROVAL, DETAILING THE PROTECTION TO BE PUT IN PLACE TO
EXISTING MAINS, METHOD OF REMOVAL OF EXISTING AC, METHOD OF DISPOSAL OF EXISTING AC AND METHOD OF CONNECTION TO EXISTING AC.

6. PIPE MATERIAL REFERENCES AS FOLLOWS:


AC - ASBESTOS CEMENT
DI - DUCTILE IRON
CI - CAST IRON
PE - POLYETHYLENE
uPVC - UNPLASTICISED POLY VINYL CHLORIDE
ST - STEEL
OTHER - REFERS TO ALL EXISTING PIPE MATERIALS OTHER THAN PE (TYPICALLY AC, DI, CI, uPVC & ST)

7. SLUICE VALVE CHAMBERS TO BE IN ACCORDANCE WITH STD-W-14 (DI) AND STD-W-15 (PE). CHAMBERS NOT SHOWN FOR CLARITY.

8. ALL THRUST FLANGES TO BE ADEQUATELY RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN FOR CLARITY.

9. DOUBLE FLANGED SEPARATION PIPE, UP TO 5m IN LENGTH, MAY BE REQUIRED TO ALLOW SEPARATION DISTANCE BETWEEN VALVE CHAMBERS.

STUB FLANGE STUB FLANGE


( WITH BACKING RING ) ( WITH BACKING RING )

DOUBLE DOUBLE
FLANGED FLANGED
SEPARATION SEPARATION
PIPE (SEE ALL PIPE (SEE
EXISTING PE SV NOTE 9) FLANGED NOTE 9) SV EXISTING PE
PIPE TEE PIPE

FUSION FUSION
WELD DISMANTLING DISMANTLING WELD
JOINT CONCENTRIC JOINT
TAPER (IF REQUIRED)
LONG BODY
FLANGE ADAPTOR
NEW DI PIPE DOUBLE DOUBLE
NEW DI PIPE FLANGED FLANGED
LONG BODY SEPARATION SEPARATION
PIPE PIPE
FLEXIBLE SOCKETED BEND (SEE NOTE 9) (SEE NOTE 9)
JOINT FLANGED (IF REQUIRED)
STEPPED OR
PLAIN ENDED EXISTING FLEXIBLE
DISMANTLING ALL DISMANTLING STEPPED OR
DI PIPE JOINT FLEXIBLE
PIPE MATERIAL COUPLING FLANGED JOINT
COUPLING
NEW DI PIPE OTHER THAN PE TEE
DISMANTLING
JOINT
SOCKETED BEND
SV (IF REQUIRED)
DOUBLE NEW FLANGED SV SV NEW FLANGED
FLANGED PLAIN ENDED DI PLAIN ENDED DI
NEW DI PIPE PIPE c/w THRUST CONCENTRIC PIPE c/w THRUST
SEPARATION FLANGE TAPER (IF FLANGE
DISMANTLING
PIPE (SEE REQUIRED)
JOINT LONG BODY
NOTE 9)
FLANGE ADAPTOR
ALL EXISTING
NEW DI PIPE
FLANGED NEW DI PIPE PIPE MATERIAL
90° ALL
TEE LONG BODY OTHER THAN PE
FLANGED
DOUBLE SV BEND FLEXIBLE SOCKETED BEND
FLANGED JOINT FLANGED (IF REQUIRED)
SEPARATION PLAIN ENDED
PIPE (SEE DOUBLE FLANGED PIPE DI PIPE
NOTE 9) (TO SUIT VALVE CHAMBER NEW DI PIPE
ARRANGEMENT) DISMANTLING
SV JOINT
SOCKETED BEND
DISMANTLING SV (IF REQUIRED)
JOINT DOUBLE
FLANGED FLANGED
PLAIN ENDED SEPARATION NEW DI PIPE
DISMANTLING
DI PIPE PIPE (SEE
JOINT
NOTE 9)
LONG BODY
FLEXIBLE ALL
JOINT FLANGED
NEW DI PIPE 90° ALL
TEE
FLANGED
SV BEND
DOUBLE
FLANGED
SEPARATION
NEW DI - EXISTING PE PIPE (SEE
DOUBLE FLANGED PIPE
(TO SUIT VALVE CHAMBER
NOTE 9)
SV ARRANGEMENT)

DISMANTLING
JOINT
FLANGED
PLAIN ENDED
DI PIPE
LONG BODY
FLEXIBLE
JOINT
NEW DI PIPE

NEW DI - EXISTING OTHER MATERIAL

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

GENERAL PIPE CONNECTIONS


1 11/'17 JMC TOC Notes added & updated MOD (Sheet 7 of 7) STD-W- 10 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. THE SEPARATION DISTANCES OUTLINED ARE MINIMUM REQUIREMENTS.
2. SPECIFIC SEPARATION CLEARANCE DISTANCES IN EXCESS OF THESE MINIMA SHALL BE PROVIDED FOR
SERVICES SUCH AS GAS, ELECTRICITY, FIBRE-OPTIC OR OIL FILLED CABLES AS THE CASE MAY BE.
THE PARTICULAR UTILITY PROVIDERS SHALL BE CONSULTED TO DETERMINE THESE MINIMUM SEPARATION
DISTANCES AND EVIDENCE OF THIS CONSULTATION, WITH THE SPECIFIED SEPARATION DISTANCES,
SHALL BE PROVIDED TO IRISH WATER AT DESIGN STAGE.
3. WATERMAIN (PROPOSED) SEPARATION DISTANCES

HORIZONTAL
300mm TO DISTRIBUTION MAINS OF LESS THAN 300mm DIAMETER.
500mm TO TRUNK MAINS BETWEEN 300mm AND 450mm DIAMETER.
3m TO ARTERIAL WATER MAINS OF GREATER THAN 450mm DIAMETER.

VERTICAL
300mm TO DISTRIBUTION MAINS OF LESS THAN 300mm DIAMETER.
500mm TO TRUNK/ARTERIAL MAINS OF DIAMETER GREATER THAN 300mm.

ANY PROPOSED PIPE CROSSING SHOULD BE LOCATED MID-WAY BETWEEN THE WATER JOINTS WITH MINIMUM
CLEAR DISTANCE OF 300mm AND UP TO 500mm. ALL CROSSINGS SHOULD BE AT LEAST 500mm AWAY FROM FITTINGS OR JOINTS.

4. WATERMAIN (EXISTING) SEPARATION DISTANCES

HORIZONTAL
500mm AT EITHER SIDE OF MAINS UP TO AND INCLUDING 200mm IN DIAMETER.
1m AT EITHER SIDE OF MAINS OF 225mm TO 250mm DIAMETER.
2m AT EITHER SIDE OF MAINS OF 300mm TO 375mm IN DIAMETER.
5m AT EITHER SIDE OF MAINS OF 400mm AND 450mm IN DIAMETER.
SPECIFIC IRISH WATER ADVISED DISTANCES FOR MAINS IN EXCESS OF 475mm DIAMETER.

5. NOTIFICATION IN WRITING IS REQUIRED SHOULD WORKS BE WITHIN THE FOLLOWING DISTANCES FROM AN EXISTING WATER MAIN OR WASTEWATER RISING MAIN:-

HORIZONTAL
1000mm AT EITHER SIDE OF EXISTING MAINS LESS THAN OR EQUAL TO 200mm DIAMETER
2000mm AT EITHER SIDE OF EXISTING MAINS OF 250mm TO 350mm DIAMETER
5000mm AT EITHER SIDE OF EXISTING MAINS OF DIAMETER GREATER THAN 350mm DIAMETER

WHERE DUCTS OR PIPES ARE TO BE LAID CLOSE TO AN EXISTING WATERMAIN OR SEWER IN THE OWNERSHIP OF IRISH WATER,
NOTIFICATION IN WRITING SHALL BE PROVIDED A MINIMUM OF 10 DAYS AHEAD OF ADVANCEMENT OF THE WORK

NOTIFICATION IN WRITING IS REQUIRED SHOULD WORKS BE WITHIN 1.5m DISTANCE OF A WASTEWATER SEWER.

REQUIREMENTS SHALL ALSO APPLY TO TRIAL HOLES OR SLIT TRENCHES TO LOCATE THE MAIN OR GAIN GROUND INFO DATA.
LARGER DIAMETERS >300mm DISTRIBUTION AND TRUNK MAINS, IRISH WATER MUST BE NOTIFIED AT LEAST 1 MONTH IN ADVANCE.

DEVELOPERS SHALL ALSO COMPLY WITH ANY NOTIFICATION REQUIREMENTS OF OTHER UTILITY PROVIDERS (ESB, GAS MAIN, TELECOMMUNICATION ETC).

6. DETAILED PROPOSALS, INCLUDING WORK METHOD STATEMENTS, INSURANCE CONFIRMATION AND DETAILS OF WORK COMPLETED OF A SIMILAR NATURE MUST
BE SUBMITTED TO IRISH WATER FOR REVIEW. ALL SUCH WORKS IN THE VICINITY OF ARTERIAL WATER MAINS AND SEWER (MAINS GREATER THAN 400mm) SHALL BE SUBJECT
TO WRITTEN AGREEMENT WITH IRISH WATER BEFORE CONSTRUCTION COMMENCES ON SITE. THIS AGREEMENT SHALL ALSO INCLUDE ANY NECESSARY PROTECTION FOR
WATER MAINS.

7. ANY DAMAGE SHALL BE NOTIFIED IMMEDIATELY TO IRISH WATER. THE PERSON WHO CAUSES THE DAMAGE TO A WATER MAIN OR FITTING WILL BE DEEMED TO HAVE
COMMITTED AN OFFENCE UNDER SECTION 45 OF THE WATER SERVICES ACT 2007.

8. WATERMAINS OF ANY SIZE SHALL NOT BE WITHIN 1m OF THE BOUNDARY TO A PREMISES.

9. UNDER NO CIRCUMSTANCES WILL IRISH WATER ACCEPT WATER MAIN INSTALLATIONS UNDER STRUCTURES, EXISTING OR PROPOSED, OR IN CLOSE PROXIMITY TO
ANY EXISTING STRUCTURES OR FEATURES THAT WILL INHIBIT ACCESS FOR POST INSTALLATION MAINTENANCE AND ACCESS.

10. WHERE THE DESIGN DEVIATES FROM THIS STANDARD DETAIL, THE DESIGN SHALL BE SUBJECT TO THE
REVIEW OF IRISH WATER.
11. SEPARATION DISTANCES BETWEEN UTILITIES MAY BE INCREASED TO PROVIDE FOR CHAMBER & DIAMETER 'C'
THRUST BLOCKS AT BENDS. (mm) (mm)
'C'
≤150 3000

200 - 600 5000

>600 8000

BUILDING
1000mm MINIMUM 750mm

BOUNDARY WALL FOOTPATH GRASS VERGE KERB

CABLE TV
MIN. 900mm

TELECOMMUNICATIONS

'A' 'A'

WATER MAIN STORM WATER


FOUNDATION

ELECTRICAL CORRIDOR (DEPTH AND LAYOUT


REQUIREMENTS TO BE CONFIRMED WITH
'B'

SERVICE PROVIDER) GAS MAIN


FOUL SEWER

DIAMETER 'A' 'B' NOTE;


(mm) NO OTHER SERVICES
(mm) (mm)
TO BE CONSTRUCTED
WITHIN THIS ZONE
<300 300 300

300 - 450 500 500

>450 3000 500

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

TYPICAL SERVICE LAYOUT


1 11/'17 JMC TOC Notes added & updated MOD INDICATING SEPARATION DISTANCES STD-W- 11 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017

METHOD STATEMENTS:
ALL WORKS SHALL BE CARRIED
OUT IN ACCORDANCE WITH BS 5837 AND INFORMED BY
NJUG VOLUME 4

PRECAUTION AREA:

EXCAVATIONS FOR PIPEWORK SHOULD NOT BE


UNDERTAKEN WITHIN THIS AREA, UNLESS AGREED WITH
IRISH WATER.

WORKS WITHIN THE PRECAUTION ZONE MUST BE


SUPERVISED BY A QUALIFIED ARBORIST. WORKS SHALL BE
SUBJECT OF A CLEAR METHOD STATEMENT OUTLINING ALL
WORKS ADJACENT TO THE TREES/SHRUBS WHICH IS TO BE
PREPARED & AGREED IN ADVANCE OF THE WORKS.

MATERIAL, PLANT & SPOIL SHALL NOT BE STORED WITHIN


THIS ZONE.

EXCLUSION AREA:

WORKS IN THIS AREA ARE TO BE AVOIDED, UNLESS


ABSOLUTELY NECESSARY & AGREED WITH IRISH WATER.

EXCAVATIONS FOR PIPEWORK SHOULD NOT BE


UNDERTAKEN WITHIN THIS AREA, UNLESS NECESSARY AND
NO OTHER OPTIONS AVAILABLE. WORKS WITHIN THE
EXCLUSION ZONE MUST BE SUPERVISED BY A QUALIFIED
ARBORIST AND AGREED WITH IRISH WATER. WORKS SHALL
BE SUBJECT OF AN ARBORICULTURAL IMPACT
ASSESSMENT AS PER BS 5837 & A CLEAR METHOD
STATEMENT OUTLINING ALL WORKS ADJACENT TO THE
TREES/SHRUBS IS TO BE PREPARED AND AGREED IN
ADVANCE OF THE WORKS.
MATERIAL, PLANT & SPOIL SHALL NOT BE STORED WITHIN
THIS ZONE.

OUTSIDE RADIUS OF PRECAUTION AREA = 4 x


GIRTH OF TREE
EXCLUSION AREA
PRECAUTION PRECAUTION GIRTH (CIRCUMFERENCE OF TREE
AREA 1m 1m AREA MEASURED AT 1.5m ABOVE GROUND LEVEL)

PREVENTION MEASURES
REQUIRED IN LINE WITH
LANDSCAPING DESIGN & SPECIAL
GIRTH x 4
PROTECTION REQUIRED. (e.g. BY NO WORKS PERMITTED
USE OF APPROPRIATE BARRIERS,
HIGH PERFORMANCE JOINTS, OR
BY USE OF POLYETHYLENE WITH
WELDED JOINTS). THE LANDSCAPE
DESIGN AND DETAILS OF THE
SPECAIL PROTECTION MEASURES
MUST BE AGREED WITH IRISH

EXISTING PLANTING
WATER

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
Revised to suit ILI recommendations
2 11/'17 JMC TOC
& changed drawing title
MOD RESTRICTIONS ON WATER INFRASTRUCTURE
1 08/'16 JMC TOC Added new section & notes MOD WORKS ADJACENT TO EXISTING TREES STD-W- 12 2
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017

1. Develop detailed design


DIAGRAM 1: DECISION FLOW CHART of the tree planting with
Outcome Decision landscape architect.
2. Consult with arborist.
STEP 1 STEP 2 (DIAGRAM 2) 3. Carry out works under
supervision of Irish Water
Main Decision Check Table A.1. of BS 5837. Check Check STD-W12A for species & size representative.
1. Utility depth Depending on the choice of tree Yes
No Trees required in Yes Then Are root barriers &/or
Do 2. Final expected stem diameter species or shrubs:
proximity to Water protection measures
Nothing - Establish minimum distance from 1. Establish increased (or
Infrastructure to be used?
tree to utility decreased) distance from utility No
- Assume no protection measures 2. Assume no protection measures
1. Plant trees at required
distance (as per step 2).
2. Carry out works under
THE DISTANCES GIVEN IN TABLE A.1. OF BS 5837 MUST BE FURTHER INFORMED BY THE SPECIES & DIAGRAM 2 BELOW. DIAGRAM 1 ABOVE supervision of Irish Water
PROVIDES A FLOW CHART TO THE DECISION PROCESS WHILST DIAGRAM 2 BELOW IS TO BE USED TO INFORM THE PLANTING REGIME. representative.

PLEASE NOTE THAT TABLE A.1. OF BS 5837 (BELOW) IS TO BE USED TO CALCULATE THE ABSOLUTE MIMIMUM DISTANCE BETWEEN NEW TREE PLANTING
FROM THE WATER INFRASTRUCTURE (THE SERVICES). THE DISTANCE IS REQUIRED TO AVOID DIRECT DAMAGE TO THE INFRASTRUCTURE FROM
FUTURE GROWTH. THE DISTANCE IS A FUNCTION OF THE DEPTH OF THE SERVICES AND THE (FINAL EXPECTED) STEM DIAMETER OF THE TREE AT
MATURITY (i.e. FINAL EXPECTED GROWTH).
TABLE A.1. Minimum distance between young trees or new planting & structures, in metres (m)
BS 5837 Final stem dia. < 300mm Final stem dia. 300mm to 600mm Final stem dia. > 600mm
Services
< 1m deep 0.5 1.5 3.0
> 1m deep -- 1.0 2.0
THUS FOR EXAMPLE:
- FOR A SERVICE LESS THAN 1 METRE DEEP, THE MINIMUM DISTANCE IS TO BE 1.5m FOR A TREE BETWEEN 300 AND 600mm STEM DIAMETER AT MATURITY.
- FOR A SERVICE GREATER THAN 1 METRE DEEP, THE MINIMUM DISTANCE IS TO BE 1.0m FOR A TREE BETWEEN 300 AND 600mm STEM DIAMETER AT MATURITY.

NOTE: RESTRICTIONS RELATE TO INFRASTRUCTURE WITHOUT ROOT INTRUSION PROTECTION.


THE DESIGN OF LANDSCAPING SHALL BE UNDERTAKEN IN CONJUNCTION WITH THE DESIGN OF WATER INFRASTRUCTURE, ETC. THE TREE/BUSH/SHRUB SHALL NOT BE LOCATED CLOSER TO
THE WATER INFRASTRUCTURE THAN INDICATED ABOVE, EXCEPT WHERE SPECIAL PROTECTION MEASURES ARE PROVIDED. WHERE THERE IS A RISK OF TREE/ROOT INTRUSION, THE WATER
INFRASTRUCTURE SHALL BE RESISTANT TO TREE ROOT INGRESS (e.g. BY USE OF APPROPRIATE BARRIERS, HIGH PERFORMANCE JOINTS, OR BY USE OF POLYETHYLENE WITH WELDED
JOINTS). THE LANDSCAPE DESIGN AND DETAILS OF THE SPECIAL PROTECTION MEASURES MUST BE AGREED WITH IRISH WATER
A TREE SHALL NOT BE PLANTED DIRECTLY OVER WATER INFRASTRUCTURE WHERE EXCAVATION OF THE INFRASTRUCTURE WOULD REQUIRE REMOVAL OF THE TREE UNLESS SUCH
PLANTING IS AGREED WITH IRISH WATER AND IN GENERAL ONLY SHALLOW ROOTING SHRUBS SHALL BE PLANTED CLOSE TO WATER INFRASTRUCTURE.
PLEASE ENSURE THAT THESE DISTANCES ARE ADHERED TO IN ORDER TO PROTECT THE TREES FROM ANY FUTURE MAINTENANCE. REFERENCE SHOULD ALSO BE MADE TO BS 5837, BS 8545
AND THE NJUG GUIDELINES VOLUME 4 FOR FURTHER INFORMATION.

DIAGRAM 2: PLANTING DISTANCES FOR DIFFERENT SPECIES


WITHOUT BARRIER PROTECTION
Examples of Large Growing Species WATERMAINS
NOTE THAT VALUES REFER TO PLANTING DISTANCES
Poplar, WITHOUT ROOT BARRIERS OR PROTECTION MEASURES
Willow.

Examples of Large Conifers & Deciduous Trees


Scots Pine, Black Pine, Cedar, Larch, Lawson's Cypress,
Ash, Beech, Sycamore, Horse Chestnut, Sweet
Chestnut, London Plane, Lime, Alder, Elm, Oak

Examples of Small SIze Amenity Trees


Mountain Ash, Whitebeam, Field Maple,Wild Cherry,
Cockspur Thorn, False Acacia, Crab Apple, Cobnut, Birch,
Hornbeam CV. Elder,Ornamental Pear.

