Standard Details
Connections and Developer Services
Construction Requirements for Self-Lay Developments
December 2017 (Revision 03)
Document IW-CDS-5020-01
IW-CDS-5020-01
Revision Log
Date Details of Revision Revision Author Approver
April 2016 General revisions & 01 T’OC M’OD
drawing added
August 2016 General revisions 02 TO’C MO’D
December 2017 General revisions & 03 TO’C MO’D
drawing added
IW-CDS-5020-01 Rev. 03 December 2017
Background
Technical Documentation has been developed by Irish Water’s Connections and
Developer Services which outlines the requirements for water services infrastructure
within developments.
These standard details have been developed to outline to developers Irish Water’s
requirements for the provision of water infrastructure that is to be installed in
developments and that would be connected to Irish Water’s networks and subsequently
vested in Irish Water.
The aim is to provide details to developers for water infrastructure, which will outline
design and construction requirements to ensure consistency in the provision of
materials, equipment and workmanship, etc. The standard details will also provide the
basis for developers’ detailed design proposals for water infrastructure, leading to the
provision of infrastructure that is suitable for connection to Irish Water’s networks and
easy operation and maintenance of the new infrastructure.
The standard details are based on best practice within the water industry. They take
account of the experience of Local Authorities in the provision of these services to new
developments. They have been successfully used by Irish Water’s own internal
functions for a variety of projects and they are in line with water utility industry norms.
There are 40 No Standard Details dealing with water infrastructure covering all aspects
of such infrastructure.
The use of the standard details is mandatory in all new Irish Water Connection
Agreement Offers issued after 1st June 2016.
IW-CDS-5020-01 Rev. 03 December 2017
Standard Details for Water Networks
Index Sheet
Drawing No. Drawing Title Rev.
STD-W-01 Water service connection responsibility 0
STD-W-02 Typical layout for water mains within developments 1
STD-W-03 Customer connection & boundary box 3
STD-W-04 General pipe connections (sheet 1 of 7) 3
STD-W-05 General pipe connections (sheet 2 of 7) 2
STD-W-06 General pipe connections (sheet 3 of 7) 2
STD-W-07 General pipe connections (sheet 4 of 7) 1
STD-W-08 General pipe connections (sheet 5 of 7) 1
STD-W-09 General pipe connections (sheet 6 of 7) 1
STD-W-10 General pipe connections (sheet 7 of 7) 1
STD-W-11 Typical service layout indicating separation distances 1
STD-W-12 Restrictions on water infrastructure works adjacent to existing trees 2
STD-W-12A Restrictions on new trees / shrubs planting adjacent to watermains 0
STD-W-13 Trench backfill & bedding 1
STD-W-14 Sluice valve for ductile iron (D.I.) pipe (<350mm dia.) (sheet 1 of 2) 3
STD-W-15 Sluice valve for polyethylene (P.E.) pipe (<350mm dia.) (sheet 2 of 2) 2
STD-W-16 On-line hydrant for ductile iron (D.I.) pipe (sheet 1 of 4) 2
STD-W-17 Off-line hydrant for ductile iron (D.I.) pipe (sheet 2 of 4) 3
STD-W-18 On-line hydrant for polyethylene (P.E.) pipe (sheet 3 of 4) 2
STD-W-19 Off-line hydrant for polyethylene (P.E.) pipe (sheet 4 of 4) 3
STD-W-20 On-line air valve for ductile iron (D.I.) pipe (sheet 1 of 4) 2
STD-W-21 Off-line air valve for ductile iron (D.I.) pipe (sheet 2 of 4) 3
STD-W-22 On-line air valve for polyethylene (P.E.) pipe (sheet 3 of 4) 2
STD-W-23 Off-line air valve for polyethylene (P.E.) pipe (sheet 4 of 4) 3
STD-W-24 Pressure reducing / sustaining valve (P.R.V. / P.S.V.) chamber 2
STD-W-25 Booster pump station arrangement 1
STD-W-26 Non Mech. Meter chamber (40 - 250mm dia.) 3
STD-W-26A Mech. Meter chamber (40 - 250mm dia.) 0
STD-W-27 Marker posts / plates 2
STD-W-28 Water main thrust & support blocks 1
STD-W-29 Duct chamber 2
STD-W-30 Scour chamber & head wall arrangements 3
STD-W-30A Washout hydrant 2
STD-W-31 Typical ditch / stream crossing for water main 1
STD-W-32 Typical bridge crossing for water main (sheet 1 of 2) 1
STD-W-33 Typical bridge crossing for water main (sheet 2 of 2) 1
STD-W-34 Security gate & fencing 2
STD-W-35 Pipe repair to existing mains 2
STD-W-36 Telemetry and wet kiosk 2
STD-W-37 Lamp bollard & lamp standard 1
These Standard Details show the acceptable typical details and outline on the minimum standards that are required by Irish Water for the
provision of water pipes and related infrastructure which are to be connected to the Irish Water Network. They shall be used in conjunction
with the associated Design Risk Assessments that have been developed which identify the risks that designers shall take into account in the
detailed design of the water and wastewater pipes and related infrastructure to be connected to the Irish Water Network. The pipes and
related infrastructure to be put in place within developments shall comply fully with these Standard Details. Ultimate responsibility (including,
but not limited to, any losses, costs, demands, damages, actions, expenses, negligence and claims) for the detailed design, construction
and provision of such pipes and related infrastructure shall rest entirely with the Developer, his/her Designer(s), Contractor(s) or other
connected party. Irish Water assumes no responsibility for and gives no guarantees, undertakings or warranties in relation to the pipes and
related infrastructure to be provided in accordance with these Standard Details.
No part of the Standard Details shall be reproduced or transmitted in any form or stored in any retrieval system of any nature without the
prior written permission of Irish Water as copyright holder, except as agreed for use.
These Standard Details shall be used in conjunction with current Irish Water Codes of Practice, which will take precedence over the
Standard Details.
These Standard Details may also be used for the installation of water & wastewater infrastructure for Asset Delivery Works & Capital Project
Works Programmes at the discretion of Irish Water.
DEC. 2017
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
CUSTOMER PROPERTY
PROPERTY BOUNDARY
FOOTPATH
ROAD
BOUNDARY BOX
225mm
DISTRIBUTION SYSTEM
SERVICE PIPE
WATER MAIN
A B C
MAINTENANCE
RESPONSIBILITY
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
2. THE MINIMUM PIPE SIZE SHALL BE 100mm INTERNAL DIAMETER IN HOUSING DEVELOPMENTS OF 40 AND UP TO 100 HOUSES. DEVELOPMENTS OF 100 HOUSES AND ABOVE SHALL HAVE A MINIMUM PIPE SIZE OF 150mm INTERNAL
DIAMETER SPINE AND 100mm BRANCH MAINS. NOMINAL INTERNAL DIAMETERS OF 80mm AND LESS MAY BE ALLOWED IN SMALLER DEVELOPMENTS BUT NOT WHERE HYDRANTS ARE LOCATED AND ONLY AFTER PRIOR WRITTEN
AGREEMENT FROM IRISH WATER
4. EVERY PREMISE SHOULD HAVE A SEPARATE SERVICE CONNECTION. THE USE OF COMMON SERVICE PIPES IS NOT ALLOWED. SERVICE CONNECTIONS SHALL BE AS SHORT AS REASONABLY POSSIBLE. LONG SERVICE
CONNECTIONS (IN EXCESS OF 15m) WILL NOT BE ALLOWED. A RIDER MAIN AT THE OPPOSITE SIDE OF THE ROAD TO THE MAIN WATER MAIN MAY BE REQUIRED SUBJECT TO APPROVAL FROM IRISH WATER. SERVICE
CONNECTIONS SHALL BE A MINIMUM PIPE SIZE OF 25mm OUTSIDE DIAMETER, 20mm INTERNAL DIAMETER.
5. WATER MAINS SHOULD BE LAID TO PROVIDE THE OPTIMUM CIRCULATION IN THE LOCAL WATER NETWORK. WATER MAINS MAY TERMINATE IN A DEAD END ONLY WITH IRISH WATER APPROVAL, IN WHICH CASE AN ON-LINE
WASHOUT HYDRANT SHALL BE PROVIDED AT THE DEAD END, LOCATED WITHIN A CHAMBER OR KIOSK.
6. VALVES SHALL BE ARRANGED IN SUCH A MANNER TO ALLOW THE NETWORK TO BE MANAGED TO ENSURE THAT NO MORE THAN 40 PROPERTIES LOSE WATER FROM A BURST ON THE SYSTEM, AT ANY ONE TIME.
7. NO DOMESTIC PROPERTY SHALL BE MORE THAN 46m FROM A HYDRANT. HYDRANT DETAILS AND LOCATIONS SHALL BE SUBJECT TO THE APPROVAL OF THE RELEVANT LOCAL AUTHORITY FIRE DEPARTMENT.
8. WATER SUPPLY MAINS SHALL BE LAID IN COMMON AREAS AND NOT THROUGH INDIVIDUAL PRIVATE GARDENS OR DRIVEWAYS ETC.
10. THE WATER MAIN PIPEWORK TO NEW DEVELOPMENTS SHOULD BE LOCATED AT THE RIGHT HAND SIDE OF THE ENTRANCE TO THE NEW DEVELOPMENT (FROM A VIEW FACING INTO THE DEVELOPMENT) IF POSSIBLE AND WHERE
THE PROPERTIES ARE EQUALLY AND REASONABLY DISTRIBUTED AT BOTH SIDES OF THE ESTATE ROADWAY.
11. AIR VALVES TO BE LOCATED AT POINTS WHERE AIR IS LIKELY TO BUILD UP.
12. THE DEVELOPER IS TO LIAISE WITH THE FIRE SERVICES AUTHORITY IN ORDER TO ENSURE FIRE FLOWS ARE AVAILABLE THROUGHOUT THE DEVELOPMENT.
13. BULK FLOW METERS SHALL BE FITTED IN ALL DEVELOPMENTS WITH A DEMAND IN EXCESS OF 20m³ PER DAY. BULK FLOW METERS SHALL HAVE A FACTORY FITTED AMR AND INSTALLED IN A SUITABLY SIZED CHAMBER.
DEVELOPMENTS WITH DEMAND LESS THAN 20m³ PER DAY SHALL BE PROVIDED WITH DEDICATED BYPASS PIPEWORK AND CHAMBER TO ACCOMMODATE LOCATION OF A TEMPORARY NIGHT FLOW METER.
14. WATERMAINS TO BE LOCATED IN GRASS VERGE . IF GRASS VERGE IS NOT AVAILABLE, WATERMAINS TO BE LOCATED UNDER FOOTPATH AWAY FROM KERB. REFER TO STD-W-11 FOR TYPICAL UTILITY LAYOUT.
S.V.
S.V. S.V.
H.
H.
H.
H.
A.V.
LEGEND
S.V.
TELECOMMUNICATIONS
H. S.V. S.V.
STORM WATER
FOUL SEWER
WATER MAIN
ELECTRICITY
BOUNDARY
GAS MAIN
CABLE TV
H.
KERB
Sc.V.
H.
S.V. Me S.V.
S.V.
GRASS VERGE BUILDING
ROAD
FOOTPATH S.V.
ROAD
SEE NOTE
1 ABOVE
H. BUILDING
TYPICAL LAYOUT
1 11/'17 JMC TOC Temp. "dead end" & note 1 ref. added MOD FOR WATER MAINS WITHIN DEVELOPMENTS STD-W- 02 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
GENERAL NOTES:
1. THE BOUNDARY BOX IS TO BE IN ACCORDANCE WITH THE IRISH WATER SPECIFICATION, INCORPORATING A G1.5
MANIFOLD, STOP-TAP, FROST PLUG & NON-RETURN VALVE.
2. THE BOUNDARY BOX SHALL BE POSITIONED IN PUBLIC SPACE & AS CLOSE AS POSSBILE TO THE PROPERTY BOUNDARY
BUT NO PART OR FITTING TO BE WITHIN 225mm OF THE PROPERTY LINE.
3. THE BOUNDARY BOX SHALL BE LOCATED WHERE IT IS SAFE TO OPEN THE COVER & ACCESS THE STOP TAP OR VISUALLY
READ THE METER, i.e. ON A FOOTPATH OR VERGE, & NOT IN A CARRIAGEWAY.
4. THE SURFACE BOX COVER ON THE BOUNDARY BOX SHOULD BE NOT LESS THAN GRADE C (BS 5834:2-2011); & THE
BOUNDARY BOX SHOULD BE LOCATED SUCH THAT HEAVIER GRADES OF COVER WOULD NOT BE REQUIRED.
5. THE SHAFT OF THE BOUNDARY BOX IS TO BE INSTALLED VERTICALLY, & THE SURFACE BOX/COVER INCLINED TO MATCH
THE SURFACE GRADIENT.
6. THE BOUNDARY BOX IS TO BE INSTALLED AT A MINIMUM DEPTH OF 600mm (+/- 25mm) TO THE CROWN OF THE INLET &
OUTLET FITTINGS ON THE OUTSIDE OF THE BOX.
