Sunteți pe pagina 1din 80

P 06.

13 Event: Controller Limited Default: IG (Hidden)


Event Group: CO Number: 01
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden

This parameter selects the error condition generated when the motor speed control demand signal
reaches its upper limit.

This parameter should be set to IG (Ignore).

P 06.14 Event: Memory Error Default: A (Hidden)


Event Group: SY Number: 01
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden

This parameter selects the error condition generated when the controller detects an error in the
internal non-volatile memory. Reload the non-volatile memory by using the “Load Default Parameters”
function to correct this error. If the problem persists, the controller must be replaced.

This parameter should be set to A (Stop feeder).

Note: The Load Default Parameters function will reset all of the controller’s internal parameters,
including Calibration and Trim. After this operation is performed, all parameters must be reset, the
feeder must be recalibrated and the analog I/O channels must be re-trimmed.

P 06.15 Event: Analog Input< Offset Default: IG (Hidden)


Event Group: WE Number: 08
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden

This parameter selects the error condition generated when the analog feedrate demand signal is
more then 0.4 mA below the minimum value (P03.04 Setpoint Offset).

This parameter should be set to IG (Ignore).

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 77


©Schenck Process Group
9.2.7 Parameter Group 07 – Belt Monitoring
The parameters in this group control the Belt Motion Monitor (BMM).

P 07.01 DI: Belt Motion Monitor Default: DI 12 – High (Hidden)


Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden

This parameter selects the digital input used for the Belt Motion Monitor (BMM).

This parameter is normally set to DI 12 - High (terminal block X4-2) and is connected to wire 115.

P 07.02 Belt Motion Delay Default: 10 sec.


Min: 0 sec Max: 50 sec

This parameter sets the maximum delay between Belt Motion Monitor (BMM) pulses before a BMM
error (P07.03 Belt Motion Error) is generated. It is the same as 196NT Setup 17 (Belt Motion Monitor
Delay). The interval is determined when the feeder is operating at its minimum design feed rate and is
equal to the time necessary for the pulley or roller which inputs the sensor to make one complete
revolution, divided by two, plus ten percent. Therefore, time intervals for motion monitors mounted to
the tension roll or belt take-up pulley will be considerably longer than those for sensors mounted to
the weigh span roller.

Example: If the motion monitor is mounted to the weigh span roller which make revolution every 20
seconds at minimum feed rate, the time interval between pulses before the belt is certain not to be
moving is: 20 / 2 = 10 + 10% = 11.

Note: To disable this function if a belt motion monitor is not installed set P07.03 Belt Motion Error
to IG.

P 07.03 Event: Belt Motion Monitor Default: IG


Event Group: WE Number: 08
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

This parameter selects the error condition generated when the belt motion monitor (BMM) pulse delay
is exceeded.

This parameter is normally set to A (Stop Feeder) if a BMM is installed. Setting it to IG (Ignore) will
disable the BMM feature.

78 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 07.04 DI: Source Belt Sensor Default: n/a (Hidden)
Options: n/a (not used)
DI 13 – High/Low

Normally Hidden

This parameter is used to specify the digital input used for the belt slip sensor. The slip sensor is
connected to a driven roller and generates a frequency input proportional to the belt speed. This
value is compared to the tachometer signal from the motor to detect belt slippage at the head pulley.
See also: parameters P 07.08 Event: Belt Slip and P 07.09 DO: Belt Slip.

This parameter is normally set to n/a.

P 07.05 BIC Active Default: NO (Hidden)


Options: NO
YES

Normally Hidden

This parameter is used to activate the moisture Belt Influence Compensation (BIC) system. The BIC
system is used in batching feeders to tare individual sections of the belt separately so that batches
that are less then a full belt length are weighted accurately.

The BIC feature is not used in continuous feeding systems and this parameter should always be set
to NO.

P 07.06 DI: BIC freeze Default: n/a (Hidden)


Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden

This parameter is used specify a digital input that is used to freeze the tare value while the BIC
feature is active.

This parameter is normally set to n/a.

P 07.07 Slip Value Default: 10.0 % LB (Hidden)


Min: 0.0 % Max: 20.0 %

Normally Hidden

This parameter specifies the maximum amount that the belt speed measured by the belt slip input
can differ from belt speed measured by the tachometer input, without generating an error.

This parameter is normally set to 10.0 % LB.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 79


©Schenck Process Group
P 07.08 Event: Belt Slip Default: IG (Hidden)
Event Group: WE Number: 08
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden

This parameter selects the error condition generated when the belt slip exceeds the limit specified in
parameter P07.07 Slip Value.

This parameter is normally set to IG.

P 07.09 DO: Belt Slip Default: n/a (Hidden)


Options: n/a (not used)
DO 1 thru DO 13 – High/Low

Normally Hidden

This parameter selects the digital output that is energized when the Belt Slip event is active.

This parameter is normally set to IG.

80 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
9.2.8 Parameter Group 08 - Display Filters
The parameters in this group select the time constants for the digital filters used that are applied to
the load cell and output signals.

P 08.01 LC Filter Default: 4.00 sec


Min: 0.25 sec Max: 300.00 sec

This parameter sets the amount of digital filtering used on the load cell signals. It is similar to the
196NT Setup 19 Weight Signal Filter.

This parameter is normally set to 4 seconds.

P 08.02 I-Display Default: 1.0 sec


Min: 0.0 sec Max: 600.0 sec

This parameter sets the amount of digital filtering used on the feedrate value displayed on the display,
EasyServe and field bus interface. It is similar to the 196NT Setup 20 Feedback Signal Filter.

This parameter is normally set to 1 second.

P 08.03 I-Analog Output Default: 1.0 sec


Min: 0.0 sec Max: 600.0 sec

This parameter sets the amount of digital filtering used on the feedrate signal sent to the analog
output channel. It is similar to the 196NT Setup 20 Feedback Signal Filter. This parameter is
normally set to 1 second.

P 08.04 Feedback filter override threshold Default: 15%


Min: 0.0% Max: 200.0%

This parameter specifies point at which the point at which the feedback filter is overridden and the
actual feedrate is displayed. This is used so that large changes are displayed quickly. This parameter
is the same as 196NT Setup 21 (Feedback filter override threshold).

This parameter is normally set to 15%.

P 08.05 Belt Load Default: 1.0 sec


Min: 0.0 sec Max: 600.0 sec

This parameter sets the amount of digital filtering used on the belt load signal sent to the analog
output channel.

This parameter is normally set to 1 second.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 81


©Schenck Process Group
P 08.06 Belt Speed Default: 1.0 sec
Min: 0.0 sec Max: 600.0 sec

This parameter sets the amount of digital filtering used on the belt speed signal sent to the analog
output channel.

This parameter is normally set to 1 second.

P 08.07 Deviation Default: 1.0 sec


Min: 0.0 sec Max: 600.0 sec

This parameter sets the amount of digital filtering used on the deviation signal sent to the analog
output channel.

This parameter is normally set to 1 second.

82 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
9.2.9 Parameter Group 09 - Limit Values
The parameters in this group are used to set the limit points at witch various events are generated as
well as selecting the type of event that are generated when the limit points are reached.

Note: Limit values are only checked after the feeder has been running for 10 seconds.

P 09.01 Value for I-Min Default: 5.0 % Io (Hidden)


Min: -10.0 % Io Max: 200.0 % Io

Normally Hidden

This parameter sets the point at which a minimum feedrate event is generated.

This parameter is normally set to 5 % of the nominal flow rate (P02.05).

P 09.02 Event: I-Min Default: IG (Hidden)


Event Group: LO Number: 02
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden

This parameter determines the type of event that is generated when the feedrate is less then the
value specified in P09.01 Value for I-Min.

This parameter is normally set to IG (Ignore)

P 09.03 Value for I-Max Default: 120.0 % Io (Hidden)


Min: -10.0 % Io Max: 200.0 % Io

Normally Hidden

This parameter sets the point at which a maximum feedrate event is generated.

This parameter is normally set to 120 % of the nominal flow rate (P02.05).

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 83


©Schenck Process Group
P 09.04 Event: I-Max Default: IG (Hidden)
Event Group: HI Number: 02
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden

This parameter determines the type of event that is generated when the feedrate exceeds the value
specified in P09.03 Value for I-Max.

This parameter is normally set to IG (Ignore)

P 09.05 Value for Q-Min Default: 60.0 % Q


Min: -10.0 % Q Max: 200.0 % Q

This parameter sets the point at which a minimum belt load event is generated.

This parameter is normally set to 60 % of the nominal belt load (calculated from the nominal flow rate
and the nominal belt speed).

P 09.06 Event: Q-Min Default: IG


Event Group: LO Number: 03
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

This parameter determines the type of event that is generated when the feedrate is less then the
value specified in P09.05 Value for Q-Min. Set this value to W2 to simulate the 196NT low density
alarm.

This parameter is normally set to IG (Ignore)

P 09.07 Value for Q-Max Default: 120.0 % Q (Hidden)


Min: -10.0 % Q Max: 200.0 % Q

Normally Hidden

This parameter sets the point at which a maximum belt load event is generated.

This parameter is normally set to 120 % of the nominal belt load (calculated from the nominal flow
rate and the nominal belt speed).

84 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 09.08 Event: Q-Max Default: IG (Hidden)
Event Group: HI Number: 03
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden

This parameter determines the type of event that is generated when the feedrate exceeds the value
specified in P09.07 Value for Q-Max.

This parameter is normally set to IG (Ignore)

P 09.09 Value for V-Min Default: 5.0 % V (Hidden)


Min: -10.0 % V Max: 200.0 % V

Normally Hidden

This parameter sets the point at which a minimum belt speed event is generated.

This parameter is normally set to 5 % of the nominal belt speed (P02.06).

P 09.10 Event: V-Min Default: IG (Hidden)


Event Group: LO Number: 04
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden

This parameter determines the type of event that is generated when the feedrate is less then the
value specified in P09.09 Value for V-Min.

This parameter is normally set to IG (Ignore)

P 09.11 Value for V-Max Default: 120.0 % V (Hidden)


Min: -10.0 % V Max: 200.0 % V

Normally Hidden

This parameter sets the point at which a maximum belt speed event is generated.

This parameter is normally set to 120 % of the nominal belt speed (P02.06).

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 85


©Schenck Process Group
P 09.12 Event: V-Max Default: IG (Hidden)
Event Group: HI Number: 04
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden

This parameter determines the type of event that is generated when the feedrate exceeds the value
specified in P09.01 Value for V-Max.

This parameter is normally set to IG (Ignore)

86 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
9.2.10 Parameter Group 10 - Calibration Data
The parameters in this group are used to either set or display the values used to calibrate the feeder
weighing system.

P 10.01 Calibration Probe Span Default: 36.0000 inch


Min: 0.0100 inch Max: 500.0000 inch

This parameter specifies the distance between the two calibration probe bosses. It is the same as
the 196NT Setup 12 Calibration Probe Span

This parameter must match the physical characteristics of the feeder but in most cases, it is set to 36
inches for new feeder installations or 38.7 inches on mechanical weighing feeder conversions.

P 10.02 Pulses per Length Default: 300.00 P/inch (Read Only)


Min: 1.00 P/inch Max: 1000000.00 P/inch

This parameter indicates the number of tachometer pulses per inch of belt travel. It is calculated by
the DT-9 during the calibration process based on the time it takes for a calibration tape to travel
between the two calibration probes.

This parameter should not normally be changed by the operator.

P 10.03 Range Correction TW Default: 1.0000 (Read Only)


Min: 0.5000 Max: 2.0000

This parameter indicates the correction factor applied to the load cell reading based on a dead weight
calibration (TW: Span Calibration). It is calculated by the DT-9 during the calibration process based
on the weigh system characteristics specified in Parameter Block 4, and on the calibration weight
specified in P10.08 Effective Check Weight.

This parameter should not normally be changed by the operator.

Note: The gross weight on the load cells is calculated based on the load cell characteristics specified
in Parameter Block 4 and the product of the three correction factors specified in P10.03 thru P10.05.

P 10.04 Range Correction TC Default: 1.0000 (Read Only)


Min: 0.5000 Max: 2.0000

This parameter indicates the correction factor applied to the load cell reading based on a chain
calibration (TC: Span Calibration). It is calculated by the DT-9 during the calibration process based
on the weigh system characteristics specified Parameter Block 4, and on the test chain weight
specified in P10.09 Test Chain Weight.

This parameter should not normally be changed by the operator.

Note: The gross weight on the load cells is calculated based on the load cell characteristics specified
Parameter Block 4 and the product of the three correction factors specified in P10.03 thru P10.05.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 87


©Schenck Process Group
P 10.05 Range Correction TM Default: 1.0000 (Read Only)
Min: 0.5000 Max: 2.0000

This parameter specifies the correction factor applied to the load cell reading based on a material
test. It is calculated by the operator based on the difference between the totalized value, indicated by
the DT-9, and the actual value, determined by an external static scale.

This parameter is normally set to 1.000.

Note: The gross weight on the load cells is calculated based on the load cell characteristics specified
Parameter Block 4 and the product of the three correction factors specified in P10.03 thru P10.05.