Examples of shrubs and bushes


Holly, Laurel, Rhododendron, Dogwood,
Christmas Tree, Magnolia, Fruit bushes, Spindle
Tree, Guelder rose, Roses

Examples of hedge plants and ground covers including


herbaceous and annuals
NOTE: OTHER SPECIES NOT
Hedge plants and ground covers may be placed over the pipeline
NAMED TO BE PLANTED TO THE
SAME SPACINGS DEPENDING Privet, Blackthorn, Snowberry, Berberis, Heathers, Cotoneaster &
ON ROOT FORMATION. Groundcovers, Herbaceous & Annuals

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE JUL. 2017
TITLE DRAWING No. REV

RESTRICTIONS ON NEW TREES / SHRUBS


PLANTING ADJACENT TO WATER MAINS STD-W-12A 0
0 11/'17 JMC TOC Initial Issue MOD
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
2. THE MINIMUM DEPTH OF COVER FROM THE FINISHED GROUND LEVEL TO THE
SEE NOTES 11 & 12
EXTERNAL CROWN OF THE PIPE SHALL BE 900mm WHERE THE PIPE IS TO BE
LOCATED IN HOUSING ESTATE ROADS. GREATER DEPTHS OF COVER AND/OR
FOOTPATH / ROAD SURFACE PIPE STRENGTH AND/OR A HIGHER CLASS OF BEDDING MATERIAL MAY BE
REQUIRED WHERE HIGH TRAFFIC LOADING IS ANTICIPATED. THE DESIRABLE
COVER FOR A WATERMAIN SHOULD BE 1200mm, WHERE PRACTICABLE &
SHOULD NOT EXCEED 3.0m.
3. CLAUSE 804 / 808 MATERIAL IN ACCORDANCE WITH THE NATIONAL ROADS
AUTHORITY SPECIFICATION FOR ROAD WORKS IS TO BE USED AS BACKFILL
BACKFILL
MATERIAL WHERE THE WATER MAIN IS LOCATED IN ROADS, FOOTPATHS OR
REFER TO NOTE 3
WHEN THE NEAREST PART OF THE TRENCH IS WITHIN 1m OF THE PAVED EDGE
FOR DETAILS
OF THE ROADWAY. CLAUSE 804 / 808 IS TO BE COMPACTED AS PER CLAUSE 802
OF THE NATIONAL ROADS AUTHORITY SPECIFICATION FOR ROAD WORKS.
CLAUSE 808 IS TO BE USED WITHIN 500mm OF CEMENT BOUND MATERIALS,
CONCRETE PAVEMENTS, CONCRETE STRUCTURES OR CONCRETE PRODUCTS.
OTHERWISE CLAUSE 804 MAY BE USED. ALTERNATIVE BACKFILL MATERIAL TO
SEE NOTE 2

THAT DESCRIBED ABOVE (CLAUSE 804 OR CLAUSE 808) OF THE PIPE TRENCH
MARKER TAPE REFER
WILL ONLY BE ALLOWED BY IRISH WATER WHERE THE ROADS AUTHORITY IN
TO NOTE 9 FOR DETAILS
WHOSE FUNCTIONAL AREA THE DEVELOPMENT IS LOCATED, PROVIDES
WRITTEN APPROVAL TO THE DEVELOPER TO THE USE SUCH ALTERNATIVE
MATERIAL.
4. SELECTED EXCAVATED MATERIAL MAY BE USED IN GREEN-FIELD AREAS ABOVE
300mm MINIMUM

GRANULAR PIPE SURROUND MATERIAL SUBJECT TO REVIEW BY IRISH WATER.


5. PIPE BEDDING SHALL COMPLY WITH WIS 4-08-02 AND IGN 4-08-01 GRANULAR
MATERIAL SHALL BE 14mm TO 5mm GRADED AGGREGATE OR 10mm SINGLE
SIZED AGGREGATE TO IS EN 13242.
6. IN SOFT GROUND CONDITIONS (CBR < 5) THE MATERIAL SHOULD BE EXCAVATED
OUT AND DISPOSED OF IN ACCORDANCE WITH THE WASTE MANAGEMENT ACT
AND CLAUSE 804 / 808 MATERIAL IN ACCORDANCE WITH THE NATIONAL ROADS
AUTHORITY SPECIFICATION FOR ROAD WORKS SHALL REPLACE THE
EXCAVATED MATERIAL, WRAPPED IN GEO-TEXTILE WRAPPING. ALTERNATIVELY,
SPECIAL PIPE SUPPORT ARRANGEMENTS, INCLUDING PILING ETC. MAY BE
PIPE BEDDING REFER TO REQUIRED WHERE THE DEPTH OF SOFT MATERIAL IS EXCESSIVE. SUCH
NOTE 5 FOR DETAILS ARRANGEMENTS SHALL BE SUBJECT TO ASSESSMENT BY IRISH WATER BEFORE
ADVANCING WITH THE WORK.
7. PIPES SHALL NOT BE SUPPORTED ON STONES OR ROCKS, OR ANY HARD
OBJECT AT ANY POINT ALONG THE TRENCH. ROCK SHALL BE EXCAVATED TO A
DEPTH OF 150mm BELOW THE ACTUAL DEPTH OF THE TRENCH WITH THE VOID
FILLED WITH CLAUSE 804 / 808 MATERIAL IN ACCORDANCE WITH THE NATIONAL
ROADS AUTHORITY SPECIFICATION FOR ROAD WORKS. THE GRANULAR
MATERIAL SHALL BE LAID ABOVE THIS VOID BACKFILL MATERIAL.
8. SHOULD MINIMUM COVER NOT BE ACHIEVABLE, CONCRETE GRADE C8/10 SHALL
BE USED AS BACKFILL MATERIAL.
'C'

9. MARKER TAPE TO BE 400mm WIDE BLUE POLYETHYLENE MATERIAL IN


ACCORDANCE WITH EN 12163, PLASTIC PIPES SHALL HAVE WARNING TAPE
INCORPORATED A REINFORCED BAND BRACING WIRE. SERVICE PIPES SHALL
HAVE 200mm WIDE MESH TAPE. MARKER TAPE TO BE LAID AT TOP OF PIPE
BEDDING LAYER.
PIPE DIAMETER - 'A'
10. TRENCH WIDTHS FOR PIPE SIZES ≤80mm MAY BE <500mm, SUBJECT TO
CONSIDERATION BEING GIVEN TO THE TRENCH DEPTH, HEALTH & SAFETY &
MINIMUM TRENCH WIDTH - 'B' CONSTRUCTION ACCESS REQUIREMENTS.
11. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY
REQUIREMENTS.
12. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF
CROSS SECTION IN ROADWAYS "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF
TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND
REQUIREMENTS.

GRASSED AREAS

DEPTH OF PIPE DIAMETER TRENCH WIDTH DEPTH OF


REINSTATED TOPSOIL
PIPE DIAMETER
'A' (mm) 'B' (mm) BEDDING
TO MATCH EXISTING 'A' (mm)
'C' (mm)
≤ 80 SEE NOTE 10
SELECTED BACKFILL ≤ 200 150
REFER TO NOTE 4 100 500
FOR DETAILS ≥ 250 200
150 600
SEE NOTE 2

200 600
MARKER TAPE REFER
TO NOTE 9 FOR DETAILS 250 750

300 750
350 750
(300mm MINIMUM IF
200mm MINIMUM

ADJACENT TO
TRAFFICKED

400 900
AREAS)

450 900

PIPE BEDDING REFER TO


NOTE 5 FOR DETAILS
'C'

PIPE DIAMETER - 'A'

MINIMUM TRENCH WIDTH - 'B'

CROSS SECTION IN GRASSED AREAS

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

TRENCH BACKFILL AND BEDDING


1 11/'17 JMC TOC Added & updated notes MOD STD-W- 13 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
2. SLUICE VALVE CHAMBERS SHALL BE COVERED WITH APPROVED HEAVY DUTY METAL COVERS TO IS 261 OR BS 5834. COVER AND FRAME SHALL BE
200 445 200 SUITABLE FOR ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
3. SLUICE VALVES SHALL BE RESILIENT SEATED AND SHALL COMPLY WITH BS 5163-1, BS 5163-2, IS EN 1074-1, IS EN 1074-2, OR EQUIVALENT E.U.
SPECIFICATIONS.
4. ALL SLUICE VALVES SHALL BE ANTI-CLOCKWISE CLOSING.
5. VALVE CHAMBER TO BE CONSTRUCTED OF PRECAST CONCRETE UNITS OR HIGH DENSITY BLOCKWORK. ALTERNATIVELY PROPRIETARY
PREFABRICATED CHAMBER UNITS MAY ALSO BE USED, SUBJECT TO REVIEW BY IRISH WATER. ROOF SLABS SHALL BE DESIGNED TO CARRY ALL LIVE
LOADS & DEAD LOADS, & CONSIST OF A REINFORCED CONCRETE SLAB OF IN-SITU CONCRETE, GRADE C30/37, WITH A MINIMUM THICKNESS OF
200

150mm. ALTERNATIVELY, PRE-CAST CONCRETE ROOFS MAY BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911, Part 4.
6. CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER STD-W-13.
7. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545.
SV 8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
280

BULL NOSE 9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS
FINISH AND PIPES AT STEEP SLOPES.
10. ANTI-CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
11. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
200

12. ALL THRUST FLANGES TO BE ADEQUATELY RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN FOR
CLARITY.
13. 450 x 450mm INTERNAL DIMENSION CHAMBERS MAY BE PROVIDED SUBJECT TO REVIEW BY IW. SUCH CHAMBERS SHALL BE PROVIDED WITH GRADE
"A" HEAVY DUTY COVER & FRAME & STAMPED "SV".
PLINTH DETAIL 14. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
15. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
IN GRASS AREAS 16. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF
TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.

MAX.
MAX.
SEE NOTES 14, 15

300
300

FINISHED GROUND LEVEL & 16. FINISHED GROUND LEVEL


COVER TO BE SET IN C50/60 COVER TO BE SET IN
MORTAR C50/60 MORTAR
CLASS B ENGINEERING BRICK

REFER TO NOTE 2 ON STD-W-13


CLASS B ENGINEERING BRICK
SET IN C50/60 MORTAR SET IN C50/60 MORTAR

150

150
CONCRETE ROOF SLAB CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB C30 / 37 REINFORCED SLAB

900 MIN.
215mm THICK 20N/mm²
EXTENSION SPINDLE 445 445 EXTENSION SPINDLE
THRUST CONCRETE BLOCKWORK
PRECAST CONCRETE UNITS IN ACCORDANCE WITH C25/30 PRECAST CONCRETE
FLANGE
(REFER TO NOTE 5.) IS EN 771-3 BEARING SLAB
THRUST
FLANGE
100

100
C25/30 PRECAST REFER TO STD -
CONCRETE BEARING SLAB W- 13 FOR
LOCALLY

LOCALLY
BEDDING AND
MIN.

MIN.
REFER TO STD - W- 13
150

150
BACKFILLING
FOR BEDDING AND DETAILS
BACKFILLING DETAILS

DUCTILE IRON DUCTILE IRON


(D.I.) PIPE (D.I.) PIPE

LONG BODY FLANGED / PLAIN ENDED FLANGED / PLAIN ENDED FLANGED / PLAIN ENDED FLANGED / PLAIN ENDED
150

150
FLEXIBLE PIPE CUT TO SUIT PIPE CUT TO SUIT LONG BODY PIPE CUT TO SUIT PIPE CUT TO SUIT LONG BODY
COUPLING FLEXIBLE
FLANGED SLUICE VALVE DISMANTLING JOINT COUPLING FLANGED DISMANTLING JOINT FLEXIBLE
CONCRETE ANTI-TORQUE SUPPORT SLUICE VALVE CONCRETE ANTI-TORQUE SUPPORT COUPLING

SECTION SECTION
445 445

75mm HIGH SV SV 75mm HIGH


280

280

LETTERING LETTERING
HEAVY DUTY COVER AND FRAME, HEAVY DUTY COVER AND FRAME,
STAMPED ''SV'' CLASS D400 STAMPED ''SV'' CLASS D400
(TO SUIT 445 x 280 OPE) (TO SUIT 445 x 280 OPE)

CONCRETE ROOF SLAB CONCRETE ROOF SLAB


C30 / 37 REINFORCED SLAB C30 / 37 REINFORCED SLAB

ROOF PLAN ROOF PLAN


50 215 600 215 50
100 600 100
50

50 50
50

215mm THICK 20N/mm²


215

PRECAST CONCRETE CONCRETE BLOCKWORK


100

UNITS IN ACCORDANCE WITH


(REFER TO NOTE 5.) IS EN 771-3
600

600
100

215
50

50

FLOOR PLAN FLOOR PLAN


SLUICE VALVE CHAMBER SLUICE VALVE CHAMBER
(PRECAST CONCRETE CONSTRUCTION) (BLOCKWORK CONSTRUCTION)

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
3 11/'17 JMC TOC Revised & Added Notes MOD
2 08/'16 JMC TOC Revised Notes 2, 3 & 6 MOD
SLUICE VALVE
1 04/'16 JMC TOC Added 2 couplings (2 details) MOD FOR DUCTILE IRON (D.I.) PIPE (< 350mm DIA. ) STD-W- 14 3
0 09/'15 JMC TOC Initial Issue SL (Sheet 1 of 2)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017

1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.


200 445 200 2. SLUICE VALVE CHAMBERS SHALL BE COVERED WITH APPROVED HEAVY DUTY METAL COVERS TO IS 261 OR BS 5834. COVER AND FRAME SHALL BE
SUITABLE FOR ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
3. SLUICE VALVES SHALL BE RESILIENT SEATED AND SHALL COMPLY WITH BS 5163-1, BS 5163-2, IS EN 1074-1, IS EN 1074-2, OR EQUIVALENT E.U.
SPECIFICATIONS.
4. ALL SLUICE VALVES SHALL BE ANTI-CLOCKWISE CLOSING.
5. VALVE CHAMBER TO BE CONSTRUCTED OF PRECAST CONCRETE UNITS OR HIGH DENSITY BLOCKWORK. ALTERNATIVELY PROPRIETARY
200

PREFABRICATED CHAMBER UNITS MAY ALSO BE USED, SUBJECT TO REVIEW BY IRISH WATER. ROOF SLABS SHALL BE DESIGNED TO CARRY ALL LIVE
LOADS & DEAD LOADS, & CONSIST OF A REINFORCED CONCRETE SLAB OF IN-SITU CONCRETE, GRADE C30/37, WITH A MINIMUM THICKNESS OF 150mm.
ALTERNATIVELY, PRE-CAST CONCRETE ROOFS MAY BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911, Part 4.
6. CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER STD-W-13.
SV 7. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545. PE PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 12201:2011.
280

BULL NOSE 8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
FINISH 9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS
AND PIPES AT STEEP SLOPES.
10. ANTI-CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
200

11. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.


12. 450 x 450mm INTERNAL DIMENSION CHAMBERS MAY BE PROVIDED SUBJECT TO REVIEW BY IW. SUCH CHAMBERS SHALL BE PROVIDED WITH GRADE "A"
HEAVY DUTY COVER & FRAME & STAMPED "SV".
13. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
PLINTH DETAIL 14. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
15. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF
IN GRASS AREA TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.

MAX.
MAX.

300
300
SEE NOTES 13, 14 & 15.
FINISHED GROUND LEVEL FINISHED GROUND LEVEL
COVER TO BE SET IN C50/60 COVER TO BE SET IN
MORTAR C50/60 MORTAR
CLASS B ENGINEERING BRICK

REFER TO NOTE 2 ON STD-W-13


CLASS B ENGINEERING BRICK
SET IN C50/60 MORTAR SET IN C50/60 MORTAR

150

150
CONCRETE ROOF SLAB CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB C30 / 37 REINFORCED SLAB

900 MIN.
EXTENSION SPINDLE 445 445 EXTENSION SPINDLE
PRECAST CONCRETE UNITS 215mm THICK 20N/mm²
(REFER TO NOTE 5.) CONCRETE BLOCKWORK
IN ACCORDANCE WITH IS EN 771-3

100

100
C25/30 PRECAST C25/30 PRECAST CONCRETE
CONCRETE BEARING SLAB BEARING SLAB

LOCALLY
LOCALLY
MIN.

MIN.
REFER TO STD - W- 13 REFER TO STD - W- 13
150

150
FOR BEDDING AND FOR BEDDING AND
BACKFILLING DETAILS BACKFILLING DETAILS

POLYETHYLENE POLYETHYLENE
(P.E.) PIPE (P.E.) PIPE
150

150
FUSION WELD FUSION WELD FUSION WELD

STUB FLANGE STUB FLANGE STUB FLANGE


WITH BACKING RING DISMANTLING WITH BACKING RING WITH BACKING RING
JOINT FLANGED DISMANTLING
FLANGED
CONCRETE ANTI-TORQUE SUPPORT SLUICE VALVE JOINT
SLUICE VALVE
CONCRETE ANTI-TORQUE SUPPORT
SECTION SECTION
445 445

75mm HIGH SV SV 75mm HIGH


280

280

LETTERING LETTERING
HEAVY DUTY COVER AND FRAME, HEAVY DUTY COVER AND FRAME,
STAMPED ''SV'' CLASS D400 STAMPED ''SV'' CLASS D400
(TO SUIT 445 x 280 OPE) (TO SUIT 445 x 280 OPE)

CONCRETE ROOF SLAB


C30 / 37 REINFORCED SLAB CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB

ROOF PLAN ROOF PLAN


50 100 100 50 50 50
600 215 600 215
50
50

215
100

215mm THICK 20N/mm²


PRECAST CONCRETE
CONCRETE BLOCKWORK
UNITS
IN ACCORDANCE WITH IS EN 771-3
(REFER TO NOTE 5.)
600

600
100

215
50

50

FLOOR PLAN FLOOR PLAN


SLUICE VALVE CHAMBER SLUICE VALVE CHAMBER
(PRECAST CONCRETE CONSTRUCTION) (BLOCKWORK CONSTRUCTION)

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

2 11/'17 JMC TOC Revised & Added Notes MOD


SLUICE VALVE
1 08/'16 JMC TOC Revised notes 2, 3 & 6 MOD FOR POLYETHYLENE (P.E.) PIPE (< 350mm DIA. ) STD-W- 15 2
0 09/'15 JMC TOC Initial Issue SL (Sheet 2 of 2)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
2. HYDRANT CHAMBERS SHALL BE COVERED WITH APPROVED HEAVY DUTY METAL COVERS TO IS 261 OR BS 5834 COVER AND FRAME SHALL BE SUITABLE
200 445 200 FOR ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
3. ALL HYDRANTS, SURFACE BOX FRAMES & COVERS SHALL COMPLY WITH THE RELEVANT PROVISIONS OF IS EN 14339, IS EN 1074-6 & BS 750. FIRE
HYDRANTS SHALL BE TYPE 2. THE HYDRANT INLET SHALL BE 80mm DIAMETER WITH PN16.
4. ALL HYDRANTS SHALL BE CLOCKWISE CLOSING.
200

5. HYDRANT CHAMBER TO BE CONSTRUCTED OF PRECAST CONCRETE UNITS OR HIGH DENSITY BLOCKWORK. ALTERNATIVELY PROPRIETARY
PREFABRICATED CHAMBER UNITS MAY ALSO BE USED, SUBJECT TO REVIEW BY IRISH WATER. ROOF SLABS SHALL BE DESIGNED TO CARRY ALL LIVE
LOADS & DEAD LOADS, & CONSIST OF A REINFORCED CONCRETE SLAB OF IN-SITU CONCRETE, GRADE C30/37, WITH A MINIMUM THICKNESS OF 150mm.
ALTERNATIVELY, PRE-CAST CONCRETE ROOFS MAY BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911, Part 4.
FH 6. CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER STD-W-13.
280

BULL NOSE 7. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545.
FINISH 8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS AND
PIPES AT STEEP SLOPES.
200

10. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.


11. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
12. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
PLINTH DETAIL 13.
14.
NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF
IN GRASS AREA TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.

MAX.
MAX.

350
350
SEE NOTES 12, 13 & 14.
FINISHED GROUND LEVEL FINISHED GROUND LEVEL
COVER TO BE SET IN C50/60 COVER TO BE SET IN

REFER TO NOTE 2 ON STD-W-13


MORTAR C50/60 MORTAR
CLASS B ENGINEERING BRICK CLASS B ENGINEERING BRICK
SET IN C50/60 MORTAR SET IN C50/60 MORTAR

150

150
900 MIN.
CONCRETE ROOF SLAB CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB C30 / 37 REINFORCED SLAB

445 DI, DOUBLE FLANGED, 445 215mm THICK 20N/mm²


DN80, RISER PIPE OF CONCRETE BLOCKWORK
PRECAST CONCRETE UNITS SUITABLE LENGTH TO IN ACCORDANCE WITH IS EN 771-3
(REFER TO NOTE 5.) SUIT SITE CONDITIONS
100

100
C25/30 PRECAST C25/30 PRECAST CONCRETE
CONCRETE BEARING SLAB BEARING SLAB

LOCALLY
LOCALLY

REFER TO STD - W- 13
MIN.