7. THE SERVICE CONNECTION PIPE SHALL NOT BE WRAPPED AROUND THE SHAFT OF THE BOUNDARY BOX OR BENT IN ANY
RADIUS LESS THAN THAT APPROVED BY THE MANUFACTURER. CUSTOMER
8. THE PIPE FITTINGS TO THE BOUNDARY BOX SHALL BE APPROVED BY THE BOUNDARY BOX MANUFACTURER. PROPERTY
9. THE BOUNDARY BOX SHALL BE INSTALLED HYGIENICALLY & LEFT CLEAN & FREE OF CONSTRUCTION WASTE OR DIRT FOR
LATER METER INSTALLATION BY IRISH WATER. PROPERTY
10. BOX TO BE FOUNDED ON 100mm DEPTH OF C12/15 CONCRETE AND SURROUNDED WITH CLAUSE 808 GRANULAR MATERIAL. BOUNDARY
11. THE DESIRABLE MINIMUM COVER FROM THE FINISHED GROUND LEVEL TO THE EXTERNAL CROWN OF A SERVICE
CONNECTION SHALL BE 750mm WITH AN ABSOLUTE MINIMUM DEPTH OF 600mm FOR SHORT DISTANCES (SUBJECT TO IRISH
WATER AGREEMENT). THE DESIRABLE MAXIMUM COVER FOR A SERVICE CONNECTION PIPE SHOULD BE 1200mm, WHERE SEE NOTE
PRACTICABLE. 6 ABOVE 225mm
IRISH WATER
12. CUSTOMER'S DISTRIBUTION PIPEWORK WITHIN THE PREMISES SHOULD BE SUITABLY SIZED TO ACCOMMODATE FLOW APPROVED
FROM 20mm INTERNAL DIAMETER SERVICE PIPE. BOUNDARY BOX
MARKER TAPE
ROAD
350 mm
WELL
100 mm
COMPACTED
CLAUSE 808
GRANULAR
BACKFILL
REFER TO NOTE 3
STD-W-13
FOR BACKFILL DETAILS
THIS DETAIL APPLIES TO WHERE
THE FINISHED SURFACE IS EITHER
UNBOUND (GRASS VERGE), BRICK TO SUIT SURFACE FINISH OF CUSTOMER
PAVING OR MACADAM, & WHERE A SURROUNDING AREA DISTRIBUTION SYSTEM
CONCRETE PLINTH IS REQUIRED 475mm
TO SUPPORT THE TOP OF THE (APPROX.) 25mm (O.D.)
BOUNDARY BOX. FITTINGS TO BE APPROVED BY
PE PIPE BOUNDARY BOX MANUFACTURER
COVER
WATER MAIN
PRECAST CONCRETE
SURROUND
REFER TO NOTE 5
STD-W-13
FOR BEDDING DETAILS
PLAN SECTION
CONCRETE SURROUND
TO BOUNDARY BOX COVER
CUSTOMER
THE CONNECTION PIPE IS TO THE CONNECTION PIPE IS TO PROPERTY
BE LAID SLACK WITH NO KINKS BE LAID SLACK WITH NO KINKS
TO MANUFACTURER'S TO MANUFACTURER'S
SPECIFICATION. SPECIFICATION.
PLAN
FOR D.I. FOR POLYETHYLENE ( PE )
WATER MAINS WATER MAIN ONLY
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
3 11/'17 JMC TOC Updated & added notes MOD TITLE DRAWING No. REV
2 08/'16 JMC TOC Revised D.I. service MOD CUSTOMER CONNECTION AND BOUNDARY BOX
tapping detail
1 04/'16 JMC TOC Added dimensions & notes MOD (25mm OD PIPE) STD-W- 03 3
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
REFER TO 1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED
NOTE 10 NEW FLANGED THRUST FLANGE (THRUST
STUB FLANGE OTHERWISE.
PLAIN ENDED BLOCK OMITTED FOR
( WITH BACKING RING )
DI PIPE CLARITY, SEE STD-W-28)
2. ALL BENDS, TEES, DEAD ENDS, ETC. OF PIPELINES TO BE
NEW PE PIPE ADEQUATELY RESTRAINED BY THRUST BLOCKS AS PER DRAWING
FLOW No. STD-W-28. THRUST BLOCKS NOT SHOWN FOR CLARITY.
LONG BODY
FLEXIBLE COUPLING DISMANTLING SV
STEPPED OR
JOINT FLEXIBLE COUPLING
THRUST FLANGE (THRUST
BLOCK OMITTED FOR NEW DI - EXISTING AC / CI / uPVC
CLARITY, SEE STD-W-28)
REFER TO
NOTE 10
NEW FLANGED PLAIN NEW FLANGED PLAIN
ENDED DI PIPE ENDED DI PIPE
NEW DI PIPE
EXISTING DI PIPE
FLOW
SV LONG BODY
LONG BODY CONCENTRIC DISMANTLING
FLEXIBLE
FLEXIBLE TAPER JOINT
COUPLING
COUPLING (IF REQUIRED)
THRUST FLANGE (THRUST
NEW DI - EXISTING DI BLOCK OMITTED FOR
CLARITY, SEE STD-W-28)
REFER TO
STUB FLANGE CONCENTRIC NOTE 10 STUB FLANGE
(WITH BACKING RING) TAPER (WITH BACKING RING)
DISMANTLING
(IF REQUIRED)
JOINT
NEW PE PIPE
EXISTING PE PIPE
FUSION FUSION
SV WELD
WELD
NEW PE - EXISTING PE
REFER TO CONCENTRIC
NEW FLANGED PLAIN NOTE 10 TAPER STUB FLANGE
ENDED DI PIPE (IF REQUIRED) (WITH BACKING RING)
NEW DI PIPE
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
Added 2 No. Extg. PE Details,
3 11/'17 JMC TOC MOD TITLE DRAWING No. REV
updated details & added notes
2 08/'16 JMC TOC Added Note 9 MOD GENERAL PIPE CONNECTIONS
1 04/'16 JMC TOC Added couplings (2 details) MOD (Sheet 1 of 7) STD-W- 04 3
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
NEW PE PIPE
NEW DI PIPE
2. ALL BENDS, TEES, DEAD ENDS, ETC. OF PIPELINES TO BE ADEQUATELY
RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28.
THRUST BLOCKS NOT SHOWN FOR CLARITY.
ALL
SV FLANGED SV
LONG BODY DISMANTLING TEE DISMANTLING LONG BODY
DOUBLE FLANGED DOUBLE FLANGED
FLEXIBLE JOINT JOINT FLEXIBLE
SEPARATION PIPE SEPARATION PIPE
COUPLING COUPLING
NEW PE / DI - EXISTING DI
SV
LONG BODY ON-LINE HYDRANT.
DISMANTLING BLANK FLANGE
FLEXIBLE REFER TO STD-W-16
JOINT
DISMANTLING COUPLING FOR DETAILS.
JOINT
DOUBLE FLANGED TEMPORARY "DEAD-END" DETAIL (FOR FUTURE EXTENSION) - DI
PIPE (TO SUIT VALVE
CHAMBER
STUB FLANGE STUB FLANGE
(WITH BACKING RING)
ARRANGEMENT) (WITH BACKING RING)
SV SV
EXISTING PE PIPE EXISTING PE PIPE
NEW PE - EXISTING PE
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
Added new D.I. pipe to details, added
2 11/'17 JMC TOC
3 No. details & updated notes
MOD GENERAL PIPE CONNECTIONS
1 08/'16 JMC TOC Added Note 10 MOD (Sheet 2 of 7) STD-W- 05 2
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
AC / CI / uPVC / DI PIPE
4. CONNECTING TO EXISTING MAINS IS TO BE CARRIED OUT BY IRISH
WATER OR AN APPROVED IRISH WATER AGENT.
EXISTING PE PIPE
EXISTING
PROTECTION TO BE PUT IN PLACE TO EXISTING MAINS, METHOD OF
REMOVAL OF EXISTING AC, METHOD OF DISPOSAL OF EXISTING AC AND
METHOD OF CONNECTION TO EXISTING AC.
COUPLING
CI - CAST IRON
PE - POLYETHYLENE
PE STUB FLANGE FUSION
uPVC - UNPLASTICISED POLY VINYL CHLORIDE
(WITH BACKING RING) WELD ST - STEEL
LONG BODY
OTHER - REFERS TO ALL EXISTING PIPE MATERIALS OTHER THAN PE
FLANGE
(TYPICALLY AC, DI, CI, uPVC & ST)
ADAPTOR
7. SLUICE VALVE CHAMBERS TO BE IN ACCORDANCE WITH STD-W-14 (DI)
CONCENTRIC TAPER AND STD-W-15 (PE). CHAMBERS NOT SHOWN FOR CLARITY.
(IF REQUIRED)
8. ALL THRUST FLANGES TO BE ADEQUATELY RESTRAINED BY THRUST
BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN
SV FOR CLARITY.
DOUBLE FLANGED PIPE STUB FLANGE 10. A HIGH LEVEL OF HEALTH & SAFETY PROCEDURES IS REQUIRED WHEN
STUB FLANGE (TO SUIT VALVE CHAMBER ( WITH BACKING WORKING ON AC MAINS, & THE OPERATION OF DISMANTLING/ REMOVAL
( WITH BACKING ARRANGEMENT) RING ) OF AC PIPES & JOINTS.
RING )
11. VALVES SHALL BE ARRANGED IN SUCH A MANNER TO ALLOW FOR
NEW PE PIPE NEW PE PIPE
NETWORK TO BE MANAGED TO ENSURE THAT NO MORE THAN 40
PROPERTIES LOSE WATER FROM A BURST ON THE SYSTEM AT ANY ONE
TIME.
ALL
FUSION FUSION
SV FLANGED SV
WELD DISMANTLING WELD
DISMANTLING DOUBLE FLANGED TEE DOUBLE FLANGED
JOINT SEPARATION PIPE SEPARATION PIPE JOINT
EXISTING
/ DI PIPE
PE PIPE
STEPPED OR
FLEXIBLE
COUPLING
NEW DI PIPE
CONCENTRIC TAPER
(IF REQUIRED)
SV
DISMANTLING
JOINT DOUBLE
FLANGED PIPE
(TO SUIT VALVE
NEW FLANGED PLAIN NEW FLANGED PLAIN
CHAMBER
ENDED DI PIPE c/w ENDED DI PIPE c/w
ARRANGEMENT)
THRUST FLANGE THRUST FLANGE
NEW DI PIPE NEW DI PIPE
ALL
FLANGED
LONG BODY DISMANTLING SV SV DISMANTLING LONG BODY
DOUBLE FLANGED TEE DOUBLE FLANGED
FLEXIBLE JOINT JOINT FLEXIBLE
COUPLING SEPARATION PIPE SEPARATION PIPE COUPLING
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
Added extg. PE pipe to details
2 11/'17 JMC TOC
& updated notes
MOD GENERAL PIPE CONNECTIONS
1 08/'16 JMC TOC Added Note 10 MOD (Sheet 3 of 7) STD-W- 06 2
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
NEW PE PIPE
5. WHEN EXISTING AC WATERMAINS ARE PRESENT A SPECIFIC METHOD
STATEMENT SHALL BE SUBMITTED TO IRISH WATER PRIOR TO WORKS
TAKING PLACE AND SUBJECT TO WRITTEN APPROVAL, DETAILING THE
PROTECTION TO BE PUT IN PLACE TO EXISTING MAINS, METHOD OF
REMOVAL OF EXISTING AC, METHOD OF DISPOSAL OF EXISTING AC AND
METHOD OF CONNECTION TO EXISTING AC.
LONG BODY
FLANGE ADAPTOR
CONCENTRIC TAPER
(IF REQUIRED)
SV
DISMANTLING
JOINT
DOUBLE
FLANGED PIPE
(TO SUIT VALVE
FLANGED PLAIN CHAMBER FLANGED PLAIN
ENDED DI PIPE c/w ARRANGEMENT) ENDED DI PIPE c/w
THRUST FLANGE THRUST FLANGE
NEW DI PIPE NEW DI PIPE
ALL
FLANGED
LONG BODY DISMANTLING SV SV DISMANTLING LONG BODY
DOUBLE FLANGED TEE DOUBLE FLANGED
FLEXIBLE JOINT JOINT FLEXIBLE
COUPLING SEPARATION PIPE SEPARATION PIPE COUPLING
NEW DI - NEW DI
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
2. ALL BENDS, TEES, DEAD ENDS, ETC. OF PIPELINES TO BE ADEQUATELY RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN FOR CLARITY.
3. BUTT FUSION WELDING AND ELECTRO FUSION JOINTING OF PIPES SHALL ONLY BE CARRIED OUT BY TRAINED OPERATIVES IN POSSESSION OF A CURRENT TRAINING CERTIFICATE, USING FULLY AUTOMATIC APPROVED JOINTING MACHINE/RIGS IN
ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. THE IDENTITY OF THE PE PIPELINE MANUFACTURER SHALL BE MADE KNOWN TO IRISH WATER PRIOR TO COMMENCEMENT OF THE INSTALLATION. CERTIFICATION AND TESTING (INCLUDING
INDEPENDENT THIRD PARTY CERTIFICATION) SHALL BE PROVIDED TO CONFIRM QUALITY ASSURANCE COMPLIANCE. EACH JOINT SHALL BE CLEARLY MARKED WITH THE JOINT LOGGED AUTOMATICALLY ON THE JOINTING MACHINE. A PRINTOUT OF THE
JOINT DETAILS, WITH A GPS LOCATION OF EACH JOINT, SHALL BE PROVIDED AND RETAINED FOR QUALITY ASSURANCE PURPOSES.
4. CONNECTING TO EXISTING MAINS IS TO BE CARRIED OUT BY IRISH WATER OR AN APPROVED IRISH WATER AGENT.
5. WHEN EXISTING AC WATERMAINS ARE PRESENT A SPECIFIC METHOD STATEMENT SHALL BE SUBMITTED TO IRISH WATER PRIOR TO WORKS TAKING PLACE AND SUBJECT TO WRITTEN APPROVAL, DETAILING THE PROTECTION TO BE PUT IN PLACE TO
EXISTING MAINS, METHOD OF REMOVAL OF EXISTING AC, METHOD OF DISPOSAL OF EXISTING AC AND METHOD OF CONNECTION TO EXISTING AC.
7. SLUICE VALVE CHAMBERS TO BE IN ACCORDANCE WITH STD-W-14 (DI) AND STD-W-15 (PE). CHAMBERS NOT SHOWN FOR CLARITY.
8. ALL THRUST FLANGES TO BE ADEQUATELY RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN FOR CLARITY.
9. DOUBLE FLANGED SEPARATION PIPE, UP TO 5m IN LENGTH, MAY BE REQUIRED TO ALLOW SEPARATION DISTANCE BETWEEN VALVE CHAMBERS.