P 10.06 Belt Circuit Time Default: 60.0 s


Min: 1.0 s Max: 9999.0 s

This parameter specifies the duration of the LB: Pulse/Belt calibration process. This process counts
the number of tachometer pulses received during the specified time and place the result in P10.11
Belt Circuit No.

This parameter should be set to 60.0 Seconds.

P 10.07 Simulation Travel (Belt Rev.) Default: 2.0


Min: 0.5 Max: 5000.0

This parameter specifies the duration, in belt revolutions, of the TC: Span Calibration process. This
process performs a span calibration using P10.09 Test Chain Weight as the calibration weight, and
places the result in P10.04 Range Correction TC.

This parameter should be set to 2.0 belt revolutions.

P 10.08 Calibration Weight Default: 70.000 lb


Min: 0.001 lb Max: 22000.000 lb

This parameter specifies the value of the calibration weight used during the span portion of a feeder
calibration (TW: Span Calibration). It is the same as the 196NT Setup 13 Calibration Weight

The correct value is normally stamped on the calibration weight.

P 10.09 Test Chain Weight Default: 4.3000 lb/inch


Min: 0.0000 lb/inch Max: 22000.000 lb/inch

This parameter specifies the value of the calibration chain used when a chain calibration (TC: Span
Calibration) is preformed. It is similar to the 196NT Setup 36 Test Chain Weight

88 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 10.10 Basic Tare Default: 0.00 lb/inch (Read Only)
Min: 0.00 lb/inch Max: 10000.00 lb/inch

This parameter indicates the weight of the empty belt. It is calculated by the DT-9 during the tare
portion of the calibration process (BS: Tare/Belt Speed).

This parameter should not normally be changed by the operator.

P 10.11 Belt Circuit No. Default: 1000000 I/U (Read Only)


Min: 0 I/U Max: 9000000 I/U

This parameter indicates the total number of tachometer pulses in one complete belt revolution. It is
calculated by the DT-9 during the tare portion of the calibration process (BS: Tare/Belt Speed).

This parameter should not normally be changed by the operator.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 89


©Schenck Process Group
9.2.11 Parameter Group 11 – Rate Controller
The parameters in this group are used to control the operation of the Motor Speed Control (MSC).

P 11.01 P-Component KP Default: 0.05000 mA/%


Min: 0.00000 mA/% Max: 1000.00000 mA/%

This parameter specifies the proportional gain of the speed control loop. Increasing this value
produces a faster response but my produce oscillation or unstable operation. Reducing this value
increases stability but produces a slower response.

This parameter should be set to 0.05000 mA/%.

Note: The DT-9 uses a PI control loop (Proportional & Integral terms, no Derivative term). The
proportional term is specified by P11.01 P-Component KP and the Integral term is specified by
P11.02 I-Component.

P 11.02 I-Component TN Default: 1.0 s


Min: 0.0 s Max: 60000.0 s

This parameter specifies the integral gain of the speed control loop. The value specified here is the
reciprocal of the actual gain value. Decreasing this parameter produces a faster response but my
produce oscillation or unstable operation and increasing it increases stability but produces a slower
response.

This parameter should be set to 1.0 sec.

Note: The DT-9 uses a PI control loop (Proportional & Integral terms, no Derivative term). The
proportional term is specified by P11.01 P-Component KP and the Integral term is specified by
P11.02 I-Component.

P 11.03 Motor Speed Control Output Default: AO 1


Options: n/a (not used)
AO 1 thru AO 6

This parameter specifies the analog output channel used to control the Motor Speed Control (MSC).

This parameter is normally set to AO 1 (terminal blocks X6-7 and X6-6) and is connected to wires 142
through 144.

90 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 11.04 Lower Limit Default: 4,0 mA
Min: 0.00 mA Max: 20.00 mA

This parameter determines the lower limit of the Motor Speed Control (MSC) demand signal. It
should always be set to the same value as P11.06 Contr.Magn. Offset.

This parameter is normally set to 4.00 mA. If a zero based signal (0-20mA or 0-10V) is used it must
be set to 0.00 mA.

P 11.05 Upper Limit Default: 20.00 mA


Min: 0.00 mA Max: 20.00 mA

This parameter determines the nominal 100% signal level for the analog input channel. It should be
set to 20.0 for a 0-20mA, 4-20mA and 0-10V input.

This parameter is normally set to 20.00 mA.

P 11.06 Controller Magnitude Offset Default: 4.00 mA


Min: 0.00 mA Max: 20.00 mA

This parameter determines the nominal 0% signal level for the analog input channel. It should always
be set to the same value as P11.04 Lower Limit.

This parameter is normally set to 4.00 mA. If a zero based signal (0-20mA or 0-10V) is used it must
be set to 0.00 mA.

P 11.07 Position at STOP Default: Lower Limit


Options: 0
Lower Limit

This parameter specifies the value of the Motor Speed Control (MSC) demand signal (see P11.03
Controller Magnitude Y) when the belt drive motor is not running.

This parameter should always be set to Lower Limit.

P 11.08 KP Speed controller Default: 0.10000 mA/%


Min: 0.00000 mA/% Max: 1000.00000 mA/%

This parameter specifies the speed control gain used during the volumetric startup period.

This parameter should always be set to 0.1000 mA/%.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 91


©Schenck Process Group
P 11.09 VAP Active Default: NO (Hidden)
Options: YES
NO

Normally Hidden.

When this parameter is set to YES the feedrate and total calculations are time shifted to adjust for the
delay between the time that the material is weighed and the time that it is discharged.

This feature is useful when small batches are being delivered but is not used on Stock feeders. It
should always be set to NO.

P 11.10 Platform Dis. Length Default: 0.00 % lb (Hidden)


Min: 0.00 % lb Max: 50.00 % lb

Normally Hidden.

This parameter specifies the distance between the center of the weigh platform and the material
discharge point in percentage of total belt length.

This parameter is only used when P11.09 VAP Active is set to YES. It should always be set to
0.0% Lb.

92 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
9.2.12 Parameter Group 12 - Moisture
Parameters in this group supply the information required when material moisture compensation is
used. Stock does not currently supply moisture measurement equipment and these parameters
should always be disabled.

P 12.01 Moisture Active Default: NO (Hidden)


Options: NO
YES

Normally Hidden – Set to NO.

This parameter is used to activate the moisture compensation system. At present Stock does not
supply moisture measurement equipment and these parameters should always be disabled.

This parameter should always be set to NO.

P 12.02 Moisture Select Default: n/a (Hidden)


Only available if Parameter: 12.01 = YES
Options: DI
FB

Normally Hidden – Set to n/a.

P 12.03 Moisture Measurement Default: n/a (Hidden)


Only available if Parameter: 12.01 = YES
Options: AI
DI4

Normally Hidden – Set to n/a.

P 12.04 Nominal Moisture Default: 10.00 % (Hidden)


Only available if Parameter: 12.01 = YES
Min: 0.00 % Max: 100.00 %

Normally Hidden – Set to 10.00%.

P 12.05 Moisture Offset Default: 4.00 mA (Hidden)


Only available if Parameter: 12.01 = YES
Min: -200.00 mA Max: 200.00 mA

Normally Hidden – Set to 4.00 mA.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 93


©Schenck Process Group
P 12.06 Moisture Range Default: 20.00 mA (Hidden)
Only available if Parameter: 12.01 = YES
Min: 0.00 mA Max: 1000.00 mA

Normally Hidden – Set to 20.00 mA.

P 12.07 DO Moisture active Default: n/a (Hidden)


Only available if Parameter: 12.01 = YES
Options: DO

Normally Hidden – Set to n/a.

P 12.08 Moisture MAX Default: 20.00 % (Hidden)


Only available if Parameter: 12.01 = YES
Min: 0.00 % Max: 100.00 %

Normally Hidden – Set to 20.00%.

P 12.09 DO Moisture MAX Default: n/a (Hidden)


Only available if Parameter: 12.01 = YES
Options: DO

Normally Hidden – Set to n/a.

P 12.10 Event Moisture MAX Default: IG (Hidden)


Only available if Parameter: 12.01 = YES
Event Group: MF Number: 05

Normally Hidden – Set to IG.

P 12.11 AO Flow Rate corr. Default: n/a (Hidden)


Only available if Parameter: 12.01 = YES
Options: AO

Normally Hidden – Set to n/a.

94 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 12.12 AO Flow Rate Offset Default: 4.00 mA (Hidden)
Only available if Parameter: 12.01 = YES
Min: -200.00 mA Max: 200.00 mA

Normally Hidden – Set to 4.00 mA.

P 12.13 AO Flow Rate Range Default: 20.00 mA (Hidden)


Only available if Parameter: 12.01 = YES
Min: 0.00 mA Max: 1000.00 mA

Normally Hidden – Set to 20.00 mA

P 12.14 Pulse Counter corr. Default: NO (Hidden)


Only available if Parameter: 12.01 = YES
Options: NO
YES

Normally Hidden – Set to NO.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 95


©Schenck Process Group
9.2.13 Parameter Group 13 – Cleanout Control
The parameters in this group control the cleanout conveyor timer and Chain Motion Monitor (CMM)

P 13.01 DO: Cleanout Timer Default: DO 10


Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden.

This parameter specifies the digital output used to energize the cleanout conveyor motor starter when
the cleanout timer feature is enabled.

This parameter is normally set to DO 10.

Note: The cleanout timer output relay is only energized when the feeder is operating in remote mode.

P 13.02 Cleanout ON Time Default: 1.00 h (Hidden)


Min: 0.00 h Max: 1000.00 h

Normally Hidden

This parameter specifies the cleanout conveyor ON time when the cleanout timer feature is enabled.

This parameter is normally set to 1.00 h.

Note: The cleanout timer output relay is only energized when the feeder is operating in remote mode.

P 13.03 Cleanout OFF Time Default: 1.00 (Hidden)


Min: 0.00 h Max: 1001.00 h

Normally Hidden

This parameter specifies the cleanout conveyor OFF time when the cleanout timer feature is enabled.

This parameter is normally set to 1.00 h.

Note: The cleanout timer output relay is only energized when the feeder is operating in remote mode.

P 13.04 DI: Chain Motion Monitor Default: n/a (not used - Hidden)
Options: n/a (not used)
DI 1 thru DI 14– High/Low

Normally Hidden.

This parameter specifies the digital input used for the Chain Motion Monitor (CMM)

This parameter is normally set to n/a.

96 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 13.05 Chain Motion Delay Default: 20 s (Hidden)
Min: 1 s Max: 1000 s

Normally Hidden.

This parameter sets the maximum delay between Chain Motion Monitor (CMM) pulses before a CMM
error (P13.06 Error Scraper) is generated.

This parameter is normally set to 20 sec. To disable this function if a CMM is not installed set P13.06
Belt Motion Error to IG.

P 13.06 Event: Chain Motion Monitor Default: IG (Hidden)


Event Group: LO Number: 04
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden.

This parameter selects the error condition generated when the Chain Motion Monitor (CMM) pulse
delay is exceeded.

This parameter is normally set to A (Stop Feeder) if a CMM is installed and IG (Ignore) if not.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 97


©Schenck Process Group
9.2.14 Parameter Group 14 - Analog Outputs
The parameters in this group select the control source for the analog output channels. On the VCU
20104 controller only one analog channel is available and it is set to feedrate feedback by default.

P 14.01 Setpoint Default: n/a (not used - Hidden)


Options: n/a (not used)
AO 1 thru AO 6

Normally Hidden.

This parameter selects the analog output channel used for the indicated signal.

Setpoint: The Setpoint value is the feedrate that the feeder is currently attempting to meet. The
source of the setpoint signal is determined by P03.02 Feedrate Setpoint. The analog output is scaled
to P02.05 Nominal Flow Rate.

This parameter is normally set to n/a (not used).

P 14.02 Setpoint Offset Default: 4.00 mA (Hidden)


Min: -200.00 mA Max: 200.00 mA

Normally Hidden.

This parameter selects the actual analog output when the control signal is zero.

This parameter is normally set to 4.00 mA.

P 14.03 Setpoint Range Default: 20.00 mA (Hidden)


Min: 0.00 mA Max: 1000.00 mA

Normally Hidden.

This parameter selects the actual analog output when the control signal is maximum.

This parameter is normally set to 20.00 mA.

98 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 14.04 Actual Flow Rate Default: AO 2 (Hidden)
Options: n/a (not used)
AO 1 thru AO 6

Normally Hidden.

This parameter selects the analog output channel used for the indicated signal.

Actual Flow Rate: The Actual Flow Rate value is the feedrate that the feeder is currently delivering.
This is the default signal source for Analog Output 2 (Set by P01.04 Analog Chanel A11). The analog
output is scaled to P02.05 Nominal Flow Rate.

This parameter is normally set to AO 2.

P 14.05 Flow Rate Offset Default: 4.00 mA (Hidden)


Min: -200.00 mA Max: 200.00 mA

Normally Hidden.

This parameter selects the actual analog output when the control signal is zero.

This parameter is normally set to 4.00 mA.

P 14.06 Flow Rate Range Default: 20.00 mA (Hidden)


Min: 0.00 mA Max: 1000.00 mA

Normally Hidden.

This parameter selects the actual analog output when the control signal is maximum.