MIN.
REFER TO STD - W- 13
150

150
FOR BEDDING AND FOR BEDDING AND
BACKFILLING DETAILS BACKFILLING DETAILS

DUCTILE IRON DUCTILE IRON


(D.I.) PIPE (D.I.) PIPE

DUCTILE IRON SOCKETTED TEE WITH DUCTILE IRON SOCKETTED TEE WITH
FLANGED BRANCH FLANGED BRANCH
SECTION SECTION
445 445

75mm HIGH FH FH 75mm HIGH


280

280

LETTERING LETTERING

HEAVY DUTY COVER AND FRAME, HEAVY DUTY COVER AND FRAME,
STAMPED '' FH '' CLASS D400 STAMPED '' FH '' CLASS D400
(TO SUIT 445 x 280 OPE) (TO SUIT 445 x 280 OPE)
CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB

ROOF PLAN ROOF PLAN


50 100 100 50 50 50
600 215 600 215
50
50

215mm THICK 20N/mm²


215

PRECAST CONCRETE
CONCRETE BLOCKWORK
100

UNITS
IN ACCORDANCE WITH IS EN 771-3
(REFER TO NOTE 5.)
600

600

FIRE FIRE
HYDRANT HYDRANT
100

215
50

50

FLOOR PLAN FLOOR PLAN


FIRE HYDRANT CHAMBER FIRE HYDRANT CHAMBER
(PRECAST CONCRETE CONSTRUCTION) (BLOCKWORK CONSTRUCTION)

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

2 11/'17 JMC TOC Revised & added notes MOD


ON - LINE HYDRANT
1 08/'16 JMC TOC Revised notes 2,3 & 6 MOD FOR DUCTILE IRON (D.I.) PIPE STD-W- 16 2
0 09/'15 JMC TOC Initial Issue SL (Sheet 1 of 4)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
2. HYDRANT CHAMBERS SHALL BE COVERED WITH APPROVED HEAVY DUTY METAL COVERS TO IS 261 OR BS 5834 COVER AND FRAME SHALL BE SUITABLE FOR
ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
200 445 200
3. ALL HYDRANTS, SURFACE BOX FRAMES & COVERS SHALL COMPLY WITH THE RELEVANT PROVISIONS OF IS EN 14339, IS EN 1074-6 & BS 750. FIRE HYDRANTS
SHALL BE TYPE 2. THE HYDRANT INLET SHALL BE 80mm DIAMETER WITH PN16.
4. ALL HYDRANTS SHALL BE CLOCKWISE CLOSING.
5. HYDRANT CHAMBER TO BE CONSTRUCTED OF PRECAST CONCRETE UNITS OR HIGH DENSITY BLOCKWORK. ALTERNATIVELY PROPRIETARY PREFABRICATED
CHAMBER UNITS MAY ALSO BE USED, SUBJECT TO REVIEW BY IRISH WATER. ROOF SLABS SHALL BE DESIGNED TO CARRY ALL LIVE LOADS & DEAD LOADS, &
CONSIST OF A REINFORCED CONCRETE SLAB OF IN-SITU CONCRETE, GRADE C30/37, WITH A MINIMUM THICKNESS OF 150mm. ALTERNATIVELY, PRE-CAST
200

CONCRETE ROOFS MAY BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911, Part 4.
6. CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER STD-W-13.
7. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545.
8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
FH
280

BULL NOSE 9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS AND PIPES
FINISH AT STEEP SLOPES.
10. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
11. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
12. TEE BRANCH: IF DEPTH OF TAKE-OFF PIPEWORK < 900mm, TAKE-OFF TEE MAY BE ROTATED TO ENSURE MIN. DEPTH OF COVER IS MAINTAINED, OR
200

ALTERNATIVELY, PROVIDE PROTECTION TO TAKE-OFF PIPE.


13. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
14. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
15. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF
TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
PLINTH DETAIL
IN GRASS AREA

MAX.

MAX.
SEE NOTES 13, 14 & 15.

350

350
FINISHED GROUND LEVEL
COVER TO BE SET IN
C50/60 MORTAR
CLASS B ENGINEERING BRICK
SET IN C50/60 MORTAR
150

150
REFER TO NOTE 2 ON STD-W-13

CONCRETE ROOF SLAB


C30 / 37 REINFORCED SLAB
300
215mm THICK 20N/mm²
900 MIN.

445 CONCRETE BLOCKWORK 445


IN ACCORDANCE WITH IS EN 771-3
PRECAST
CONCRETE DI, DOUBLE FLANGED,
UNITS (REFER DN80, RISER PIPE OF
TO NOTE 5.) SUITABLE LENGTH TO
SUIT SITE CONDITIONS
C25/30 PRECAST
100

100
80mm DIA.
PLAIN ENDED CONCRETE BEARING SLAB
PIPE CONC. THRUST BLOCK TO BEND OPE TO BE SEALED
CUT TO SUIT 80mm DIA. PLAIN ENDED (REFER TO DRG. No. STD-W-28 USING A SUITABLE
PIPE CUT TO SUIT FOR DETAILS) MATERIAL
80mm DIA.
DOUBLE FLANGED
LONG BODY LONG BODY 90° BEND

SOCKETTED LEVEL
FLANGE ADAPTOR FLANGE ADAPTOR SECTION SECTION
INVERT TEE
WITH 80mm DIA. 445 445
FLANGED BRANCH

75mm HIGH
LETTERING FH 75mm HIGH FH
280

280

LETTERING
HEAVY DUTY COVER AND FRAME,
STAMPED '' FH '' CLASS D400
HEAVY DUTY COVER AND FRAME,
(TO SUIT 445 x 280 OPE)
STAMPED '' FH '' CLASS D400
(TO SUIT 445 x 280 OPE)
CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB
CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB
ROOF PLAN ROOF PLAN

50 100 100 50 50 50
600 215 600 215
50
50

215
100

PRECAST CONCRTETE UNITS


(REFER TO NOTE 5.)
600
600

FIRE HYDRANT
100

215

215mm THICK 20N/mm²


50

CONCRETE BLOCKWORK
IN ACCORDANCE WITH IS EN 771-3
50

FLOOR PLAN FLOOR PLAN


FIRE HYDRANT CHAMBER FIRE HYDRANT CHAMBER
(PRECAST CONCRETE CONSTRUCTION) (BLOCKWORK CONSTRUCTION)

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
Revised & added notes, &
3 11/'17 JMC TOC MOD TITLE DRAWING No. REV
revised pipework
2 08/'16 JMC TOC Revised notes 2,3 & 6 MOD
OFF - LINE HYDRANT
1 04/'16 JMC TOC Added thrust blocks MOD FOR DUCTILE IRON (D.I.) PIPE STD-W- 17 3
0 09/'15 JMC TOC Initial Issue SL (Sheet 2 of 4)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017

1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.


200 445 200 2. HYDRANT CHAMBERS SHALL BE COVERED WITH APPROVED HEAVY DUTY METAL COVERS TO IS 261 OR BS 5834 COVER AND FRAME SHALL BE SUITABLE FOR
ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
3. ALL HYDRANTS, SURFACE BOX FRAMES & COVERS SHALL COMPLY WITH THE RELEVANT PROVISIONS OF IS EN 14339, IS EN 1074-6 & BS 750. FIRE HYDRANTS
SHALL BE TYPE 2. THE HYDRANT INLET SHALL BE 80mm DIAMETER WITH PN16.
4. ALL HYDRANTS SHALL BE CLOCKWISE CLOSING.
200

5. HYDRANT CHAMBER TO BE CONSTRUCTED OF PRECAST CONCRETE UNITS OR HIGH DENSITY BLOCKWORK. ALTERNATIVELY PROPRIETARY PREFABRICATED
CHAMBER UNITS MAY ALSO BE USED, SUBJECT TO REVIEW BY IRISH WATER. ROOF SLABS SHALL BE DESIGNED TO CARRY ALL LIVE LOADS & DEAD LOADS, &
CONSIST OF A REINFORCED CONCRETE SLAB OF IN-SITU CONCRETE, GRADE C30/37, WITH A MINIMUM THICKNESS OF 150mm. ALTERNATIVELY, PRE-CAST
FH CONCRETE ROOFS MAY BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911, Part 4.
280

BULL NOSE 6. CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER STD-W-13.
FINISH 7. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545. PE PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 12201:2011.
8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS AND PIPES AT
200

STEEP SLOPES.
10. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
11. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
12. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
PLINTH DETAIL 13.
14.
NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF
IN GRASS AREA TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.

MAX.

MAX.
SEE NOTES 12, 13 & 14.
350

350
FINISHED GROUND LEVEL FINISHED GROUND LEVEL
COVER TO BE SET IN C50/60 CLASS B COVER TO BE SET IN
MORTAR ENGINEERING BRICK C50/60 MORTAR
SET IN C50/60 MORTAR

REFER TO NOTE 2
150

150
CONCRETE ROOF SLAB

ON STD-W-13
CONCRETE ROOF SLAB

900 MIN.
C30 / 37 REINFORCED SLAB C30 / 37 REINFORCED SLAB

DI, DOUBLE FLANGED,


DN80, RISER PIPE OF 215mm THICK 20N/mm²
445 445
SUITABLE LENGTH TO CONCRETE BLOCKWORK
SUIT SITE CONDITIONS IN ACCORDANCE WITH IS EN 771-3
PRECAST CONCRETE
(RISER CAN BE PE MATERIAL)
UNITS
(REFER TO NOTE 5.)
PRECAST CONCRETE
100

100
PRECAST CONCRETE BEARING SLAB
BEARING SLAB

LOCALLY
LOCALLY
MIN.

MIN.
150

150
REFER TO STD - W- 13
REFER TO STD - W- 13 POLYETHYLENE POLYETHYLENE FOR BEDDING AND
FOR BEDDING AND (P.E.) PIPE (P.E.) PIPE BACKFILLING DETAILS
BACKFILLING DETAILS

FUSION WELD FUSION WELD FUSION WELD FUSION WELD


FUSION WELD POLYETHYLENE TEE WITH FUSION WELD POLYETHYLENE TEE WITH
FLANGED BRANCH OR FLANGED BRANCH OR
SECTION ELECTRO FUSION SADDLE SECTION ELECTRO FUSION SADDLE
445
445

75mm HIGH FH FH 75mm HIGH


280

280

LETTERING LETTERING

HEAVY COVER AND FRAME, HEAVY DUTY COVER AND FRAME,


STAMPED '' FH '' CLASS D400 STAMPED '' FH '' CLASS D400
(TO SUIT 445 x 280 OPE) (TO SUIT 445 x 280 OPE)

CONCRETE ROOF SLAB


C30 / 37 REINFORCED SLAB CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB

ROOF PLAN ROOF PLAN


100 100
50

50 600 50 50 215 600 215 50


50

215

PRECAST CONCRETE 215mm THICK 20N/mm²


100

UNITS CONCRETE BLOCKWORK


(REFER TO NOTE 5.) IN ACCORDANCE WITH IS EN 771-3
600

600

FIRE FIRE
HYDRANT HYDRANT
100

215
50

FLOOR PLAN FLOOR PLAN


50

FIRE HYDRANT CHAMBER FIRE HYDRANT CHAMBER


(PRECAST CONCRETE CONSTRUCTION) (BLOCKWORK CONSTRUCTION)
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

2 11/'17 JMC TOC Revised & added notes MOD


ON - LINE HYDRANT
1 08/'16 JMC TOC Revised notes 2,3 & 6 MOD FOR POLYETHYLENE (P.E.) PIPE STD-W- 18 2
0 09/'15 JMC TOC Initial Issue SL (Sheet 3 of 4)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017

1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.


2. HYDRANT CHAMBERS SHALL BE COVERED WITH APPROVED HEAVY DUTY METAL COVERS TO IS 261 OR BS 5834 COVER AND FRAME SHALL BE SUITABLE FOR ROAD AND
200 445 200 TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
3. ALL HYDRANTS, SURFACE BOX FRAMES & COVERS SHALL COMPLY WITH THE RELEVANT PROVISIONS OF IS EN 14339, IS EN 1074-6 & BS 750. FIRE HYDRANTS SHALL BE
TYPE 2. THE HYDRANT INLET SHALL BE 80mm DIAMETER WITH PN16.
4. ALL HYDRANTS SHALL BE CLOCKWISE CLOSING.
5. HYDRANT CHAMBER TO BE CONSTRUCTED OF PRECAST CONCRETE UNITS OR HIGH DENSITY BLOCKWORK. ALTERNATIVELY PROPRIETARY PREFABRICATED CHAMBER
UNITS MAY ALSO BE USED, SUBJECT TO REVIEW BY IRISH WATER. ROOF SLABS SHALL BE DESIGNED TO CARRY ALL LIVE LOADS & DEAD LOADS, & CONSIST OF OF A
REINFORCED CONCRETE SLAB OF IN-SITU CONCRETE, GRADE C30/37, WITH A MINIMUM THICKNESS OF 150mm. ALTERNATIVELY, PRE-CAST CONCRETE ROOFS MAY BE
200

USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5011, Part 4.
6. CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER STD-W-13.
7. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545. PE PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 12201:2011.
FH 8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
280

BULL NOSE 9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS AND PIPES AT STEEP
FINISH SLOPES.
10. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
11. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
200

12. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
13. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
14. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF TRANSPORT,
TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.

PLINTH DETAIL
IN GRASS AREA

MAX.

MAX.
SEE NOTES 12, 13 & 14.

350

350
FINISHED GROUND LEVEL
COVER TO BE SET IN
150
C50/60 MORTAR
CLASS B ENGINEERING BRICK
SET IN C50/60 MORTAR

150
REFER TO NOTE 2 ON STD-W-13

CONCRETE ROOF SLAB


C30 / 37 REINFORCED SLAB
215mm THICK 20N/mm²
900 MIN.

445 CONCRETE BLOCKWORK 445


IN ACCORDANCE WITH IS EN 771-3
PRECAST
CONCRETE DI, DOUBLE FLANGED,
300 UNITS (REFER TO DN80, RISER PIPE OF
NOTE 5.) SUITABLE LENGTH TO
SUIT SITE CONDITIONS

C25 / 30 PRECAST CONCRETE


100

100
BEARING SLAB
FUSION STUB FLANGE
WITH BACKING CONC. THRUST BLOCK TO BEND OPE TO BE SEALED
WELD (REFER TO DRG. No. STD-W-28 USING A SUITABLE
RING
FOR DETAILS) MATERIAL
80mm DIA.
DOUBLE FLANGED
POLYETHYLENE 90° BEND
(PE) PIPE
POLYETHYLENE TEE
FUSION
WELD
SECTION SECTION
(OR ELECTROFUSION
SADDLE) LONG BODY
FLANGE ADAPTOR 445
80mm DIA. FLANGED 445
PLAIN ENDED PIPE
CUT TO SUIT

75mm HIGH FH 75mm HIGH FH


280

280

LETTERING LETTERING
HEAVY DUTY COVER AND FRAME,
STAMPED '' FH '' CLASS D400
HEAVY DUTY COVER AND FRAME,
(TO SUIT 445 x 280 OPE)
STAMPED '' FH '' CLASS D400
CONCRETE ROOF SLAB (TO SUIT 445 x 280 OPE)
C30 / 37 REINFORCED SLAB
CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB

ROOF PLAN ROOF PLAN


50 100 100 50 50 50
600 215 600 215
50
50

215
100

PRECAST CONCRTETE UNITS


(REFER TO NOTE 5.)
600

600

FIRE HYDRANT
100

215

215mm THICK 20N/mm²


50

CONCRETE BLOCKWORK
IN ACCORDANCE WITH IS EN 771-3
50

FLOOR PLAN FLOOR PLAN


FIRE HYDRANT CHAMBER FIRE HYDRANT CHAMBER
(PRECAST CONCRETE CONSTRUCTION) (BLOCKWORK CONSTRUCTION)

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
Revised & added notes, &
3 11/'17 JMC TOC MOD TITLE DRAWING No. REV
revised pipework
2 08/'16 JMC TOC Revised notes 2, 3 & 6 MOD
OFF - LINE HYDRANT
1 04/'16 JMC TOC Added thrust blocks MOD FOR POLYETHYLENE (P.E.) PIPE STD-W- 19 3
0 09/'15 JMC TOC Initial Issue SL (Sheet 4 of 4)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017

DIAMETER OF MAIN UP TO 250 (mm) 250 TO 350 (mm) 1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
2. AIR VALVE CHAMBERS SHALL BE COVERED WITH APPROVED VENTILATED HEAVY DUTY DUCTILE IRON COVERS TO IS EN 124 RATING D400.
DIAMETER OF BRANCH 80mm 100mm COVER AND FRAME SHALL BE SUITABLE FOR ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
3. AIR VALVES SHALL COMPLY WITH THE REQUIREMENTS OF IS EN 1074-4. AIR VALVES SHALL BE DOUBLE ORIFICE TYPE AND SHALL INCLUDE
AN ISOLATING VALVE. THE ISOLATING VALVE SHALL BE EITHER A GATE VALVE CONFORMING TO IS EN 1074-2 & SHALL BE OF A BOLTLESS
BORE OF VALVE INLET 80mm 100mm
BONNET DESIGN, OR A BUTTERFLY VALVE TO IS EN 1074-2.
4. SERVICE CONNECTIONS SHALL NOT BE PROVIDED WITHIN 2m OF THE AIR VALVE LOCATION.
200 600 200 5. AIR VALVE CHAMBERS TO BE OF PRECAST CONCRETE UNITS OR HIGH DENSITY BLOCKWORK. ALTERNATIVE PROPRIETARY
PREFABRICATED CHAMBER UNITS MAY ALSO BE USED, SUBJECT TO REVIEW BY IRISH WATER.
6. PRECAST CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER STD-W-13.
7. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545.
200
8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS,
DEAD ENDS AND PIPES AT STEEP SLOPES.
10. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
11. THE LOCATION OF THE AIR VALVE SHALL BE THE SUBJECT OF PARTICULAR AGREEMENT WITH IRISH WATER TO ENSURE THAT THE RISK OF
BULL NOSE CONTAMINATION THROUGH THE VALVE IS ELIMINATED.
FINISH 12. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
AV 13. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
600

14. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
15. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE
DEPT. OF TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
200

MAXIMUM
PLINTH DETAIL

250
IN GRASS AREA SEE NOTES 13, 14 & 15.
FINISHED GROUND LEVEL
MAXIMUM

COVER TO BE SET IN COVER TO BE SET IN


C50/60 MORTAR C50/60 MORTAR
250

CLASS B ENGINEERING
BRICK SET IN C50/60
PRECAST CONCRETE UNITS MORTAR 215mm THICK 20N/mm² CONCRETE

REFER TO NOTE 2 ON STD-W-13


(REFER TO NOTE 6.) BLOCKWORK IN ACCORDANCE
WITH IS EN 771-3
DOUBLE AIR VALVE 900 MIN.
DOUBLE AIR VALVE

ISOLATING VALVE ISOLATING VALVE


D.I. RISER PIPE TO SUIT D.I. RISER PIPE TO SUIT
DEPTH OF COVER TO MAIN & DEPTH OF COVER TO MAIN &
TO ENABLE ROTATION OF TO ENABLE ROTATION OF
100

100

HANDLE (90° DOWNWARDS) HANDLE (90° DOWNWARDS)


WITH ENOUGH CLEARANCE WITH ENOUGH CLEARANCE
LOCALLY

LOCALLY
TO CONCRETE BEARING SLAB. REFER TO STD - W- 13 TO CONCRETE BEARING SLAB.
MIN.