DISMANTLING DISMANTLING
JOINT JOINT
SV SV
CONCENTRIC CONCENTRIC
TAPER (IF REQUIRED) TAPER (IF REQUIRED)
ALL ALL
NEW SV FLANGED SV NEW FLANGED PLAIN SV FLANGED SV FLANGED PLAIN
FLANGED DOUBLE FLANGED FLANGED DOUBLE FLANGED
TEE ENDED DI PIPE TEE ENDED DI PIPE
PLAIN ENDED PIPE (TO SUIT PLAIN ENDED PIPE (TO SUIT
DI PIPE DI PIPE c/w THRUST c/w THRUST
VALVE CHAMBER FLANGE VALVE CHAMBER FLANGE
DISMANTLING ARRANGEMENT) DISMANTLING ARRANGEMENT)
NEW DI PIPE JOINT NEW DI PIPE NEW DI JOINT NEW DI
PIPE PIPE
SV SV
CONCENTRIC CONCENTRIC
TAPER (IF REQUIRED) TAPER (IF REQUIRED)
LONG BODY LONG BODY
FLANGE FLANGE EXISTING
ADAPTOR STUB PIPE MATERIAL
ADAPTOR
FLANGE OTHER THAN PE
EXISTING
STUB ( WITH
PIPE MATERIAL
FLANGE NEW FLANGE BACKING NEW FLANGE
OTHER THAN PE
( WITH PLAIN ENDED PIPE RING ) PLAIN ENDED PIPE
BACKING (CUT TO SUIT) NEW FLANGED (CUT TO SUIT) NEW FLANGED
RING ) ALL PLAIN ENDED DI ALL PLAIN ENDED DI
FLANGED PIPE c/w THRUST FLANGED PIPE c/w THRUST
EXISTING SV SV EXISTING FLANGE SV SV FLANGE
TEE TEE
PE PIPE PE PIPE
FUSION FUSION
DOUBLE FLANGED DOUBLE FLANGED STEPPED OR DISMANTLING DOUBLE FLANGED DOUBLE FLANGED DISMANTLING STEPPED OR
WELD DISMANTLING SEPARATION PIPE SEPARATION PIPE
DISMANTLING WELD
SEPARATION PIPE SEPARATION PIPE
JOINT JOINT FLEXIBLE JOINT JOINT FLEXIBLE
(SEE NOTE 9) (SEE NOTE 9) (SEE NOTE 9) (SEE NOTE 9)
COUPLING COUPLING
2. ALL BENDS, TEES, DEAD ENDS, ETC. OF PIPELINES TO BE ADEQUATELY RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN FOR CLARITY.
3. BUTT FUSION WELDING AND ELECTRO FUSION JOINTING OF PIPES SHALL ONLY BE CARRIED OUT BY TRAINED OPERATIVES IN POSSESSION OF A CURRENT TRAINING CERTIFICATE, USING FULLY AUTOMATIC APPROVED JOINTING MACHINE/RIGS IN
ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. THE IDENTITY OF THE PE PIPELINE MANUFACTURER SHALL BE MADE KNOWN TO IRISH WATER PRIOR TO COMMENCEMENT OF THE INSTALLATION. CERTIFICATION AND TESTING (INCLUDING
INDEPENDENT THIRD PARTY CERTIFICATION) SHALL BE PROVIDED TO CONFIRM QUALITY ASSURANCE COMPLIANCE. EACH JOINT SHALL BE CLEARLY MARKED WITH THE JOINT LOGGED AUTOMATICALLY ON THE JOINTING MACHINE. A PRINTOUT OF THE
JOINT DETAILS, WITH A GPS LOCATION OF EACH JOINT, SHALL BE PROVIDED AND RETAINED FOR QUALITY ASSURANCE PURPOSES.
4. CONNECTING TO EXISTING MAINS IS TO BE CARRIED OUT BY IRISH WATER OR AN APPROVED IRISH WATER AGENT.
5. WHEN EXISTING AC WATERMAINS ARE PRESENT A SPECIFIC METHOD STATEMENT SHALL BE SUBMITTED TO IRISH WATER PRIOR TO WORKS TAKING PLACE AND SUBJECT TO WRITTEN APPROVAL, DETAILING THE PROTECTION TO BE PUT IN PLACE TO
EXISTING MAINS, METHOD OF REMOVAL OF EXISTING AC, METHOD OF DISPOSAL OF EXISTING AC AND METHOD OF CONNECTION TO EXISTING AC.
7. SLUICE VALVE CHAMBERS TO BE IN ACCORDANCE WITH STD-W-14 (DI) AND STD-W-15 (PE). CHAMBERS NOT SHOWN FOR CLARITY.
8. ALL THRUST FLANGES TO BE ADEQUATELY RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN FOR CLARITY.
9. DOUBLE FLANGED SEPARATION PIPE, UP TO 5m IN LENGTH, MAY BE REQUIRED TO ALLOW SEPARATION DISTANCE BETWEEN VALVE CHAMBERS.
DOUBLE DOUBLE
FLANGED FLANGED
SEPARATION SEPARATION
NEW PE PIPE (SEE PIPE (SEE
NEW PE
PIPE SV NOTE 9) ALL FLANGED NOTE 9) SV
TEE PIPE
FUSION FUSION
WELD DISMANTLING DISMANTLING WELD
JOINT CONCENTRIC JOINT
TAPER (IF REQUIRED)
NEW PE
PIPE
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
2. ALL BENDS, TEES, DEAD ENDS, ETC. OF PIPELINES TO BE ADEQUATELY RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN FOR CLARITY.
3. BUTT FUSION WELDING AND ELECTRO FUSION JOINTING OF PIPES SHALL ONLY BE CARRIED OUT BY TRAINED OPERATIVES IN POSSESSION OF A CURRENT TRAINING CERTIFICATE, USING FULLY AUTOMATIC APPROVED JOINTING MACHINE/RIGS IN
ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. THE IDENTITY OF THE PE PIPELINE MANUFACTURER SHALL BE MADE KNOWN TO IRISH WATER PRIOR TO COMMENCEMENT OF THE INSTALLATION. CERTIFICATION AND TESTING (INCLUDING
INDEPENDENT THIRD PARTY CERTIFICATION) SHALL BE PROVIDED TO CONFIRM QUALITY ASSURANCE COMPLIANCE. EACH JOINT SHALL BE CLEARLY MARKED WITH THE JOINT LOGGED AUTOMATICALLY ON THE JOINTING MACHINE. A PRINTOUT OF THE
JOINT DETAILS, WITH A GPS LOCATION OF EACH JOINT, SHALL BE PROVIDED AND RETAINED FOR QUALITY ASSURANCE PURPOSES.
4. CONNECTING TO EXISTING MAINS IS TO BE CARRIED OUT BY IRISH WATER OR AN APPROVED IRISH WATER AGENT.
5. WHEN EXISTING AC WATERMAINS ARE PRESENT A SPECIFIC METHOD STATEMENT SHALL BE SUBMITTED TO IRISH WATER PRIOR TO WORKS TAKING PLACE AND SUBJECT TO WRITTEN APPROVAL, DETAILING THE PROTECTION TO BE PUT IN PLACE TO
EXISTING MAINS, METHOD OF REMOVAL OF EXISTING AC, METHOD OF DISPOSAL OF EXISTING AC AND METHOD OF CONNECTION TO EXISTING AC.
7. SLUICE VALVE CHAMBERS TO BE IN ACCORDANCE WITH STD-W-14 (DI) AND STD-W-15 (PE). CHAMBERS NOT SHOWN FOR CLARITY.
8. ALL THRUST FLANGES TO BE ADEQUATELY RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN FOR CLARITY.
9. DOUBLE FLANGED SEPARATION PIPE, UP TO 5m IN LENGTH, MAY BE REQUIRED TO ALLOW SEPARATION DISTANCE BETWEEN VALVE CHAMBERS.
DOUBLE DOUBLE
FLANGED FLANGED
SEPARATION SEPARATION
PIPE (SEE ALL PIPE (SEE
EXISTING PE SV NOTE 9) FLANGED NOTE 9) SV EXISTING PE
PIPE TEE PIPE
FUSION FUSION
WELD DISMANTLING DISMANTLING WELD
JOINT CONCENTRIC JOINT
TAPER (IF REQUIRED)
LONG BODY
FLANGE ADAPTOR
NEW DI PIPE DOUBLE DOUBLE
NEW DI PIPE FLANGED FLANGED
LONG BODY SEPARATION SEPARATION
PIPE PIPE
FLEXIBLE SOCKETED BEND (SEE NOTE 9) (SEE NOTE 9)
JOINT FLANGED (IF REQUIRED)
STEPPED OR
PLAIN ENDED EXISTING FLEXIBLE
DISMANTLING ALL DISMANTLING STEPPED OR
DI PIPE JOINT FLEXIBLE
PIPE MATERIAL COUPLING FLANGED JOINT
COUPLING
NEW DI PIPE OTHER THAN PE TEE
DISMANTLING
JOINT
SOCKETED BEND
SV (IF REQUIRED)
DOUBLE NEW FLANGED SV SV NEW FLANGED
FLANGED PLAIN ENDED DI PLAIN ENDED DI
NEW DI PIPE PIPE c/w THRUST CONCENTRIC PIPE c/w THRUST
SEPARATION FLANGE TAPER (IF FLANGE
DISMANTLING
PIPE (SEE REQUIRED)
JOINT LONG BODY
NOTE 9)
FLANGE ADAPTOR
ALL EXISTING
NEW DI PIPE
FLANGED NEW DI PIPE PIPE MATERIAL
90° ALL
TEE LONG BODY OTHER THAN PE
FLANGED
DOUBLE SV BEND FLEXIBLE SOCKETED BEND
FLANGED JOINT FLANGED (IF REQUIRED)
SEPARATION PLAIN ENDED
PIPE (SEE DOUBLE FLANGED PIPE DI PIPE
NOTE 9) (TO SUIT VALVE CHAMBER NEW DI PIPE
ARRANGEMENT) DISMANTLING
SV JOINT
SOCKETED BEND
DISMANTLING SV (IF REQUIRED)
JOINT DOUBLE
FLANGED FLANGED
PLAIN ENDED SEPARATION NEW DI PIPE
DISMANTLING
DI PIPE PIPE (SEE
JOINT
NOTE 9)
LONG BODY
FLEXIBLE ALL
JOINT FLANGED
NEW DI PIPE 90° ALL
TEE
FLANGED
SV BEND
DOUBLE
FLANGED
SEPARATION
NEW DI - EXISTING PE PIPE (SEE
DOUBLE FLANGED PIPE
(TO SUIT VALVE CHAMBER
NOTE 9)
SV ARRANGEMENT)
DISMANTLING
JOINT
FLANGED
PLAIN ENDED
DI PIPE
LONG BODY
FLEXIBLE
JOINT
NEW DI PIPE
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
HORIZONTAL
300mm TO DISTRIBUTION MAINS OF LESS THAN 300mm DIAMETER.
500mm TO TRUNK MAINS BETWEEN 300mm AND 450mm DIAMETER.
3m TO ARTERIAL WATER MAINS OF GREATER THAN 450mm DIAMETER.
VERTICAL
300mm TO DISTRIBUTION MAINS OF LESS THAN 300mm DIAMETER.
500mm TO TRUNK/ARTERIAL MAINS OF DIAMETER GREATER THAN 300mm.
ANY PROPOSED PIPE CROSSING SHOULD BE LOCATED MID-WAY BETWEEN THE WATER JOINTS WITH MINIMUM
CLEAR DISTANCE OF 300mm AND UP TO 500mm. ALL CROSSINGS SHOULD BE AT LEAST 500mm AWAY FROM FITTINGS OR JOINTS.
HORIZONTAL
500mm AT EITHER SIDE OF MAINS UP TO AND INCLUDING 200mm IN DIAMETER.
1m AT EITHER SIDE OF MAINS OF 225mm TO 250mm DIAMETER.
2m AT EITHER SIDE OF MAINS OF 300mm TO 375mm IN DIAMETER.
5m AT EITHER SIDE OF MAINS OF 400mm AND 450mm IN DIAMETER.
SPECIFIC IRISH WATER ADVISED DISTANCES FOR MAINS IN EXCESS OF 475mm DIAMETER.
5. NOTIFICATION IN WRITING IS REQUIRED SHOULD WORKS BE WITHIN THE FOLLOWING DISTANCES FROM AN EXISTING WATER MAIN OR WASTEWATER RISING MAIN:-
HORIZONTAL
1000mm AT EITHER SIDE OF EXISTING MAINS LESS THAN OR EQUAL TO 200mm DIAMETER
2000mm AT EITHER SIDE OF EXISTING MAINS OF 250mm TO 350mm DIAMETER
5000mm AT EITHER SIDE OF EXISTING MAINS OF DIAMETER GREATER THAN 350mm DIAMETER
WHERE DUCTS OR PIPES ARE TO BE LAID CLOSE TO AN EXISTING WATERMAIN OR SEWER IN THE OWNERSHIP OF IRISH WATER,
NOTIFICATION IN WRITING SHALL BE PROVIDED A MINIMUM OF 10 DAYS AHEAD OF ADVANCEMENT OF THE WORK
NOTIFICATION IN WRITING IS REQUIRED SHOULD WORKS BE WITHIN 1.5m DISTANCE OF A WASTEWATER SEWER.
REQUIREMENTS SHALL ALSO APPLY TO TRIAL HOLES OR SLIT TRENCHES TO LOCATE THE MAIN OR GAIN GROUND INFO DATA.
LARGER DIAMETERS >300mm DISTRIBUTION AND TRUNK MAINS, IRISH WATER MUST BE NOTIFIED AT LEAST 1 MONTH IN ADVANCE.
DEVELOPERS SHALL ALSO COMPLY WITH ANY NOTIFICATION REQUIREMENTS OF OTHER UTILITY PROVIDERS (ESB, GAS MAIN, TELECOMMUNICATION ETC).