This parameter is normally set to 20.00 mA.

P 14.07 Belt Load Default: n/a (not used – Hidden)


Options: n/a (not used)
AO 1 thru AO 6

Normally Hidden.

This parameter selects the analog output channel used for the indicated signal.

Belt Load: The Belt Load value is the current weight of material on the belt per unit length (lbs/inch).
The analog output is scaled to the nominal belt load, which is calculated using P02.05 Nominal Flow
Rate and P02.06 Nominal Speed.

This parameter is normally set to n/a (not used).

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 99


©Schenck Process Group
P 14.08 Belt Load Offset Default: 4.00 mA (Hidden)
Min: -200.00 mA Max: 200.00 mA

Normally Hidden.

This parameter selects the actual analog output when the control signal is zero.

This parameter is normally set to 4.00 mA.

P 14.09 Belt Load Range Default: 20.00 mA (Hidden)


Min: 0.00 mA Max: 1000.00 mA

Normally Hidden.

This parameter selects the actual analog output when the control signal is maximum.

This parameter is normally set to 20.00 mA.

P 14.10 Speed Default: n/a (not used – Hidden)


Options: n/a (not used)
AO 1 thru AO 6

Normally Hidden.

This parameter selects the analog output channel used for the indicated signal.

Speed: The Speed value is the current belt speed. The analog output is scaled to P02.06 Nominal
Speed.

This parameter is normally set to n/a (not used).

P 14.11 Speed Offset Default: 4.00 mA (Hidden)


Min: -200.00 mA Max: 200.00 mA

Normally Hidden.

This parameter selects the actual analog output when the control signal is zero.

This parameter is normally set to 4.00 mA.

100 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 14.12 Speed Range Default: 20.00 mA (Hidden)
Min: 0.00 mA Max: 1000.00 mA

Normally Hidden.

This parameter selects the actual analog output when the control signal is maximum.

This parameter is normally set to 20.00 mA.

P 14.13 Deviation Default: n/a (not used – Hidden)


Options: n/a (not used)
AO 1 thru AO 6

Normally Hidden.

This parameter selects the analog output channel used for the indicated signal.

Deviation: The Setpoint value indicates the amount that the actual feedrate deviates from the
feedrate setpoint.

This parameter is normally set to n/a (not used).

P 14.14 Deviation Offset Default: 4.00 mA (Hidden)


Min: -200.00 mA Max: 200.00 mA

Normally Hidden.

See P14.15 Deviation Range.

This parameter is normally set to 4.00 mA.

P 14.15 Deviation Range Default: 20.00 mA (Hidden)


Min: 0.00 mA Max: 1000.00 mA

Normally Hidden.

The output signal is generated as follows:

Current = 10 mA + (P14.14 / 2) + (P11.16 – 11.15) X (Deviation / 100)

Note: Deviation can have either a positive or a negative value.

This parameter is normally set to 20.00 mA.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 101


©Schenck Process Group
nd
P 14.16 Actual Flow Rate (2 ) Default: n/a (not used)
Options: n/a (not used)
AO 1 thru AO 6

This parameter is used when a second analog output proportional to feedrate is required. A second
analog output card is required and is normally installed in position A10. In this case both parameter
nd
P01.03 Analog Channel A10 and P14.16 Actual Flow Rate (2 ) must be set to AO 3.

Actual Flow Rate: The Actual Flow Rate value is the feedrate that the feeder is currently delivering.
This is the default signal source for Analog Output 2 (Set by P01.04 Analog Chanel A11). The analog
output is scaled to P02.05 Nominal Flow Rate.

This parameter is normally set to n/a (not used).

102 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
9.2.15 Parameter Group 15 - Digital Inputs
The parameters in this group are used to associate various controller functions with specific digital
input channels and to associate events with those functions. Most of the functions specified in this
group are hard wired on the controller and cannot be changed.

P 15.01 DI: Acknowledge Events Default: n/a (not used – Hidden)


Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden.

This parameter specifies the digital input used to remotely acknowledge error conditions.

This function is not normally used and this parameter should be set to n/a (not used).

P 15.02 DI: VLG Mode Default: n/a (not used – Hidden)


Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden.

This parameter specifies the digital input used to indicate that the VMO is in local mode.

This function is not used and this parameter should always be set to n/a (not used).

P 15.03 Event: External Event 1 Default: IG (Hidden)


Event Group: SC Number: 05
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden.

This parameter specifies the event that is generated when the input specified in P15.04 DI External
Event 1 is active.

This function is not used and this parameter should be set to IG (Ignore).

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 103


©Schenck Process Group
P 15.04 DI: External Event 1 Default: n/a (not used – Hidden)
Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden.

This parameter specifies the digital input used to remotely generate External Event 1.

This function is not used and this parameter should be set to n/a (not used).

P 15.05 Event: NAMUR Error V103-DI 13 Default: IG (Hidden)


Event Group: WE Number: 02
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden.

This parameter specifies the event that is generated when the signal to the NAMUR device on DI 13
(NAMUR Belt Motion Monitor) is lost. This normally indicates damage to the wiring or the device.

Note: Loss of signal to the NAMUR Belt Motion Monitor will generate a BMM error in addition to a
NAMUR error.

This function is not used and this parameter should be set to IG (Ignore).

P 15.06 Event: NAMUR Error V103-DI 14 Default: IG (Hidden)


Event Group: WE Number: 03
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden.

This parameter specifies the event that is generated when the signal to the NAMUR device on DI 14
(NAMUR Tachometer) is lost. This normally indicates damage to the wiring or the device.

Note: Loss of signal to the NAMUR tachometer will generate a loss of tachometer error in addition to
a NAMUR error.

This function is not used and this parameter should be set to IG (Ignore).

104 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 15.07 DI: Reset Totalizer 1 Default: n/a (not used – Hidden)
Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden.

This parameter specifies the digital input used to remotely reset totalizer 1. The totalizer is reset on
the rising edge of the signal.

This function is not used and this parameter should be set to n/a (not used).

P 15.08 DI: Reset Totalizer 2 Default: n/a (not used – Hidden)


Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden.

This parameter specifies the digital input used to remotely reset totalizer 2. The totalizer is reset on
the rising edge of the signal.

This function is not used and this parameter should be set to n/a (not used).

P 15.09 DI: Discharge Pluggage Default: DI 5 - High (Hidden)


Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden.

This parameter specifies the digital input used for the discharge pluggage switch (LSFD). It is
internally programmed as a failsafe input. When the parameter is set to HIGH, open contact (low
signal) on the input will produce an event.

This parameter is normally set to DI 5 – High (terminal block X2-4) and is connected to wire 109.

P 15.10 Discharge Pluggage Delay Default: 2 s


Min: 0 s Max: 50 s

This parameter specifies the delay between the time that a discharge pluggage is detected and the
time that the discharge pluggage event is generated. It is the same as Setup 16 (Discharge
Pluggage Delay) on the 196NT.

This parameter is normally set to 2 seconds.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 105


©Schenck Process Group
P 15.11 Event: Discharge Pluggage Default: A
Event Group: WM Number: 07
Options: IG (Ignore)
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

This parameter specifies the event that is generated when a discharge pluggage is detected.

This parameter is normally set to A (Stop feeder). It can be set to IG (Ignore) to disable the discharge
pluggage event.

P 15.12 DI: Coal on Belt Switch Default: DI 7 - High


Options: n/a (not used)
DI 1 thru DI 12 – High/Low

This parameter specifies the digital input used for the Coal on belt switch (LSFB),

This parameter is normally set to DI 7 – High (terminal block X3-6) and is connected to wire 108 if a
coal on belt switch is installed on the feeder. It can be set to n/a (not use) to disable the coal on
belt input.

P 15.13 Loss of Flow Delay Default: 1s


Min: 0 s Max: 50 s

This parameter specifies the delay between the time that a loss of material on the belt is detected
(coal on belt switch is inactive) and the time that the Loss of material event is generated. It is the
same as Setup 39 (Loss of Flow Delay) on the 196NT.

This parameter is normally set to 1 second.

Note: The loss of flow event can be disabled by setting P15.14 Loss of material to IG (Ignore).

P 15.14 Event: Loss of Material Default: IG


Event Group: WM Number: 08
Options: IG (Ignore)
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

This parameter specifies the event that is generated when a loss of material is detected (coal on belt
switch is inactive).

This parameter is normally set to A (Stop feeder). It can be set to IG (Ignore) to disable the Loss of
material event.

106 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 15.15 Event: Coal on Belt Default: A
Event Group: WM Number: 12
Options: IG (Ignore)
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

This parameter specifies the event that is generated when the feeder attempts to run in Local mode
with material on the belt (coal on belt switch is active).

This parameter should always be set to A (Stop feeder).

P 15.16 Belt Paddle Feedback Permissive Default: Prop to Rate


Options: Prop to Rate
Low Lim. if Empty

This parameter specifies the source for the feedback signal when a loss of material (coal on belt
switch is inactive) on the belt is detected. If it is set to Prop to Rate, the feedback signal always
follows the actual feedrate value; if it is set to Low Lim if Empty, the feedback signal is set to zero
when a loss of material is detected (coal on belt switch is inactive). It is similar to Setup 24 – (Belt
Paddle Feedback Permissive) on the 196NT.

This parameter is normally set to Prop. To Rate.

Note: This parameter should always be set to Low Lim. If Empty when the DT-9 is used on a
volumetric feeder.

P 15.17 DI: Motor Feedback Default: DI 4 – High (Hidden)


Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden.

This parameter specifies the digital input used to indicate that the motor speed control has been
energized.

This parameter is normally set to DI 4 – High (terminal block X2-6) and is connected to wire 110.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 107


©Schenck Process Group
P 15.18 Event: Motor Starter Default: A (Hidden)
Event Group: WM Number: 09
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden.

This parameter specifies the type of event that is generated when the motor feedback signal (P15.17)
does not follow the motor start signal (P16.04 through P16.07).

This parameter should always be set to A (Stop Feeder)

P 15.19 DI: Coal Flow Monitor Default: DI 10 – High (Hidden)


Options:: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden.

This parameter specifies the digital input used to indicate that the coal flow monitor has detected a
loss of flow.

This parameter is normally set to DI 10 – High (terminal block X4-7) and is connected to wire 116.

P 15.20 Level/Temperature Sensor Delay Default: 100.0 lb


Min: 0 lb Max: 10000000 lb

This parameter specifies the delay between the time that a loss of material flow is indicated by the
coal flow monitor (P15.19) and the time that the Coal Flow Error event is generated. It is specified in
units of lbs so that a head seal can be maintained regardless of the feedrate. It is similar to Setup 18
(Level/Temperature Sensor Delay) on the 196NT.

This parameter is normally set to 100 lbs to provide a quick response without nuisance trips.

P 15.21 Event: Coal Flow Default: A


Event Group: WM Number: 11
Options: IG (Ignore)
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

This parameter specifies the type of event that is generated when a loss of material flow is detected.

This parameter should be set to A (Stop Feeder) when a coal flow monitor is installed and IG (ignore)
when one is not.

108 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 15.22 DI: Configuration Lock Default: DI 6 – High (Hidden)
Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden.

This parameter specifies the digital input used prevent the parameters from being changed.

This parameter is normally set to DI 6 – High (terminal block X2-2) and is connected to wire 117.

P 15.23 DI: Remote Control Default: DI 1 (not used)


Options: n/a (not used)
DI 1 thru DI 14 – High/Low

This parameter specifies the digital input used to force the feeder into Remote mode.

This parameter is normally set to DI 1 – High (terminal block X1-6) and is connected to wire 118.

Note: This input is only active when parameter P 03.12 Mode Select Enable/Disable is set to
Keyboard, Remote & Local.

P 15.24 DI: OFF/Maint CTRL Default: n/a (not used - Hidden)


Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden.

This parameter specifies the digital input used to force the feeder into Off mode.

This function is not used and this parameter should be set to n/a (not used).

P 15.25 DI: Local Start Default: DI 9 - High (Hidden)


Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden.

This parameter specifies the digital input used to force the feeder into Local mode.

This parameter is normally set to DI 9 – High (terminal block X3-2) and is connected to wire 119.

Note: This input is only active when parameter P 03.12 Mode Select Enable/Disable is set to
Keyboard & Local or Keyboard, Remote & Local.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 109


©Schenck Process Group
P 15.26 DI: Jog Forward Default: n/a (not used – Hidden)
Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden.

This parameter specifies the digital input used to jog the feeder forward.

This function is not used and this parameter should be set to n/a (not used).

P 15.27 DI: Jog Backwards Default: n/a (not used - Hidden)


Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden.

This parameter specifies the digital input used to jog the feeder in reverse.

This function is not used and this parameter should be set to n/a (not used).

P 15.28 Event: External Event 2 Default: IG (Hidden)


Event Group: SC Number: 06
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden.

This parameter specifies the event that is generated when the input specified in P15.29 DI External
Event 2 is active.

This function is not used and this parameter should be set to IG (Ignore).

P 15.29 DI: External Event 2 Default: n/a (not used – Hidden)


Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden.

This parameter specifies the digital input used to remotely generate External Event 2.

This function is not used and this parameter should be set to n/a (not used).

110 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 15.30 Event: External Event 3 Default: IG (Hidden)
Event Group: SC Number: 11
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden.