MIN.
FOR BEDDING AND
150

150
C25 / 30 PRECAST BACKFILLING DETAILS C25 / 30 PRECAST
CONCRETE BEARING CONCRETE BEARING
SLAB SLAB
DUCTILE IRON DUCTILE IRON
(D.I.) PIPE (D.I.) PIPE

SECTION DUCTILE IRON SOCKETTED TEE WITH SECTION DUCTILE IRON SOCKETTED TEE WITH
FLANGED BRANCH FLANGED BRANCH
1030
800 600
600

AV 75mm HIGH
AV
1030
800

600

600

LETTERING

HEAVY DUTY DUCTILE IRON


COVER AND FRAME, STAMPED
''AV'' CLASS D400 (ALL CLASS
D400 COVERS TO HAVE A FRAME
DEPTH OF 150 - 100mm AND OPE
SIZE TO BE 600mm x 600mm)

ROOF PLAN
ROOF PLAN
900 50 215 600 215 50
50

50 100 100 50
600
50

215
100

PRECAST CONCRETE 215mm THICK 20N/mm²


UNITS CONCRETE BLOCKWORK
(REFER TO NOTE 6.) IN ACCORDANCE WITH IS EN 771-3
900

600

600

DOUBLE DOUBLE
AIR VALVE AIR VALVE
100

215
50

FLOOR PLAN FLOOR PLAN


50

DOUBLE AIR VALVE DOUBLE AIR VALVE


(PRECAST CONCRETE CONSTRUCTION) (BLOCKWORK CONSTRUCTION)
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

2 11/'17 JMC TOC Updated & revised notes MOD


ON - LINE AIR VALVE
1 08/'16 JMC TOC Revised notes 2,3,4 & 7 MOD FOR DUCTILE IRON (D.I.) PIPE STD-W- 20 2
0 09/'15 JMC TOC Initial Issue SL (Sheet 1 of 4)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017

1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.


UP TO 250 (mm) 250 TO 350 (mm) 2. AIR VALVE CHAMBERS SHALL BE COVERED WITH APPROVED VENTILATED HEAVY DUTY DUCTILE IRON COVERS TO IS EN 124 RATING
DIAMETER OF MAIN D400. COVER AND FRAME SHALL BE SUITABLE FOR ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
3. AIR VALVES SHALL COMPLY WITH THE REQUIREMENTS OF IS EN 1074-4. AIR VALVES SHALL BE DOUBLE ORIFICE TYPE AND SHALL
INCLUDE AN ISOLATING VALVE. THE ISOLATING VALVE SHALL BE EITHER A GATE VALVE CONFORMING TO IS EN 1074-2 & SHALL BE OF A
DIAMETER OF BRANCH 80mm 100mm BOLTLESS BONNET DESIGN, OR A BUTTERFLY VALVE TO IS EN 1074-2.
4. SERVICE CONNECTIONS SHALL NOT BE PROVIDED WITHIN 2m OF THE AIR VALVE LOCATION.
BORE OF VALVE INLET 80mm 100mm 5. AIR VALVE CHAMBERS TO BE OF PRECAST CONCRETE UNITS OR HIGH DENSITY BLOCKWORK. ALTERNATIVE PROPRIETARY
PREFABRICATED CHAMBER UNITS MAY ALSO BE USED, SUBJECT TO REVIEW BY IRISH WATER.
6. PRECAST CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER
200 600 200 STD-W-13.
7. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545.
8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
200

9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS,
DEAD ENDS AND PIPES AT STEEP SLOPES.
10. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
11. THE LOCATION OF THE AIR VALVE SHALL BE THE SUBJECT OF PARTICULAR AGREEMENT WITH IRISH WATER TO ENSURE THAT THE
RISK OF CONTAMINATION THROUGH THE VALVE IS ELIMINATED.
BULL NOSE 12. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
FINISH 13. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
AV 14. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
600

15. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY
THE DEPT. OF TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
200

PLINTH DETAIL
IN GRASS AREA
SEE NOTES 13, 14 & 15.
FINISHED GROUND LEVEL
COVER TO BE SET IN
MAXIMUM

MAXIMUM
C50/60 MORTAR
FLANGED
250

250
PLAIN ENDED PIPE CLASS B ENGINEERING BRICK
NOTE 2 ON STD-W-13)

SET IN C50/60 MORTAR


MIN. 900 (REFER TO

CUT TO SUIT
PRECAST CONCRETE UNITS
LONG BODY (REFER TO NOTE 6.)
FLEXIBLE 215mm THICK 20N/mm²
COUPLING CONCRETE BLOCKWORK
LONG BODY 300 IN ACCORDANCE WITH IS EN 771-3
ROCKER
FLANGED ADAPTOR
PIECE DOUBLE AIR VALVE
DOUBLE FLANGED ISOLATING VALVE
90° SHORT RADIUS
BEND CONC. THRUST BLOCK
TO DUCKFOOT BEND
(REFER TO DRG. No.
STD-W-28 FOR DETAILS)
PLAIN ENDED
100

100
PIPE CONCRETE BASE C25 / 30
CUT TO SUIT 75mm CONCRETE
OPE TO BE CLEAN CUT DOUBLE FLANGED BLINDING GRADE
AND SEALED USING SECTION 90° DUCKFOOT BEND C12 / 15
OPE TO BE SEALED SECTION
A SUITABLE MATERIAL USING A SUITABLE
SOCKETED TEE WITH
DOUBLE AIR VALVE MATERIAL DOUBLE AIR VALVE
FLANGED BRANCH 800 1030
600 600

AV 75mm HIGH
AV
1030
800

600

600

LETTERING

HEAVY DUTY DUCTILE IRON


COVER AND FRAME, STAMPED
''AV'' CLASS D400 (ALL CLASS
D400 COVERS TO HAVE A FRAME
DEPTH OF 150 - 100mm AND OPE
SIZE TO BE 600mm x 600mm)
ROOF PLAN
ROOF PLAN
900 50 215 600 215 50
50

50 100 100 50
600
50

215
100

PRECAST CONCRETE
900

UNITS
600

600

(REFER TO NOTE 6.)

DOUBLE AIR VALVE


215mm THICK 20N/mm²
CONCRETE BLOCKWORK
IN ACCORDANCE
100

WITH IS EN 771-3
215
50

50

FLOOR PLAN FLOOR PLAN


DOUBLE AIR VALVE DOUBLE AIR VALVE
(PRECAST CONCRETE CONSTRUCTION) (BLOCKWORK CONSTRUCTION)

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
3 11/'17 JMC TOC Added & updated Notes MOD
2 08/'16 JMC TOC Revised notes 2,3,4 & 7 MOD
OFF - LINE AIR VALVE
1 04/'16 JMC TOC Added thrust blocks MOD FOR DUCTILE IRON (D.I.) PIPE STD-W- 21 3
0 09/'15 JMC TOC Initial Issue SL (Sheet 2 of 4)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017

1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.


2. AIR VALVE CHAMBERS SHALL BE COVERED WITH APPROVED VENTILATED HEAVY DUTY DUCTILE IRON COVERS TO IS EN 124 RATING
DIAMETER OF MAIN UP TO 250 (mm) 250 TO 350 (mm) D400. COVER AND FRAME SHALL BE SUITABLE FOR ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
3. AIR VALVES SHALL COMPLY WITH THE REQUIREMENTS OF IS EN 1074-4. AIR VALVES SHALL BE DOUBLE ORIFICE TYPE AND SHALL INCLUDE
AN ISOLATING VALVE. THE ISOLATING VALVE SHALL BE EITHER A GATE VALVE CONFORMING TO IS EN 1074-2 & SHALL BE OF A BOLTLESS
DIAMETER OF BRANCH 80mm 100mm BONNET DESIGN, OR A BUTTERFLY VALVE TO IS EN 1074-2.
4. SERVICE CONNECTIONS SHALL NOT BE PROVIDED WITHIN 2m OF THE AIR VALVE LOCATION.
5. AIR VALVE CHAMBERS TO BE OF PRECAST CONCRETE UNITS OR HIGH DENSITY BLOCKWORK. ALTERNATIVE PROPRIETARY
BORE OF VALVE INLET 80mm 100mm
PREFABRICATED CHAMBER UNITS MAY ALSO BE USED, SUBJECT TO REVIEW BY IRISH WATER.
6. PRECAST CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER
200 600 200 STD-W-13.
7. DUCTILE IRON PIPES / FITTINGS AND PE PIPES / FITTINGS TO BE IN ACCORDANCE WITH IS EN 545 AND IS EN 12201:2011.
200 8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS,
DEAD ENDS AND PIPES AT STEEP SLOPES.
10. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
11. THE LOCATION OF THE AIR VALVE SHALL BE THE SUBJECT OF PARTICULAR AGREEMENT WITH IRISH WATER TO ENSURE THAT THE RISK
OF CONTAMINATION THROUGH THE VALVE IS ELIMINATED.
BULL NOSE 12. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
FINISH 13. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
AV
600

14. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
15. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY
THE DEPT. OF TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
200

MAXIMUM
PLINTH DETAIL

250
FINISHED GROUND LEVEL
IN GRASS AREA SEE NOTES 13, 14 & 15.
MAXIMUM

COVER TO BE SET IN COVER TO BE SET IN


250

C50/60 MORTAR C50/60 MORTAR


CLASS B ENGINEERING BRICK
SET IN C50/60 MORTAR

REFER TO NOTE 2 ON STD-W-13


PRECAST CONCRETE
UNITS 215mm THICK 20N/mm² CONCRETE
(REFER TO NOTE 6.) BLOCKWORK IN ACCORDANCE
WITH IS EN 771-3
DOUBLE AIR VALVE
900 MIN.
DOUBLE AIR VALVE

ISOLATING VALVE ISOLATING VALVE


D.I. RISER PIPE TO SUIT D.I. RISER PIPE TO SUIT
DEPTH OF COVER TO MAIN & DEPTH OF COVER TO MAIN &
TO ENABLE ROTATION OF TO ENABLE ROTATION OF
100

100

HANDLE (90° DOWNWARDS) HANDLE (90° DOWNWARDS)


WITH ENOUGH CLEARANCE WITH ENOUGH CLEARANCE
LOCALLY

LOCALLY
TO CONCRETE BEARING SLAB TO CONCRETE BEARING SLAB
MIN.

MIN.
REFER TO STD - W- 13
150

150
(RISER CAN BE PE FITTING). (RISER CAN BE PE FITTING).
FOR BEDDING AND
C25 / 30 PRECAST BACKFILLING DETAILS C25 / 30 PRECAST
CONCRETE BEARING CONCRETE BEARING
SLAB POLYETHYLENE POLYETHYLENE SLAB
(P.E.) PIPE (P.E.) PIPE

FUSION WELD FUSION WELD FUSION WELD FUSION WELD


FUSION WELD POLYETHYLENE TEE WITH FLANGED FUSION WELD POLYETHYLENE TEE WITH FLANGED BRANCH
SECTION BRANCH OR ELECTRO FUSION SADDLE SECTION OR ELECTRO FUSION SADDLE
1030
800
600 600

AV 75mm HIGH
AV 75mm HIGH
1030
800

600

600

LETTERING LETTERING

HEAVY DUTY DUCTILE IRON


COVER AND FRAME, STAMPED
''AV'' CLASS D400 (ALL CLASS
D400 COVERS TO HAVE A FRAME
DEPTH OF 150 - 100mm AND OPE
SIZE TO BE 600mm x 600mm)

ROOF PLAN
900 215
ROOF
600
PLAN 215 50
50
50

50 100 100 50
600
50

215
100

215mm THICK 20N/mm² CONCRETE


PRECAST CONCRETE
BLOCKWORK IN ACCORDANCE
UNITS
WITH IS EN 771-3
(REFER TO NOTE 6.)

FITTING FITTING
OPERATION OPERATION
DIAMETER DIAMETER
STANCAD STANCAD
900

600

600

DOUBLE DOUBLE
AIR VALVE AIR VALVE
100

215
50

FLOOR PLAN FLOOR PLAN


50

DOUBLE AIR VALVE DOUBLE AIR VALVE


(PRECAST CONCRETE CONSTRUCTION) (BLOCKWORK CONSTRUCTION)
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

2 11/'17 JMC TOC Added & updated notes MOD


ON - LINE AIR VALVE
1 08/'16 JMC TOC Revised notes 2,3,4 & 7 MOD FOR POLYETHYLENE (P.E.) PIPE STD-W- 22 2
0 09/'15 JMC TOC Initial Issue SL (Sheet 3 of 4)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017

1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.


UP TO 250 (mm) 250 TO 350 (mm) 2. AIR VALVE CHAMBERS SHALL BE COVERED WITH APPROVED VENTILATED HEAVY DUTY DUCTILE IRON COVERS TO IS EN 124 RATING
DIAMETER OF MAIN D400. COVER AND FRAME SHALL BE SUITABLE FOR ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
3. AIR VALVES SHALL COMPLY WITH THE REQUIREMENTS OF IS EN 1074-4. AIR VALVES SHALL BE DOUBLE ORIFICE TYPE AND SHALL
INCLUDE AN ISOLATING VALVE. THE ISOLATING VALVE SHALL BE EITHER A GATE VALVE CONFORMING TO IS EN 1074-2 & SHALL BE
DIAMETER OF BRANCH 80mm 100mm OF A BOLTLESS BONNET DESIGN, OR A BUTTERFLY VALVE TO IS EN 1074-2.
4. SERVICE CONNECTIONS SHALL NOT BE PROVIDED WITHIN 2m OF THE AIR VALVE LOCATION.
BORE OF VALVE INLET 80mm 100mm 5. AIR VALVE CHAMBERS TO BE OF PRECAST CONCRETE UNITS OR HIGH DENSITY BLOCKWORK. ALTERNATIVE PROPRIETARY
PREFABRICATED CHAMBER UNITS MAY ALSO BE USED, SUBJECT TO REVIEW BY IRISH WATER.
6. PRECAST CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER
STD-W-13.
200 600 200 7. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545. PE PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS
EN 12201:2011.
8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
200

9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS,
TAPERS, DEAD ENDS AND PIPES AT STEEP SLOPES.
10. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
11. THE LOCATION OF THE AIR VALVE SHALL BE THE SUBJECT OF PARTICULAR AGREEMENT WITH IRISH WATER TO ENSURE THAT THE
RISK OF CONTAMINATION THROUGH THE VALVE IS ELIMINATED.
BULL NOSE
12. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
FINISH
AV 13. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
600

14. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
15. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS"
BY THE DEPT. OF TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
200

PLINTH DETAIL
IN GRASS AREA
SEE NOTES 13, 14 & 15.
FINISHED GROUND LEVEL
REFER TO NOTE 2 ON STD-W-13

COVER TO BE SET IN
MAXIMUM

MAXIMUM
C50/60 MORTAR CLASS B
250

250
CLASS B ENGINEERING BRICK
SET IN C50/60 MORTAR ENGINEERING
PRECASTCONCRETE UNITS BRICK SET IN
C50/60
900 MIN.

FLANGED PLAIN ENDED PIPE (REFER TO NOTE 6.)


MORTAR
CUT TO SUIT
215mm THICK 20N/mm²
CONCRETE BLOCKWORK
300 IN ACCORDANCE WITH IS EN 771-3
FUSION STUB FLANGE
WELD WITH BACKING DOUBLE AIR VALVE
RING ISOLATING VALVE

CONC. THRUST BLOCK


TO DUCKFOOT BEND
(REFER TO DRG. No.
90° POLYETHYLENE BEND STD-W-28 FOR DETAILS)
100

100
FUSION
WELD FUSION CONCRETE FLOOR SLAB
WELD C25 / 30 REINFORCED SLAB
LONG BODY DOUBLE FLANGED
POLYETHYLENE TEE 75mm CONCRETE BLINDING
FLANGE ADAPTOR 90° DUCKFOOT BEND
(OR ELECTROFUSION GRADE C12 / 15
SADDLE) OPE TO BE CLEAN CUT SECTION OPE TO BE SEALED
USING A SUITABLE
SECTION
AND SEALED USING
MATERIAL
A SUITABLE MATERIAL
800 1030
600 600

AV 75mm HIGH
AV
1030
800

600

600

LETTERING

HEAVY DUTY DUCTILE IRON


COVER AND FRAME, STAMPED
''AV'' CLASS D400 (ALL CLASS
D400 COVERS TO HAVE A FRAME
DEPTH OF 150 - 100mm AND OPE
SIZE TO BE 600mm x 600mm)
ROOF PLAN
ROOF PLAN
900 50 215 600 215 50
50

50 100 100 50
600
50

215
100

PRECAST CONCRETE
900

600

600

UNITS
(REFER TO NOTE 6.)

DOUBLE AIR VALVE


215mm THICK 20N/mm²
CONCRETE BLOCKWORK
IN ACCORDANCE
100

WITH IS EN 771-3
215
50

50

FLOOR PLAN FLOOR PLAN


DOUBLE AIR VALVE DOUBLE AIR VALVE
(PRECAST CONCRETE CONSTRUCTION) (BLOCKWORK CONSTRUCTION)

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
3 11/'17 JMC TOC Added & updated notes MOD
2 08/'16 JMC TOC Revised notes 2,3,4 & 7 MOD
OFF - LINE AIR VALVE
1 04/'16 JMC TOC Added thrust blocks MOD FOR POLYETHYLENE (P.E.) PIPE STD-W- 23 3
0 09/'15 JMC TOC Initial Issue SL (Sheet 4 of 4)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
MANHOLE STEPS TO COMPLY HINGED 4 LEAF HEAVY 1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
WITH IS EN 13101, TYPE D, CLASS DUTY COVER AND FRAME, 2. STRUCTURAL DESIGN AND REINFORCEMENT DETAIL TO BE PROVIDED BY THE
1, GALVANISED MILD STEEL & STAMPED '' PRV '' CLASS DEVELOPER AND SUBMITTED TO IRISH WATER FOR REVIEW.
PLASTIC ENCAPSULATED. D400 TO IS EN 124 3. CONCRETE FOR PRESSURE REDUCING / SUSTAINING CHAMBER TO BE C30 / 37. ROOF
SEE NOTES 14, 15 & 16.
SLABS SHALL BE DESIGNED TO CARRY ALL LIVE LOADS & DEAD LOADS, & CONSIST OF
PRECAST A REINFORCED CONCRETE SLAB OF IN-SITU CONCRETE, GRADE C30/37, WITH A
CONCRETE COVER TO BE SET IN 1 No. MIN., 3 No. MAX.

675 (MAX.)
MINIMUM THICKNESS OF 225mm. ALTERNATIVELY, PRE-CAST CONCRETE ROOFS MAY
ROOF SLAB C50/60 MORTAR COURSES OF CLASS B BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911, Part 4.
ENGINEERING BRICKS SET IN 4. PRECAST UNITS COMPLETED WITH RUBBER SEALING GASKET BETWEEN UNITS,
FINISHED GROUND LEVEL
C50/60 MORTAR COMPLYING WITH THE REQUIREMENTS OF IS EN 1917 AND BS 5911-PART 3, COMPLETE
WITH 150mm CONCRETE SURROUND MAY BE USED AS AN ACCEPTABLE ALTERNATIVE.
900 MIN. (REFER TO
NOTE 2 ON STD-13)

CABLE DUCTS WITH CONCRETE SURROUND TO BE GRADE C16/20 IN ACCORDANCE WITH IS EN 206.
DRAW CORDS AS SPECIFIED 5. PRESSURE REDUCING VALVES REQUIRE A MINIMUM LENGTH OF PIPE EQUIVALENT TO 5
225 TO KIOSK (REFER TO STD-W-29) TIMES THE DIAMETER, ON EACH SIDE OF THE VALVE TO BE COMPLETELY FREE OF
LONG BODY
FLEXIBLE LONG BODY FITTINGS, VALVES, REDUCERS ETC., OR TO PRV/PSV MANUFACTURER'S
300
COUPLING FLEXIBLE COUPLING REQUIREMENTS.
MIN.
6. P.R.V. / P.S.V. CHAMBER SHALL BE COVERED WITH APPROVED HEAVY DUTY METAL
COVERS TO IS EN 124 RATING D400. COVER AND FRAME SHALL BE SUITABLE FOR
FLOW FLOW ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
7. 200mm ALL ROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GRASS
AREAS.