6. DETAILED PROPOSALS, INCLUDING WORK METHOD STATEMENTS, INSURANCE CONFIRMATION AND DETAILS OF WORK COMPLETED OF A SIMILAR NATURE MUST
BE SUBMITTED TO IRISH WATER FOR REVIEW. ALL SUCH WORKS IN THE VICINITY OF ARTERIAL WATER MAINS AND SEWER (MAINS GREATER THAN 400mm) SHALL BE SUBJECT
TO WRITTEN AGREEMENT WITH IRISH WATER BEFORE CONSTRUCTION COMMENCES ON SITE. THIS AGREEMENT SHALL ALSO INCLUDE ANY NECESSARY PROTECTION FOR
WATER MAINS.
7. ANY DAMAGE SHALL BE NOTIFIED IMMEDIATELY TO IRISH WATER. THE PERSON WHO CAUSES THE DAMAGE TO A WATER MAIN OR FITTING WILL BE DEEMED TO HAVE
COMMITTED AN OFFENCE UNDER SECTION 45 OF THE WATER SERVICES ACT 2007.
9. UNDER NO CIRCUMSTANCES WILL IRISH WATER ACCEPT WATER MAIN INSTALLATIONS UNDER STRUCTURES, EXISTING OR PROPOSED, OR IN CLOSE PROXIMITY TO
ANY EXISTING STRUCTURES OR FEATURES THAT WILL INHIBIT ACCESS FOR POST INSTALLATION MAINTENANCE AND ACCESS.
10. WHERE THE DESIGN DEVIATES FROM THIS STANDARD DETAIL, THE DESIGN SHALL BE SUBJECT TO THE
REVIEW OF IRISH WATER.
11. SEPARATION DISTANCES BETWEEN UTILITIES MAY BE INCREASED TO PROVIDE FOR CHAMBER & DIAMETER 'C'
THRUST BLOCKS AT BENDS. (mm) (mm)
'C'
≤150 3000
>600 8000
BUILDING
1000mm MINIMUM 750mm
CABLE TV
MIN. 900mm
TELECOMMUNICATIONS
'A' 'A'
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
METHOD STATEMENTS:
ALL WORKS SHALL BE CARRIED
OUT IN ACCORDANCE WITH BS 5837 AND INFORMED BY
NJUG VOLUME 4
PRECAUTION AREA:
EXCLUSION AREA:
PREVENTION MEASURES
REQUIRED IN LINE WITH
LANDSCAPING DESIGN & SPECIAL
GIRTH x 4
PROTECTION REQUIRED. (e.g. BY NO WORKS PERMITTED
USE OF APPROPRIATE BARRIERS,
HIGH PERFORMANCE JOINTS, OR
BY USE OF POLYETHYLENE WITH
WELDED JOINTS). THE LANDSCAPE
DESIGN AND DETAILS OF THE
SPECAIL PROTECTION MEASURES
MUST BE AGREED WITH IRISH
EXISTING PLANTING
WATER
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
Revised to suit ILI recommendations
2 11/'17 JMC TOC
& changed drawing title
MOD RESTRICTIONS ON WATER INFRASTRUCTURE
1 08/'16 JMC TOC Added new section & notes MOD WORKS ADJACENT TO EXISTING TREES STD-W- 12 2
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
PLEASE NOTE THAT TABLE A.1. OF BS 5837 (BELOW) IS TO BE USED TO CALCULATE THE ABSOLUTE MIMIMUM DISTANCE BETWEEN NEW TREE PLANTING
FROM THE WATER INFRASTRUCTURE (THE SERVICES). THE DISTANCE IS REQUIRED TO AVOID DIRECT DAMAGE TO THE INFRASTRUCTURE FROM
FUTURE GROWTH. THE DISTANCE IS A FUNCTION OF THE DEPTH OF THE SERVICES AND THE (FINAL EXPECTED) STEM DIAMETER OF THE TREE AT
MATURITY (i.e. FINAL EXPECTED GROWTH).
TABLE A.1. Minimum distance between young trees or new planting & structures, in metres (m)
BS 5837 Final stem dia. < 300mm Final stem dia. 300mm to 600mm Final stem dia. > 600mm
Services
< 1m deep 0.5 1.5 3.0
> 1m deep -- 1.0 2.0
THUS FOR EXAMPLE:
- FOR A SERVICE LESS THAN 1 METRE DEEP, THE MINIMUM DISTANCE IS TO BE 1.5m FOR A TREE BETWEEN 300 AND 600mm STEM DIAMETER AT MATURITY.
- FOR A SERVICE GREATER THAN 1 METRE DEEP, THE MINIMUM DISTANCE IS TO BE 1.0m FOR A TREE BETWEEN 300 AND 600mm STEM DIAMETER AT MATURITY.
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE JUL. 2017
TITLE DRAWING No. REV
THAT DESCRIBED ABOVE (CLAUSE 804 OR CLAUSE 808) OF THE PIPE TRENCH
MARKER TAPE REFER
WILL ONLY BE ALLOWED BY IRISH WATER WHERE THE ROADS AUTHORITY IN
TO NOTE 9 FOR DETAILS
WHOSE FUNCTIONAL AREA THE DEVELOPMENT IS LOCATED, PROVIDES
WRITTEN APPROVAL TO THE DEVELOPER TO THE USE SUCH ALTERNATIVE
MATERIAL.
4. SELECTED EXCAVATED MATERIAL MAY BE USED IN GREEN-FIELD AREAS ABOVE
300mm MINIMUM
GRASSED AREAS
200 600
MARKER TAPE REFER
TO NOTE 9 FOR DETAILS 250 750
300 750
350 750
(300mm MINIMUM IF
200mm MINIMUM
ADJACENT TO
TRAFFICKED
400 900
AREAS)
450 900
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
150mm. ALTERNATIVELY, PRE-CAST CONCRETE ROOFS MAY BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911, Part 4.
6. CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER STD-W-13.
7. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545.
SV 8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
280
BULL NOSE 9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS
FINISH AND PIPES AT STEEP SLOPES.
10. ANTI-CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
11. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
200
12. ALL THRUST FLANGES TO BE ADEQUATELY RESTRAINED BY THRUST BLOCKS AS PER DRAWING No. STD-W-28. THRUST BLOCKS NOT SHOWN FOR
CLARITY.
13. 450 x 450mm INTERNAL DIMENSION CHAMBERS MAY BE PROVIDED SUBJECT TO REVIEW BY IW. SUCH CHAMBERS SHALL BE PROVIDED WITH GRADE
"A" HEAVY DUTY COVER & FRAME & STAMPED "SV".
PLINTH DETAIL 14. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
15. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
IN GRASS AREAS 16. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF
TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
MAX.
MAX.
SEE NOTES 14, 15
300
300
150
150
CONCRETE ROOF SLAB CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB C30 / 37 REINFORCED SLAB
900 MIN.
215mm THICK 20N/mm²
EXTENSION SPINDLE 445 445 EXTENSION SPINDLE
THRUST CONCRETE BLOCKWORK
PRECAST CONCRETE UNITS IN ACCORDANCE WITH C25/30 PRECAST CONCRETE
FLANGE
(REFER TO NOTE 5.) IS EN 771-3 BEARING SLAB
THRUST
FLANGE
100
100
C25/30 PRECAST REFER TO STD -
CONCRETE BEARING SLAB W- 13 FOR
LOCALLY
LOCALLY
BEDDING AND
MIN.
MIN.
REFER TO STD - W- 13
150
150
BACKFILLING
FOR BEDDING AND DETAILS
BACKFILLING DETAILS
LONG BODY FLANGED / PLAIN ENDED FLANGED / PLAIN ENDED FLANGED / PLAIN ENDED FLANGED / PLAIN ENDED
150
150
FLEXIBLE PIPE CUT TO SUIT PIPE CUT TO SUIT LONG BODY PIPE CUT TO SUIT PIPE CUT TO SUIT LONG BODY
COUPLING FLEXIBLE
FLANGED SLUICE VALVE DISMANTLING JOINT COUPLING FLANGED DISMANTLING JOINT FLEXIBLE
CONCRETE ANTI-TORQUE SUPPORT SLUICE VALVE CONCRETE ANTI-TORQUE SUPPORT COUPLING
SECTION SECTION
445 445
280
LETTERING LETTERING
HEAVY DUTY COVER AND FRAME, HEAVY DUTY COVER AND FRAME,
STAMPED ''SV'' CLASS D400 STAMPED ''SV'' CLASS D400
(TO SUIT 445 x 280 OPE) (TO SUIT 445 x 280 OPE)
50 50
50
600
100
215
50
50
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
3 11/'17 JMC TOC Revised & Added Notes MOD
2 08/'16 JMC TOC Revised Notes 2, 3 & 6 MOD
SLUICE VALVE
1 04/'16 JMC TOC Added 2 couplings (2 details) MOD FOR DUCTILE IRON (D.I.) PIPE (< 350mm DIA. ) STD-W- 14 3
0 09/'15 JMC TOC Initial Issue SL (Sheet 1 of 2)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
PREFABRICATED CHAMBER UNITS MAY ALSO BE USED, SUBJECT TO REVIEW BY IRISH WATER. ROOF SLABS SHALL BE DESIGNED TO CARRY ALL LIVE
LOADS & DEAD LOADS, & CONSIST OF A REINFORCED CONCRETE SLAB OF IN-SITU CONCRETE, GRADE C30/37, WITH A MINIMUM THICKNESS OF 150mm.
ALTERNATIVELY, PRE-CAST CONCRETE ROOFS MAY BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911, Part 4.
6. CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER STD-W-13.
SV 7. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545. PE PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 12201:2011.
280
BULL NOSE 8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
FINISH 9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS
AND PIPES AT STEEP SLOPES.
10. ANTI-CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
200
MAX.
MAX.
300
300
SEE NOTES 13, 14 & 15.
FINISHED GROUND LEVEL FINISHED GROUND LEVEL
COVER TO BE SET IN C50/60 COVER TO BE SET IN
MORTAR C50/60 MORTAR
CLASS B ENGINEERING BRICK
150
150
CONCRETE ROOF SLAB CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB C30 / 37 REINFORCED SLAB
900 MIN.
EXTENSION SPINDLE 445 445 EXTENSION SPINDLE
PRECAST CONCRETE UNITS 215mm THICK 20N/mm²
(REFER TO NOTE 5.) CONCRETE BLOCKWORK
IN ACCORDANCE WITH IS EN 771-3
100
100
C25/30 PRECAST C25/30 PRECAST CONCRETE
CONCRETE BEARING SLAB BEARING SLAB
LOCALLY
LOCALLY
MIN.
MIN.
REFER TO STD - W- 13 REFER TO STD - W- 13
150
150
FOR BEDDING AND FOR BEDDING AND
BACKFILLING DETAILS BACKFILLING DETAILS
POLYETHYLENE POLYETHYLENE
(P.E.) PIPE (P.E.) PIPE
150
150
FUSION WELD FUSION WELD FUSION WELD
280
LETTERING LETTERING
HEAVY DUTY COVER AND FRAME, HEAVY DUTY COVER AND FRAME,
STAMPED ''SV'' CLASS D400 STAMPED ''SV'' CLASS D400
(TO SUIT 445 x 280 OPE) (TO SUIT 445 x 280 OPE)
215
100
600
100
215
50
50
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
5. HYDRANT CHAMBER TO BE CONSTRUCTED OF PRECAST CONCRETE UNITS OR HIGH DENSITY BLOCKWORK. ALTERNATIVELY PROPRIETARY
PREFABRICATED CHAMBER UNITS MAY ALSO BE USED, SUBJECT TO REVIEW BY IRISH WATER. ROOF SLABS SHALL BE DESIGNED TO CARRY ALL LIVE
LOADS & DEAD LOADS, & CONSIST OF A REINFORCED CONCRETE SLAB OF IN-SITU CONCRETE, GRADE C30/37, WITH A MINIMUM THICKNESS OF 150mm.
ALTERNATIVELY, PRE-CAST CONCRETE ROOFS MAY BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911, Part 4.
FH 6. CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER STD-W-13.
280
BULL NOSE 7. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545.
FINISH 8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS AND
PIPES AT STEEP SLOPES.
200
MAX.
MAX.
350
350
SEE NOTES 12, 13 & 14.
FINISHED GROUND LEVEL FINISHED GROUND LEVEL
COVER TO BE SET IN C50/60 COVER TO BE SET IN
150
150
900 MIN.
CONCRETE ROOF SLAB CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB C30 / 37 REINFORCED SLAB
100
C25/30 PRECAST C25/30 PRECAST CONCRETE
CONCRETE BEARING SLAB BEARING SLAB
LOCALLY
LOCALLY
REFER TO STD - W- 13
MIN.
MIN.
REFER TO STD - W- 13
150
150
FOR BEDDING AND FOR BEDDING AND
BACKFILLING DETAILS BACKFILLING DETAILS
DUCTILE IRON SOCKETTED TEE WITH DUCTILE IRON SOCKETTED TEE WITH
FLANGED BRANCH FLANGED BRANCH
SECTION SECTION
445 445
280
LETTERING LETTERING
HEAVY DUTY COVER AND FRAME, HEAVY DUTY COVER AND FRAME,
STAMPED '' FH '' CLASS D400 STAMPED '' FH '' CLASS D400
(TO SUIT 445 x 280 OPE) (TO SUIT 445 x 280 OPE)
CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB
PRECAST CONCRETE
CONCRETE BLOCKWORK
100
UNITS
IN ACCORDANCE WITH IS EN 771-3
(REFER TO NOTE 5.)
600
600
FIRE FIRE
HYDRANT HYDRANT
100
215
50
50
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
CONCRETE ROOFS MAY BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911, Part 4.
6. CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER STD-W-13.
7. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545.
8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
FH
280
BULL NOSE 9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS AND PIPES
FINISH AT STEEP SLOPES.
10. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
11. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
12. TEE BRANCH: IF DEPTH OF TAKE-OFF PIPEWORK < 900mm, TAKE-OFF TEE MAY BE ROTATED TO ENSURE MIN. DEPTH OF COVER IS MAINTAINED, OR
200
MAX.