This parameter specifies the event that is generated when the input specified in P15.31 DI External
Event 3 is active.

This function is not used and this parameter should be set to IG (Ignore).

P 15.31 DI: External Event 3 Default: n/a (not used – Hidden)


Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden.

This parameter specifies the digital input used to remotely generate External Event 3.

This function is not used and this parameter should be set to n/a (not used).

P 15.32 Event: External Event 4 Default: IG (Hidden)


Event Group: SC Number: 12
Options: IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden.

This parameter specifies the event that is generated when the input specified in P15.33 DI External
Event 4 is active.

This function is not used and this parameter should be set to IG (Ignore).

P 15.33 DI: External Event 4 Default: n/a (not used – Hidden)


Options: n/a (not used)
DI 1 thru DI 14 – High/Low

Normally Hidden.

This parameter specifies the digital input used to remotely generate External Event 4.

This function is not used and this parameter should be set to n/a (not used).

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 111


©Schenck Process Group
9.2.16 Parameter Group 16 - Digital Outputs
The parameters in this group are used to associate various controller functions with specific digital
output channels. Most of the functions specified in this group are hard wired at assembly.

P 16.01 DO: Start Feeder Default: DO 11 – High (Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to start the feeder.

This parameter is normally set to DO 11 – High and is connected to wires 7 and 8.

P 16.02 DO: Feeder Running Default: n/a (not used - Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to indicate that the feeder is running.

This function is not used and this parameter should be set to n/a (Not used).

P 16.03 DO: Feeder Running 2 Default: n/a (not used - Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to indicate that the feeder is running. This output is a
duplicate of P 16.02 DO: Feeder Running.

This function is not used and this parameter should be set to n/a (not used).

P 16.04 DO: Feeder Run Forward Default: DO 7 High (Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to start the feeder running forward. This output is
similar to the K6 relay on the 196 NT.

This parameter must be set to DO 7 – High and is connected to wires 177-179.

112 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 16.05 DO: Feeder Run Forward 2 Default: n/a (not used - Hidden)
Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the second digital output used to start the feeder running forward. This
output is a duplicate of P 16.04 DO: Feeder Run Forward.

This function is not used and this parameter should be set to n/a (not used).

P 16.06 DO: Feeder Run Reverse Default: DO 2 - High (Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to start the feeder in reverse. This output is similar to
the K2 relay on the 196 NT.

This parameter must be set to DO 2 – High and is connected to wires 156-158.

P 16.07 DO: Feeder Run Reverse 2 Default: DO 3 - High (Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the second digital output used to start the feeder in reverse. This output is a
duplicate of P 16.06 DO: Feeder Run Reverse.

This parameter must be set to DO 3 – High and is connected to wires 159-161.

P 16.08 DO: Start Pre-feeder Default: n/a (not used - Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to start the pre-feeder.

This function is not used and this parameter should be set to n/a (not used).

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 113


©Schenck Process Group
P 16.09 DO: Alarm Default: DO 1 High (Hidden)
Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to annunciate and alarm condition
(Event type A - feeder Stopped). This output is similar to the K1 relay on the 196 NT.

This parameter must be set to DO 1 – High and is connected to wires 150-152.

Note: Set this parameter to DO 1 – Low to simulate the K1 failsafe function of the 196NT.

P 16.10 DO: Alarm 2 Default: n/a (not used - Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to annunciate and alarm condition
(Event type A - feeder Stopped). This output is a duplicate of P 16.09 DO: Alarm.

This function is not used and this parameter should be set to n/a (not used).

P 16.11 DO: Deviation Default: n/a (not used - Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to indicate that a deviation event is active.

This function is not used and this parameter should be set to n/a (not used).

P 16.12 DO: I-MIN Default: n/a (not used - Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to indicate that a low flow rate event is active.

This function is not used and this parameter should be set to n/a (not used).

114 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 16.13 DO: I-MAX Default: n/a (not used - Hidden)
Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to indicate that a high flow rate event is active.

This function is not used and this parameter should be set to n/a (not used).

P 16.14 DO: Q-MIN Default: n/a (not used - Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to indicate that a low belt load event is active.

This function is not used and this parameter should be set to n/a (not used).

P 16.15 DO: Q-MAX Default: n/a (not used - Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to indicate that a high belt load event is active.

This function is not used and this parameter should be set to n/a (not used).

P 16.16 DO: v-MIN Default: n/a (not used - Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to indicate that a low belt speed event is active.

This function is not used and this parameter should be set to n/a (not used).

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 115


©Schenck Process Group
P 16.17 DO: v-MAX Default: n/a (not used - Hidden)
Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to indicate that a high belt speed event is active.

This function is not used and this parameter should be set to n/a (not used).

P 16.18 DO: Volumetric Mode Default: DO 5 - High (Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to indicate that the feeder is in volumetric mode. This
output is similar to the K4 relay on the 196 NT.

This parameter must be set to DO 5 – High and is connected to wires 165-167.

P 16.19 DO: Volumetric Mode 2 Default: n/a (not used - Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to indicate that the feeder is in volumetric mode. This
output is a duplicate of P 16.18 DO: Volumetric Mode.

This function is not used and this parameter should be set to n/a (not used).

P 16.20 DO: VMO Mode Default: n/a (not used - Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to indicate that the feeder is in VMO Mode.

This function is not used and this parameter should be set to n/a (not used).

116 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 16.21 DO: WARNING Default: DO 8 - High (Hidden)
Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to annunciate a warning condition (Event type W1 or
W2). This output is similar to the K7 relay on the 196 NT.

This parameter must be set to DO 8 – High and is connected to wires 183-185.

Note: Set this parameter to DO 8 – Low to simulate the K7 failsafe function of the 196NT.

P 16.22 DO: WARNING 2 Default: n/a (not used - Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to annunciate a warning condition (Event type W1 or
W2). This output is a duplicate of P 16.22 DO: Warning.

This function is not used and this parameter should be set to n/a (not used).

P 16.23 DO: Feeding Default: DO 6 - High (Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to indicate that the belt drive motor is running and
there is material on the belt. This output is similar to the K5 relay on the 196 NT.

This parameter must be set to DO 6 – High and is connected to wires 171-173.

P 16.24 DO: Feeding 2 Default: n/a (not used - Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to indicate that the belt drive motor is running and
there is material on the belt. This output is a duplicate of P 16.23 DO: Feeding.

This function is not used and this parameter should be set to n/a (not used).

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 117


©Schenck Process Group
P 16.25 DO: Remote CTRL Default: DO 4 High (Hidden)
Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to indicate that the feeder is in remote mode. This
output is similar to the Kx relay on the 196 NT.

This parameter must be set to DO 4 – High and is connected to wires 162-164.

P 16.26 DO: Remote CTRL 2 Default: n/a (not used - Hidden)


Options: n/a (not used)
DO 1 thru DO 13 - High/Low

Normally Hidden.

This parameter specifies the digital output used to indicate that the feeder is in remote mode. This
output is a duplicate of P 16.25 DO: Remote CTRL.

This function is not used and this parameter should be set to n/a (not used).

118 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
9.2.17 Parameter Group 17 – Analog Calibration
The parameters in this group are used to trim the analog output values. They can be set manually
but they are normally set using he Analog Trim Function (see section 5.6)

P 17.01 Analog Input 1 Min Default: 4.00 mA


Min: 1.00 mA Max: 7.00 mA

See section 4.5, Analog Trim Function.

P 17.02 Analog Input 1 Max Default: 20.00 mA


Min: 17.00 mA Max: 23.00 mA

See section 4.5, Analog Trim Function.

P 17.03 Analog Input 2 Min Default: 4.00 mA


Min: 1.00 mA Max: 7.00 mA

See section 4.5, Analog Trim Function.

P 17.04 Analog Input 2 Max Default: 20.00 mA


Min: 17.00 mA Max: 23.00 mA

See section 4.5, Analog Trim Function.

P 17.05 Analog Input 3 Min Default: 4.00 mA


Min: 1.00 mA Max: 7.00 mA

See section 4.5, Analog Trim Function.

P 17.06 Analog Input 3 Max Default: 20.00 mA


Min: 17.00 mA Max: 23.00 mA

See section 4.5, Analog Trim Function.

P 17.07 Analog Input 4 Min Default: 4.00 mA


Min: 1.00 mA Max: 7.00 mA

See section 4.5, Analog Trim Function.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 119


©Schenck Process Group
P 17.08 Analog Input 4 Max Default: 20.00 mA
Min: 17.00 mA Max: 23.00 mA

See section 4.5, Analog Trim Function.

P 17.09 Analog Input 5 Min Default: 4.00 mA


Min: 1.00 mA Max: 7.00 mA

See section 4.5, Analog Trim Function.

P 17.10 Analog Input 5 Max Default: 20.00 mA


Min: 17.00 mA Max: 23.00 mA

See section 4.5, Analog Trim Function.

P 17.11 Analog Output 1 Min Default: 4.00 mA


Min: 1.00 mA Max: 7.00 mA

See section 4.5, Analog Trim Function.

P 17.12 Analog Output 1 Max Default: 20.00 mA


Min: 17.00 mA Max: 23.00 mA

See section 4.5, Analog Trim Function.

P 17.13 Analog Output 2 Min Default: 4.00 mA


Min: 1.00 mA Max: 7.00 mA

See section 4.5, Analog Trim Function.

P 17.14 Analog Output 2 Max Default: 20.00 mA


Min: 17.00 mA Max: 23.00 mA

See section 4.5, Analog Trim Function.

P 17.15 Analog Output 3 Min Default: 4.00 mA


Min: 1.00 mA Max: 7.00 mA

See section 4.5, Analog Trim Function.

120 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 17.16 Analog Output 3 Max Default: 20.00 mA
Min: 17.00 mA Max: 23.00 mA

See section 4.5, Analog Trim Function.

P 17.17 Analog Output 4 Min Default: 4.00 mA


Min: 1.00 mA Max: 7.00 mA

See section 4.5, Analog Trim Function.

P 17.18 Analog Output 4 Max Default: 20.00 mA


Min: 17.00 mA Max: 23.00 mA

See section 4.5, Analog Trim Function.

P 17.19 Analog Output 5 Min Default: 4.00 mA


Min: 1.00 mA Max: 7.00 mA

See section 4.5, Analog Trim Function.

P 17.20 Analog Output 5 Max Default: 20.00 mA


Min: 17.00 mA Max: 23.00 mA

See section 4.5, Analog Trim Function.

P 17.21 Analog Output 6 Min Default: 4.00 mA


Min: 1.00 mA Max: 7.00 mA

See section 4.5, Analog Trim Function.

P 17.22 Analog Output 6 Max Default: 20.00 mA


Min: 17.00 mA Max: 23.00 mA

See section 4.5, Analog Trim Function.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 121


©Schenck Process Group
9.2.18 Parameter Group 18 - 2-Sensor Slip
The parameters in this group control the DT-9 belt slip sensor system. This system is not currently
supported and is disabled and hidden by default.

P 18.01 2-Sensor Slip active Default: NO (Hidden)


Options: NO
YES

Normally Hidden.

This parameter is used to enable the DT-9 slip sensor system.

The slip sensor system is not currently supported on the VCU 20104. This parameter should always
be set to NO.

P 18.02 Source Sensor 1 Default: Speed (Hidden)


Options: n/a (not used)
DI 1 thru DI 12 – High/Low

Normally Hidden.

This parameter specifies the type of input used for the first of the two sensors used in slip detection.

The slip sensor system is not currently supported and this parameter should always be set to Speed.

P 18.03 DI: Sensor 1 Default: n/a (not used - Hidden)


Options: n/a (not used)
DI 1 thru DI 12 – High/Low

Normally Hidden.

This parameter specifies the digital input used for the first slip sensor. It is only active if P18.02
Source Sensor 1 is set to DI.

The slip sensor system is not currently supported and this parameter should always be set to n/a
(not used).

122 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 18.04 Char. Value Sensor 1 Default: 100.00 P/inch (Hidden)
Min: 0.01 P/inch Max: 1000000.00 P/inch (Hidden)

Normally Hidden.

This parameter specifies the number of pluses that the first slip sensor generates in one inch of
belt travel.

The slip sensor system is not currently supported and this parameter should always be set to
100 P/inch.

P 18.05 DI: Sensor 2 Default: n/a (not used - Hidden)


Options: n/a (not used)
DI 1 thru DI 12 – High/Low

Normally Hidden.

This parameter specifies the digital input used for the second slip sensor.

The slip sensor system is not currently supported and this parameter should always be set to n/a
(not used).

P 18.06 Char. Value Sensor 2 Default: 100.00 P/inch (Hidden)


Min: 0.01 P/inch Max: 1000000.00 P/inch (Hidden)

Normally Hidden.

This parameter specifies the number of pluses that the second slip sensor generates in one inch of
belt travel.

The slip sensor system is not currently supported and this parameter should always be set to
100.00 P/inch.

P 18.07 Slip Value 2 Default: 2.00 % LB (Hidden)


Min: 0.00 % LB Max: 10.00 % LB (Hidden)

Normally Hidden

This parameter specifies the minimum difference between the two sensors (in percent of total belt
length, LB) required to generate a belt slip event.