MIN.
300
8. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
FLANGED PLAIN ENDED 9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD
250

PIPE WITH THRUST FLANGE DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS AND PIPES AT STEEP
ROCKER PIPE SLOPES.
WATER TIGHT SEAL
10. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545. PE PIPES
FLANGED PLAIN ENDED VARIES
250 250 THICKENED FLOOR AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 12201:2011
PIPE WITH THRUST FLANGE
BENEATH SUMP 11. ALL CHAMBERS TO BE CHECKED FOR UPLIFT BY THE DEVELOPER, BASED ON GROUND
75mm CONCRETE BLINDING DISMANTLING CONCRETE CAST STRAINER PRESSURE REDUCING / CONDITIONS WITHIN THE SITE, SHOULD ANTI-FLOTATION MEASURES BE REQUIRED
GRADE C12 / 15 JOINT IN-SITU CRADLE SUSTAINING VALVE THEY SHALL BE SUBJECT TO REVIEW BY IRISH WATER.
12. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
13. PIPEWORK TO BE DOWNSIZED IF REQUIRED TO ACCOMMODATE THE REQUIRED RANGE
SECTION OF PRESSURE REDUCTION.
14. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD
AUTHORITY'S REQUIREMENTS.
VARIES
15. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY
REQUIREMENTS.
16. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES
FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF TRANSPORT, TOURISM &
SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
CAST-IN RECESSED
LIFTING EYES
OPENING TO ALLOW
FOR PRV TO BE LIFTED HINGED 4 LEAF HEAVY STUB FLANGE
IN & OUT VERTICALLY DUTY COVER AND FRAME, WITH BACKING
STAMPED '' PRV '' CLASS RING
VARIES

D400 TO IS EN 124 400

PRV PRV
3 No. COURSES MAX. OR DI PE
1 No. COURSE MINIMUM
OF ENGINEERING BRICKWORK

CONCRETE ROOF SLAB


C30 / 37 REINFORCED SLAB

PE TO DI DETAIL
ROOF PLAN
VARIES

250 VARIES 250 CABLE DUCTS WITH DRAW CORDS


400 x 400 x 200mm AS SPECIFIED TO KIOSK
DEEP SUMP (REFER TO STD-W-29) MARK No. DESCRIPTION
250

1 FLANGED PLAIN ENDED PIPE (STANDARD)


2 ALL FLANGED TEE
3 (DIA. VARIES) SLUICE VALVE
300 4 (DIA. VARIES) LONG BODY FLEXIBLE COUPLING
VARIES

VARIES

400 MIN. 400 WATER TIGHT SEAL 5 (DIA. VARIES) DISMANTLING JOINT
6 FLANGED PLAIN ENDED PIPE (CUT TO SUIT)
7 90° DEGREE SOCKETED BEND
FLOW FLOW 8 PLAIN ENDED PIPE (CUT TO SUIT)
9 SPIGOT & SOCKET PIPE (STANDARD)
10 FLANGED PLAIN ENDED PIPE (CUT TO SUIT)
MIN.
300

11 (DIA. VARIES) PLAIN ENDED PIPE (CUT TO SUIT)


ROCKER PIPE
12 DOUBLE FLANGED TAPER ( WHERE REQUIRED )
250

13 SOCKETED TEE WITH FLANGED BRANCH & HYDRANT

FLOOR PLAN KIOSK

HYDRANT PRV INTERNAL


DIAMETER COVER
(REFER TO CHAMBER
STD-W-16) 'A' (mm) DIMENSIONS
DIMENSIONS

4 4 4 4 50 - 100 1500 x 1200 1200 x 600


7 8 8 8 7

101 - 250 2200 x 1500 1800 x 900


13 8 8 8
6
PRESSURE REDUCING / AIR VALVE
SUSTAINING VALVE CHAMBER (REFER TO
STD-W-20) 6 HYDRANT
(REFER TO STD-W-16,
5 5 17, 18 & 19)
3 3
12 12
4 1 5 4

1 2 1 9 4 10 1 2 1 13 11 9
3

TYPICAL BYPASS ARRANGEMENT


REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
Revised & added notes, & added
2 11/'17 JMC TOC chamber sizing table, fittings & kiosk MOD TITLE DRAWING No. REV

Added steps, moved sump PRESSURE REDUCING / SUSTAINING VALVE


1 08/'16 JMC TOC & revised cover notes MOD
STD-W- 24 2
0 09/'15 JMC TOC Initial Issue SL (P.R.V. / P.S.V.) CHAMBER
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017

1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.

VARIES 2. DETAILS OF THE PROPOSED BOOSTING ARRANGEMENT SHALL BE PROVIDED TO IRISH


WATER AT CONNECTION APPLICATION STAGE AND AT THE DETAILED DESIGN STAGE OF
THE DEVELOPMENT FOR ASSESSMENT.

3. KIOSK TO BE CONSTRUCTED FROM THERMOSETTING U.V. & WEATHER RESISTANT PLASTIC


POWDER COATED & HOT DIPPED GALVANISED STEEL (MINIMUM 4mm THICKNESS) IN
ACCORDANCE WITH BS EN 1461. STAINLESS STEEL OR NON-METALLIC MATERIALS, SUCH
TOP VENT ON AS GLASS REINFORCED PLASTIC (GRP), MAY BE USED AS AN ALTERNATIVE KIOSK
OPPOSITE SIDE MATERIAL, PARTICULARLY IN SEVERE ENVIRONMENTS, SUBJECT TO AGREEMENT WITH
IRISH WATER.

4. KIOSK TO HAVE SINGLE OR DOUBLE STEEL/GRP DOORS WITH MULTIPLE LOCKS TO LPS 1175
SR4 OR EN 1627. MINIMUM DOUBLE LOCKS WITH BOLTS THAT ENGAGE INTO THE SILL &
VENT HEADER AS WELL AS BETWEEN THE TWO LEAVES OR LEAF & FRAME. LEADING EDGE OF
LEAVES TO HAVE EITHER REBATED EDGES OR FITTED WITH ASTRAGALS.

EX. G.L. 5. COLOUR TO BE HOLLY GREEN 14 C 39 IN ACCORDANCE WITH BS 4800:2011.

6. THE QUALITY OF KIOSK CONSTRUCTION SHALL ENSURE THAT THE FOLLOWING IS


ACHIEVED:
VARIES

(b) A FIRE RESISTANCE (RETENTION OF STABILITY, INTEGRITY AND INSULATION)


EQUIVALENT TO CLASS 2 OF BS 476, WHEN TESTED IN ACCORDANCE WITH BS 476 FOR
A PERIOD EXCEEDING 30 MINUTES.
(c) AN IP RATING OF IP65 OR EQUIVALENT.

7. ALL DUCTING TO BE INSTALLED WITH DRAW CORDS.


VARIES
8. WATER TIGHT SEALS TO BE PROVIDED AROUND ALL DUCTING ENTERING/EXITING THE
BOOSTER PUMP STATION.

9. CONCRETE PATH NOTE AS PER THE KIOSK DRAWING STD-W-36.

10. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.

11. BOOSTER PUMPS TO BE LOCATED IN IN AREA THAT IS NOT PRONE TO FLOODING.


PREFABRICATED
2000

KIOSK 12. PROVISION TO BE MADE IN THE SIZING OF THE KIOSK FOR THE SAFE REPAIR/MAINTENANCE
OF THE BOOSTER PUMPS & FOR THEIR REMOVAL IF REQUIRED.

EX. G.L.

CONCRETE
150

VARIES
PLINTH

BOOSTER PUMPS
(DUTY / STANDBY OR
DUTY/ASSIST) 450mm CONCRETE PLINTH
GRADE C25/30 TO SUIT
2000

CONCRETE PATH PUMP ARRANGEMENT


REFER TO NOTE 8
FOR DETAILS
EXISTING
GROUND
LEVEL
450

TELEMETRY AND POWER DUCTS TO KIOSK


(REFER TO DRAWING STD-W-36 FOR KIOSK DETAILS)

600 VARIES 600


INLET
75mm THICK
CONCRETE WATER MAIN
BLINDING
GRADE C12/ 25

600 150 VARIES 150 600


600

OUTLET
150

WATER MAIN

TELEMETRY AND POWER DUCTS TO KIOSK


(REFER TO DRAWING STD-W-36 FOR KIOSK DETAILS)
VARIES

INLET
150

WATER MAIN
600

BOOSTER PUMPS
(DUTY / STANDBY OR
DUTY/ASSIST)

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

1 08/'16 JMC TOC Added note 4 BOOSTER PUMP STATION ARRANGEMENT


0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017

1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.


2. STRUCTURAL DESIGN AND REINFORCEMENT DETAIL TO BE PROVIDED BY THE DEVELOPER AND SUBMITTED TO IRISH WATER FOR REVIEW. ROOF SLABS SHALL BE DESIGNED TO CARRY
ALL LIVE LOADS & DEAD LOADS, & CONSIST OF A REINFORCED CONCRETE SLAB OF IN-SITU CONCRETE, GRADE C30/37, WITH A MINIMUM THICKNESS OF 225mm. ALTERNATIVELY, PRE-CAST
CONCRETE ROOFS MAY BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911, Part 4.
3. CONCRETE FOR FLOW METER CHAMBER TO BE C30 / 37.
4. PRECAST UNITS COMPLETED WITH RUBBER SEALING GASKET BETWEEN UNITS, COMPLYING WITH THE REQUIREMENTS OF IS EN 1917 AND BS 5911-PART 3, COMPLETE WITH 150mm
CONCRETE SURROUND MAY BE USED AS AN ACCEPTABLE ALTERNATIVE. CONCRETE SURROUND TO BE GRADE C16/20 IN ACCORDANCE WITH IS EN 206.
5. METER CHAMBER SHALL BE COVERED WITH APPROVED HEAVY DUTY METAL COVERS TO IS EN 124 RATING D400. COVER AND FRAME SHALL BE SUITABLE FOR ROAD AND TRAFFIC
CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
6. 200mm ALL ROUND, 100mm DEEP CONCRETE PLINTH AROUND COVER IN GRASS AREAS.
7. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
8. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545. PE PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 12201:2011.
9. ALL CHAMBERS TO BE CHECKED FOR UPLIFT BY THE DEVELOPER BASED ON GROUND CONDITIONS WITHIN THE SITE. SHOULD ANTI FLOATATION MEASURES BE REQUIRED THEY SHALL BE
SUBJECT TO REVIEW BY IRISH WATER.
10. PIPEWORK TO BE DOWNSIZED TO ACCOMMODATE THE REQUIRED RANGE OF THE FLOW METER. STRAIGHT PIPE LENGTHS UPSTREAM AND DOWNSTREAM OF THE METER TO BE PROVIDED.
THE METER SHALL BE CAPABLE OF ACCURATE NIGHT FLOW MEASUREMENTS.
11. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
12. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
13. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
14. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF TRANSPORT, TOURISM & SPORT, OR
TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
HEAVY DUTY COVER AND
FRAME, STAMPED '' Me ''
CLASS D400 TO IS EN 124 COVER TO BE SET IN
SEE NOTES 12, 13 & 14. (OPE VARIES, SEE TABLE) C50/60 MORTAR

675 (MAX.)
CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB
1 No. MIN. OR 3 No. COURSES MAX.OF CLASS B
FINISHED GROUND LEVEL ENGINEERING BRICKWORK SET IN C50/60 MORTAR

MANHOLE STEPS TO COMPLY WITH IS EN 13101, TYPE D,


NOTE 2 ON
(REFER TO

CLASS 1, GALVANISED MILD STEEL & PLASTIC ENCAPSULATED.


900 MIN.

STD-13)

225

WATER TIGHT SEAL OFF-LINE DISMANTLING


VARIES. HYDRANT JOINT
MINIMUM x 5 DIAMETER (REFER TO
FLANGED / PLAIN DI FLANGED MINIMUM x 10 DIAMETER STD-W-17) DI FLANGED FLANGED / PLAIN
ENDED PIPE CUT TAPER DISMANTLING NON MECH. 300 LONG BODY TAPER ENDED PIPE CUT
LONG BODY
TO SUIT JOINT FLOW METER MIN. FLEXIBLE JOINT TO SUIT
FLEXIBLE JOINT 400
400

FLOW MIN. FLOW


300

ROCKER PIPE ROCKER PIPE


250

LONG BODY SLUICE VALVE SLUICE VALVE LONG BODY


(REFER TO STD-W-14) D.I. FLANGED D.I. PLAIN ENDED PIPE LEVEL (REFER TO STD-W-14)
FLEXIBLE WITH THRUST FLANGE INVERT FLEXIBLE
PLAIN ENDED PIPE
COUPLING (CUT TO SUIT) TEE COUPLING
FLANGED PLAIN WITH THRUST FLANGE 250 VARIES 250 FLANGED PLAIN
ENDED DI PIPE (CUT TO SUIT) ENDED DI PIPE
DISMANTLING
THICKENED FLOOR CONCRETE CAST 75mm CONCRETE JOINT
SLAB UNDER SUMP IN-SITU CRADLE BLINDING
C12 / 15

SECTION
METER INTERNAL
DIAMETER COVER
CHAMBER
'A' (mm) DIMENSIONS
DIMENSIONS
VARIES
50 - 100 1200 x 1200 750 x 750

101 - 250 1500 x 1500 900 x 900


CAST-IN RECESSED LIFTING EYES

PE STUB FLANGE DI FLANGED HEAVY DUTY COVER AND FRAME,


VARIES

WITH BACKING RING TAPER STAMPED '' Me '' CLASS D400 TO IS


EN 124 (OPE SIZE VARIES)
Me
1 No. MIN. OR
3 No. COURSES MAX.OF CLASS B
ENGINEERING BRICKWORK
SET IN C50/60 MORTAR

CONCRETE ROOF SLAB


C30 / 37 REINFORCED
CONCRETE SLAB
PE TO DI DETAIL ROOF PLAN
SUMP 400mm x 400mm
VARIES
x 200mm DEEP OFF-LINE HYDRANT
250 VARIES 250 FOR METER
CALIBRATION
(REFER TO STD-W-17)
250

WATER TIGHT SEAL

300
VARIES

VARIES

400 MIN. 400

FLOW FLOW
MIN.
300

THRUST FLANGE
250

LEVEL SLUICE
SLUICE VALVE 25mm O.D. TAPPING TO BE INVERT TEE VALVE
PROVIDED
CABLE DUCT TO KIOSK PRESSURE TAPPING DUCT TO KIOSK
TO BE INSTALLED TO BE INSTALLED
WITH DRAW CORD WITH DRAW CORD
(REFER TO STD-W-36) (REFER TO STD-W-36)
DUCT END TO BE SEALED DUCT END TO BE SEALED

FLOOR PLAN

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
Revised notes & added table
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
3 11/'17 JMC TOC MOD
& hydrant TITLE DRAWING No. REV
2 08/'16 JMC TOC Added steps & revised MOD
cover notes
1 04/'16 JMC TOC Added couplings to details MOD NON-MECH. METER CHAMBER (40 - 250mm DIA.) STD-W- 26 3
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
2. STRUCTURAL DESIGN AND REINFORCEMENT DETAIL TO BE PROVIDED BY THE DEVELOPER AND SUBMITTED TO IRISH WATER FOR REVIEW. ROOF SLABS SHALL BE DESIGNED TO CARRY ALL LIVE LOADS & DEAD LOADS, & CONSIST OF
A REINFORCED CONCRETE SLAB OF IN-SITU CONCRETE, GRADE C30/37, WITH A MINIMUM THICKNESS OF 225mm. ALTERNATIVELY, PRE-CAST CONCRETE ROOFS MAY BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH
BS 5011, Part 4.
3. CONCRETE FOR CHAMBERS TO BE C30 / 37.
4. PRECAST UNITS COMPLETED WITH RUBBER SEALING GASKET BETWEEN UNITS, COMPLYING WITH THE REQUIREMENTS OF IS EN 1917 AND BS 5911-PART 3, COMPLETE WITH 150mm CONCRETE SURROUND MAY BE USED AS AN
ACCEPTABLE ALTERNATIVE. CONCRETE SURROUND TO BE GRADE C16/20 IN ACCORDANCE WITH IS EN 206.
5. CHAMBERS SHALL BE COVERED WITH APPROVED HEAVY DUTY METAL COVERS TO IS EN 124 RATING D400. COVER AND FRAME SHALL BE SUITABLE FOR ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
6. 200mm ALL ROUND, 100mm DEEP CONCRETE PLINTH AROUND COVER IN GRASS AREAS.
7. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
8. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545. PE PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 12201:2011.
9. ALL CHAMBERS TO BE CHECKED FOR UPLIFT BY THE DEVELOPER BASED ON GROUND CONDITIONS WITHIN THE SITE. SHOULD ANTI FLOATATION MEASURES BE REQUIRED THEY SHALL BE SUBJECT TO REVIEW BY IRISH WATER.
10. PIPEWORK TO BE DOWNSIZED TO ACCOMMODATE THE REQUIRED RANGE OF THE FLOW METER. STRAIGHT PIPE LENGTHS UPSTREAM AND DOWNSTREAM OF THE METER TO BE PROVIDED. IF THE METER IS NOT CAPABLE OF
ACCURATE NIGHT FLOW MEASUREMENTS, A BY-PASS FLOW METER SHALL BE PROVIDED WITH APPROPRIATE VALVES, FITTINGS AND PIPEWORK.
11. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
12. A SINGLE METER CHAMBER MAY BE USED, WHERE APPLICABLE, TO THE METER SUPPLIER'S REQUIREMENTS, TO LOCATE BOTH THE METER & STRAINER.
13. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
14. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
15. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND
REQUIREMENTS.

HINGED DOUBLE LEAF HEAVY


MANHOLE STEPS TO COMPLY WITH IS EN 13101, COVER TO BE SET
SEE NOTES 13, 14 & 15. DUTY COVER AND FRAME, 1 No. MIN. OR 3 No.
TYPE D, CLASS 1, GALVANISED MILD STEEL & IN C50/60 MORTAR
STAMPED '' Me '' CLASS D400 COURSES MAX.OF CLASS B
CONCRETE ROOF SLAB PLASTIC ENCAPSULATED.
C30 / 37 REINFORCED SLAB ENGINEERING BRICKWORK
SET IN C50/60 MORTAR
WATER TIGHT SEAL MANHOLE STEPS TO COMPLY WITH
900 MINIMUM

600 MAX. IS EN 13101, TYPE D, CLASS 1,


GALVANISED MILD STEEL &
225

LONG
PLASTIC ENCAPSULATED.
VARIES BODY VARIES
DI FLANGED FLEXIBLE
OFF-LINE
FLANGED / PLAIN TAPER JOINT DISMANTLING DI FLANGED
HYDRANT
ENDED PIPE CUT (IF REQUIRED) TAPER
LONG BODY 600 MAX. 300 (REFER TO JOINT
TO SUIT STRAINER MIN. MECH. METER
FLEXIBLE JOINT STD-W-17)

FLOW

ROCKER PIECE
MIN.
300

(0.6m TYPICAL)
DISMANTLING
ROCKER PIECE
250

LONG BODY SLUICE VALVE JOINT (0.6m TYPICAL) SLUICE VALVE


(REFER TO D.I. FLANGED DISMANTLING LEVEL
FLEXIBLE (REFER TO
STD-WNMP-14) PLAIN ENDED PIPE JOINT INVERT
COUPLING STD-W-14)
WITH THRUST FLANGE VARIES 250 TEE
250
(CUT TO SUIT)
CONCRETE CAST
THICKENED FLOOR 75mm CONCRETE IN-SITU CRADLE
SLAB UNDER SUMP MINIMUM x 5 DIAMETER
BLINDING Min 5 x Dia.
C12 / 15

PE STUB FLANGE DI FLANGED


SECTION
WITH BACKING RING TAPER D.I. PLAIN ENDED
PIPE WITH
THRUST FLANGE
(CUT TO SUIT)

CAST-IN RECESSED LIFTING EYES

PE TO DI DETAIL HINGED DOUBLE LEAF HEAVY DUTY COVER


AND FRAME, STAMPED '' Me '' CLASS D400
(OPE SIZE VARIES)
Me Me
1 No. MIN. OR 3 No.
COURSES MAX.OF CLASS B
ENGINEERING BRICKWORK
SET IN C50/60 MORTAR

CONCRETE ROOF SLAB


C30 / 37 REINFORCED
CONCRETE SLAB
ROOF PLAN
SUMP 400mm
x 400mm x VARIES VARIES
25mm O.D. TAPPING
200mm DEEP TO BE PROVIDED
250 VARIES 250 250 VARIES 250
CABLE DUCT TO KIOSK TO BE INSTALLED
CABLE WITH DRAW CORD (UP TO 20m)
250

DUCTING (REFER TO STD-WNMP-36)


DUCT END TO BE SEALED
600 MAX.
OFF-LINE HYDRANT
300 300 FOR METER
VARIES
VARIES

MIN. MIN. CALIBRATION


(REFER TO STD-W-17)
MIN.
MIN.
300

300

SLUICE VALVE
250

LEVEL
INVERT TEE
600 MAX.
600 MAX.