MAX.
SEE NOTES 13, 14 & 15.
350
350
FINISHED GROUND LEVEL
COVER TO BE SET IN
C50/60 MORTAR
CLASS B ENGINEERING BRICK
SET IN C50/60 MORTAR
150
150
REFER TO NOTE 2 ON STD-W-13
100
80mm DIA.
PLAIN ENDED CONCRETE BEARING SLAB
PIPE CONC. THRUST BLOCK TO BEND OPE TO BE SEALED
CUT TO SUIT 80mm DIA. PLAIN ENDED (REFER TO DRG. No. STD-W-28 USING A SUITABLE
PIPE CUT TO SUIT FOR DETAILS) MATERIAL
80mm DIA.
DOUBLE FLANGED
LONG BODY LONG BODY 90° BEND
SOCKETTED LEVEL
FLANGE ADAPTOR FLANGE ADAPTOR SECTION SECTION
INVERT TEE
WITH 80mm DIA. 445 445
FLANGED BRANCH
75mm HIGH
LETTERING FH 75mm HIGH FH
280
280
LETTERING
HEAVY DUTY COVER AND FRAME,
STAMPED '' FH '' CLASS D400
HEAVY DUTY COVER AND FRAME,
(TO SUIT 445 x 280 OPE)
STAMPED '' FH '' CLASS D400
(TO SUIT 445 x 280 OPE)
CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB
CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB
ROOF PLAN ROOF PLAN
50 100 100 50 50 50
600 215 600 215
50
50
215
100
FIRE HYDRANT
100
215
CONCRETE BLOCKWORK
IN ACCORDANCE WITH IS EN 771-3
50
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
Revised & added notes, &
3 11/'17 JMC TOC MOD TITLE DRAWING No. REV
revised pipework
2 08/'16 JMC TOC Revised notes 2,3 & 6 MOD
OFF - LINE HYDRANT
1 04/'16 JMC TOC Added thrust blocks MOD FOR DUCTILE IRON (D.I.) PIPE STD-W- 17 3
0 09/'15 JMC TOC Initial Issue SL (Sheet 2 of 4)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
5. HYDRANT CHAMBER TO BE CONSTRUCTED OF PRECAST CONCRETE UNITS OR HIGH DENSITY BLOCKWORK. ALTERNATIVELY PROPRIETARY PREFABRICATED
CHAMBER UNITS MAY ALSO BE USED, SUBJECT TO REVIEW BY IRISH WATER. ROOF SLABS SHALL BE DESIGNED TO CARRY ALL LIVE LOADS & DEAD LOADS, &
CONSIST OF A REINFORCED CONCRETE SLAB OF IN-SITU CONCRETE, GRADE C30/37, WITH A MINIMUM THICKNESS OF 150mm. ALTERNATIVELY, PRE-CAST
FH CONCRETE ROOFS MAY BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911, Part 4.
280
BULL NOSE 6. CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER STD-W-13.
FINISH 7. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545. PE PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 12201:2011.
8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS AND PIPES AT
200
STEEP SLOPES.
10. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
11. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
12. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
PLINTH DETAIL 13.
14.
NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF
IN GRASS AREA TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
MAX.
MAX.
SEE NOTES 12, 13 & 14.
350
350
FINISHED GROUND LEVEL FINISHED GROUND LEVEL
COVER TO BE SET IN C50/60 CLASS B COVER TO BE SET IN
MORTAR ENGINEERING BRICK C50/60 MORTAR
SET IN C50/60 MORTAR
REFER TO NOTE 2
150
150
CONCRETE ROOF SLAB
ON STD-W-13
CONCRETE ROOF SLAB
900 MIN.
C30 / 37 REINFORCED SLAB C30 / 37 REINFORCED SLAB
100
PRECAST CONCRETE BEARING SLAB
BEARING SLAB
LOCALLY
LOCALLY
MIN.
MIN.
150
150
REFER TO STD - W- 13
REFER TO STD - W- 13 POLYETHYLENE POLYETHYLENE FOR BEDDING AND
FOR BEDDING AND (P.E.) PIPE (P.E.) PIPE BACKFILLING DETAILS
BACKFILLING DETAILS
280
LETTERING LETTERING
215
600
FIRE FIRE
HYDRANT HYDRANT
100
215
50
USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5011, Part 4.
6. CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER STD-W-13.
7. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545. PE PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 12201:2011.
FH 8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
280
BULL NOSE 9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS AND PIPES AT STEEP
FINISH SLOPES.
10. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
11. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
200
12. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
13. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
14. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF TRANSPORT,
TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
PLINTH DETAIL
IN GRASS AREA
MAX.
MAX.
SEE NOTES 12, 13 & 14.
350
350
FINISHED GROUND LEVEL
COVER TO BE SET IN
150
C50/60 MORTAR
CLASS B ENGINEERING BRICK
SET IN C50/60 MORTAR
150
REFER TO NOTE 2 ON STD-W-13
100
BEARING SLAB
FUSION STUB FLANGE
WITH BACKING CONC. THRUST BLOCK TO BEND OPE TO BE SEALED
WELD (REFER TO DRG. No. STD-W-28 USING A SUITABLE
RING
FOR DETAILS) MATERIAL
80mm DIA.
DOUBLE FLANGED
POLYETHYLENE 90° BEND
(PE) PIPE
POLYETHYLENE TEE
FUSION
WELD
SECTION SECTION
(OR ELECTROFUSION
SADDLE) LONG BODY
FLANGE ADAPTOR 445
80mm DIA. FLANGED 445
PLAIN ENDED PIPE
CUT TO SUIT
280
LETTERING LETTERING
HEAVY DUTY COVER AND FRAME,
STAMPED '' FH '' CLASS D400
HEAVY DUTY COVER AND FRAME,
(TO SUIT 445 x 280 OPE)
STAMPED '' FH '' CLASS D400
CONCRETE ROOF SLAB (TO SUIT 445 x 280 OPE)
C30 / 37 REINFORCED SLAB
CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB
215
100
600
FIRE HYDRANT
100
215
CONCRETE BLOCKWORK
IN ACCORDANCE WITH IS EN 771-3
50
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
Revised & added notes, &
3 11/'17 JMC TOC MOD TITLE DRAWING No. REV
revised pipework
2 08/'16 JMC TOC Revised notes 2, 3 & 6 MOD
OFF - LINE HYDRANT
1 04/'16 JMC TOC Added thrust blocks MOD FOR POLYETHYLENE (P.E.) PIPE STD-W- 19 3
0 09/'15 JMC TOC Initial Issue SL (Sheet 4 of 4)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
DIAMETER OF MAIN UP TO 250 (mm) 250 TO 350 (mm) 1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
2. AIR VALVE CHAMBERS SHALL BE COVERED WITH APPROVED VENTILATED HEAVY DUTY DUCTILE IRON COVERS TO IS EN 124 RATING D400.
DIAMETER OF BRANCH 80mm 100mm COVER AND FRAME SHALL BE SUITABLE FOR ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
3. AIR VALVES SHALL COMPLY WITH THE REQUIREMENTS OF IS EN 1074-4. AIR VALVES SHALL BE DOUBLE ORIFICE TYPE AND SHALL INCLUDE
AN ISOLATING VALVE. THE ISOLATING VALVE SHALL BE EITHER A GATE VALVE CONFORMING TO IS EN 1074-2 & SHALL BE OF A BOLTLESS
BORE OF VALVE INLET 80mm 100mm
BONNET DESIGN, OR A BUTTERFLY VALVE TO IS EN 1074-2.
4. SERVICE CONNECTIONS SHALL NOT BE PROVIDED WITHIN 2m OF THE AIR VALVE LOCATION.
200 600 200 5. AIR VALVE CHAMBERS TO BE OF PRECAST CONCRETE UNITS OR HIGH DENSITY BLOCKWORK. ALTERNATIVE PROPRIETARY
PREFABRICATED CHAMBER UNITS MAY ALSO BE USED, SUBJECT TO REVIEW BY IRISH WATER.
6. PRECAST CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER STD-W-13.
7. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545.
200
8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS,
DEAD ENDS AND PIPES AT STEEP SLOPES.
10. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
11. THE LOCATION OF THE AIR VALVE SHALL BE THE SUBJECT OF PARTICULAR AGREEMENT WITH IRISH WATER TO ENSURE THAT THE RISK OF
BULL NOSE CONTAMINATION THROUGH THE VALVE IS ELIMINATED.
FINISH 12. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
AV 13. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
600
14. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
15. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE
DEPT. OF TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
200
MAXIMUM
PLINTH DETAIL
250
IN GRASS AREA SEE NOTES 13, 14 & 15.
FINISHED GROUND LEVEL
MAXIMUM
CLASS B ENGINEERING
BRICK SET IN C50/60
PRECAST CONCRETE UNITS MORTAR 215mm THICK 20N/mm² CONCRETE
100
LOCALLY
TO CONCRETE BEARING SLAB. REFER TO STD - W- 13 TO CONCRETE BEARING SLAB.
MIN.
MIN.
FOR BEDDING AND
150
150
C25 / 30 PRECAST BACKFILLING DETAILS C25 / 30 PRECAST
CONCRETE BEARING CONCRETE BEARING
SLAB SLAB
DUCTILE IRON DUCTILE IRON
(D.I.) PIPE (D.I.) PIPE
SECTION DUCTILE IRON SOCKETTED TEE WITH SECTION DUCTILE IRON SOCKETTED TEE WITH
FLANGED BRANCH FLANGED BRANCH
1030
800 600
600
AV 75mm HIGH
AV
1030
800
600
600
LETTERING
ROOF PLAN
ROOF PLAN
900 50 215 600 215 50
50
50 100 100 50
600
50
215
100
600
600
DOUBLE DOUBLE
AIR VALVE AIR VALVE
100
215
50
9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS,
DEAD ENDS AND PIPES AT STEEP SLOPES.
10. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
11. THE LOCATION OF THE AIR VALVE SHALL BE THE SUBJECT OF PARTICULAR AGREEMENT WITH IRISH WATER TO ENSURE THAT THE
RISK OF CONTAMINATION THROUGH THE VALVE IS ELIMINATED.
BULL NOSE 12. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
FINISH 13. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
AV 14. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
600
15. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY
THE DEPT. OF TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
200
PLINTH DETAIL
IN GRASS AREA
SEE NOTES 13, 14 & 15.
FINISHED GROUND LEVEL
COVER TO BE SET IN
MAXIMUM
MAXIMUM
C50/60 MORTAR
FLANGED
250
250
PLAIN ENDED PIPE CLASS B ENGINEERING BRICK
NOTE 2 ON STD-W-13)
CUT TO SUIT
PRECAST CONCRETE UNITS
LONG BODY (REFER TO NOTE 6.)
FLEXIBLE 215mm THICK 20N/mm²
COUPLING CONCRETE BLOCKWORK
LONG BODY 300 IN ACCORDANCE WITH IS EN 771-3
ROCKER
FLANGED ADAPTOR
PIECE DOUBLE AIR VALVE
DOUBLE FLANGED ISOLATING VALVE
90° SHORT RADIUS
BEND CONC. THRUST BLOCK
TO DUCKFOOT BEND
(REFER TO DRG. No.
STD-W-28 FOR DETAILS)
PLAIN ENDED
100
100
PIPE CONCRETE BASE C25 / 30
CUT TO SUIT 75mm CONCRETE
OPE TO BE CLEAN CUT DOUBLE FLANGED BLINDING GRADE
AND SEALED USING SECTION 90° DUCKFOOT BEND C12 / 15
OPE TO BE SEALED SECTION
A SUITABLE MATERIAL USING A SUITABLE
SOCKETED TEE WITH
DOUBLE AIR VALVE MATERIAL DOUBLE AIR VALVE
FLANGED BRANCH 800 1030
600 600
AV 75mm HIGH
AV
1030
800
600
600
LETTERING
50 100 100 50
600
50
215
100
PRECAST CONCRETE
900
UNITS
600
600
WITH IS EN 771-3
215
50
50
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
3 11/'17 JMC TOC Added & updated Notes MOD
2 08/'16 JMC TOC Revised notes 2,3,4 & 7 MOD
OFF - LINE AIR VALVE
1 04/'16 JMC TOC Added thrust blocks MOD FOR DUCTILE IRON (D.I.) PIPE STD-W- 21 3
0 09/'15 JMC TOC Initial Issue SL (Sheet 2 of 4)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
14. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
15. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY
THE DEPT. OF TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
200
MAXIMUM
PLINTH DETAIL
250
FINISHED GROUND LEVEL
IN GRASS AREA SEE NOTES 13, 14 & 15.
MAXIMUM
100
LOCALLY
TO CONCRETE BEARING SLAB TO CONCRETE BEARING SLAB
MIN.
MIN.
REFER TO STD - W- 13
150
150
(RISER CAN BE PE FITTING). (RISER CAN BE PE FITTING).
FOR BEDDING AND
C25 / 30 PRECAST BACKFILLING DETAILS C25 / 30 PRECAST
CONCRETE BEARING CONCRETE BEARING
SLAB POLYETHYLENE POLYETHYLENE SLAB
(P.E.) PIPE (P.E.) PIPE
AV 75mm HIGH
AV 75mm HIGH
1030
800
600
600
LETTERING LETTERING
ROOF PLAN
900 215
ROOF
600
PLAN 215 50
50
50
50 100 100 50
600
50
215
100
FITTING FITTING
OPERATION OPERATION
DIAMETER DIAMETER
STANCAD STANCAD
900
600
600
DOUBLE DOUBLE
AIR VALVE AIR VALVE
100
215
50
9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-W-28 AT ALL TEES, BENDS,
TAPERS, DEAD ENDS AND PIPES AT STEEP SLOPES.
10. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
11. THE LOCATION OF THE AIR VALVE SHALL BE THE SUBJECT OF PARTICULAR AGREEMENT WITH IRISH WATER TO ENSURE THAT THE
RISK OF CONTAMINATION THROUGH THE VALVE IS ELIMINATED.