The slip sensor system is not currently supported and this parameter should always be set to
2.0% LB.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 123


©Schenck Process Group
P 18.08 Event: Slip 2 Default: IG (Hidden)
Event Group: WM Number: 05
Options: IG (Ignore)
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

Normally Hidden.

This parameter specifies the type of event that is generated when belt slippage is detected.

The slip sensor system is not currently supported and this parameter should always be set to IG.

P 18.09 DO: Slip 2 Default: n/a (not used - Hidden)


Options: n/a (not used)
DO 1 thru DO 14 - High/Low

Normally Hidden.

This parameter the digital output that is activate when a belt slippage event is generated.

The slip sensor system is not currently supported and this parameter should always be set to n/a
(not used).

124 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
9.2.19 Parameter Group 19 – Maintenance Interval
The parameters in this group allow an event to be generated to indicate that periodic maintenance is
required.

P 19.01 Maintenance Electrical Default: 3000 h


Min: 1 h Max: 10000 h

This parameter specifies the time intervals between maintenance events based on the total amount of
time the DT-9 is powered.

This parameter is normally set to 3000 hours.

P 19.02 Event: Maintenance Electrical Default: IG


Event Group: SC Number: 04
Options: IG (Ignore)
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

This parameter specifies the type of event that is generated when the time interval specified in
P19.01 Maintenance Elec. has expired.

This parameter is normally set to IG to disable the maintenance event.

P 19.03 Maintenance Feeder Run Default: 3000 h


Min: 1 h Max: 10000 h

This parameter specifies the time intervals between maintenance events based on the total amount of
time the belt drive motor is energized.

This parameter is normally set to 3000 hours.

P 19.04 Event: Maintenance Feeder Run Default: IG


Event Group: SC Number: 03
Options: IG (Ignore)
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)

This parameter specifies the type of event that is generated when the time interval specified in
P19.03 Maintenance Feeder Run. has expired.

This parameter is normally set to IG to disable the maintenance event.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 125


©Schenck Process Group
9.2.20 Parameter Group 20 - Reports
The parameters in this group are used to specify the time that material total data logging occurs.

P 20.01 Hourly Start Default: 0 min


Min: 0 min Max: 59 min

This parameter specifies the time that the hourly total is saved to the total data logging system. It is
the same as Setup 37 (Hourly total time) on the 196NT.

This parameter is set according to customer preference.

P 20.02 Daily Start Default: 0 min


Min: 0 min Max: 1493 min

This parameter specifies the time that the daily total is saved to the total data logging system. It is the
same as Setup 38 (Daily total time) on the 196NT.

This parameter is set according to customer preference.

126 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
9.2.21 Parameter Group 21 - Comm. EasyServe
The parameters in this group control serial communication between EasyServe and the DT-9.

Note: EasyServe is normally connected using Ethernet and these parameters are not used.

P 21.01 Own Address Default: 1 (Hidden)


Min: 1 Max: 11

Normally Hidden.

This parameter specifies the serial loop address of the DT-9. This address and baud rates (see
below) much match the address specified in EasyServe.

This parameter is normally set to 1.

Note: The station address is designed for systems with Service bus. If Service bus is not used, select
address 1.

P 21.02 Baud Rate Default: 38400 (Hidden)


Options: 38400

Normally Hidden.

This parameter specifies the baud rate used for serial communication with EasyServe.

This parameter can only be set to 38400.

P 21.03 Format Data Default: 8-N-1 (Hidden)


Options: 8-N-1

Normally Hidden.

This parameter specifies the communications protocol used for serial communication between
EasyServe and the DT-9.

This parameter can only be set to 8-N-1.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 127


©Schenck Process Group
9.2.22 Parameter Group 22 - Comm. Fieldbus
The parameters in this group are used to control the various types of fieldbus communications that
are supported by the DT-9. Contact Stock for a detailed description of Fieldbus communications.

Note: Fieldbus communications are disabled and hidden by default.

128 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
9.2.23 Parameter Group 23 - Ethernet
The parameters in this group control the DT-9 Ethernet ports.

P 23.01 IP Address Default: 192.168.240.1

This parameter specifies the DT-9 IP address.

This parameter should be set to the default value of 192.168.240.1 for normal communication with
EasyServe and the (optional) touch screen display.

P 23.02 Net Mask Default: 255.255.255.0

This parameter specifies the DT-9 subnet mask.

This parameter is normally set to 255.255.255.0.

P 23.03 Gateway Default: 0.0.0.0

This parameter specifies the network gate way used to connect the DT-9.

This parameter is normally set to 0.0.0.0.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 129


©Schenck Process Group
9.2.24 Parameter Group 24 - PLS Outputs
This parameter group is used to specify analog and digital output channels that are under Fieldbus
control. Contact Stock for a detailed description of Fieldbus communications.

Note: Fieldbus communications are disabled and hidden by default.

9.2.25 Parameter Group 25 – Fixed Mode Config.


This parameter group is used to specify fixed data points that are used with Fieldbus communication.
Contact Stock for a detailed description of Fieldbus communications.

Note: Fieldbus communications are disabled and hidden by default.

9.2.26 Parameter Group 26 – FCB Analog Output


This parameter group is used to associate Function Block analog outputs with physical I/O points.
Contact Stock for a detailed description of Function Control Blocks.

Note: Function Control Block parameters are disabled and hidden by default.

9.2.27 Parameter Group 27 – FCB Digital Output


This parameter group is used to associate Function Block digital outputs with physical I/O points.
Contact Stock for a detailed description of Function Control Blocks.

Note: Function Control Block parameters are disabled and hidden by default.

130 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
10 Event (Error) Messages
Event messages report abnormal states, e.g. errors or limit value excess.

Always correct the cause of a fault before acknowledging it. The feeder has the potential to cause
injuries or damage if this procedure is not followed.

There are four different event classes:

Event Class Code Display / Effect


All measuring and control operations are aborted.
Alarm A System goes to safe state. This type of event is the
same as a feeder trip on the 196NT.
The event is annunciated and remains active until it
has been acknowledged. Measuring and control
Warning 1 W1
tasks are not affected. This type of event is similar to
some type of alarms on the 196NT
The event is annunciated and remains active until
the cause has been corrected. It is not necessary to
Warning 2 W2 acknowledge this type of event. Measuring and
control tasks are not affected. This type of event is
similar to some type of alarms on the 196NT
Event is not annunciated. Measuring and control
Ignore IG
tasks are not affected.

Event are classified in the following groups with the priority shown.

Event Group Symbol


System message SY
Sequence monitoring SC
Electrical system WE
Mechanical system WM
Material flow MF
Interlocking IL
Controllers CO
Calibration CA
Maximum HI
Minimum LO

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 131


©Schenck Process Group
Note: In the following list, parameters related to the indicated event are shown in parenthesis.

Event Group: Calibration


CA-01 LC Input ( P 06.04 )
Normally disabled and hidden.

Load cell cable wrong.


Measuring amplifier A/D converter is in saturated state.
Supply voltage is below 19V.
Error must be available for minimum 3s.

Action:
• Check cabling.
• If cabling is OK, load cell amplifier could be defective.
• Check for either possibility. If scale cannot be restarted after remedy of fault, turn
device off and restart.
CA-02 Tacho Input ( P 06.03 )
Input frequency is zero or exceeds 3600 Hz.

Action:
• Insure that the motor is turning.
• Insure that parameter P 04.06 Speed Measurement is set to the correct input.
• Check the tachometer wiring.
• Check the tachometer signal using a frequency counter or oscilloscope.

Event Group: Controller


CO-01 Controller Limited ( P 06.13 )
Normally disabled and hidden.

Feed rate controller control magnitude has reached upper response threshold. After some
time, message HI-5 (Deviation) is additionally output.
1. Material flow missing or irregular.
2. External feed rate controller wrongly set.

Action:
• Check material discharge and control magnitude (service value Y). At nominal feed
rate, Y should be 10 to 14mA.
CO-05 Event Vol on Failure ( P 05.02 )
Normally disabled and hidden.

Indicates that the system is in volumetric mode due to failure in the weighing system.

Action:
• Check for load cell wiring errors or imbalanced load cell inputs.

132 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
Event Group: Electrical System
WE-01 Power Failure ( P 06.08 )
Normally disabled and hidden.

This event is generated when power is lost. If P06.08 Event: Power failure is set to A, the
feeder will be in OFF/Maint Mode when power is restored.
WE-02 Event: NAMUR Error V103-DI13 ( P 15.05 )
This event should only be enabled when a NAMUR sensor is connected to DI 13.

The connection to the sensor on DI 13 (X5-5 and X5-6) has been lost.

Action:
• Insure that a NAMUR device is connected to DI 13.
• Check the DI 13 wiring.
WE-03 Event: NAMUR Error V103-DI14 ( P 15.06 )
This event should only be enabled when a NAMUR sensor is connected to DI 14.

The connection to the sensor on DI 14 (X5-3 and X5-4)has been lost.

Action:
• Insure that a NAMUR device is connected to DI 14.
• Check the DI 14 wiring.
WE-08 Analog Input< Offset ( P 06.15 )
Normally disabled and hidden.

The signal available across an analog input is smaller than the set zero point elevation.
Action: Check analog input (Sig+ & Sig-) wiring.

Event Group: Interlock


IL-01 Run Disabled ( P 03.11 )
Normally set to W2.

When a touch screen HMI is used, parameter P03.10 Run Enable must be set to DI 8,
which is connected to the stop switch mounted under the HMI. This switch is used to stop
the feeder in the event that the HMI is disabled or disconnected. Parameter P03.11 is
normally set to W2 so that there is an indication on the display when the feeder is disabled.

Action:
• Check the position of the Run Enable switch. Check the wiring to the Run
Enable switch.

Note: The Run Enable switch is not normally used with the Stock 196NT display and in this
case P03.10 Run Enable must be set to n/a to allow motor operation.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 133


©Schenck Process Group
Event Group: Material Flow
MF-05 Moisture > MAX ( P 12.10 )
Normally disabled and hidden.

The value of the moisture input signal is greater then the maximum signal set by P12.08.
MF-14 Remote TCI too small ( P 02.15 )
The TCI is required to operate at a frequency greater then its limit. See the description of
P 02.14 Pulse Length Total for more information.

Action:
• Set P02.13 Totalizer Increment and/or P02.14 Remote Totalizer Pulse Width to a
smaller value.

Event Group: MAX


HI-01 LC Input > MAX ( P 06.06 )
Normally disabled and hidden.

Load cell load is higher than 110% of load cells rated capacities.
Full scale value:
125% with 2.85mV/V load cells
175% with 2mV/V load cells
HI-02 I > MAX ( P 09.04 )
Normally disabled and hidden.

Flow rate exceeds set maximum value.


HI-03 Load > MAX ( P 09.08 )
Normally disabled and hidden.

Belt load exceeds set maximum value.


HI-04 v > MAX ( P 09.12 )
Normally disabled and hidden.

Belt speed exceeds set MAX value.


HI-05 Deviation ( P 06.12 )
The difference between the actual feedrate and the feedrate demand setpoint has
exceeded the value specified in P06.10 “Threshold Deviation” for a time greater then the
limit specified by P06.09 “Time Deviation”.

Action:
• Check for loss or material on belt.

134 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
Event Group: Mechanic
WM-02 Event: Slip ( P 07.08 )
Normally disabled and hidden.

WM-05 Slip Error 2 ( P 18.08 )


Normally disabled and hidden.

The difference between the belt speed calculated using sensor 1 (P18.02) and sensor
2(P18.05) has exceeded the limit specified by P 18.07 Slip Value 2.
WM-06 Chain Motion Monitor ( P 13.06 )
Normally disabled and hidden.

The Chain Motion Monitor (CMM) pulse delay (P13.05) has been exceeded.
WM-07 Discharge Pluggage ( P 15.11 )
The discharge pluggage switch (LSFD) detected a build up of coal at the feeder discharge.
This is a fail safe input. This event is generated when the LSFD signal is lost.

Action:
• Insure that discharge is clear.
• Check LSFD wiring.
WM-08 Loss of Material ( P 15.14 )
The coal on belt switch (LSFB) has indicated a loss of material on the belt while running in
Remote.
WM-09 Motor Starter Error ( P 15.18 )
The motor starter of VFD has failed to start the feeder when instructed to by the controller.
WM-10 Belt Motion Error ( P 07.03 )
The Belt Motion Monitor (BMM) pulse delay (P07.02) has been exceeded.
WM-11 Coal Flow Error ( P 15.21 )
The (optional) coal flow monitor has indicated a loss of material in the downspout above
the feeder.
WM-12 Coal on Belt ( P 15.15 )
Coal was detected by the coal on belt switch (LSFB) when the feeder was running in local
or calibrate mode.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 135


©Schenck Process Group
Event Group: MIN
LO-01 LC Input < MIN ( P 06.05 )
Normally disabled and hidden.

Load cell load is smaller than 3% of load cell rated capacities.


LO-02 I < MIN ( P 09.02 )
Normally disabled and hidden.

Flow rate smaller than set minimum value.


LO-03 Load < MIN ( P 09.06 )
Normally disabled and hidden.

Belt load smaller than set minimum value.