THRUST FLANGE FLOOR PLAN

METER INTERNAL
DIAMETER COVER
CHAMBER
'A' (mm) DIMENSIONS
DIMENSIONS

50 - 100 1200 x 1200 750 x 750

101 - 250 1500 x 1500 900 x 900

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE JUN. 2017
TITLE DRAWING No. REV

MECH. METER CHAMBER (40 - 250mm DIA.) STD-W-26A 0 25mm O.D. TAPP
0 11/'17 JMC TOC Initial Issue MOD PROVIDED
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. WHERE PRACTICAL MARKER PLATES SHALL BE FIXED TO
265 100 ADJACENT WALLS OR ALTERNATIVELY ATTACHED TO MARKER
3 No. H6 BARS POSTS.

2. PLATES TO BE FIXED IN POSITION USING WALL PLUGS AND


STAINLESS STEEL SCREWS.
MARKER
PLATE 3. MARKER PLATES TO BE MANUFACTURED IN ACCORDANCE WITH
BS 3251.
660

660
4. FOR HYDRANT PLATE ALL CHARACTERS SHOULD BE BLACK AND
3 No. H6 BARS THE REMAINDER OF THE FRONT FACE SHOULD CONFORM TO
COLOUR REFERENCE No. 309 (CANARY YELLOW) OF BS 381C.

5. PIPE DIAMETER ON HYDRANT PLATE TO REFER TO WATERMAIN


NOT BRANCH.
1110

1110
6. SLUICE VALVE, AIR VALVE, SCOUR VALVE, WASHOUT HYDRANT
AND METER PLATES SHOULD BE CAST IRON. ALL CHARACTERS
SHOULD BE BLACK ON WHITE PAINT BACKGROUND.
ALTERNATIVE MATERIAL MAY BE USED SUBJECT TO
ACCEPTANCE BY IRISH WATER.
450

450
CONCRETE 7. CONCRETE SURROUND TO MARKER POST TO BE GRADE C25 / 30
SURROUND AND IN ACCORDANCE WITH IS EN 206/2013.

8. PLASTIC MARKER POSTS ARE NOT ACCEPTABLE.


100

100
9. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.

100 100 100 100


465 300

ELEVATION SECTION REINFORCEMENT


265
DETAILS
100

PLAN

DIAMETER OF WATERMAIN
(100mm) - 40mm HIGH TEXT
180

H 100
50
205

160

2
50

DISTANCE OF MARKER
FROM HYDRANT
(2m) - 40mm HIGH TEXT

HYDRANT
180

100 100 100 100


40

AV WM SV WO
205

80

2 2 2 2
WASHOUT
AIR VALVE WATER MAIN SLUICE VALVE
HYDRANT

100 100 100 100


PRV
ScV PSV Me BM
2 2 2 2
SCOUR VALVE PRESSURE REDUCING/SUSTAINING METER BULK METER
VALVE

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

2 11/'17 JMC TOC Added BM plate & updated notes MOD


1 04/'16 JMC TOC Added washout hydrant plate MOD MARKER POSTS / PLATES STD-W- 27 2
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
A/2 A/2 B/2 B/2 (A or B)/2 (A or B)/2 FLEXIBLE COMPRESSIBLE STAINLESS
FILLER MATERIAL STEEL STRAPS
STAINLESS STEEL

E
E

E
ANCHOR BOLTS

NTS
1000

G/2
2
25x25mm CHAMFER

G/2
GRADE C25 / 30 MASS

50 MIN.
50 MIN.
50 MIN.
CONCRETE SUPPORT

G/2
BLOCK
50 MIN.

G/2
0
100
90 DEGREE BEND 45 DEGREE BEND NTS BEND WITH EXTENSION PIECES DOWEL BARS
C/2 C/2 D/2 D/2 E 50 MIN.

VARIES (MIN. 300 + O.D.)

20
VARIES

0
TEE E VARIES E
CONCRETE

E
THRUST

E
FLANGE TEE WITH EXTENSION PIECES PLINTH PIPE PLINTH SUPPORT (ABOVE GROUND)
R
TE

F/2
WA IN ROAD SURFACE
GROUND A

50 MIN.
M

50 MIN.
SURFACE REINFORCEMENT

F/2
300

VARIES
PROFILE TO DEVELOPER'S

DN x 2.5
300
VARIES

SECTIONAL ELEVATION FOR BEND OR TEE DETAILS


22.5 DEGREE BEND 11.25 DEGREE BEND TRENCH
G/2
500

200
COLLAR

F/2
100 DN x 2.5 100 BOTTOM
HORIZONTAL BENDS
LONGITUDINAL SECTION PIPE DI PE DI PE
TRENCH

DN / 2 DN DN / 2

F/2
300

150
PIPE SUPPORT DETAILS FOR
IW-CDS-5020-01 Rev. 03 December 2017

300 300

200
ELEVATION
G/2

INCLINED SLOPES, FOR PIPE


300 GRADIENT > 10° TO HORIZONTAL. PLAN SECTION
SUPPORTS PLACED AT MAX. 5 THRUST BLOCK FOR

300
WATER METER INTERVALS CENTRE TO
MAIN DUCTILE IRON TO POLYETHYLENE CHANGE OVER

F/2
CENTRE ALONG PIPE WHERE PIPE
IS ON SLOPE. MIN. 1 SUPPORT

E
F/2
REQUIRED FOR PIPE 1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.

H, J, or K
200
LENGTH > 3 METERS IN SLOPE.
300

2. CONCRETE THRUST BLOCKS (ANCHORAGE) SHALL BE POSITIONED SYMMETRICALLY


C ELEVATION 100 DN x 2 100 PLAN WITH RESPECT TO THE CONNECTING PIPE & BENDS.
H, J or K 3. TRENCH DIMENSIONS : REFER TO DRAWING No's. STD-W-13.
ELEVATION CROSS - SECTION TAPER 4. THRUST BLOCKS SHALL BEAR ON UNDISTURBED SOIL. IF FOR ANY REASON THEY
STEEL ELEVATION PIPE SUPPORT DETAILS FOR INCLINED SLOPES
E CANNOT THEN THE DEVELOPER SHALL NOTIFY IRISH WATER IMMEDIATELY WITH A
ANCHOR PROPOSED SOLUTION.
SURFACE BOX ROAD SURFACE
STRAPS 5. THRUST BLOCK REINFORCEMENT REQUIRES SPECIFIC DESIGN.
300
6. FOR TEST PRESSURES GREATER THAN 18 BAR, THRUST BLOCK DESIGN IS TO BE

G/2
TRENCH

G/2
SUBMITTED TO IRISH WATER FOR REVIEW.
VARIES

BOTTOM 7. THRUST BLOCKS ARE DESIGNED FOR AN AVERAGE BEARING PRESSURE OF 100 KN/m
THRUST
500

FLANGE (TYPICAL FOR SOFT CLAY) FOR OTHER CONDITIONS. ACTUAL DIMENSIONS MAY BE

G/2
PIPE
ALTERED ON INSTRUCTIONS FROM IRISH WATER.

TRENCH

F/2 F/2
8. CONCRETE IN THRUST BLOCKS SHALL BE GRADE C20/25.

H, J, or K
PLAN
PLAN 9. COMPRESSIBLE FILLER FOR CONCRETE PROTECTION TO BE IN ACCORDANCE WITH BS
PLAN NOTE:

G/2
ANTI-TORQUE EN 622-1 AND BS EN 622-4. BITUMINOUS MATERIAL SHALL NOT BE PUT IN CONTACT WITH
300

CONCAVE BEND CONVEX BEND H FOR 45 DEGREE BEND J 500


SUPPORT 300 PLASTIC PIPES. THE THICKNESS OF COMPRESSIBLE FILLER FOR MAINS < 450mm IN
FOR 22.5 DEGREE BEND K PLAN DIAMETER IS TO BE 18mm.
FOR 11.25 DEGREE BEND DEAD END THRUST BLOCK FOR SLUICE VALVE / GATE VALVE SECTION
VERTICAL BENDS 10. CONCRETE THRUST BLOCKS FOR POLYETHYLENE PIPE TO COMPLY WITH THE
FOR VALVE BOX ARRANGEMENT MANUFACTURES REQUIREMENTS.
11. POLYETHYLENE PIPES SHALL BE WRAPPED IN PLASTIC SHEETING HAVING A
< 12 BAR TEST PRESSURE 12 BAR TO 15 BAR TEST PRESSURE 15 BAR TO 18 BAR TEST PRESSURE COMPOSITION IN ACCORDANCE WITH BS 6076 BEFORE BEING CAST INTO CONCRETE.
12. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
NOM. DIMENSIONS NOM. DIMENSIONS NOM. DIMENSIONS
DIA. DIA. DIA.
(mm) A B C D E F G H J K (mm) A B C D E F G H J K (mm) A B C D E F G H J K
100 600 330 160 80 200 350 390 700 600 400 100 700 380 190 100 200 350 510 750 600 400 100 750 400 205 100 220 400 530 800 650 400 TABLE OF DIMENSIONS FOR STEEPLY
150 950 510 260 130 225 450 660 900 750 600 150 1135 620 320 160 225 450 760 950 750 600 150 1250 700 350 180 250 500 890 1000 850 650 INCLINED PIPELINES
200 1150 600 310 160 300 650 790 1050 900 700 200 1400 750 380 190 300 650 980 1150 950 700 200 1650 890 450 230 320 700 1170 1250 1000 800 GRADIENT SPACING
250 1350 750 380 200 300 800 970 1200 1000 750 250 1730 940 480 240 320 800 1210 1350 1050 850 250 1960 1060 540 270 350 900 1370 1450 1150 900
1 IN 2 & STEEPER 5.5m
300 1580 850 450 220 320 950 1110 1300 1100 850 300 2090 1130 580 300 380 950 1480 1500 1200 950 300 2300 1200 640 320 500 1100 1630 1650 1300 1050
350 2100 1150 570 290 450 1000 1450 1550 1200 900 350 2600 1410 720 360 500 1050 1840 1700 1350 1050 350 2930 1580 830 410 750 1200 2070 1850 1500 1150
BELOW 1 IN 2 TO 1 IN 4 11.0m
400 2550 1400 700 350 500 1050 1800 1700 1250 1000 400 2980 1610 820 420 750 1200 2110 1850 1500 1150 400 3510 1900 970 190* 1000 1300 2490 2000 1600 1250
450 3000 1630 830 420 680 1100 2130 1800 1450 1150 450 3400 1840 940 470 900 1300 2330 2000 1600 1250 450 3810 2270 1160 580 1000 1350 2970 2150 1700 1350 1 IN 4 TO 1 IN 5 16.6m
500 3590 1950 990 500 800 1200 2540 1950 1600 1250 500 4090 2210 1130 570 1000 1400 2890 2200 1750 1350 500 4340* 2380 1210 610 1000 1400 3700 2250 1750 1400
1 IN 5 TO 1 IN 6 22.0m
600 4100 2200 1120 570 850 1400 2880 2100 1700 1300 600 5010* 2710* 1380 700 1000 1500 3550* 2350 1900 1500 600 6370* 3450* 1760 890 1000 1500 4500* 2400 2050 1650

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER SUPPLY NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

Anti-torque support note & thrust


1 11/'17 JMC TOC flange added & notes updated MOD WATER MAIN THRUST AND SUPPORT BLOCKS STD-W-28 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017

TRENCH WIDTH TO BE MIN. 500mm 1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
AND DEPENDENT ON
DUCT NUMBERS 2. STRUCTURAL DESIGN AND REINFORCEMENT DETAILS TO BE PROVIDED BY THE
DEVELOPER AND SUBMITTED TO IRISH WATER FOR REVIEW.
GROUND SURFACE
3. DUCT ARRANGEMENT MAY VARY DEPENDING ON REQUIREMENTS.
600 mm MIN.

TO DUCTS

REFER TO DRG. No.


COVER

APPROVED MARKER TAPES 4. CABLE DUCTS TO BE IN ACCORDANCE WITH BS 4460 AND BS EN 1401. DUCTS FOR ESB
STD-W-13 FOR
USE TO BE IN ACCORDANCE WITH ESB SPECIFICATION.
BACKFILL DETAILS

200
75
5. PROPRIETARY DUCT CHAMBER MAY BE USED SUBJECT TO REVIEW FROM IRISH WATER.

75
CABLE DUCTS 6. LONG RADIUS BENDS MAY BE USED FOR CHANGES IN DIRECTION OF UP TO 45°
DUCT CHAMBERS SHALL BE PROVIDED FOR ALL BENDS GREATER THAN 45°.

200
APPROVED SAND
7. DUCT CHAMBERS TO BE LOCATED AT 50m INTERVALS MAXIMUM.

8. APPROPRIATE MARKER TAPE SHALL BE LAID 200mm ABOVE THE EXTERNAL CROWN
OF THE DUCT AND SHOULD INCORPORATE REINFORCED TRACING WIRE.
TRACING WIRES SHALL BE CONNECTED ACROSS CHAMBERS.
ELECTRICAL MARKER TAPE TO BE USED IN ACCORDANCE WITH ESB SPECIFICATION.
SECTION C - C 9. ALL CHAMBERS TO BE CHECKED FOR UPLIFT BY THE DEVELOPER BASED
ON GROUND CONDITIONS WITHIN THE SITE. SHOULD ANTI FLOATATION
MEASURES BE REQUIRED THEY SHALL BE SUBJECT TO REVIEW
FROM IRISH WATER.

10. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.

11. ALL DUCTING TO BE INSTALLED WITH DRAW CORDS/ROPES, TO ALLOW PULL THROUGH
OF CABLES.

12. CABLE DUCT INTERFACE WITH CHAMBER WALL TO BE SEALED TO PREVENT INGRESS OF
B GROUNDWATER TO CHAMBER.

C C
CABLE DUCT

75mm DIA. PVC DRAIN


TO NEAREST SURFACE
WATER OUTLET FITTED
WITH NON-RETURN VALVE
225

1350
900

A A

CABLE DUCT CABLE DUCT


225

225 900 225

1350

PLAN

COVER TO BE SET IN COVER TO BE SET IN


C50/60 MORTAR C50/60 MORTAR

COVER & FRAME COVER & FRAME


(CLASS D400), IN ACCORDANCE WITH (CLASS D400), IN ACCORDANCE WITH
EN124 AND BS7903 EN124 AND BS7903

GROUND SURFACE GROUND SURFACE


MINIMUM 600mm

CONCRETE GRADE CONCRETE GRADE


75 C 30/37 75 C 30/37

CABLE DUCTS CABLE DUCTS


75

75
150

150
225

75mm BLINDING 75mm BLINDING


GRADE C12/15 CONCRETE GRADE C12/15 CONCRETE

225 900 225 225 900 225

1350 1350

SECTION A - A SECTION B - B

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

2 11/'17 JMC TOC Updated notes MOD


1 08/'16 JMC TOC Revised cover notes MOD DUCT CHAMBER STD-W- 29 2
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
2. STRUCTURAL REINFORCEMENT AND DESIGN DETAIL TO BE PROVIDED BY THE DEVELOPER AND SUBMITTED TO IRISH WATER FOR
REVIEW. ROOF SLABS SHALL BE DESIGNED TO CARRY ALL LIVE LOADS & DEAD LOADS, & CONSIST OF A REINFORCED CONCRETE SLAB
DIAMETER OF WATERMAIN DIAMETER OF SCOUR OF IN-SITU CONCRETE, GRADE C30/37, WITH A MINIMUM THICKNESS OF 225mm. ALTERNATIVELY, PRE-CAST CONCRETE ROOFS MAY BE
(mm) (mm) USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911, Part 4.
3. CONCRETE FOR SCOUR CHAMBER AND HEADWALL TO BE C30 / 37.
4. PREFABRICATED CHAMBER AND HEADWALL MAY ALSO BE USED, SUBJECT TO REVIEW FROM IRISH WATER.
NOT EXCEEDING 75 50 5. SCOUR CHAMBER SHALL BE COVERED WITH APPROVED HEAVY DUTY METAL COVERS TO IS EN 124 RATING D400. COVER AND FRAME
SHALL BE SUITABLE FOR ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW IRISH WATER.
6. 200mm ALL ROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GRASS AREAS.
100 TO 200 75
7. FINAL DETAIL TO BE REVIEWED BY IRISH WATER AND RELEVANT REGULATORY AUTHORITIES.
8. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS,
200 TO 350 100 DEAD ENDS AND PIPES AT STEEP SLOPES.
9. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
10. ALL PIPEWORK AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545. PE PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN
12201:2011.
11. ALL CHAMBERS TO BE CHECKED FOR UPLIFT BY THE DEVELOPER BASED ON GROUND CONDITIONS WITHIN THE SITE. SHOULD ANTI
FLOATATION MEASURES BE REQUIRED THEY SHALL BE SUBJECT TO AGREEMENT WITH IRISH WATER.
SCOUR CHAMBER 12. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
COVER TO BE SET (COVER STAMPED '' ScV '') 13. BACKFILL AND REINSTATEMENT OF RIVER BED AND BANK TO BE SUBJECT TO AGREEMENT WITH IRISH WATER & RELEVANT
IN C50\60 MORTAR AUTHORITIES.

675 (MAX.)
D.I. SLUICE VALVE AND CHAMBER 1 No. MIN.,3 No. MAX. COURSE OF CLASS B
(COVER STAMPED '' ScV '' ENGINEERING BRICKS SET IN C50/60 MORTAR
REFER TO STD-W-14)
MANHOLE STEPS TO COMPLY WITH IS EN 13101,
TYPE D, CLASS 1, GALVANISED MILD STEEL &
PLASTIC ENCAPSULATED.

225 HANDRAILING MAY BE REQUIRED TO


DESIGNERS RISK ASSESSMENT
600 (MIN.)
CONCRETE GRADE C 30/37

150 SIDE WALL SLOPES TO MATCH


D.I. PLAIN EXISTING EMBANKMENT
ENDED PIPE
300 150

FLAP VALVE
FLAP VALVE
1:50 SLOPE
WATER LEVEL
ROCKER PIPES

225

45°
TO BE PROVIDED
ORIGINAL BED LEVEL

225
300

ROCKER PIPES 75 CONCRETE BLINDING


TO BE PROVIDED C 12 / 15
1000
200

75 CONCRETE BLINDING 300 400 260


C 12 / 15
EXISTING EMBANKMENT
SECTION 1000

D.I. SLUICE VALVE AND CHAMBER


(COVER STAMPED '' ScV ''
2
LONG BODY REFER TO STD-W-14)
FLEXIBLE JOINT 1
1200 mm DIA. SCOUR CHAMBER REINFORCED CONCRETE
FLANGE AND SPIGOT PRECAST (COVER STAMPED '' ScV '') BASE SLAB C25/ 30
(STANDARD) CONCRETE
RINGS
ALL FLANGED LONG BODY 225
LEVEL INVERT FLEXIBLE JOINT
TEE LONG BODY
FLEXIBLE JOINT
FLAP VALVE
PIPE DIA.
0

+ 450
20
Ø1

DISMANTLING
JOINT FLANGED PLAIN
D.I. FLANGED FLAP VALVE
ENDED DI PIPE PLAIN ENDED PIPE
ROCKER PIPES WITH THRUST FLANGE
225

TO BE PROVIDED PLAIN ENDED PIPE


PLAIN ENDED PIPE
WITH THRUST FLANGE
WITH THRUST FLANGE
FLANGE AND SPIGOT
400 x 400 x 200mm
(STANDARD)
DEEP SUMP
1
LONG BODY 150 THICK CONCRETE
FLEXIBLE JOINT SURROUND GRADE C16 / 20 2

PLAN (DUCTILE IRON WATER MAIN)


P.E. WATER MAIN

FUSION WELD
STUB FLANGE
WITH BACKING RING
D.I. SLUICE VALVE
HEAVY DUTY COVER AND FRAME,
AND CHAMBER
STAMPED '' ScV '' CLASS D400
(COVER STAMPED
(TO SUIT MIN. 600 SQ. OPE)
'' ScV '' REFER TO
STD-W-14)
DISMANTLING
JOINT ScV

ALL FLANGED
LEVEL INVERT TEE

STUB FLANGE
WITH BACKING RING

FUSION WELD

P.E. WATER MAIN

PLAN (POLYETHYLENE WATER MAIN) ROOF PLAN


REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
3 11/'17 JMC TOC Updated notes MOD TITLE DRAWING No. REV
2 08/'16 JMC TOC Added steps & revised MOD
access cover & ope SCOUR CHAMBER
1 04/'16 JMC TOC Added 1 No. flexible joint MOD
AND HEAD WALL ARRANGEMENTS STD-W- 30 3
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
COVER TO BE SET IN WASHOUT HYDRANT CHAMBER
D.I. SCOUR VALVE AND CHAMBER (COVER
C50\60 MORTAR (COVER STAMPED '' WO '')
STAMPED '' ScV '' REFER TO STD-W-14)
(REFER TO NOTE 2 ON STD-W-13)
BULL NOSE
75mm HIGH FINISH
REFER TO DRG. No. LETTERING
STD-W-17 FOR HYDRANT,
900 MIN.