BULL NOSE
12. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
FINISH
AV 13. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
600
14. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
15. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS"
BY THE DEPT. OF TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
200
PLINTH DETAIL
IN GRASS AREA
SEE NOTES 13, 14 & 15.
FINISHED GROUND LEVEL
REFER TO NOTE 2 ON STD-W-13
COVER TO BE SET IN
MAXIMUM
MAXIMUM
C50/60 MORTAR CLASS B
250
250
CLASS B ENGINEERING BRICK
SET IN C50/60 MORTAR ENGINEERING
PRECASTCONCRETE UNITS BRICK SET IN
C50/60
900 MIN.
100
FUSION
WELD FUSION CONCRETE FLOOR SLAB
WELD C25 / 30 REINFORCED SLAB
LONG BODY DOUBLE FLANGED
POLYETHYLENE TEE 75mm CONCRETE BLINDING
FLANGE ADAPTOR 90° DUCKFOOT BEND
(OR ELECTROFUSION GRADE C12 / 15
SADDLE) OPE TO BE CLEAN CUT SECTION OPE TO BE SEALED
USING A SUITABLE
SECTION
AND SEALED USING
MATERIAL
A SUITABLE MATERIAL
800 1030
600 600
AV 75mm HIGH
AV
1030
800
600
600
LETTERING
50 100 100 50
600
50
215
100
PRECAST CONCRETE
900
600
600
UNITS
(REFER TO NOTE 6.)
WITH IS EN 771-3
215
50
50
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
3 11/'17 JMC TOC Added & updated notes MOD
2 08/'16 JMC TOC Revised notes 2,3,4 & 7 MOD
OFF - LINE AIR VALVE
1 04/'16 JMC TOC Added thrust blocks MOD FOR POLYETHYLENE (P.E.) PIPE STD-W- 23 3
0 09/'15 JMC TOC Initial Issue SL (Sheet 4 of 4)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
MANHOLE STEPS TO COMPLY HINGED 4 LEAF HEAVY 1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
WITH IS EN 13101, TYPE D, CLASS DUTY COVER AND FRAME, 2. STRUCTURAL DESIGN AND REINFORCEMENT DETAIL TO BE PROVIDED BY THE
1, GALVANISED MILD STEEL & STAMPED '' PRV '' CLASS DEVELOPER AND SUBMITTED TO IRISH WATER FOR REVIEW.
PLASTIC ENCAPSULATED. D400 TO IS EN 124 3. CONCRETE FOR PRESSURE REDUCING / SUSTAINING CHAMBER TO BE C30 / 37. ROOF
SEE NOTES 14, 15 & 16.
SLABS SHALL BE DESIGNED TO CARRY ALL LIVE LOADS & DEAD LOADS, & CONSIST OF
PRECAST A REINFORCED CONCRETE SLAB OF IN-SITU CONCRETE, GRADE C30/37, WITH A
CONCRETE COVER TO BE SET IN 1 No. MIN., 3 No. MAX.
675 (MAX.)
MINIMUM THICKNESS OF 225mm. ALTERNATIVELY, PRE-CAST CONCRETE ROOFS MAY
ROOF SLAB C50/60 MORTAR COURSES OF CLASS B BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911, Part 4.
ENGINEERING BRICKS SET IN 4. PRECAST UNITS COMPLETED WITH RUBBER SEALING GASKET BETWEEN UNITS,
FINISHED GROUND LEVEL
C50/60 MORTAR COMPLYING WITH THE REQUIREMENTS OF IS EN 1917 AND BS 5911-PART 3, COMPLETE
WITH 150mm CONCRETE SURROUND MAY BE USED AS AN ACCEPTABLE ALTERNATIVE.
900 MIN. (REFER TO
NOTE 2 ON STD-13)
CABLE DUCTS WITH CONCRETE SURROUND TO BE GRADE C16/20 IN ACCORDANCE WITH IS EN 206.
DRAW CORDS AS SPECIFIED 5. PRESSURE REDUCING VALVES REQUIRE A MINIMUM LENGTH OF PIPE EQUIVALENT TO 5
225 TO KIOSK (REFER TO STD-W-29) TIMES THE DIAMETER, ON EACH SIDE OF THE VALVE TO BE COMPLETELY FREE OF
LONG BODY
FLEXIBLE LONG BODY FITTINGS, VALVES, REDUCERS ETC., OR TO PRV/PSV MANUFACTURER'S
300
COUPLING FLEXIBLE COUPLING REQUIREMENTS.
MIN.
6. P.R.V. / P.S.V. CHAMBER SHALL BE COVERED WITH APPROVED HEAVY DUTY METAL
COVERS TO IS EN 124 RATING D400. COVER AND FRAME SHALL BE SUITABLE FOR
FLOW FLOW ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
7. 200mm ALL ROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GRASS
AREAS.
MIN.
300
8. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
FLANGED PLAIN ENDED 9. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD
250
PIPE WITH THRUST FLANGE DRAWING STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS AND PIPES AT STEEP
ROCKER PIPE SLOPES.
WATER TIGHT SEAL
10. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545. PE PIPES
FLANGED PLAIN ENDED VARIES
250 250 THICKENED FLOOR AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 12201:2011
PIPE WITH THRUST FLANGE
BENEATH SUMP 11. ALL CHAMBERS TO BE CHECKED FOR UPLIFT BY THE DEVELOPER, BASED ON GROUND
75mm CONCRETE BLINDING DISMANTLING CONCRETE CAST STRAINER PRESSURE REDUCING / CONDITIONS WITHIN THE SITE, SHOULD ANTI-FLOTATION MEASURES BE REQUIRED
GRADE C12 / 15 JOINT IN-SITU CRADLE SUSTAINING VALVE THEY SHALL BE SUBJECT TO REVIEW BY IRISH WATER.
12. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
13. PIPEWORK TO BE DOWNSIZED IF REQUIRED TO ACCOMMODATE THE REQUIRED RANGE
SECTION OF PRESSURE REDUCTION.
14. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD
AUTHORITY'S REQUIREMENTS.
VARIES
15. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY
REQUIREMENTS.
16. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES
FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF TRANSPORT, TOURISM &
SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
CAST-IN RECESSED
LIFTING EYES
OPENING TO ALLOW
FOR PRV TO BE LIFTED HINGED 4 LEAF HEAVY STUB FLANGE
IN & OUT VERTICALLY DUTY COVER AND FRAME, WITH BACKING
STAMPED '' PRV '' CLASS RING
VARIES
PRV PRV
3 No. COURSES MAX. OR DI PE
1 No. COURSE MINIMUM
OF ENGINEERING BRICKWORK
PE TO DI DETAIL
ROOF PLAN
VARIES
VARIES
400 MIN. 400 WATER TIGHT SEAL 5 (DIA. VARIES) DISMANTLING JOINT
6 FLANGED PLAIN ENDED PIPE (CUT TO SUIT)
7 90° DEGREE SOCKETED BEND
FLOW FLOW 8 PLAIN ENDED PIPE (CUT TO SUIT)
9 SPIGOT & SOCKET PIPE (STANDARD)
10 FLANGED PLAIN ENDED PIPE (CUT TO SUIT)
MIN.
300
1 2 1 9 4 10 1 2 1 13 11 9
3
4. KIOSK TO HAVE SINGLE OR DOUBLE STEEL/GRP DOORS WITH MULTIPLE LOCKS TO LPS 1175
SR4 OR EN 1627. MINIMUM DOUBLE LOCKS WITH BOLTS THAT ENGAGE INTO THE SILL &
VENT HEADER AS WELL AS BETWEEN THE TWO LEAVES OR LEAF & FRAME. LEADING EDGE OF
LEAVES TO HAVE EITHER REBATED EDGES OR FITTED WITH ASTRAGALS.
KIOSK 12. PROVISION TO BE MADE IN THE SIZING OF THE KIOSK FOR THE SAFE REPAIR/MAINTENANCE
OF THE BOOSTER PUMPS & FOR THEIR REMOVAL IF REQUIRED.
EX. G.L.
CONCRETE
150
VARIES
PLINTH
BOOSTER PUMPS
(DUTY / STANDBY OR
DUTY/ASSIST) 450mm CONCRETE PLINTH
GRADE C25/30 TO SUIT
2000
OUTLET
150
WATER MAIN
INLET
150
WATER MAIN
600
BOOSTER PUMPS
(DUTY / STANDBY OR
DUTY/ASSIST)
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
675 (MAX.)
CONCRETE ROOF SLAB
C30 / 37 REINFORCED SLAB
1 No. MIN. OR 3 No. COURSES MAX.OF CLASS B
FINISHED GROUND LEVEL ENGINEERING BRICKWORK SET IN C50/60 MORTAR
STD-13)
225
SECTION
METER INTERNAL
DIAMETER COVER
CHAMBER
'A' (mm) DIMENSIONS
DIMENSIONS
VARIES
50 - 100 1200 x 1200 750 x 750
300
VARIES
VARIES
FLOW FLOW
MIN.
300
THRUST FLANGE
250
LEVEL SLUICE
SLUICE VALVE 25mm O.D. TAPPING TO BE INVERT TEE VALVE
PROVIDED
CABLE DUCT TO KIOSK PRESSURE TAPPING DUCT TO KIOSK
TO BE INSTALLED TO BE INSTALLED
WITH DRAW CORD WITH DRAW CORD
(REFER TO STD-W-36) (REFER TO STD-W-36)
DUCT END TO BE SEALED DUCT END TO BE SEALED
FLOOR PLAN
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
Revised notes & added table
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
3 11/'17 JMC TOC MOD
& hydrant TITLE DRAWING No. REV
2 08/'16 JMC TOC Added steps & revised MOD
cover notes
1 04/'16 JMC TOC Added couplings to details MOD NON-MECH. METER CHAMBER (40 - 250mm DIA.) STD-W- 26 3
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
2. STRUCTURAL DESIGN AND REINFORCEMENT DETAIL TO BE PROVIDED BY THE DEVELOPER AND SUBMITTED TO IRISH WATER FOR REVIEW. ROOF SLABS SHALL BE DESIGNED TO CARRY ALL LIVE LOADS & DEAD LOADS, & CONSIST OF
A REINFORCED CONCRETE SLAB OF IN-SITU CONCRETE, GRADE C30/37, WITH A MINIMUM THICKNESS OF 225mm. ALTERNATIVELY, PRE-CAST CONCRETE ROOFS MAY BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH
BS 5011, Part 4.
3. CONCRETE FOR CHAMBERS TO BE C30 / 37.
4. PRECAST UNITS COMPLETED WITH RUBBER SEALING GASKET BETWEEN UNITS, COMPLYING WITH THE REQUIREMENTS OF IS EN 1917 AND BS 5911-PART 3, COMPLETE WITH 150mm CONCRETE SURROUND MAY BE USED AS AN
ACCEPTABLE ALTERNATIVE. CONCRETE SURROUND TO BE GRADE C16/20 IN ACCORDANCE WITH IS EN 206.
5. CHAMBERS SHALL BE COVERED WITH APPROVED HEAVY DUTY METAL COVERS TO IS EN 124 RATING D400. COVER AND FRAME SHALL BE SUITABLE FOR ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
6. 200mm ALL ROUND, 100mm DEEP CONCRETE PLINTH AROUND COVER IN GRASS AREAS.
7. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
8. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 545. PE PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 12201:2011.
9. ALL CHAMBERS TO BE CHECKED FOR UPLIFT BY THE DEVELOPER BASED ON GROUND CONDITIONS WITHIN THE SITE. SHOULD ANTI FLOATATION MEASURES BE REQUIRED THEY SHALL BE SUBJECT TO REVIEW BY IRISH WATER.
10. PIPEWORK TO BE DOWNSIZED TO ACCOMMODATE THE REQUIRED RANGE OF THE FLOW METER. STRAIGHT PIPE LENGTHS UPSTREAM AND DOWNSTREAM OF THE METER TO BE PROVIDED. IF THE METER IS NOT CAPABLE OF
ACCURATE NIGHT FLOW MEASUREMENTS, A BY-PASS FLOW METER SHALL BE PROVIDED WITH APPROPRIATE VALVES, FITTINGS AND PIPEWORK.
11. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
12. A SINGLE METER CHAMBER MAY BE USED, WHERE APPLICABLE, TO THE METER SUPPLIER'S REQUIREMENTS, TO LOCATE BOTH THE METER & STRAINER.
13. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
14. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
15. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF TRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND
REQUIREMENTS.
LONG
PLASTIC ENCAPSULATED.
VARIES BODY VARIES
DI FLANGED FLEXIBLE
OFF-LINE
FLANGED / PLAIN TAPER JOINT DISMANTLING DI FLANGED
HYDRANT
ENDED PIPE CUT (IF REQUIRED) TAPER
LONG BODY 600 MAX. 300 (REFER TO JOINT
TO SUIT STRAINER MIN. MECH. METER
FLEXIBLE JOINT STD-W-17)
FLOW
ROCKER PIECE
MIN.
300
(0.6m TYPICAL)
DISMANTLING
ROCKER PIECE
250
300
SLUICE VALVE
250
LEVEL
INVERT TEE
600 MAX.
600 MAX.
METER INTERNAL
DIAMETER COVER
CHAMBER
'A' (mm) DIMENSIONS
DIMENSIONS
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE JUN. 2017
TITLE DRAWING No. REV
MECH. METER CHAMBER (40 - 250mm DIA.) STD-W-26A 0 25mm O.D. TAPP
0 11/'17 JMC TOC Initial Issue MOD PROVIDED
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
1. WHERE PRACTICAL MARKER PLATES SHALL BE FIXED TO
265 100 ADJACENT WALLS OR ALTERNATIVELY ATTACHED TO MARKER
3 No. H6 BARS POSTS.
660
4. FOR HYDRANT PLATE ALL CHARACTERS SHOULD BE BLACK AND
3 No. H6 BARS THE REMAINDER OF THE FRONT FACE SHOULD CONFORM TO
COLOUR REFERENCE No. 309 (CANARY YELLOW) OF BS 381C.