LO-04 v < MIN ( P 09.10 )
Normally disabled and hidden.

Belt speed is smaller than set minimum value.

136 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
Event Group: Sequence Monitoring
SC-01 Setpoint Limited ( P 06.07 )
Normally disabled and hidden.

Depending on selected mode:


a) In gravimetric mode, setpoint is limited to nominal feed rate.
b) In volumetric mode, limitation starts from values exceeding 3 times the nominal value.
c) Emergency setpoint is active (P 06.18).
SC-02 Stand-By ( P 06.01)
Normally disabled and hidden.

Scale is in standby mode, i.e. setpoint is smaller than set standby limit (Parameter P06.03
"Standby Limit"). Material pre-feeder cuts off.
SC-03 Maint Feeder Run. ( P 19.04 )
Normally disabled.

Total of scale run times exceeds "Scale ON-Time".


After every time interval elapsed, a message is output. This message simply informs you
that service work is required.
SC-04 Maintenance Int. Elec ( P 19.02 )
Normally disabled.

Total of power-on time exceeds value of "Voltage On-Time" parameter.


After every time interval elapsed, a message is output. This message simply informs you
that service work is required.
SC-05 External Event 1 ( P 15.03 )
Normally disabled and hidden.

External event 1 (See 15.04) is enabled, and external event 1 input (See P15.03) is active.

SC-06 External Event 2 ( P 15.28 )


Normally disabled and hidden.

External event 2 (See 15.29) is enabled, and external event 2 input (See P15.28) is active.

SC-11 External Event 3 ( P 15.30 )


Normally disabled and hidden.

External event 3 (See 15.31) is enabled, and external event 3 input (See P15.30) is active.

SC-12 External Event 4 ( P 15.32 )


Normally disabled and hidden.

External event 4 (See 15.33) is enabled, and external event 4 input (See P15.32) is active.

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 137


©Schenck Process Group
Event Group: System Message
SY-01 Memory Error ( P 06.14 )
Error has been detected by cyclic check of program and parameter memories. If SY 01 is
output immediately after power-up.
Call the "Load Default Parameters" function. If this does not help, contact Stock service; in
most cases the controller is inoperable.
SY-07 Communication VHM ( P 01.01 )
Normally disabled.

Communications has been lost between the DT-9 controller and the touch screen display
for more then 10 seconds.

Action:
• Check cable connections.
SY-08 Cyclic Communication Host ( P 22.03 )
Normally disabled and hidden.

Interruption of serial communication exceeds the timeout period.

Action:
• Check cabling.
SY-12 Communications ARM7 ( P 01.02 )
This parameter selects the error condition generated when communications between the
ARM9 main processor and the ARM7 auxiliary processor are lost.

Action:
• Check cable connections between boards.
• Replace controller.

138 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
11 Appendix A
Appendix A includes a list of all DT-9 parameters divided into functional parameter blocks. Listed are
number, name and Sys ID. The Sys ID is the DT-9 internal ID number for the single parameters.

11.1 Parameter Overview


VCF20171-002 2669
01 - Hardware Modules
Number: Name Default Customer Sys ID
P 01.01 Event: Communication VHM IG 4218
P 01.02 Event: Communication ARM7 A 5752
P 01.03 Analog Channel A10 NO 5746
P 01.04 Analog Channel A11 NO 5747
P 01.05 Analog Channel A12 NO 5748
P 01.06 Analog Channel A13 NO
02 - Feeder Definition
Number: Name Default Customer Sys ID
P 02.01 Language ENGLISH 4224
P 02.02 Units English 4225
P 02.03 Scale Name DISOCONT TERSUS 6238
RetroFit
P 02.04 Password 10000 4292
P 02.05 Nominal Flow Rate Io 50000.0 lb/h 4226
P 02.06 Nominal Speed 3.0000 inch/s 4227
P 02.07 Display Formats SELECTABLE 4228
P 02.08 Flow Rate Units ----.- lb/h 4229
P 02.09 Counter 1 Unit ------- lb 4230
P 02.10 Counter 2 Unit ------- lb 4232
P 02.11 Counter 3 Unit ------- lb 4233
P 02.12 DO: Pulse Counter DO
P 02.13 Totalizer Increment 100.00 lb 4254
P 02.14 Remote Totalizer Pulse Width 0.100 s 4231
P 02.15 Event: Remote TCI too small W2 5745
P 02.16 Maintenance Speed 50 % 5670
P 02.17 DO: FRI Frequency DO
P 02.18 Remote FRI Frequency 10.000 Hz/(t/h) 5708
03 - Control Sources
Number: Name Default Customer Sys ID
P 03.01 Feeder Start DI 4241
P 03.02 Feedrate Setpoint AI 4242
P 03.03 Setpoint Range 20.00 mA 4243
P 03.04 Setpoint Offset 4.00 mA 4244
P 03.05 Maximum Feedrate 50000.0 lb/h 5686
P 03.06 Minimum Feedrate 5000.0 lb/h 5687
P 03.07 DI: Raise Setpoint n/a 5722
P 03.08 DI: Lower Setpoint n/a 5723
P 03.09 Raise/Lower Response Time 30 s 5709

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 139


©Schenck Process Group
P 03.10 Run Enable DI 4245
P 03.11 Event: Run Disabled W2 4246
P 03.12 Mode Select Enable/Disable Keyb.,Remote & 5707
Local
P 03.13 Speed Setpoint 900 rpm 5682
P 03.14 Run Mode Select Frate Setpoint 5684
04 - Rated Data
Number: Name Default Customer Sys ID
P 04.01 LC Characteristic Value 3.0000 mV/V 4257
P 04.02 LC Rated Cap. 100.000 lb 4258
P 04.03 Effective Platform Length 18.000 inch 4259
P 04.04 Lever Ratio 1.0000 4260
P 04.05 Angle 0.00 degree 4261
P 04.06 Speed Measurement DI
P 04.07 Belt load LC left LC 4263
P 04.08 Belt load LC right LC 4269
P 04.09 Tachometer: Pulses per Rev 60.0 P/rev 5690
P 04.10 Load cross section 157.00 inch2 5730
05 - Feeder Control
Number: Name Default Customer Sys ID
P 05.01 Volum on LC failure YES 4270
P 05.02 Event: Volum on failure IG 4271
P 05.03 Afterfl.Totalizer 0.0 s 4274
P 05.04 Zero Drop-Out Active NO 4679
P 05.05 Zero Drop-Out Limit 1.00 % Q 4680
06 - Feeder Monitoring
Number: Name Default Customer Sys ID
P 06.01 Event: Stand-By IG 4289
P 06.02 Stand-By Limit Value 5 % Io 4290
P 06.03 Event: Tachometer Input A 4291
P 06.04 Event: LC Input IG 4293
P 06.05 Event: LC Input < MIN IG 4294
P 06.06 Event: LC Input > MAX IG 4295
P 06.07 Event: Setpoint Limited IG 4296
P 06.08 Event: Power Failure IG 4297
P 06.09 Time Deviation 20.0 s 4298
P 06.10 Threshold Deviation 5.0 % 4299
P 06.11 Factor Deviation 1.0 4320
P 06.12 Event: Deviation W2 4300
P 06.13 Event: Controller Limited IG 4301
P 06.14 Event: Memory W1 4302
P 06.15 Event: Analog Input < Offset IG 5418
07 - Belt Monitoring
Number: Name Default Customer Sys ID
P 07.01 DI: Belt Motion Monitor n/a 5724
P 07.02 Belt Motion Monitor Delay 10 s 5698
P 07.03 Event: Belt Motion Monitor IG 5725
P 07.04 DI: Source Belt Sensor n/a

140 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 07.05 BIC Active NO
P 07.06 DI: BIC Freeze n/a
P 07.07 Slip Value 10.00% LB
P 07.08 Event: Slip IG
P 07.09 DO: Belt Slip n/a
08 - Display Filters
Number: Name Default Customer Sys ID
P 08.01 LC Filter 4.0 s 4334
P 08.02 I-Display 1.0 s 4328
P 08.03 I-Analog Output 1.0 s 4329
P 08.04 Feedback Filter Override 15.00 % 5702
Threshold
P 08.05 Belt Load 1.0 s 4331
P 08.06 Belt Speed 1.0 s 4332
P 08.07 Deviation 1.0 s 4333
09 - Limit Values
Number: Name Default Customer Sys ID
P 09.01 Value for I-Min 5.0 % Io 4337
P 09.02 Event: I-Min IG 4338
P 09.03 Value for I-Max 120.0 % Io 4339
P 09.04 Event: I-Max IG 4340
P 09.05 Value for Q-Min 60.0 % Q 4341
P 09.06 Event: Q-Min IG 4342
P 09.07 Value for Q-Max 120.0 % Q 4343
P 09.08 Event: Q-Max IG 4344
P 09.09 Value for V-Min 5.0 % V 4345
P 09.10 Event: V-Min IG 4346
P 09.11 Value for V-Max 120.0 % V 4347
P 09.12 Event: V-Max IG 4348
10 - Calibration Data
Number: Name Default Customer Sys ID
P 10.01 Calibration Probe Span 36.0000 inch 5693
P 10.02 Pulses per length 300.00 P/inch 4256
P 10.03 Range Correction TW 1.0000 5731
P 10.04 Range Correction TC 1.0000 5732
P 10.05 Range Correction TM 1.0000 5733
P 10.06 Belt Circuit Time 60.0 s 4353
P 10.07 Simulation Travel (Belt Rev.) 2.0 5703
P 10.08 Calibration Weight 70.000 lb 4354
P 10.09 Test Chain Weight 4.3000 lb/inch 5715
P 10.10 Basic Tare 0.00 lb/inch 4355
P 10.11 Belt Circuit No. 1000000.00 P/B 4357
11 - Rate controller
Number: Name Default Customer Sys ID
P 11.01 P-Component KP 0.05000 mA/% 4369
P 11.02 I-Component TN 1.0 s 4370
P 11.03 Motor Speed Control Output AO 4400
P 11.04 Lower Limit 4.00 mA 4371

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 141


©Schenck Process Group
P 11.05 Upper Limit 20.00 mA 4372
P 11.06 Controller Magnitude Offset 4.00 mA 4373
P 11.07 Position at STOP Lower Limit 4374
P 11.08 KP speed controller 0.07000 mA/% 5734
P 11.09 VAP Active NO 4480
P 11.10 Platform Dis.Length 0.00 % LB 4482
12 - Moisture
Number: Name Default Customer Sys ID
P 12.01 Moisture Active NO 5386
P 12.02 Moisture Select n/a 5399
P 12.03 AI: Moisture Measurement n/a 5387
P 12.04 Nominal Moisture 10.00 % 5388
P 12.05 Moisture Offset 4.00 mA 5389
P 12.06 Moisture Range 20.00 mA 5390
P 12.07 DO: Moisture active n/a 5400
P 12.08 Moisture MAX 20.00 % 5391
P 12.09 DO: Moisture MAX n/a 5392
P 12.10 Event: Moisture MAX W1 5393
P 12.11 AO: Flow Rate corrected n/a 5394
P 12.12 AO: Flow Rate Offset 4.00 mA 5395
P 12.13 AO: Flow Rate Range 20.00 mA 5396
P 12.14 Pulse Counter corrected NO 5397
13 - Cleanout Control
Number: Name Default Customer Sys ID
P 13.01 DO: Cleanout Timer DO 10 4277
P 13.02 Cleanout ON Time 1.00 h 4278
P 13.03 Cleanout OFF Time 1.00 h 4279
P 13.04 DI: Chain Motion Monitor n/a 4404
P 13.05 Chain Motion Delay 20 s 4405
P 13.06 Event: Chain Motion Monitor IG 4406
14 - Analog Outputs
Number: Name Default Customer Sys ID
P 14.01 Setpoint n/a 4385
P 14.02 Setpoint Offset 4.00 mA 4386
P 14.03 Setpoint Range 20.00 mA 4387
P 14.04 Actual Flow Rate AO 2 4388
P 14.05 Flow Rate Offset 4.00 mA 4389
P 14.06 Flow Rate Range 20.00 mA 4390
P 14.07 Belt Load n/a 4391
P 14.08 Belt Load Offset 4.00 mA 4392
P 14.09 Belt Load Range 20.00 mA 4393
P 14.10 Speed n/a 4394
P 14.11 Speed Offset 4.00 mA 4395
P 14.12 Speed Range 20.00 mA 4396
P 14.13 Deviation n/a 4397
P 14.14 Deviation Offset 4.00 mA 4398
P 14.15 Deviation Range 20.00 mA 4399