REFER TO DRG. No. PRECAST CONCRETE HEAVY DUTY COVER


STD-W-14 FOR VALVE, CHAMBER & COVER AND FRAME, STAMPED ''
PRECAST CONCRETE DETAILS ScV '' CLASS D400 (TO ScV
SEE NOTE
CHAMBER & COVER SUIT 445 x 280 OPE)
14 BELOW DI, DOUBLE FLANGED,
DETAILS DN80, RISER PIPE OF SUITABLE C30/37 REINFORCED
LENGTH TO SUIT SITE CONDITIONS CONCRETE ROOF SLAB
DOUBLE FLANGED 90° BEND WITH
ALL CONC. THRUST BLOCK TO BEND PLINTH DETAIL
FLANGED REFER TO DRG. No. STD-W-30 FOR (REFER TO DRG. No. STD-W-28 FOR
LEVEL ROCKER PIPES & PIPE JOINT DETAILS DETAILS) IN GRASS AREA
INVERT TEE

SECTION (PRECAST CONCRETE CHAMBER OPTION)


WASHOUT HYDRANT CHAMBER
D.I. SCOUR VALVE AND CHAMBER (COVER COVER TO BE SET IN
(COVER STAMPED '' WO '')
STAMPED '' ScV '' REFER TO STD-W-14) C50\60 MORTAR

REFER TO DRG. No.


REFER TO DRG. No. STD-W-17 FOR HYDRANT, 75mm HIGH
STD-W-14 FOR VALVE, BLOCKWORK CHAMBER LETTERING
CONCRETE BLOCKWORK & COVER DETAILS
CHAMBER & COVER HEAVY DUTY COVER
SEE NOTE DI, DOUBLE FLANGED, WO
DETAILS AND FRAME, STAMPED
14 BELOW DN80, RISER PIPE OF
'' WO '' CLASS D400 (TO
SUITABLE LENGTH TO
SUIT 445 x 280 OPE)
SUIT SITE CONDITIONS
C30/37 REINFORCED
DOUBLE FLANGED 90° BEND WITH
ALL CONCRETE ROOF SLAB
CONC. THRUST BLOCK TO BEND
REFER TO DRG. No. STD-W-30 FOR
FLANGED
ROCKER PIPES & PIPE JOINT DETAILS
(REFER TO DRG. No. STD-W-28 FOR ROOF
LEVEL DETAILS)
INVERT TEE PLAN
SECTION (BLOCKWORK CHAMBER OPTION)
LONG BODY FLEXIBLE JOINT
FLANGE AND SPIGOT D.I. SCOUR VALVE AND CHAMBER
(STANDARD) (COVER STAMPED '' ScV ''. REFER TO
STD-W-14). SEE NOTE 14 BELOW
ALL FLANGED LEVEL INVERT
TEE REFER TO DRG. No.
STD-W-17 FOR
CHAMBER DETAILS

REFER TO DRG. No. WASHOUT


STD-W-30 FOR ROCKER HYDRANT
DISMANTLING JOINT PIPES & PIPE JOINT DETAILS
FLANGE AND SPIGOT
(STANDARD) WASHOUT HYDRANT CHAMBER WASHOUT HYDRANT CHAMBER
LONG BODY
(PRECAST CONCRETE OPTION) (BLOCKWORK OPTION)
FLEXIBLE JOINT

PLAN (DUCTILE IRON


WATER MAIN) 1.
2.
ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
STRUCTURAL REINFORCEMENT AND DESIGN DETAIL TO BE PROVIDED BY THE DEVELOPER AND SUBMITTED TO IRISH WATER FOR
P.E. WATER MAIN REVIEW.
3. HYDRANT CHAMBERS SHALL BE COVERED WITH APPROVED HEAVY DUTY METAL COVERS TO IS 261 AND BS 5834 COVER AND FRAME
FUSION WELD SHALL BE SUITABLE FOR ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
4. HYDRANTS SHALL BE DOUBLE FLANGED DRILLED TO PN 16. THEY SHALL COMPLY WITH BS 750: 2012. THE HYDRANT SHALL
STUB FLANGE
INCORPORATE A SCREW DOWN GATE VALVE, UNDERGROUND ''GUIDE TO HEAD'' TYPE WITH SCREW DOWN CONNECTION OUTLET
WITH BACKING RING AND FALSE SPINDLE CAP AND IRON CHAIN.
D.I. SCOUR VALVE AND 5. ALL HYDRANTS SHALL BE CLOCKWISE CLOSING.
CHAMBER (COVER STAMPED 6. HYDRANT CHAMBER & SCOUR VALVE CHAMBER TO BE CONSTRUCTED OF PRECAST CONCRETE UNITS OR HIGH DENSITY
'' ScV '' REFER TO STD-W-14). BLOCKWORK. ALTERNATIVELY PROPRIETARY PREFABRICATED CHAMBER UNITS MAY ALSO BE USED, SUBJECT TO REVIEW FROM
SEE NOTE 14 BELOW. IRISH WATER. ROOF SLABS SHALL BE DESIGNED TO CARRY ALL LIVE LOADS & DEAD LOADS, & CONSIST OF A REINFORCED
CONCRETE SLAB OF IN-SITU CONCRETE, GRADE C30/37, WITH A MINIMUM THICKNESS OF 150mm. ALTERNATIVELY, PRE-CAST
DISMANTLING CONCRETE ROOFS MAY BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911, Part 4.
JOINT 7. CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER STD-W-13.
8. 200mm ALL ROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GRASS AREAS.
SEE NOTE 14 BELOW 9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS,
TAPERS, DEAD ENDS AND PIPES AT STEEP SLOPES.
ALL FLANGED 10. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
LEVEL INVERT TEE 11. ALL PIPEWORK AND FITTINGS FOR WASHOUT HYDRANT CHAMBER CONNECTION SHALL BE DUCTILE IRON. PIPES AND FITTINGS ON
MAIN LINE SHALL BE: PE PIPES & FITTINGS IN ACCORDANCE WITH IS EN 12201:2011, OR DUCTILE IRON PIPES AND FITTINGS IN
STUB FLANGE
ACCORDANCE WITH IS EN 545.
WITH BACKING RING
12. ALL CHAMBERS TO BE CHECKED FOR UPLIFT BY THE DEVELOPER BASED ON GROUND CONDITIONS WITHIN THE SITE. SHOULD ANTI
FUSION WELD FLOATATION MEASURES BE REQUIRED THEY SHALL BE SUBJECT TO AGREEMENT WITH IRISH WATER.
13. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
P.E. WATER MAIN 14. WHERE HYDRANTS ARE INSTALLED ON TRUNK MAINS OR PRINCIPAL MAINS, A SEPARATE SCOUR VALVE IS REQUIRED. THE PURPOSE
OF THE SCOUR VALVE IS TO ISOLATE THE WASHOUT HYDRANT FOR MAINTENANCE PURPOSES & ALSO TO REDUCE THE VELOCITY
PLAN (POLYETHYLENE OF THE DISCHARGE FLOW WHERE HIGH HEAD VALUES ARE CONCERNED. A "SANDWICH" OR "SPADE" VALVE MAY BE USED IN LIEU OF
A SEPARATE SCOUR VALVE, SUBJECT TO PRIOR REVIEW BY IRISH WATER.
WATER MAIN)
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE APR. 2016
TITLE DRAWING No. REV
Revised Chamber Base Detail &
2 11/'17 JMC TOC MOD
updated & added notes WASHOUT HYDRANT
1 08/'16 JMC TOC Revised note 7 MOD STD-W-30A 2
0 04/'16 JMC TOC Initial Issue MOD
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.

2. O.D. REFERS TO OUTSIDE DIAMETER OF PIPES OR COLLARS.

3. BENDS AT RESPECTIVE CROSSINGS SHALL BE AS INDICATED ON THE LONGITUDINAL SECTION


DRAWING.
150 150 PLASTIC SHEETING IN
ACCORDANCE WITH BS 6076
4. PIPEWORK AT CROSSING POINT TO BE POLYETHYLENE JOINED USING BUTT FUSION WELDING.

150
5. POLYETHYLENE PIPES SHALL BE WRAPPED IN PLASTIC SHEETING HAVING A COMPOSITION IN
ACCORDANCE WITH BS 6076 BEFORE BEING CAST INTO CONCRETE.

6. THRUST BLOCKS TO BE PROVIDED AS PER STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS

150
AND PIPES AT STEEP SLOPES.

7. ALL DUCTILE IRON PIPEWORK AND FITTINGS SHALL BE IN ACCORDANCE WITH IS EN 545. PE PIPES
AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 12201:2011.
CROSS SECTION 8. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
(CONCRETE SURROUND) 9. PIPEWORK FOR WATERMAIN CAN BE EITHER DUCTILE IRON OR POLYETHYLENE. PIPEWORK AT
CROSSING POINT TO BE PE IN BOTH CASES.

10. BACKFILL AND REINSTATEMENT OF RIVER BED AND BANK TO BE SUBJECT TO AGREEMENT WITH
RELEVANT AUTHORITY & IRISH WATER.
AIR VALVE TO BE LOCATED AT
BOTH SIDES OF THE CROSSING.

500mm MIN. OR TO REQUIREMENTS


FOR AIR VALVE / CHAMBER DETAILS,
REFER TO STD-W-20, 21, 22, & 23. FOR SCOUR VALVE / CHAMBER

OF RELEVANT AUTHORITY
DETAILS REFER TO STD-W-30
5000mm 5000mm
BANK EDGE

BANK EDGE
BED OF STREAM

DI / PE
FUSION FUSION
REFER TO NOTE 3 WELD WELD
FOR BENDS DI / PE

FOR THRUST BLOCK DETAILS


REFER TO STD-W-28
O.D. + 300mm

300 300 POLYETHYLENE 300 300 LONG BODY


PIPEWORK FLEXIBLE JOINT
STUB FLANGE WITH CONCRETE SURROUND GRADE C 25/30. STUB FLANGE WITH
BACKING RING FOR BACKING RING FOR FOR THRUST BLOCK DETAILS
DI/PE CONNECTION DI/PE CONNECTION REFER TO STD-W-28
SECTION

AIR VALVE TO BE LOCATED AT FOR THRUST BLOCK DETAILS


BOTH SIDES OF THE CROSSING. REFER TO STD-W-28
O.D. + 300mm

FOR AIR VALVE / CHAMBER DETAILS,


REFER TO STD-W-20, 21, 22, & 23.

300 POLYETHYLENE PIPEWORK 300


CONCRETE SURROUND GRADE C 25/30.
FOR THRUST BLOCK DETAILS
REFER TO STD-W-28
FOR SCOUR VALVE /
CHAMBER DETAILS
REFER TO STD-W-30

FOR HEAD WALL DETAILS


REFER TO STD-W-30

PLAN
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
TYPICAL
1 11/'17 JMC TOC Updated pipe depth dimension MOD DITCH / STREAM CROSSING STD-W- 31 1
0 09/'15 JMC TOC Initial Issue SL FOR WATER MAIN
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017

BRIDGE PARAPET 1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.


TAPPING WITH TRANSITION
150 150 90° ELBOW (MALE) 2. AT BRIDGE CROSSING ALL PIPEWORK TO BE DUCTILE IRON IN ACCORDANCE WITH IS EN 545.
32mm DIA.
P.E. PIPE 3. O.D. REFERS TO OUTSIDE DIAMETER OF PIPES OR COLLARS.

4. BENDS AT RESPECTIVE CROSSINGS SHALL BE INDICATED ON THE LONGITUDINAL SECTION DRAWING.

5. THE DEVELOPER IS TO SEEK ADVICE FROM IRISH WATER AS TO WHETHER A DUPLICATE MAIN IS TO BE

150
PROVIDED THROUGH THE BRIDGE CROSSING. IF NECESSARY THE DEVELOPER IS TO SUBMIT A DESIGN TO
IRISH WATER FOR REVIEW.
REFER TO STD-W-03
SOCKET OUTLINE 6. THRUST BLOCKS TO BE PROVIDED AS PER STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS AND PIPES
FOR TAPPING DETAIL
AT STEEP SLOPES.
DUCTILE IRON
WATER MAIN 7. THE QUALITY OF THE KIOSK CONSTRUCTION SHALL ENSURE THAT THE FOLLOWING IS ACHIEVED:

(a) A THERMAL TRANSMITTANCE OF 1.5W PER m² K

150
(b) A FIRE RESISTANCE (RETENTION OF STABILITY, INTEGRITY AND INSULATION) EQUIVALENT TO CLASS 2
OF BS 476, WHEN TESTED IN ACCORDANCE WITH BS 476 FOR A PERIOD EXCEEDING 30 MINUTES.

8. KIOSK (MIN. 600 HIGH x 450 WIDE x 300mm DEEP) - TO BE CONSTRUCTED FROM THERMOSETTING U.V. &
WEATHER RESISTANT PLASTIC POWDER COATED & HOT DIPPED GALVANISED MILD STEEL (MIN. 4mm
THICKNESS) TO BS EN 1461. STAINLESS STEEL OR NON-METALLIC MATERIALS, SUCH AS GLASS
REINFORCED PLASTIC (GRP), MAY BE USED AS AN ALTERNATIVE KIOSK MATERIAL, PARTICULARLY IN
SEVERE ENVIRONMENTS, SUBJECT TO AGREEMENT WITH IRISH WATER. COLOUR TO BE HOLLY GREEN BS
4800 14 C 39. KIOSK TO HAVE HINGED, LOCKABLE ACCESS DOOR (HINGES AND LOCKS TO BE STAINLESS
STEEL).

9. THE KIOSK SHALL BE LOCATED OFF THE FOOTPATH SO AS NOT TO IMPEDE PEDESTRIANS AND POSITIONED
SO AS TO FACILITATE SAFE ACCESS FOR MAINTENANCE PERSONNEL.

10. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.

SECTION A - A 11. DETAIL FOR PE WATERMAIN TO BE AS PER THIS DETAIL. BRIDGE CROSSING PIPEWORK TO BE DI IN BOTH
CASES.
(AIR VALVE CONNECTION) KIOSK
SINGLE AIR VALVE (SEE NOTES 7, 8 & 9)

EXPOSED PIPEWORK DUCTILE IRON


TO BE INSULATED PIPEWORK
SLUICE VALVE TO BE PROVIDED 32mm DIA. P.E. PIPE
USING PIPE LAGGING
EACH SIDE OF CROSSING TO
ISOLATE SECTION ROAD LEVEL

CONCRETE SURROUND
GRADE C 25/30.

FLEXIBLE
JOINT

LONG BODY
FOR SCOUR VALVE / FLEXIBLE JOINT
CHAMBER DETAILS
REFER TO STD-W-30 SECTION

A
POLYETHYLENE POLYETHYLENE
OR DUCTILE IRON OR DUCTILE IRON
PIPEWORK PIPEWORK

AIR VALVE

CONCRETE PLINTH
(300 HIGH x 600 LONG
FOR SCOUR VALVE /
x 450 WIDE) WITH A 32mm DIA. P.E. PIPE BRIDGE PARAPET
CHAMBER DETAILS
FINISHED LEVEL OF
REFER TO STD-W-30
150 ABOVE GROUND
A
KIOSK
(600 HIGH x 450 WIDE
x 300 DEEP)

FOR HEAD WALL DETAILS


REFER TO STD-W-30

PLAN

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
TYPICAL
1 11/'17 JMC TOC Updated & added notes MOD BRIDGE CROSSING FOR WATER MAIN STD-W- 32 1
0 09/'15 JMC TOC Initial Issue SL (Sheet 1 of 2)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017

1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.

2. O.D. REFERS TO OUTSIDE DIAMETER OF PIPES OR COLLARS.

3. BENDS AT RESPECTIVE CROSSINGS SHALL BE INDICATED ON THE LONGITUDINAL SECTION DRAWING.


150 150 PLASTIC SHEETING IN
ACCORDANCE WITH BS 6076 4. PIPEWORK AT CROSSING POINT TO BE JOINED USING BUTT FUSION WELDING.

150
5. POLYETHYLENE PIPES SHALL BE WRAPPED IN PLASTIC SHEETING HAVING A COMPOSITION IN ACCORDANCE WITH BS 6076
BEFORE BEING CAST INTO CONCRETE.

6. THRUST BLOCKS TO BE PROVIDED AS PER STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS AND PIPES AT STEEP
150

SLOPES.

7. THE DEVELOPER IS TO SEEK ADVICE FROM IRISH WATER AS TO WHETHER A DUPLICATE MAIN IS TO BE PROVIDED AT THE
BRIDGE CROSSING. IF NECESSARY THE DEVELOPER IS TO SUBMIT A DESIGN TO IRISH WATER FOR REVIEW.

8. BACKFILL AND REINSTATEMENT REQUIREMENTS OF THE RIVER BED AND BANK IS SUBJECT TO AGREEMENT WITH
RELEVANT AUTHORITY & IRISH WATER.
CROSS SECTION 9. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
(CONCRETE SURROUND) 10. ALL DUCTILE IRON PIPEWORK TO BE IN ACCORDANCE WITH IS EN 545. ALL POLYETHYLENE PIPEWORK TO BE IN
ACCORDANCE WITH IS EN 12201.

11. PIPEWORK FOR WATERMAIN CAN BE EITHER DUCTILE IRON OR POLYETHYLENE. PIPEWORK AT THE CROSSING POINT TO
BE PE IN BOTH CASES.

AIR VALVE TO BE LOCATED AT FOR SCOUR VALVE / CHAMBER


BOTH SIDES OF THE CROSSING. 500mm MIN. OR TO REQUIREMENTS DETAILS REFER TO STD-W-30
FOR AIR VALVE / CHAMBER DETAILS, OF RELEVANT AUTHORITY 5000mm
REFER TO STD-W-20, 21, 22 & 23.

BANK EDGE
O.D. COLLAR + 300mm

BED OF
REFER TO NOTE 3 DI / PE STREAM
FOR BENDS

FOR THRUST BLOCK DI / PE


DETAILS REFER
TO STD-W-28

300 300 300 300


POLYETHYLENE
PIPEWORK
STUB FLANGE WITH FUSION FUSION STUB FLANGE WITH
CONCRETE SURROUND WELD LONG BODY
AIR VALVE TO BE LOCATED AT BACKING RING WELD BACKING RING
GRADE C 25/30. FLEXIBLE JOINT
BOTH SIDES OF THE CROSSING.
FOR AIR VALVE / CHAMBER DETAILS,
REFER TO STD-W-20, 21, 22 & 23.
SECTION

ENSURE STRUCTURE
SAFE DISTANCE TO

IS NOT IMPACTED
ROAD

BRIDGE PARAPET

POLYETHYLENE
OR DUCTILE IRON
PIPEWORK

300 300
O.D. COLLAR + 300mm

POLYETHYLENE
OR DUCTILE IRON
PIPEWORK FOR SCOUR VALVE /
CHAMBER DETAILS
REFER TO STD-W-30

FOR HEAD WALL DETAILS


REFER TO STD-W-32

PLAN

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
TYPICAL
1 11/'17 JMC TOC Notes added & updated MOD BRIDGE CROSSING FOR WATER MAIN STD-W- 33 1
0 09/'15 JMC TOC Initial Issue SL (Sheet 2 of 2)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017

1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.


FENCE PILLAR SPACING AS PER
MANUFACTURERS SPECIFICATION 2. SECURITY FENCING SHALL COMPRISE 2.4m HIGH, CORROSION RESISTANT MILD STEEL
FENCING, GALVANISED AND PLASTIC COATED FINISHED, WITH SIMILAR TYPE ACCESS
GATES.
PVC INSERT CAP ANTI-CLIMB FEATURES
3. THE ACCESS GATES SHALL BE OF SUFFICIENT WIDTH TO ACCOMMODATE MAINTENANCE
VEHICLES, TANKERS, ETC. THE SECURITY GATES SHALL BE PROVIDED WITH SLIDE BOLTS,
SHOOTING BOLTS AND PADLOCKS. IF OPENING OUTWARDS, THE ACCESS GATES SHALL BE
SET BACK FROM PARKING AND ACCESS AREAS BY THE WIDTH OF THE LEAF OF THE GATE.
FENCE PILLARS
4. BOLTS - UNLESS TAMPER RESISTANT FIXINGS ARE USED, ALL BOLTS TO THE ACCESS
GATES & FENCING SHALL BE BURRED OVER.