1110
6. SLUICE VALVE, AIR VALVE, SCOUR VALVE, WASHOUT HYDRANT
AND METER PLATES SHOULD BE CAST IRON. ALL CHARACTERS
SHOULD BE BLACK ON WHITE PAINT BACKGROUND.
ALTERNATIVE MATERIAL MAY BE USED SUBJECT TO
ACCEPTANCE BY IRISH WATER.
450
450
CONCRETE 7. CONCRETE SURROUND TO MARKER POST TO BE GRADE C25 / 30
SURROUND AND IN ACCORDANCE WITH IS EN 206/2013.
100
9. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
PLAN
DIAMETER OF WATERMAIN
(100mm) - 40mm HIGH TEXT
180
H 100
50
205
160
2
50
DISTANCE OF MARKER
FROM HYDRANT
(2m) - 40mm HIGH TEXT
HYDRANT
180
AV WM SV WO
205
80
2 2 2 2
WASHOUT
AIR VALVE WATER MAIN SLUICE VALVE
HYDRANT
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
E
E
E
ANCHOR BOLTS
NTS
1000
G/2
2
25x25mm CHAMFER
G/2
GRADE C25 / 30 MASS
50 MIN.
50 MIN.
50 MIN.
CONCRETE SUPPORT
G/2
BLOCK
50 MIN.
G/2
0
100
90 DEGREE BEND 45 DEGREE BEND NTS BEND WITH EXTENSION PIECES DOWEL BARS
C/2 C/2 D/2 D/2 E 50 MIN.
20
VARIES
0
TEE E VARIES E
CONCRETE
E
THRUST
E
FLANGE TEE WITH EXTENSION PIECES PLINTH PIPE PLINTH SUPPORT (ABOVE GROUND)
R
TE
F/2
WA IN ROAD SURFACE
GROUND A
50 MIN.
M
50 MIN.
SURFACE REINFORCEMENT
F/2
300
VARIES
PROFILE TO DEVELOPER'S
DN x 2.5
300
VARIES
200
COLLAR
F/2
100 DN x 2.5 100 BOTTOM
HORIZONTAL BENDS
LONGITUDINAL SECTION PIPE DI PE DI PE
TRENCH
DN / 2 DN DN / 2
F/2
300
150
PIPE SUPPORT DETAILS FOR
IW-CDS-5020-01 Rev. 03 December 2017
300 300
200
ELEVATION
G/2
300
WATER METER INTERVALS CENTRE TO
MAIN DUCTILE IRON TO POLYETHYLENE CHANGE OVER
F/2
CENTRE ALONG PIPE WHERE PIPE
IS ON SLOPE. MIN. 1 SUPPORT
E
F/2
REQUIRED FOR PIPE 1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
H, J, or K
200
LENGTH > 3 METERS IN SLOPE.
300
G/2
TRENCH
G/2
SUBMITTED TO IRISH WATER FOR REVIEW.
VARIES
BOTTOM 7. THRUST BLOCKS ARE DESIGNED FOR AN AVERAGE BEARING PRESSURE OF 100 KN/m
THRUST
500
FLANGE (TYPICAL FOR SOFT CLAY) FOR OTHER CONDITIONS. ACTUAL DIMENSIONS MAY BE
G/2
PIPE
ALTERED ON INSTRUCTIONS FROM IRISH WATER.
TRENCH
F/2 F/2
8. CONCRETE IN THRUST BLOCKS SHALL BE GRADE C20/25.
H, J, or K
PLAN
PLAN 9. COMPRESSIBLE FILLER FOR CONCRETE PROTECTION TO BE IN ACCORDANCE WITH BS
PLAN NOTE:
G/2
ANTI-TORQUE EN 622-1 AND BS EN 622-4. BITUMINOUS MATERIAL SHALL NOT BE PUT IN CONTACT WITH
300
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER SUPPLY NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
TRENCH WIDTH TO BE MIN. 500mm 1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
AND DEPENDENT ON
DUCT NUMBERS 2. STRUCTURAL DESIGN AND REINFORCEMENT DETAILS TO BE PROVIDED BY THE
DEVELOPER AND SUBMITTED TO IRISH WATER FOR REVIEW.
GROUND SURFACE
3. DUCT ARRANGEMENT MAY VARY DEPENDING ON REQUIREMENTS.
600 mm MIN.
TO DUCTS
APPROVED MARKER TAPES 4. CABLE DUCTS TO BE IN ACCORDANCE WITH BS 4460 AND BS EN 1401. DUCTS FOR ESB
STD-W-13 FOR
USE TO BE IN ACCORDANCE WITH ESB SPECIFICATION.
BACKFILL DETAILS
200
75
5. PROPRIETARY DUCT CHAMBER MAY BE USED SUBJECT TO REVIEW FROM IRISH WATER.
75
CABLE DUCTS 6. LONG RADIUS BENDS MAY BE USED FOR CHANGES IN DIRECTION OF UP TO 45°
DUCT CHAMBERS SHALL BE PROVIDED FOR ALL BENDS GREATER THAN 45°.
200
APPROVED SAND
7. DUCT CHAMBERS TO BE LOCATED AT 50m INTERVALS MAXIMUM.
8. APPROPRIATE MARKER TAPE SHALL BE LAID 200mm ABOVE THE EXTERNAL CROWN
OF THE DUCT AND SHOULD INCORPORATE REINFORCED TRACING WIRE.
TRACING WIRES SHALL BE CONNECTED ACROSS CHAMBERS.
ELECTRICAL MARKER TAPE TO BE USED IN ACCORDANCE WITH ESB SPECIFICATION.
SECTION C - C 9. ALL CHAMBERS TO BE CHECKED FOR UPLIFT BY THE DEVELOPER BASED
ON GROUND CONDITIONS WITHIN THE SITE. SHOULD ANTI FLOATATION
MEASURES BE REQUIRED THEY SHALL BE SUBJECT TO REVIEW
FROM IRISH WATER.
11. ALL DUCTING TO BE INSTALLED WITH DRAW CORDS/ROPES, TO ALLOW PULL THROUGH
OF CABLES.
12. CABLE DUCT INTERFACE WITH CHAMBER WALL TO BE SEALED TO PREVENT INGRESS OF
B GROUNDWATER TO CHAMBER.
C C
CABLE DUCT
1350
900
A A
1350
PLAN
75
150
150
225
1350 1350
SECTION A - A SECTION B - B
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
675 (MAX.)
D.I. SLUICE VALVE AND CHAMBER 1 No. MIN.,3 No. MAX. COURSE OF CLASS B
(COVER STAMPED '' ScV '' ENGINEERING BRICKS SET IN C50/60 MORTAR
REFER TO STD-W-14)
MANHOLE STEPS TO COMPLY WITH IS EN 13101,
TYPE D, CLASS 1, GALVANISED MILD STEEL &
PLASTIC ENCAPSULATED.
FLAP VALVE
FLAP VALVE
1:50 SLOPE
WATER LEVEL
ROCKER PIPES
225
45°
TO BE PROVIDED
ORIGINAL BED LEVEL
225
300
+ 450
20
Ø1
DISMANTLING
JOINT FLANGED PLAIN
D.I. FLANGED FLAP VALVE
ENDED DI PIPE PLAIN ENDED PIPE
ROCKER PIPES WITH THRUST FLANGE
225
FUSION WELD
STUB FLANGE
WITH BACKING RING
D.I. SLUICE VALVE
HEAVY DUTY COVER AND FRAME,
AND CHAMBER
STAMPED '' ScV '' CLASS D400
(COVER STAMPED
(TO SUIT MIN. 600 SQ. OPE)
'' ScV '' REFER TO
STD-W-14)
DISMANTLING
JOINT ScV
ALL FLANGED
LEVEL INVERT TEE
STUB FLANGE
WITH BACKING RING
FUSION WELD
150
5. POLYETHYLENE PIPES SHALL BE WRAPPED IN PLASTIC SHEETING HAVING A COMPOSITION IN
ACCORDANCE WITH BS 6076 BEFORE BEING CAST INTO CONCRETE.
6. THRUST BLOCKS TO BE PROVIDED AS PER STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS
150
AND PIPES AT STEEP SLOPES.
7. ALL DUCTILE IRON PIPEWORK AND FITTINGS SHALL BE IN ACCORDANCE WITH IS EN 545. PE PIPES
AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 12201:2011.
CROSS SECTION 8. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
(CONCRETE SURROUND) 9. PIPEWORK FOR WATERMAIN CAN BE EITHER DUCTILE IRON OR POLYETHYLENE. PIPEWORK AT
CROSSING POINT TO BE PE IN BOTH CASES.
10. BACKFILL AND REINSTATEMENT OF RIVER BED AND BANK TO BE SUBJECT TO AGREEMENT WITH
RELEVANT AUTHORITY & IRISH WATER.
AIR VALVE TO BE LOCATED AT
BOTH SIDES OF THE CROSSING.
OF RELEVANT AUTHORITY
DETAILS REFER TO STD-W-30
5000mm 5000mm
BANK EDGE
BANK EDGE
BED OF STREAM
DI / PE
FUSION FUSION
REFER TO NOTE 3 WELD WELD
FOR BENDS DI / PE
PLAN
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
TYPICAL
1 11/'17 JMC TOC Updated pipe depth dimension MOD DITCH / STREAM CROSSING STD-W- 31 1
0 09/'15 JMC TOC Initial Issue SL FOR WATER MAIN
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
5. THE DEVELOPER IS TO SEEK ADVICE FROM IRISH WATER AS TO WHETHER A DUPLICATE MAIN IS TO BE
150
PROVIDED THROUGH THE BRIDGE CROSSING. IF NECESSARY THE DEVELOPER IS TO SUBMIT A DESIGN TO
IRISH WATER FOR REVIEW.
REFER TO STD-W-03
SOCKET OUTLINE 6. THRUST BLOCKS TO BE PROVIDED AS PER STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS AND PIPES
FOR TAPPING DETAIL
AT STEEP SLOPES.
DUCTILE IRON
WATER MAIN 7. THE QUALITY OF THE KIOSK CONSTRUCTION SHALL ENSURE THAT THE FOLLOWING IS ACHIEVED:
150
(b) A FIRE RESISTANCE (RETENTION OF STABILITY, INTEGRITY AND INSULATION) EQUIVALENT TO CLASS 2
OF BS 476, WHEN TESTED IN ACCORDANCE WITH BS 476 FOR A PERIOD EXCEEDING 30 MINUTES.
8. KIOSK (MIN. 600 HIGH x 450 WIDE x 300mm DEEP) - TO BE CONSTRUCTED FROM THERMOSETTING U.V. &
WEATHER RESISTANT PLASTIC POWDER COATED & HOT DIPPED GALVANISED MILD STEEL (MIN. 4mm
THICKNESS) TO BS EN 1461. STAINLESS STEEL OR NON-METALLIC MATERIALS, SUCH AS GLASS
REINFORCED PLASTIC (GRP), MAY BE USED AS AN ALTERNATIVE KIOSK MATERIAL, PARTICULARLY IN
SEVERE ENVIRONMENTS, SUBJECT TO AGREEMENT WITH IRISH WATER. COLOUR TO BE HOLLY GREEN BS
4800 14 C 39. KIOSK TO HAVE HINGED, LOCKABLE ACCESS DOOR (HINGES AND LOCKS TO BE STAINLESS
STEEL).
9. THE KIOSK SHALL BE LOCATED OFF THE FOOTPATH SO AS NOT TO IMPEDE PEDESTRIANS AND POSITIONED
SO AS TO FACILITATE SAFE ACCESS FOR MAINTENANCE PERSONNEL.
SECTION A - A 11. DETAIL FOR PE WATERMAIN TO BE AS PER THIS DETAIL. BRIDGE CROSSING PIPEWORK TO BE DI IN BOTH
CASES.
(AIR VALVE CONNECTION) KIOSK
SINGLE AIR VALVE (SEE NOTES 7, 8 & 9)
CONCRETE SURROUND
GRADE C 25/30.
FLEXIBLE
JOINT
LONG BODY
FOR SCOUR VALVE / FLEXIBLE JOINT
CHAMBER DETAILS
REFER TO STD-W-30 SECTION
A
POLYETHYLENE POLYETHYLENE
OR DUCTILE IRON OR DUCTILE IRON
PIPEWORK PIPEWORK
AIR VALVE
CONCRETE PLINTH
(300 HIGH x 600 LONG
FOR SCOUR VALVE /
x 450 WIDE) WITH A 32mm DIA. P.E. PIPE BRIDGE PARAPET
CHAMBER DETAILS
FINISHED LEVEL OF
REFER TO STD-W-30
150 ABOVE GROUND
A
KIOSK
(600 HIGH x 450 WIDE
x 300 DEEP)
PLAN
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
TYPICAL
1 11/'17 JMC TOC Updated & added notes MOD BRIDGE CROSSING FOR WATER MAIN STD-W- 32 1
0 09/'15 JMC TOC Initial Issue SL (Sheet 1 of 2)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
150
5. POLYETHYLENE PIPES SHALL BE WRAPPED IN PLASTIC SHEETING HAVING A COMPOSITION IN ACCORDANCE WITH BS 6076
BEFORE BEING CAST INTO CONCRETE.
6. THRUST BLOCKS TO BE PROVIDED AS PER STD-W-28 AT ALL TEES, BENDS, TAPERS, DEAD ENDS AND PIPES AT STEEP
150
SLOPES.
7. THE DEVELOPER IS TO SEEK ADVICE FROM IRISH WATER AS TO WHETHER A DUPLICATE MAIN IS TO BE PROVIDED AT THE
BRIDGE CROSSING. IF NECESSARY THE DEVELOPER IS TO SUBMIT A DESIGN TO IRISH WATER FOR REVIEW.