142 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 14.16 AO: Actual Flow Rate 2 n/a 4306
15 - Digital Inputs
Number: Name Default Customer Sys ID
P 15.01 DI: Acknowledge Events n/a 4419
P 15.02 DI: VLG Mode n/a
P 15.03 Event: External Event 1 IG 4417
P 15.04 DI: External Event 1 n/a 4418
P 15.05 Event: NAMUR Error V103-D13 IG
P 15.06 Event: NAMUR Error V103-D14 IG
P 15.07 DI: Reset Totalizer 1 n/a 5414
P 15.08 DI: Reset Totalizer 2 n/a 5415
P 15.09 DI: Discharge Pluggage DI 5 5716
P 15.10 Discharge Pluggage Delay 2s 5697
P 15.11 Event: Discharge Pluggage A 5717
P 15.12 DI: Coal on belt switch DI 7 5718
P 15.13 Loss of Flow Trip Delay 1s 5704
P 15.14 Event: Loss of material IG 5719
P 15.15 Event: Coal on Belt A 5754
P 15.16 Belt Paddle Feedback prop to Rate 5705
Permissive
P 15.17 DI: Motor feedback DI 4 5720
P 15.18 Event: Motor Start A 5721
P 15.19 DI: Coal Flow Monitor DI 10 5726
P 15.20 Level/Temperature 100.0000 lb 5699
Sensor Delay
P 15.21 Event: Coal Flow A 5727
P 15.22 DI: Configuration Lock DI 6 5728
P 15.23 DI: Remote CTRL DI 1 5735
P 15.24 DI: OFF/Maint CTRL n/a 5736
P 15.25 DI: Local Start DI 9 5737
P 15.26 DI: Jog forward n/a 5738
P 15.27 DI: Jog backward n/a 5739
P 15.28 Event: External Event 2 IG 4430
P 15.29 DI: External Event 2 n/a 4431
P 15.30 Event: External Event 3 IG 4730
P 15.31 DI: External Event 3 n/a 4731
P 15.32 Event: External Event 4 IG 4732
P 15.33 DI: External Event 4 n/a 4733
16 - Digital Outputs
Number: Name Default Customer Sys ID
P 16.01 DO: Start feeder DO 11 4433
P 16.02 DO: Feeder running n/a 4434
P 16.03 DO: Feeder running 2 n/a 5671
P 16.04 DO: Feeder Run Forward DO 7 5740
P 16.05 DO: Feeder Run Forward 2 n/a 5672
P 16.06 DO: Feeder Run Reverse DO 2 5741
P 16.07 DO: Feeder Run Reverse 2 DO 3 5673
P 16.08 DO: Start Prefeeder n/a 4435

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 143


©Schenck Process Group
P 16.09 DO: ALARM DO 1 4436
P 16.10 DO: ALARM 2 n/a 5674
P 16.11 DO: Deviation n/a 4437
P 16.12 DO: I-MIN n/a 4438
P 16.13 DO: I-MAX n/a 4439
P 16.14 DO: Q-MIN n/a 4440
P 16.15 DO: Q-MAX n/a 4441
P 16.16 DO: v-MIN n/a 4442
P 16.17 DO: v-MAX n/a 4443
P 16.18 DO: Volumetric Mode DO 5 4444
P 16.19 DO: Volumetric Mode 2 n/a 5675
P 16.20 DO: VMO Mode n/a
P 16.21 DO: WARNING DO 8 4759
P 16.22 DO: WARNING 2 n/a 5676
P 16.23 DO: Feeding DO 6 5742
P 16.24 DO: Feeding 2 n/a 5677
P 16.25 DO: Remote CTRL DO 4 5750
P 16.26 DO: Remote CTRL 2 n/a 5678
17 - Analog Calibration
Number: Name Default Customer Sys ID
P 17.01 Analog Input 1 Min 4.00 mA 5755
P 17.02 Analog Input 1 Max 20.00 mA 5756
P 17.03 Analog Input 2 Min 4.00 mA 5757
P 17.04 Analog Input 2 Max 20.00 mA 5758
P 17.05 Analog Input 3 Min 4.00 mA 5759
P 17.06 Analog Input 3 Max 20.00 mA 5760
P 17.07 Analog Input 4 Min 4.00 mA
P 17.08 Analog Input 4 Max 20.00 mA
P 17.09 Analog Input 5 Min 4.00 mA
P 17.10 Analog Input 5 Max 20.00 mA
P 17.11 Analog Output 1 Min 4.00 mA 5765
P 17.12 Analog Output 1 Max 20.00 mA 5766
P 17.13 Analog Output 2 Min 4.00 mA 5767
P 17.14 Analog Output 2 Max 20.00 mA 5768
P 17.15 Analog Output 3 Min 4.00 mA 5769
P 17.16 Analog Output 3 Max 20.00 mA 5770
P 17.17 Analog Output 4 Min 4.00 mA
P 17.18 Analog Output 4 Max 20.00 mA
P 17.19 Analog Output 5 Min 4.00 mA
P 17.20 Analog Output 5 Max 20.00 mA
P 17.21 Analog Output 6 Min 4.00 mA
P 17.22 Analog Output 6 Max 20.00 mA
18 - 2-Sensor Slip
Number: Name Default Customer Sys ID
P 18.01 2-Sensor Slip active NO 5433
P 18.02 Source Sensor 1 Speed 5434
P 18.03 DI: Sensor 1 n/a 5435

144 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
P 18.04 Characteristic Value Sensor 1 100.00 P/inch 5436
P 18.05 DI: Sensor 2 n/a 5437
P 18.06 Characteristic Value Sensor 2 100.00 P/inch 5438
P 18.07 Slip Value 2 2.00 % LB 5439
P 18.08 Event: Slip 2 IG 5440
P 18.09 DO: Slip 2 n/a 5443
19 - Maintenance Interval
Number: Name Default Customer Sys ID
P 19.01 Maintenance Electric 3000 h 4465
P 19.02 Event: Maintenance Electric IG 4466
P 19.03 Maintenance Feeder Run 3000 h 4467
P 19.04 Event: Maintenance Feeder IG 4468
Run
20 - Reports
Number: Name Default Customer Sys ID
P 20.01 Hourly Total Time 0 min 5743
P 20.02 Daily Total Time 0 min 5744
21 - Communication EasyServe
Number: Name Default Customer Sys ID
P 21.01 Own Address 1 4520
P 21.02 Baud Rate 38400 4521
P 21.03 Format Data 8-N-1 6189
22 - Communication Fieldbus
Number: Name Default Customer Sys ID
P 22.01 Protocol Type NO 4528
P 22.02 Timeout Host 5s 4529
P 22.03 Event: Cyclic Communication A 4530
Host
P 22.04 Modbus-Version compatible Stock 5729
P 22.05 Word Sequence I:std/L:std 6246
P 22.06 Byte Sequence High - Low 6245
P 22.07 Configuration FIXED_COMP_8_16 4661
P 22.08 Address 1 4531
P 22.09 Resolution 4096 4533
P 22.10 Baud rate 19200 4535
P 22.11 Data Format 8-O-1 4656
P 22.12 Physics RS232 6186
P 22.13 Address 16 4539
P 22.14 FLOAT-Format IEEE 4540
P 22.15 Address 63 4541
P 22.16 Baud rate 125K 4542
P 22.17 Parameter NO 4658
P 22.18 Preset Count 2 4734
P 22.19 READ_ID Count 6 4659

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 145


©Schenck Process Group
23 - Ethernet
Number: Name Default Customer Sys ID
P 23.01 IP Address 192.168.240.1 6235
P 23.02 Net Mask 255.255.255.0 6236
P 23.03 Gateway 0.0.0.0 6237
24 - PLS Outputs
Number: Name Default Customer Sys ID
P 24.01 DO: PLS Binary OUT 1 n/a 4662
P 24.02 DO: PLS Binary OUT 2 n/a 4663
P 24.03 DO: PLS Binary OUT 3 n/a 4664
P 24.04 DO: PLS Binary OUT 4 n/a 4665
P 24.05 DO: PLS Binary OUT 5 n/a 4666
P 24.06 DO: PLS Binary OUT 6 n/a 4667
P 24.07 DO: PLS Binary OUT 7 n/a 4668
P 24.08 DO: PLS Binary OUT 8 n/a 4669
P 24.09 AO: PLS Analog OUT 1 n/a 4670
P 24.10 AO: PLS Analog OUT 2 n/a 4671
25 - Fixed mode configuration
Number: Name Default Customer Sys ID
P 25.01 ID Preset Value 1 320 6247
P 25.02 ID Preset Value 2 352 6248
P 25.03 ID Preset Value 3 384 6249
P 25.04 ID Preset Value 4 592 6250
P 25.05 ID Preset Value 5 0 6251
P 25.06 ID Preset Value 6 0 6252
P 25.07 ID Preset Value 7 0 6253
P 25.08 ID Preset Value 8 0 6254
P 25.09 ID Read Value 1 752 6256
P 25.10 ID Read Value 2 816 6257
P 25.11 ID Read Value 3 1552 6258
P 25.12 ID Read Value 4 1872 6259
P 25.13 ID Read Value 5 1894 6260
P 25.14 ID Read Value 6 2230 6261
P 25.15 ID Read Value 7 2232 6262
P 25.16 ID Read Value 8 2234 6263
P 25.17 ID Read Value 9 0 6264
P 25.18 ID Read Value 10 0 6265
P 25.19 ID Read Value 11 0 6266
P 25.20 ID Read Value 12 0 6267
P 25.21 ID Read Value 13 0 6268
P 25.22 ID Read Value 14 0 6269
P 25.23 ID Read Value 15 0 6270
P 25.24 ID Read Value 16 0 6271

146 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
26 - FCB analog output
Number: Name Default Customer Sys ID
P 26.01 FCB_AOUT 1 n/a 20481
P 26.02 Offset FCB_AOUT 1 4.00 mA 6272
P 26.03 Range FCB_AOUT 1 20.00 mA 6273
P 26.04 Reference FCB_AOUT 1 1000.00 6274
P 26.05 FCB_AOUT 2 n/a 20482
P 26.06 Offset FCB_AOUT 2 4.00 mA 6275
P 26.07 Range FCB_AOUT 2 20.00 mA 6276
P 26.08 Reference FCB_AOUT 2 1000.00 6277
P 26.09 FCB_AOUT 3 n/a 20483
P 26.10 Offset FCB_AOUT 3 4.00 mA 6278
P 26.11 Range FCB_AOUT 3 20.00 mA 6279
P 26.12 Reference FCB_AOUT 3 10000.00 6280
P 26.13 FCB_AOUT 4 n/a 20484
P 26.14 Offset FCB_AOUT 4 4.00 mA 6281
P 26.15 Range FCB_AOUT 4 20.00 mA 6282
P 26.16 Reference FCB_AOUT 4 1000.00 6283
P 26.17 FCB_AOUT 5 n/a 20485
P 26.18 Offset FCB_AOUT 5 4.00 mA 6284
P 26.19 Range FCB_AOUT 5 20.00 mA 6285
P 26.20 Reference FCB_AOUT 5 1000.00 6286
27 - FCB digital output
Number: Name Default Customer Sys ID
P 27.01 FCB_DOUT 1 n/a 20529
P 27.02 FCB_DOUT 2 n/a 20530
P 27.03 FCB_DOUT 3 n/a 20531
P 27.04 FCB_DOUT 4 n/a 20532
P 27.05 FCB_DOUT 5 n/a 20533
P 27.06 FCB_DOUT 6 n/a 20534
P 27.07 FCB_DOUT 7 n/a 20535
P 27.08 FCB_DOUT 8 n/a 20536
P 27.09 FCB_DOUT 9 n/a 20537
P 27.10 FCB_DOUT 10 n/a 20538
P 27.11 FCB_DOUT 11 n/a 20539
P 27.12 FCB_DOUT 12 n/a 20540
P 27.13 FCB_DOUT 13 n/a 20541
P 27.14 FCB_DOUT 14 n/a 20542
P 27.15 FCB_DOUT 15 n/a 20543
P 27.16 FCB_DOUT 16 n/a 20544
P 27.17 FCB_DOUT 17 n/a 20545
P 27.18 FCB_DOUT 18 n/a 20546
P 27.19 FCB_DOUT 19 n/a 20547
P 27.20 FCB_DOUT 20 n/a 20548

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 147


©Schenck Process Group
148 DISOCONT® Tersus (DT-9) Configuration and Operations Manual
©Schenck Process Group
12 Appendix B
Appendix B describes the default I/O points.

12.1 Default Digital Inputs


Note: The default parameter must be set to n/a if the digital input is reallocated.

Input Terminal Wire Default Parameter Comments:


Number Block Number
DI 1 X1-6 118 P15.23 DI: Remote CTRL Not normally used.
P03.12 must be set to
Keyboard Only or
Keyboard & Local if this
point is reallocated.
DI 2 X1-4 112 P03.01 DI: Feeder Start Start contact from
customer DCS
DI 3 X1-2 113 P03.07 DI: Raise Setpoint Not Normally used.
Must be enabled when
P03.02 Feedrate
Setpoint is set to R-L.
DI 4 X2-6 110 P15.17 DI: Motor Feedback Running contact from
motor speed control
DI 5 X2-4 109 P15.09DI: Discharge Limit Switch Feeder
Pluggage Discharge (LSFD)
DI 6 X2-2 117 P15.22 DI: Configuration Keyboard lock
Lock
DI 7 X3-6 108 P15.12 DI: Coal on Belt Limit Switch Feeder
Switch Belt (LSFB)
DI 8 X3-4 111 P03.10 DI: Run enabled Must be enabled when
(optional) touch screen
HMI is used.
DI 9 X3-2 119 P15.25 DI: Local Start Not normally used.
P03.12 must be set to
Keyboard Only if this
point is reallocated.
DI 10 X4-7 116 P15.19 DI: Coal Flow Monitor Set P15.21 Event: Coal
Flow to A, W1 or W2 to
enable the coal flow
monitor or IG to disable
it.
DI 11 X4-5 114 P03.08 DI: Lower Setpoint Not Normally used.
Must be enabled when
P03.02 Feedrate
Setpoint is set to R-L.
DI 12 X4-2 115 P07.01 DI: Belt Motion Set P07.03 Event: Belt
Monitor Motion Monitor to A,
W1 or W2 to enable the
belt motion monitor or
IG to disable it.
DI 13 X5-5 n/a P07.01 DI: Belt Motion NAMUR BMM input
X5-6 Monitor

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 149


©Schenck Process Group
DI 14 X5-3 n/a P04.06 Speed Measurement NAMUR Tachometer
X5-4 input
DI 15 X5-1 145, 146 P04.06 Speed Measurement Can only be used for
X5-2 tachometer input.

