“BEAT IT”
AHU Extreme High Vibration
## “910 mm/s RMS” ##
Your cost of time: Each time you use reviewing the data, performing tests or discussing the problem is
10 points towards your total cost for the case study history. Any special test you request will be
discussed with you to insure proper understanding of procedures involved. You have 90 minutes
available to review the data you’ve collected and make up a report on your assessment and
highlight findings done.
Information Provided : You are on site collecting all the data that your requires. The collection display
of the spectrums collected are listed below. The significant motor nameplate info is as follow
Motor RPM : 2,700.00 , Fan RPM : 2,625.00 Loading : Variable Speed Drive
Your Observations: The unit is obviously Vibrating Heavily . Humming noise was heard emulating
from AHU units . You feel high vibration of this unit even as you approach it. The vibration
collected form on line mounted sensor on Fans and motors are the only FFT Spectrum analysis
available.
Fan
FNDE FDE
Motor
MDE MNDE
Vertical
Horizontal
Axial
AHU 10
Motor DE -
Vel 6Pack 1000 Hz Spectrum Overalls 11.2 mm/s RMS 20/1/2016 2:47:05 PM
Horizontal
Motor NDE -
Vel 6Pack 1000 Hz Spectrum Overalls 10.38 mm/s RMS 20/1/2016 2:47:26 PM
Horizontal
Fan DE – Horizontal Vel 6Pack 1000 Hz Spectrum Overalls 910.3 mm/s RMS 20/1/2016 2:51:18 PM
Demod Spectrum
Fan DE – Horizontal Vel 6Pack 1000 Hz 1.762 g RMS 20/1/2016 2:51:18 PM
Overalls
Fan NDE -
Vel 6Pack 1000 Hz Spectrum Overalls 13.91 mm/s RMS 20/1/2016 2:48:14 PM
Horizontal
Hz
Hz
00 Spectrum O/All 9.031
O/All 15.83 g
g RMS
RMS
71
80
60
mm/s RMS
40
20
0 100 200 300 400 500 600 700 800 900 1,000
Hz
4
mm/s RMS
45Hz Spectrum
20/1/2016 2:48:14 PM
Cursor A: 28.75 Hz 4.538 mm/s
O/All 13.91 mm/s RMS
6
4
mm/s RMS
SS
00 100 200 300 400 500 600 700 800 900 1,000
100 0.01 200 300 High
400 Freq
Demod Spectrum
500
Spectrum 600 0.05 700 800 900 1,000
RM
00 0.02 0.03 0.04 0.06 0.07
S
0.1 0.2 0.3 Spectrum
0.4 0.5 0.6 0.7
RM
High Freq Hz
Waveform
RM
0 Demod Hz
Waveform
Hz
00 secs
secs
gg
00
/s
Waveform O/All
O/All 0.6559
0.1996 g RMS
g RMS
RMS
gg
O/All 14.09 mm/s
mm
O/All
O/All 0.626
0.203 gg RMS
RMS
11/2/2016 9:40:18 AM True pk-
pk-pk 3.631 gg
True pk 1.086
Crest
O/All Fac
15.12 tor
mm/s 2.901
RMS
Crest Fac tor 2.675
True pk- pk 63.75 mm/s
30 Crest Fac tor 2.108
20
10
mm/s
0
-10
-20
-30
0 O/All 0.2484
O/All 6.518
O/All
O/All mm/s
0.5687
0.2579 gg RMS
g
RMS
RMS
Cursor A: 0.06372 secs 3.791
True
True mm/s1.799
pk-pk
pk-pk 4.058 g g
Crest
O/All 6.652
Crest Factor
Factor 3.568
mm/s3.488
RMS
15 True pk-pk 35.96 mm/s
Crest Factor 2.703
10
0
mm/s
-5
-10
-15
-20
Before After
gg RRMS
MS
Hz
Hz
00 Spectrum O/All 0.1303
O/All 0.3656 gg RMS
RMS
Power (mm/... 31/5/2016 1:33:41 PM
11
2
Cursor A: 43.75 Hz 1.426 mm/s
O/All 3.301 mm/s RMS
1.8
43.75Hz
1.6 z
1.4
1.2
mm/s RMS
0.8
0.6
0.4
0.2
0 100 200 300 400 500 600 700 800 900 1,000
Hz
11
2.5
2
45Hzz
mm/s RMS
1.5
0.5
0 100 200 300 400 500 600 700 800 900 1,000
Hz
Provide an estimate of the mode shape for the natural frequency that is being
excited.
• AC Induction
• General Electric
• 400 Horsepower
• 1780 RPM
• 509LL Frame
• 460 Volt
• 442 Amps
PdMA Corporation
Problem Description
• Four (4) Variable Frequency Drive failures
within a short life span (all within 3 years)
• Electric Motor recently refurbished
• VFD’s always replaced with new components
at a cost of $45,000 each
• Frequent trips of the motor causing additional
process problems
PdMA Corporation
Initial Standard Test
• Data collected from Test Date 07/28/2003
Frequency 1200
appeared to be within mH Ph 2 to 3
Avg. Inductance
% Res. Imbalance
2.790
2.713
0.15
PdMA Corporation
Polarization Index Test
Final value less than 400 Mohm
PdMA Corporation
Standard Test - At Motor Leads
Test Date 07/28/2003
Test Time 10:08:57 AM
• Data collected from Baseline
Frequency 1200
motor leads to isolate Mohm Ph 1 to Gnd
Charge Time 60
circuit from motor to Voltage
Motor Temp
1000
30
disconnect Measured Mohm
Corrected Mohm
3400.0
1700.0
motor User
Notes Yes
Polarization Index - At Motor
Final value increased to over 12000 Mohm
PdMA Corporation
Remedial Actions
• Due to problem with low Mohm values
apparently residing between the local
disconnect and motor junction box, we
suspected water in the conduit
• Conduit was removed
• NO water found
• Spirits were low
PdMA Corporation
Remedial Actions (Continued)
• Due to some abrasions on lead-wire jacket, it
was decided to have it replaced
• Would allow further investigation of the
conduit - still leaning on water in conduit
• Would allow further investigation of the circuit
for other possible sources of our problem
PdMA Corporation
New Lead Wire
• Old lead wire was removed from conduit
• New lead wire was brought to project site for
measurement and cutting
• We were faithfully inspecting conduit for
water
• During lead wire measurement, our problem
was found!
PdMA Corporation
Root Cause
PdMA Corporation
Before/After Lead Change
Test Date 07/28/2003 07/28/2003
• Corrected Mohm Test Time 10:08:57 AM
Baseline
03:03:13 PM
PdMA Corporation
Problem Follow-Up
• Unit has operated flawlessly for 9 months without
as much as a nuisance trip
• Process problems have as a result been
tremendously reduced
• Maintenance budget has experienced a much
needed rest from drive replacement costs
• Huge “round of applause” for our PdMA MCE
Testing Technology
PdMA Corporation
Nick Kang
• 25 Years
– Field Vibration Diagnostic
– Certified Vibration Institute VI (USA) –
Course Trainer
* Certified Infrared Thermal Inspection Specialist