8. BACKFILL AND REINSTATEMENT REQUIREMENTS OF THE RIVER BED AND BANK IS SUBJECT TO AGREEMENT WITH
RELEVANT AUTHORITY & IRISH WATER.
CROSS SECTION 9. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
(CONCRETE SURROUND) 10. ALL DUCTILE IRON PIPEWORK TO BE IN ACCORDANCE WITH IS EN 545. ALL POLYETHYLENE PIPEWORK TO BE IN
ACCORDANCE WITH IS EN 12201.
11. PIPEWORK FOR WATERMAIN CAN BE EITHER DUCTILE IRON OR POLYETHYLENE. PIPEWORK AT THE CROSSING POINT TO
BE PE IN BOTH CASES.
BANK EDGE
O.D. COLLAR + 300mm
BED OF
REFER TO NOTE 3 DI / PE STREAM
FOR BENDS
ENSURE STRUCTURE
SAFE DISTANCE TO
IS NOT IMPACTED
ROAD
BRIDGE PARAPET
POLYETHYLENE
OR DUCTILE IRON
PIPEWORK
300 300
O.D. COLLAR + 300mm
POLYETHYLENE
OR DUCTILE IRON
PIPEWORK FOR SCOUR VALVE /
CHAMBER DETAILS
REFER TO STD-W-30
PLAN
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
TYPICAL
1 11/'17 JMC TOC Notes added & updated MOD BRIDGE CROSSING FOR WATER MAIN STD-W- 33 1
0 09/'15 JMC TOC Initial Issue SL (Sheet 2 of 2)
No. Date Drn Chk Description App
IW-CDS-5020-01 Rev. 03 December 2017
2400
V-BEAM
REINFORCING PROFILE EACH GATE LEAF IN SUCH A WAY THAT THEY CANNOT BE REMOVED BUT ALLOW THE GATE
TO BE SECURED IN BOTH THE OPEN & CLOSED POSITION.
6. THE SECURITY RATING SHALL BE EITHER BASIC +, ENHANCED OR ENHANCED +. THE FENCE
STANDARD WILL BE BASED ON THE SECURITY RATING OF THE SITE & IS TO BE AGREED
WITH IRISH WATER.
ANTI-CLIMB &
ENHANCED + 50 x 50 Type: 868 4mm 2.4m
ANTI-BURROW
B
A
4000 mm MINIMUM
METAL PILLARS
RHS FRAME
LOCKABLE
SLIPBOLT
2400
RSA
SLAMPLATE
DROPBOLTS
GRADE C30/37
CONCRETE IN BASE
FOUNDATION DETAIL FOUNDATION DETAIL
TO MANUFACTURERS TO MANUFACTURERS 75mm CONCRETE
SPECIFICATION SPECIFICATION BLINDING, GRADE C12/15
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
5 4 3 4 5 11.EXISTING PE PIPE.
TYPE 3 REPAIR
REPLACEMENT
ASBESTOS CEMENT PIPE
9 4 10 4 9
TYPE 4 REPAIR
REPLACEMENT SECTION FOR
uPVC MAIN
11 13 12 13 11
TYPE 5 REPAIR
REPLACEMENT SECTION OF
PE MAIN
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
2. THE KIOSK SHALL BE LOCATED OFF THE FOOTPATH SO AS NOT TO IMPEDE PEDESTRIANS AND POSITIONED SO AS TO FACILITATE SAFE ACCESS FOR MAINTENANCE PERSONNEL.
3. KIOSK TO BE CONSTRUCTED FROM THERMOSETTING U.V. & WEATHER RESISTANT PLASTIC POWDER COATED & HOT DIPPED GALVANISED MILD STEEL PLATE (MINIMUM 4mm THICKNESS) TO BS EN 1461.
STAINLESS STEEL OR NON-METALLIC MATERIALS, SUCH AS GLASS REINFORCED PLASTIC (GRP), MAY BE USED AS AN ALTERNATIVE KIOSK MATERIAL, PARTICULARLY IN SEVERE ENVIRONMENTS,
SUBJECT TO AGREEMENT WITH IRISH WATER.
4. KIOSK TO HAVE SINGLE OR DOUBLE STEEL/GRP DOORS WITH MULTIPLE LOCKS TO LPS 1175 SR4 OR EN 1627. MINIMUM DOUBLE LOCKS WITH BOLTS THAT ENGAGE INTO THE SILL & HEADER AS WELL AS
BETWEEN THE TWO LEAVES OR LEAF & FRAME. LEADING EDGE OF LEAVES TO HAVE EITHER REBATED EDGES OR FITTED WITH ASTRAGALS.
5. COLOUR TO BE HOLLY GREEN BS 4800 14 C39. INTERIOR FINISH TO BE WHITE UNLESS APPROVED BY IRISH WATER.
6. THE QUALITY OF KIOSK CONSTRUCTION SHALL ENSURE THAT THE FOLLOWING IS ACHIEVED:
7. KIOSK TO BE BOLTED TO THE PLINTH THROUGH A BOTTOM FLANGE WITH GALVANISED MILD STEEL OR STAINLESS STEEL ANCHOR BOLTS.
8. THE BOTTOM FLANGE SHALL BE SEATED ON A NEOPRENE GASKET AND SEALED WITH MASTIC.
9. REAR WALL SHALL BE REINFORCED WITH STAINLESS STEEL SECTIONS TO WHICH A MARINE PLY WOOD , 18mm THICK BOARD IS FIXED.
10. THE DEVELOPER SHALL BE RESPONSIBLE FOR THE ULTIMATE SIZING OF THE KIOSK TO ENSURE ADEQUATE SPACE REQUIREMENTS.
13. THE ROOF OF THE KIOSK SHALL BE REMOVABLE (BOLTS) TO FACILITATE BACKBOARD REMOVAL.
15. A 750mm WIDE x 100mmTHICK FOOTPATH OF C25/30 CONCRETE ON 50mm SAND BLINDING ON 300mm CLAUSE 804 GRANULAR MATERIAL TO BE PROVIDED AROUND KIOSK.
(EACH SIDE)
CAP ON PVC DUCT
450
75mm THICK
150
150
450mm THICK
CONCRETE
CONCRETE 600 SLOW BEND
PLINTH BLINDING 750 700
GRADE C25/ 30 GRADE C12/15
75mm THICK PVC DUCTING WITH
CONCRETE DRAW - CORD
BLINDING
GRADE C12/15
CROSS SECTION CROSS SECTION
(WET KIOSK) (TELEMETRY KIOSK)
RECESS
MIN. 1200
MIN. 1200
DOUBLE
DOORS
150 150 150 150
450
450
150
150
150
MIN. 300
MIN. 400
MIN. 600
POWER IN
DUCT
PLAN
NOTE:
ALL KIOSK DIMENSIONS ARE MINIMUM DIMENSIONS & MAY REFER TO
VARY TO SUIT THE KIOSK REQUIREMENT. PLAN STD-W-29 FOR
DUCT CHAMBER DETAILS
WET KIOSK TELEMETRY KIOSK
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
470
3. LAMP STANDARD TO BE REVIEWED BY IRISH WATER.
SHAFT
100
305
762
75 BLINDING
ARMOURED CABLING TO DUCT
600 100mm DIA. T.PIECE 100mm DIA. DUCT
SECTION SECTION
600 300
600 x 450 CABLE JUNCTION BOX MIN. 100 DIA. CABLE DUCT
(SIMILAR TO DUCT CHAMBER
DETAIL ON DRG. No. STD-W-29)
PLAN
PLAN
LAMP STANDARD LAMP BOLLARD
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
1 11/'17 JMC TOC Notes updated MOD LAMP BOLLARD AND LAMP STANDARD STD-W- 37 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
STANDARD DETAILS FOR WATER NETWORKS: REVISION LOG - 03 (1st Dec. 2017)
DRG No. DRAWING TITLE MATERIAL CHANGES EDITORIAL CHANGES REV COMMENTS
STD-W-01 WATER SERVICE CONNECTION RESPONSIBILITY 0 No change
STD-W-02 TYPICAL LAYOUT FOR WATER MAINS WITHIN DEVELOPMENTS Temp. “dead end” & note 1 ref. added 1 Drawing revised
STD-W-03 CUSTOMER CONNECTION & BOUNDARY BOX Updated & added notes 3 Drawing revised
STD-W-04 GENERAL PIPE CONNECTIONS (Sheet 1 of 7) Added 2 No. extg. PE details & updated details Added notes 3 Drawing revised
STD-W-05 GENERAL PIPE CONNECTIONS (Sheet 2 of 7) Added w DI pipe to details & updated 3 No. details Updated notes 2 Drawing revised
STD-W-06
IW-CDS-5020-01 Rev. 03 December 2017
GENERAL PIPE CONNECTIONS (Sheet 3 of 7) Added extg. PE pipe to details Updated notes 2 Drawing revised
STD-W-07 GENERAL PIPE CONNECTIONS (Sheet 4 of 7) Updated & added notes 1 Drawing revised
STD-W-08 GENERAL PIPE CONNECTIONS (Sheet 5 of 7) Updated & added notes 1 Drawing revised
STD-W-09 GENERAL PIPE CONNECTIONS (Sheet 6 of 7) Updated & added notes 1 Drawing revised
STD-W-10 GENERAL PIPE CONNECTIONS (Sheet 7 of 7) Updated & added notes 1 Drawing revised
STD-W-11 TYPICAL SERVICE LAYOUT INDICATING SEPARATION DISTANCES Updated & added notes 1 Drawing revised
STD-W-12 RESTRICTIONS ON EXISTING TREES / SHRUBS PLANTING ADJACENT TO Revised to suit ILI recommendations Changed drawing title 2 Drawing revised
WATERMAINS
STD-W-12A RESTRICTIONS ON NEW TREES / SHRUBS PLANTING ADJACENT TO 0 New Drawing
WATERMAINS
STD-W-13 TRENCH BACKFILL & BEDDING Updated & added notes 1 Drawing revised
STD-W-14 SLUICE VALVE FOR DUCTILE IRON (D.I.) PIPE (<350mm DIA.) (Sheet 1 of Updated & added notes 3 Drawing revised
2)
STD-W-15 SLUICE VALVE FOR POLYETHYLENE (P.E.) PIPE (<350mm DIA.) (Sheet 2 of Revised & added notes 2 Drawing revised
2)
STD-W-16 ON-LINE HYDRANT FOR DUCTILE IRON (D.I.) PIPE (Sheet 1 of 4) Revised & added notes 2 Drawing revised
STD-W-17 OFF-LINE HYDRANT FOR DUCTILE IRON (D.I.) PIPE (Sheet 2 of 4) Revised & added notes, & revised pipework 3 Drawing revised
STD-W-18 ON-LINE HYDRANT FOR POLYETHYLENE (P.E.) PIPE (Sheet 3 of 4) Revised & added notes 2 Drawing revised
STD-W-19 OFF-LINE HYDRANT FOR POLYETHYLENE (P.E.) PIPE (Sheet 4 of 4) Revised & added notes, & revised pipework 3 Drawing revised
STD-W-20 ON-LINE AIR VALVE FOR DUCTILE IRON (D.I.) PIPE (Sheet 1 of 4) Updated & revised notes 2 Drawing revised
STD-W-21 OFF-LINE AIR VALVE FOR DUCTILE IRON (D.I.) PIPE (Sheet 2 of 4) Updated & added notes 3 Drawing revised
STD-W-22 ON-LINE AIR VALVE FOR POLYETHYLENE (P.E.) PIPE (Sheet 3 of 4) Updated & added notes 2 Drawing revised
STD-W-23 OFF-LINE AIR VALVE FOR POLYETHYLENE (P.E.) PIPE (Sheet 4 of 4) Updated & added notes 3 Drawing revised
STD-W-24 PRESSURE REDUCING / SUSTAINING VALVE (P.R.V. / P.S.V.) CHAMBER Revised & added notes, & added chamber sizing 2 Drawing revised
table, fittings & kiosk
STD-W-25 BOOSTER PUMP STATION ARRANGEMENT 1 No change
STD-W-26 NON-MECH METER CHAMBER (40 -250mm DIA.) Revised notes & added table & hydrant Changed drawing title 3 Drawing revised
STD-W-26A MECH METER CHAMBER (40 -250mm DIA.) 0 New Drawing
STD-W-27 MARKER POSTS / PLATES Added BM plate Updated notes 2 Drawing revised
STD-W-28 WATER MAIN THRUST & SUPPORT BLOCKS Anti-Torque support note & thrust flange added Note 6 updated 1 Drawing revised
STD-W-29 DUCT CHAMBER Updated notes 2 Drawing revised
STD-W-30 SCOUR CHAMBER & HEAD WALL ARRANGEMENTS Updated notes 3 Drawing revised
WASHOUT HYDRANT Revised chamber base detail & updated & added 2 Drawing revised
STD-W-30A notes
STD-W-31 TYPICAL DITCH / STREAM CROSSING FOR WATER MAIN Updated pipe depth dimension 1 Drawing revised
STD-W-32 TYPICAL BRIDGE CROSSING FOR WATER MAIN (Sheet 1 of 2) Updated & added notes 1 Drawing revised
STD-W-33 TYPICAL BRIDGE CROSSING FOR WATER MAIN (Sheet 2 of 2) Updated pipe depth dimension, updated & added 1 Drawing revised
notes
STD-W-34 SECURITY GATE & FENCING Fencing table updated 2 Drawing revised
STD-W-35 PIPE REPAIR TO EXISTING MAINS Updated note 10 2 Drawing revised
STD-W-36 TELEMETRY AND WET KIOSK Note 10 revised 2 Drawing revised
STD-W-37 LAMP BOLLARD & LAMP STANDARD Updated notes 1 Drawing revised
/ INDEX SHEET Inclusion of STD-W-12A & STD-W-26A Drawing revisions updated Nov. 2017 Drawing revisions updated
/ Design Risk Assessment for Water Standard Details Inclusion of STD-W-12A & STD-W-26A General Amendments v4.01 Document revised