12.2 Default Digital Outputs


Note: The default parameter must be set to n/a if the digital output is reallocated.

Each output is a single form C contact (NO, C, NC).

Output Terminal Wire Default Parameter Comments:


Number Block Number
DO 1 X10-1 thru 150-152 P16.09 DO: Alarm Feeder has tripped.
X10-3
DO 2 X10-4 thru 156-158 P16.06 DO: Feeder Run
X10-6 Reverse
DO 3 X11-1 thru 159-161 P16.07 DO: Feeder Run
X11-3 Reverse (2)
DO 4 X11-4 thru 162-164 P16.25 DO: Remote CTRL Feeder is ready for
X11-6 normal (remote)
operation.
DO 5 X13-1 thru 165-167 P16.18 DO: Volumetric Weigh system error.
X13-3 Feeding in volumetric
mode.
DO 6 X13-4 thru 171-173 P16.23 DO: Feeding Running in Remote with
X13-6 coal on the belt.
DO 7 X14-1 thru 177-179 P16.04 DO: Feeder Run
X14-3 Forward
DO 8 X14-4 thru 180-182 P16.21 DO: Warning Minor error condition.
X14-6
DO 9 X15-1 thru 194-196 n/a Spare Contact
X15-3
DO 10 X15-4 thru 197-198 P13.01 DO: Cleanout Timer
X15-6
DO 11 X16-1 7, 8 P16.01 DO: Start Feeder
X16-2
DO 12 X16-3 thru 186-189 P02.12 DO: Pulse Counter Pulsed based on
X16-6 amount of coal
delivered.
DO 13 X6-1 134, 135 P02.17 DO: FRI Frequency Frequency signal
X6-2 proportional to feedrate.

150 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
12.3 Default Analog I/O
Output Terminal Wire Default Parameter Comments:
Number Block Numbers
AI 1 X6-3 Sig +, Sig- P03.02 Feedrate Setpoint Customer Demand
X6-4 Signal
AO 1 X6-8 142-144 P11.03 AO: Motor Speed
X6-9 Control
AO 2 X6-7 139-141 P14.04 AO: Actual Flow Rate Customer Feedback
X6-8 Signal
A 10 X12-1 n/a P01.03 Analog Channel A 10 Not used
X12-2
A 11 X12-3 n/a P01.04 Analog Channel A 11 Not used
X12-4
A 12 X12-5 n/a P01.05 Analog Channel A 12 Not used
X12-6
A 13 X12-7 n/a P01.06 Analog Channel A 13 Not used
X12-8

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 151


©Schenck Process Group
152 DISOCONT® Tersus (DT-9) Configuration and Operations Manual
©Schenck Process Group
13 Appendix C
Appendix C lists the data addresses available with the trending display.

13.1 Trending Data


Data Data Value Comments:
Address
1872 Feedrate lb/h
1874 Totalizer 1 lb
1876 Totalizer 2 lb
1878 Totalizer 3 lb
1880 Belt Load lb/f
1884 Belt Speed f/s
1894 Setpoint lb/h
1904 Deviation %
1906 Moisture %
1908 Corrected Feedrate lb/h
1910 Totalizer 1 corr. lb
1912 Totalizer 2 corr. lb
1914 Totalizer 3 corr. lb
1920 Analog Output 1 Raw mA
1938 Belt Slip %
1942 Relative Feedrate %
1944 Relative Belt Load %
1946 External Setpoint lb/h
1950 Tachometer: Hz
1952 Utilize LC 1 %
1954 Loadcell VAP mV/V
1956 Loadcell BIC mV/V
1958 Loadcell mV/V
1960 Controller Magnitude mA
1996 Nominal Belt Load lb/f
2008 Actual Tare lb/f
2042 Setpoint %
2078 Corr. Rel. Feedrate %
2082 2-Sensor Slip %
2212 Analog Output 2 Raw mA
2214 Analog Input 1 Raw mA
2224 Loadcell 1 mV/V
2226 Loadcell 2 mV/V
2228 Utilize LC 2 %
2230 Gravimetric Total lb
2232 Volumetric Total lb
2234 Material Total lb
2236 Rate lb/h
2238 Analog Input 2 Raw mA
2240 Analog Input 3 Raw mA

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 153


©Schenck Process Group
2242 Analog Input 4 Raw mA
2244 Analog Input 5 Raw mA
2246 Analog Input 1 mA
2248 Analog Input 2 mA
2250 Analog Input 3 mA
2252 Analog Input 4 mA
2254 Analog Input 5 mA
2256 Analog Output 3 Raw mA
2258 Analog Output 4 Raw mA
2260 Analog Output 5 Raw mA
2262 Analog Output 6 Raw mA
2264 Analog Output 1 mA
2266 Analog Output 2 mA
2268 Analog Output 3 mA
2270 Analog Output 4 mA
2272 Analog Output 5 mA
2274 Analog Output 6 mA
2276 Speed rpm
2278 Belt Speed inch/s
2280 Nominal Belt Load lb/inch
2282 Actual Tare lb/inch
2284 Belt Load lb/inch
2286 Speed Setpoint rpm
2288 FRI output Hz
2290 Nominal Density lb/ft3
2292 Density lb/ft3
2294 Gravimetric Total corrected lb
2296 Volumetric Total corr. Lb
2298 Material Total corr. Lb
2300 Belt Load (average) lb/inch
2310 Belt Motion Counter s
2312 Digital Mode output Hz
2316 Belt Speed %

154 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group
196NT Display, 37 Expert Mode, 44, 51
A/Alarm (Definition), 52, 131 FB (Definition), 52
About this Manual, v Feedrate Control, 11
AI (Definition), 52 Gravimetric Mode, 12
Analog I/O Points, 27, 151 Hidden Parameters, 51
Analog Trim, 33 HMI – Calibration, 35
Analog Trim, 27 HMI - Configuration, 29
AO (Definition), 52 HMI - Data Log Values, 33
Appendix A, 139 HMI – Date and Time, 35
Appendix B, 149 HMI - Display Functions, 31
Appendix C, 153 HMI - Event Log Values, 33
Basic (CAL 1), 20 HMI - Home Screen, 31
Belt Load, 10 HMI – Load Factory Defaults, 35
Belt Load, Nominal, 26, 59 HMI - Login, 29
Belt Speed, 11 HMI - Operation using the Touch Screen HMI, 29
Calibration, 17 HMI - Parameter Log Values, 33
Calibration probe location, 20, 22 HMI - Parameter Setup, 33
Calibration Weight Test, 49 HMI - Setup Screen, 32
Chain Test, 49 HMI – Simulation Mode, 35
Commonly Changed Parameters, 15 HMI - Trend Screen, 32
Default Analog I/O, 151 HMI - Trim Analog I/O, 33
Default Digital Inputs, 149 HMI – Typical Operating Procedures, 35
Default Digital Outputs, 150 HMI - Values Screen, 32
Default Parameters, 35, 43, 51 HMI Configuration - Calibration Screen, 31
Definitions, 9 HMI Configuration - Communication Screen, 30
DI (Definition), 52 HMI Configuration - Configuration Screen, 30
Digital Inputs, 149 HMI Configuration - Display Settings Screen, 30
Digital Outputs, 150 HMI Configuration – Exiting Configuration, 31
DISOCONT Tersus/DT-9?, 9 HMI Configuration - Feeder Screen, 30
DO (Definition), 52 HMI Configuration - Network Screen, 30
DT-9 Parameter List, 55 HMI Display Functions, 31
EasyServe, 39 I (Definition), 10, 52
EasyServe – Calibration, 45 IG/Ignore (Definition), 52, 131
EasyServe – Connection (WARNING), 40 LB: Pulses per Belt, 25
EasyServe – Events, 45 LC (Definition), 52
EasyServe – Expert Mode, 44, 51 Load Default Parameters, 35, 43
EasyServe – Hidden Parameters, 44 Local Mode, 12
EasyServe – Installation, 39 LS (Definition), 52
EasyServe – IP Address, 40 Material Test, 50
EasyServe - Load Default Parameters, 43 Measuring Principle, 10
EasyServe – Network Connection, 40 Modes, 12
EasyServe – Operating the Feeder, 44 Nominal Belt Load, 26, 59
EasyServe – Options, 47 OFF/Maintenance Mode, 12
EasyServe – PAR files, 42 OP (Definition), 52
EasyServe – Parameter Attributes, 44 Operation using EasyServe, 39
EasyServe – Parameter files, 42 Operation using the 196NT Display, 37
EasyServe – Parameters, 42 Operation using the Touch Screen HMI, 29
EasyServe – Print Parameters, 44 Overview, 9
EasyServe – Registration/Access to Parameters, 42 P (Definition), 10
EasyServe – Scale Operation Screens, 44 Parameter Attributes, 51
EasyServe – Service Values, 45 Parameter Attributes, 44
EasyServe – Setting Time, 47 Parameter Group 01 - Hardware Modules, 55
EasyServe – System Requirements, 39 Parameter Group 02 - Feeder Definitions, 58
EasyServe – Trends, 46 Parameter Group 03 - Control Sources, 64
Electrostatic Sensitive Devices, v Parameter Group 04 - Feeder Rated Data, 68
Error Messages, 131 Parameter Group 05 - Feeder Control, 71
Error Types, 131 Parameter Group 06 - Feeder Monitoring, 73
Event (Error) Messages, 131 Parameter Group 07 - Belt Monitoring, 78
Event Classes, 131 Parameter Group 08 - Display Filters, 81
Event Groups, 131 Parameter Group 09 - Limit Values, 83
Event Types, 131 Parameter Group 10 - Calibration Data, 87

DISOCONT® Tersus (DT-9) Configuration and Operations Manual 155


©Schenck Process Group
Parameter Group 11 – Rate Controller, 90 Read Only Parameters, 51
Parameter Group 12 - Moisture, 93 Remote Mode, 12
Parameter Group 13 - Cleanout Control, 96 Retro-reflective Tape Clips, 20, 22
Parameter Group 14 - Analog Outputs, 98 Safety Instructions, 7
Parameter Group 15 - Digital Inputs, 103 Setup, 13
Parameter Group 16 - Digital Outputs, 112 Setup Notes, 13
Parameter Group 18 - 2-Sensor Slip, 122 Setup Parameters, 15, 55
Parameter Group 19 – Maintenance Interval, 125 Span (CAL 2), 22
Parameter Group 20 - Reports, 126 Startup and Functional Check, 14
Parameter Group 21 - Comm. EasyServe, 127 TA: Tare, 25
Parameter Group 22 - Comm. Fieldbus, 128 TC: Span Calibration, 24
Parameter Group 23 - Ethernet, 129 Testing, 49
Parameter Group 24 - PLS Outputs, 130 Testing - Calibration Weight Test, 49
Parameter Group 25 – Fixed Mode Config., 130 Testing - Chain Test, 49
Parameter Group 26 – FCB Analog Output, 130 Testing - Material Test, 50
Parameter Group 27 – FCB Digital Output, 130 Totals, 11
Parameter Group Cleanout Control, 119 Touch Screen HMI Configuration, 29
Parameter Overview, 139 Trending Data, 153
Parameters, 51 Typical Operating Procedures, 35
Parameters – Abbreviations, 52 V (Definition), 10, 52
Parameters - Default Parameters, 51 VCU 20103, 9
Parameters - General Information, 51 VCU 20104, 9
Parameters – Hardware Configuration, 52 VEA (Definition), 52
Parameters – Inputs/Outputs, 52 Volumetric Control Mode, 12
Parameters – Parameter Attributes, 51 Volumetric Mode, 12
Parameters – Parameter Groups, 51 VSE (Definition), 52
Parameters – Parameter List, 55 W1/Warning 1 (Definition), 52, 131
Parameters - Printing, 44 W2/Warning 2 (Definition), 52, 131
Passwords, 7 Weigh Roller Adjustment, 19
Performing Calibrations, 18 Weigh Span Length, 11
Print Parameters, 44 What is the DISOCONT Tersus/DT-9?, 9
Probe Error, 20, 22 Xd (Definition), 10
Q (Definition), 10, 52 Y (Definition), 10
QB (Definition), 10 Z (Definition), 10

156 DISOCONT® Tersus (DT-9) Configuration and Operations Manual


©Schenck Process Group

S-ar putea să vă placă și