5. GATE HINGES SHALL BE DESIGNED SO THAT IT IS IMPOSSIBLE TO REMOVE THE GATE BY


LIFTING WHEN IT IS IN A CLOSED & LOCKED POSITION. DROP BOLTS SHALL BE FITTED TO

2400
V-BEAM
REINFORCING PROFILE EACH GATE LEAF IN SUCH A WAY THAT THEY CANNOT BE REMOVED BUT ALLOW THE GATE
TO BE SECURED IN BOTH THE OPEN & CLOSED POSITION.

6. THE SECURITY RATING SHALL BE EITHER BASIC +, ENHANCED OR ENHANCED +. THE FENCE
STANDARD WILL BE BASED ON THE SECURITY RATING OF THE SITE & IS TO BE AGREED
WITH IRISH WATER.

7. CORNER BRACING AND POST DETAIL TO MANUFACTURER'S SPECIFICATION.

125mm WIDE x 150mm DEEP 8. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.


FOUNDATION DETAIL CONCRETE SILL UNDER FOUNDATION DETAIL
TO MANUFACTURERS FENCE TO IRISH WATER'S TO MANUFACTURERS 9. ALL FENCE MATERIALS AND WORKMANSHIP TO BE IN ACCORDANCE WITH IS EN 1722-14 :
SPECIFICATION REQUIREMENTS (ENHANCED SPECIFICATION 2006.
+ SECURITY RATING ONLY)
10. DIMENSIONS OF GATE PILLARS, GATE FRAME, FENCE PILLARS, FENCE RUNNERS,
GRADE C30/37 DIAGONALS, ETC. TO BE TO MANUFACTURER'S SPECIFICATION.
CONCRETE IN BASE 75 CONCRETE
BLINDING, GRADE C12/15 11. FENCE/GATE DESIGN AND DETAILS TO BE PROVIDED TO IRISH WATER FOR REVIEW/
VETTING BEFORE MANUFACTURE.
PANEL - ELEVATION
12. PEDESTRIAN GATE SHALL BE PROVIDED IF DEEMED NECESSARY BY IRISH WATER.

13. COLOUR TO BE HOLLY GREEN 14 C 39 IN ACCORDANCE WITH BS 4800:2011.


SECURITY MESH SPACING ADDITIONAL 14. A 125mm WIDE x 150mm DEEP CONCRETE SILL GRADE C20/25 CONCRETE SHALL BE
BAR THICKNESS HEIGHT
RATING AxB FEATURES PROVIDED TO IRISH WATER'S REQUIREMENTS (ENHANCED + SECURITY RATING ONLY).

BASIC + 150 x 50 Type: 868 5mm 2.4m ANTI-CLIMB

ENHANCED 150 x 50 Type: 868 5mm 2.4m ANTI-CLIMB

ANTI-CLIMB &
ENHANCED + 50 x 50 Type: 868 4mm 2.4m
ANTI-BURROW

B
A

4000 mm MINIMUM

METAL PILLARS
RHS FRAME

LOCKABLE
SLIPBOLT
2400

RSA
SLAMPLATE

FIN. GROUND LEVEL

DROPBOLTS

GRADE C30/37
CONCRETE IN BASE
FOUNDATION DETAIL FOUNDATION DETAIL
TO MANUFACTURERS TO MANUFACTURERS 75mm CONCRETE
SPECIFICATION SPECIFICATION BLINDING, GRADE C12/15

GATES & PIERS - ELEVATION


METAL PILLARS
OUTSIDE

GATES & PIERS - PLAN

ENTRANCE GATE DETAILS

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

2 11/'17 JMC TOC Fencing table updated MOD


1 08/'16 JMC TOC Revised notes & table MOD SECURITY GATE AND FENCING STD-W- 34 2
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
LEGEND:

1. STAINLESS STEEL WRAP AROUND CLAMP (GRADE 1.4571), ELASTOMER


RUBBER GASKET WITH VULCANIZED REINFORCEMENT SHEET OF
2 1 2 STAINLESS STEEL.

2. EXISTING ST / uPVC/ DI OR CI PIPE.

3. REPLACEMENT SECTION (MINIMUM 1.0 M ) OF PLAIN ENDED DUCTILE


IRON PIPE.

4. MULTI FIT UNIVERSAL COUPLING.


TYPE 1 REPAIR
5. EXISTING CAST IRON OR DUCTILE IRON PIPE.
COUPLING CLAMP FOR
6. EXISTING ASBESTOS MAIN.
DI, uPVC, ST AND CI
7. REPLACEMENT OF FULL SECTION OF AC MAIN WITH A FULL LENGTH OF
AN ALTERNATIVE IRISH WATER APPROVED PIPE MATERIAL.

8. SPECIAL TRANSITIONAL COUPLER (TO FIT TURNED END OF AC PIPE).

9. EXISTING PVC MAIN.

10.REPLACEMENT SECTION OF AN ALTERNATIVE IRISH WATER APPROVED


PIPE MATERIAL (MINIMUM 1.0m) CUT TO LENGTH.

5 4 3 4 5 11.EXISTING PE PIPE.

12.REPLACEMENT SECTION OF PE PIPE.

13.FUSION WELDED COUPLING.

14.PIPE MATERIAL REFERENCES AS FOLLOWS:


AC - ASBESTOS CEMENT.
TYPE 2 REPAIR DI - DUCTILE IRON.
CI - CAST IRON.
REPLACEMENT SECTION OF PE - POLYETHYLENE.
uPVC - UNPLASTICISED POLY VINYL CHLORIDE.
CAST IRON / DUCTILE IRON ST - STEEL.

15.REPAIRS TO EXISTING WATER MAINS THAT ARE IN OWNERSHIP OF IRISH


WATER SHALL BE CARRIED OUT BY IRISH WATER OR AN AGENT OF
IRISH WATER.

16.REPAIRS TO EXISTING WATER MAINS TO BE CARRIED OUT BY


CONTRACTORS WHO ARE DEEMED COMPETENT BY IRISH WATER TO
CARRY OUT SUCH REPAIRS. THESE REPAIRS SHALL BE CARRIED OUT
IN ACCORDANCE WITH AN AGREED METHOD STATEMENT, SAFETY
AND HEALTH PLAN AND HYGIENE PLAN.

6 8 7 8 6 17. A HIGH LEVEL OF HEALTH & SAFETY PROCEDURES IS REQUIRED WHEN


WORKING ON AC MAINS, & THE OPERATION OF DISMANTLING/ REMOVAL
OF AC PIPES & JOINTS.

TYPE 3 REPAIR
REPLACEMENT
ASBESTOS CEMENT PIPE

9 4 10 4 9

TYPE 4 REPAIR
REPLACEMENT SECTION FOR
uPVC MAIN

11 13 12 13 11

TYPE 5 REPAIR
REPLACEMENT SECTION OF
PE MAIN

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

2 11/'17 JMC TOC Updated Note 10 MOD


1 08/'16 JMC TOC Added Note 17 MOD PIPE REPAIR TO EXISTING MAINS STD-W- 35 2
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.

2. THE KIOSK SHALL BE LOCATED OFF THE FOOTPATH SO AS NOT TO IMPEDE PEDESTRIANS AND POSITIONED SO AS TO FACILITATE SAFE ACCESS FOR MAINTENANCE PERSONNEL.

3. KIOSK TO BE CONSTRUCTED FROM THERMOSETTING U.V. & WEATHER RESISTANT PLASTIC POWDER COATED & HOT DIPPED GALVANISED MILD STEEL PLATE (MINIMUM 4mm THICKNESS) TO BS EN 1461.
STAINLESS STEEL OR NON-METALLIC MATERIALS, SUCH AS GLASS REINFORCED PLASTIC (GRP), MAY BE USED AS AN ALTERNATIVE KIOSK MATERIAL, PARTICULARLY IN SEVERE ENVIRONMENTS,
SUBJECT TO AGREEMENT WITH IRISH WATER.

4. KIOSK TO HAVE SINGLE OR DOUBLE STEEL/GRP DOORS WITH MULTIPLE LOCKS TO LPS 1175 SR4 OR EN 1627. MINIMUM DOUBLE LOCKS WITH BOLTS THAT ENGAGE INTO THE SILL & HEADER AS WELL AS
BETWEEN THE TWO LEAVES OR LEAF & FRAME. LEADING EDGE OF LEAVES TO HAVE EITHER REBATED EDGES OR FITTED WITH ASTRAGALS.

5. COLOUR TO BE HOLLY GREEN BS 4800 14 C39. INTERIOR FINISH TO BE WHITE UNLESS APPROVED BY IRISH WATER.

6. THE QUALITY OF KIOSK CONSTRUCTION SHALL ENSURE THAT THE FOLLOWING IS ACHIEVED:

(a) A THERMAL TRANSMITTANCE OF 1.5W PER m²K.


(b) A FIRE RESISTANCE (RETENTION OF STABILITY, INTEGRITY AND INSULATION) EQUIVALENT TO CLASS 2 OF BS 476, WHEN TESTED IN ACCORDANCE WITH BS 476 FOR A PERIOD EXCEEDING 30 MINUTES.
(c) AN IP RATING OF IP65 OR EQUIVALENT.

7. KIOSK TO BE BOLTED TO THE PLINTH THROUGH A BOTTOM FLANGE WITH GALVANISED MILD STEEL OR STAINLESS STEEL ANCHOR BOLTS.

8. THE BOTTOM FLANGE SHALL BE SEATED ON A NEOPRENE GASKET AND SEALED WITH MASTIC.

9. REAR WALL SHALL BE REINFORCED WITH STAINLESS STEEL SECTIONS TO WHICH A MARINE PLY WOOD , 18mm THICK BOARD IS FIXED.

10. THE DEVELOPER SHALL BE RESPONSIBLE FOR THE ULTIMATE SIZING OF THE KIOSK TO ENSURE ADEQUATE SPACE REQUIREMENTS.

11. TELEMETRY DUCTING TO BE IN ACCORDANCE WITH BS 4660 AND BS EN 1401.

12. ELECTRICAL REQUIREMENTS TO BE IN ACCORDANCE WITH ESB SPECIFICATION.

13. THE ROOF OF THE KIOSK SHALL BE REMOVABLE (BOLTS) TO FACILITATE BACKBOARD REMOVAL.

14. ALL EXPOSED PIPEWORK TO BE ADEQUATELY INSULATED WITH PIPE LAGGING.

15. A 750mm WIDE x 100mmTHICK FOOTPATH OF C25/30 CONCRETE ON 50mm SAND BLINDING ON 300mm CLAUSE 804 GRANULAR MATERIAL TO BE PROVIDED AROUND KIOSK.

16. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.

MIN. 300 MIN. 400

REMOVABLE 4 No. VENTS


WATER - TIGHT
MIN. 1200

(EACH SIDE)
CAP ON PVC DUCT

150 150 150 150


450

450
75mm THICK
150

150
450mm THICK
CONCRETE
CONCRETE 600 SLOW BEND
PLINTH BLINDING 750 700
GRADE C25/ 30 GRADE C12/15
75mm THICK PVC DUCTING WITH
CONCRETE DRAW - CORD
BLINDING
GRADE C12/15
CROSS SECTION CROSS SECTION
(WET KIOSK) (TELEMETRY KIOSK)

MIN. 600 HEAVY DUTY MIN. 1600 TELEMETRY


STEEL HINGES KIOSK
WET KIOSK

RECESS
MIN. 1200

MIN. 1200

DOUBLE
DOORS
150 150 150 150
450

450
150

150

450mm THICK CONCRETE 900 450mm THICK CONCRETE 1900


75mm THICK CONCRETE 75mm THICK CONCRETE
PLINTH GRADE C25/ 30 PLINTH GRADE C25/ 30
BLINDING GRADE C12/15 BLINDING GRADE C12/15

FRONT ELEVATION FRONT ELEVATION


(WET KIOSK) (TELEMETRY KIOSK)

150 MIN. 1600 150


150 150 REMOVABLE
WATER - TIGHT
CAP ON PVC DUCT
150
150 150

150
MIN. 300

MIN. 400

MIN. 600

POWER IN
DUCT
PLAN

NOTE:
ALL KIOSK DIMENSIONS ARE MINIMUM DIMENSIONS & MAY REFER TO
VARY TO SUIT THE KIOSK REQUIREMENT. PLAN STD-W-29 FOR
DUCT CHAMBER DETAILS
WET KIOSK TELEMETRY KIOSK
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

2 11/'17 JMC TOC Note 10 revised MOD


1 08/'16 JMC TOC Added Note 4 MOD TELEMETRY AND WET KIOSK STD-W- 36 2
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
510
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.

2. LAMP BOLLARD TO BE REVIEWED BY IRISH WATER.

470
3. LAMP STANDARD TO BE REVIEWED BY IRISH WATER.

4. ELECTRICAL DUCTING TO BE IN ACCORDANCE WITH ESB SPECIFICATION.

APPROVED LAMP STANDARD

SHAFT

4000 OR 5000 AS SPECIFIED

INSPECTION DOOR 610 x 108


APPROVED LAMP BOLLARD

CONCRETE GRADE C30/37


200
GROUND LEVEL

100
305

762

CABLE ENTRY SLOT 152 x 76


150 DIA. CABLE DUCT

CONCRETE GRADE C30/37

75 BLINDING
ARMOURED CABLING TO DUCT
600 100mm DIA. T.PIECE 100mm DIA. DUCT

SECTION SECTION
600 300

APPROVED LAMP BOLLARD


CONCRETE GRADE C30/37
300
600

600 x 450 CABLE JUNCTION BOX MIN. 100 DIA. CABLE DUCT
(SIMILAR TO DUCT CHAMBER
DETAIL ON DRG. No. STD-W-29)

PLAN
PLAN
LAMP STANDARD LAMP BOLLARD
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV

1 11/'17 JMC TOC Notes updated MOD LAMP BOLLARD AND LAMP STANDARD STD-W- 37 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
STANDARD DETAILS FOR WATER NETWORKS: REVISION LOG - 03 (1st Dec. 2017)

DRG No. DRAWING TITLE MATERIAL CHANGES EDITORIAL CHANGES REV COMMENTS
STD-W-01 WATER SERVICE CONNECTION RESPONSIBILITY 0 No change
STD-W-02 TYPICAL LAYOUT FOR WATER MAINS WITHIN DEVELOPMENTS Temp. “dead end” & note 1 ref. added 1 Drawing revised
STD-W-03 CUSTOMER CONNECTION & BOUNDARY BOX Updated & added notes 3 Drawing revised
STD-W-04 GENERAL PIPE CONNECTIONS (Sheet 1 of 7) Added 2 No. extg. PE details & updated details Added notes 3 Drawing revised
STD-W-05 GENERAL PIPE CONNECTIONS (Sheet 2 of 7) Added w DI pipe to details & updated 3 No. details Updated notes 2 Drawing revised
STD-W-06
IW-CDS-5020-01 Rev. 03 December 2017

GENERAL PIPE CONNECTIONS (Sheet 3 of 7) Added extg. PE pipe to details Updated notes 2 Drawing revised
STD-W-07 GENERAL PIPE CONNECTIONS (Sheet 4 of 7) Updated & added notes 1 Drawing revised
STD-W-08 GENERAL PIPE CONNECTIONS (Sheet 5 of 7) Updated & added notes 1 Drawing revised
STD-W-09 GENERAL PIPE CONNECTIONS (Sheet 6 of 7) Updated & added notes 1 Drawing revised
STD-W-10 GENERAL PIPE CONNECTIONS (Sheet 7 of 7) Updated & added notes 1 Drawing revised
STD-W-11 TYPICAL SERVICE LAYOUT INDICATING SEPARATION DISTANCES Updated & added notes 1 Drawing revised
STD-W-12 RESTRICTIONS ON EXISTING TREES / SHRUBS PLANTING ADJACENT TO Revised to suit ILI recommendations Changed drawing title 2 Drawing revised
WATERMAINS
STD-W-12A RESTRICTIONS ON NEW TREES / SHRUBS PLANTING ADJACENT TO 0 New Drawing
WATERMAINS
STD-W-13 TRENCH BACKFILL & BEDDING Updated & added notes 1 Drawing revised
STD-W-14 SLUICE VALVE FOR DUCTILE IRON (D.I.) PIPE (<350mm DIA.) (Sheet 1 of Updated & added notes 3 Drawing revised
2)
STD-W-15 SLUICE VALVE FOR POLYETHYLENE (P.E.) PIPE (<350mm DIA.) (Sheet 2 of Revised & added notes 2 Drawing revised
2)
STD-W-16 ON-LINE HYDRANT FOR DUCTILE IRON (D.I.) PIPE (Sheet 1 of 4) Revised & added notes 2 Drawing revised
STD-W-17 OFF-LINE HYDRANT FOR DUCTILE IRON (D.I.) PIPE (Sheet 2 of 4) Revised & added notes, & revised pipework 3 Drawing revised
STD-W-18 ON-LINE HYDRANT FOR POLYETHYLENE (P.E.) PIPE (Sheet 3 of 4) Revised & added notes 2 Drawing revised
STD-W-19 OFF-LINE HYDRANT FOR POLYETHYLENE (P.E.) PIPE (Sheet 4 of 4) Revised & added notes, & revised pipework 3 Drawing revised
STD-W-20 ON-LINE AIR VALVE FOR DUCTILE IRON (D.I.) PIPE (Sheet 1 of 4) Updated & revised notes 2 Drawing revised
STD-W-21 OFF-LINE AIR VALVE FOR DUCTILE IRON (D.I.) PIPE (Sheet 2 of 4) Updated & added notes 3 Drawing revised
STD-W-22 ON-LINE AIR VALVE FOR POLYETHYLENE (P.E.) PIPE (Sheet 3 of 4) Updated & added notes 2 Drawing revised
STD-W-23 OFF-LINE AIR VALVE FOR POLYETHYLENE (P.E.) PIPE (Sheet 4 of 4) Updated & added notes 3 Drawing revised
STD-W-24 PRESSURE REDUCING / SUSTAINING VALVE (P.R.V. / P.S.V.) CHAMBER Revised & added notes, & added chamber sizing 2 Drawing revised
table, fittings & kiosk
STD-W-25 BOOSTER PUMP STATION ARRANGEMENT 1 No change
STD-W-26 NON-MECH METER CHAMBER (40 -250mm DIA.) Revised notes & added table & hydrant Changed drawing title 3 Drawing revised
STD-W-26A MECH METER CHAMBER (40 -250mm DIA.) 0 New Drawing
STD-W-27 MARKER POSTS / PLATES Added BM plate Updated notes 2 Drawing revised
STD-W-28 WATER MAIN THRUST & SUPPORT BLOCKS Anti-Torque support note & thrust flange added Note 6 updated 1 Drawing revised
STD-W-29 DUCT CHAMBER Updated notes 2 Drawing revised
STD-W-30 SCOUR CHAMBER & HEAD WALL ARRANGEMENTS Updated notes 3 Drawing revised
WASHOUT HYDRANT Revised chamber base detail & updated & added 2 Drawing revised
STD-W-30A notes
STD-W-31 TYPICAL DITCH / STREAM CROSSING FOR WATER MAIN Updated pipe depth dimension 1 Drawing revised
STD-W-32 TYPICAL BRIDGE CROSSING FOR WATER MAIN (Sheet 1 of 2) Updated & added notes 1 Drawing revised
STD-W-33 TYPICAL BRIDGE CROSSING FOR WATER MAIN (Sheet 2 of 2) Updated pipe depth dimension, updated & added 1 Drawing revised
notes
STD-W-34 SECURITY GATE & FENCING Fencing table updated 2 Drawing revised
STD-W-35 PIPE REPAIR TO EXISTING MAINS Updated note 10 2 Drawing revised
STD-W-36 TELEMETRY AND WET KIOSK Note 10 revised 2 Drawing revised
STD-W-37 LAMP BOLLARD & LAMP STANDARD Updated notes 1 Drawing revised
/ INDEX SHEET Inclusion of STD-W-12A & STD-W-26A Drawing revisions updated Nov. 2017 Drawing revisions updated
/ Design Risk Assessment for Water Standard Details Inclusion of STD-W-12A & STD-W-26A General Amendments v4.01 Document revised