Documente Academic
Documente Profesional
Documente Cultură
4.42
4.12
Skid Foundation
PLAN
0.35
0.550
0.2
ELEVATION
II - Operating Condition
Poper/A + Mx/Zx + Mz/Zz = (227.47/12.9064 + 55.42/6.29 + 48.21/9.51)= (Due to wind) 31.51 kN/m2
Poper/A - Mx/Zx - Mz/Zz = (227.47/12.9064 - 55.42/6.29 - 48.21/9.51)= (Due to wind) 3.75 kN/m2
5 Sliding Check Wind Load
I - Static Condition
=190.463*0.4/ (2.92*1.054*4.96)
x Direction= 4.99 >1.5 HENCE SAFE
=190.463*0.4/ (4.42*1.054*4.96)
z direction= 3.3 >1.5 HENCE SAFE
II - Operating Condition
=227.463*0.4/ (2.92*1.054*4.96)
x Direction= 5.96 >1.5 HENCE SAFE
=227.463*0.4/ (4.42*1.054*4.96)
z direction= 3.94 >1.5 HENCE SAFE
II - Operating Condition
=(227.463*2.92/2)/55.42)
x direction= 6 >1.5 HENCE SAFE
=(227.463*4.42/2)/48.21)
PH dosing Skid (T-7568) Foundation
7 Design of Reinforcement
As,min=0.18% of section =(0.18/100)*488*1000
889.20 mm2/m
As,provided= 12Tor @ 150 mm. c/c
= 753.98 mm2/m (50% each on both face) HENCE SAFE
4.22
3.92
Skid Foundation
PLAN
0.35
0.550
0.2
ELEVATION
II - Operating Condition
Poper/A + Mx/Zx + Mz/Zz = (208.41/11.5206 + 45.96/5.25 + 43.84/8.11)= (Due to wind) 32.26 kN/m2
Poper/A - Mx/Zx - Mz/Zz = (208.41/11.5206 - 45.96/5.25 - 43.84/8.11)= (Due to wind) 3.94 kN/m2
5 Sliding Check Wind Load
I - Static Condition
=171.40825*0.4/ (2.73*1.054*4.96)
x Direction= 4.81 >1.5 HENCE SAFE
=171.40825*0.4/ (4.22*1.054*4.96)
z direction= 3.11 >1.5 HENCE SAFE
II - Operating Condition
=208.40825*0.4/ (2.73*1.054*4.96)
x Direction= 5.84 >1.5 HENCE SAFE
=208.40825*0.4/ (4.22*1.054*4.96)
z direction= 3.78 >1.5 HENCE SAFE
II - Operating Condition
=(208.40825*2.73/2)/45.96)
x direction= 6.19 >1.5 HENCE SAFE
=(208.40825*4.22/2)/43.84)
LP dosing Skid (T-7569) Foundation
7 Design of Reinforcement
As,min=0.18% of section =(0.18/100)*488*1000
889.20 mm2/m
As,provided= 12Tor @ 150 mm. c/c
= 753.98 mm2/m (50% each on both face) HENCE SAFE
4.43
4.13
Skid Foundation
PLAN
0.35
0.550
0.2
ELEVATION
II - Operating Condition
Poper/A + Mx/Zx + Mz/Zz = (385/21.81775 + 74.52/17.91 + 70.87/16.11)= (Due to wind) 26.21 kN/m2
Poper/A - Mx/Zx - Mz/Zz = (385/21.81775 - 74.52/17.91 - 70.87/16.11)= (Due to wind) 9.09 kN/m2
5 Sliding Check Wind Load
I - Static Condition
=339.9940625*0.4/ (4.925*1.054*4.96)
x Direction= 5.29 >1.5 HENCE SAFE
=339.9940625*0.4/ (4.43*1.054*4.96)
z direction= 5.88 >1.5 HENCE SAFE
II - Operating Condition
=384.9940625*0.4/ (4.925*1.054*4.96)
x Direction= 5.98 >1.5 HENCE SAFE
=384.9940625*0.4/ (4.43*1.054*4.96)
z direction= 6.65 >1.5 HENCE SAFE
II - Operating Condition
=(384.9940625*4.925/2)/74.52)
x direction= 12.73 >1.5 HENCE SAFE
=(384.9940625*4.43/2)/70.87)
HP & IP dosing Skid (T-7570) Foundation
7 Design of Reinforcement
As,min=0.18% of section =(0.18/100)*488*1000
889.20 mm2/m
As,provided= 12Tor @ 150 mm. c/c
= 753.98 mm2/m (50% each on both face) HENCE SAFE