Documente Academic
Documente Profesional
Documente Cultură
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2017.2781905, IEEE
Transactions on Power Systems
1
DC system
Abstract—The outcome of recent numerical simulation shows PDCpf Post-fault DC power flow
that the conversion of an AC transmission line to a simultaneous
PDcad Additional DC power flow during post-fault
AC-DC line improves the system stability. This paper presents a
mathematical model, suitable for the stability analysis of a condition
simultaneous AC-DC transmission system, transmitting both AC Pacm Maximum value of the AC power in
and DC power simultaneously through an existing AC line. The simultaneous AC-DC system
model is based on the principle of equal area criterion. The Post fault steady AC power
salient feature of this model is the introduction of a solution Difference between Pac and PDcad
technique of an integral component of the model which avoids the
trial and error approach for the analysis. The model development Tcr Critical clearing time for pure AC system
process considers a single machine-infinite bus system with a TCR Critical clearing time in simultaneous AC-
transmission line connecting the machine and the infinite bus. DC system
The process also considers the severe most fault at the sending Vdc DC voltage in simultaneous AC-DC system
end bus. The validation of the model is executed through two
Xgr Summation of Xte and XTr
different approaches; comparison of the results obtained
applying the proposed model to the power system with the Xte Reactance of generator and transformer
published ones in the literature and with the results obtained XTr Reactance of transmission line
using standard software, MATLAB simulink, based circuit ωs Angular frequency
simulations. The model is also applied to a realistic system and
IEEE benchmark systems to verify its capability of evaluating the δ0 Pre-fault steady state torque angle in case of
benefits of a simultaneous AC-DC transmission system. pure AC system
δcr Critical clearing angle for pure AC system
δac Torque angle due to AC power transfer in
Index Terms— Simultaneous AC-DC transmission system, simultaneous AC-DC system
critical clearing angle, critical clearing time, stability
δCR Critical clearing angle in simultaneous AC-
improvement, equal area criterion.
DC system
δm Maximum rotor angle
NOMENCLATURE
I. INTRODUCTION
Eg Internally generated voltage of the generator
Er
Eφm
Receiving end voltage
Maximum phase voltage of pure AC system
T HE necessity of the use of power transmission systems at
their highest capacity is increasing day by day due to ever
increasing demand and the limitations of constructing new
H Inertia constant of the generator transmission infrastructures. As the construction of new
Pl Steady state power flow through pure AC transmission line is a difficult task nowadays, particularly in
line the industrialized countries, the application of series
Pcomb Combined steady state AC-DC power flow compensation can be a short term solution [1]. But, this
Pac Steady state AC power in simultaneous AC- compensation scheme generates subsynchronous resonance
DC system problem. To overcome the limitations of increasing the
loadability of the existing AC transmission line, researchers
Pdc Steady state DC power in simultaneous AC-
are proposing a novel approach of simultaneous AC-DC
Mohammad Tawhidul Alam is with the Electrical and Electronic
power flow through an existing AC line [2]. The simultaneous
Engineering Department, Ahsanullah University of Science and Technology, AC-DC power transmission system also increases the stability
Dhaka, Bangladesh.(e-mail: tawhidul_bclt@yahoo.com) [3].
Q. Ahsan is with the Electrical and Electronic Engineering Department, The stability of a power system is its ability to return to
Bangladesh University of Engineering and Technology, Dhaka, Bangladesh. normal or stable operation after perturbation due to
(e-mail: qahsan@eee.buet.ac.bd) abnormalities. The steady state stability limit is one of the
0885-8950 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2017.2781905, IEEE
Transactions on Power Systems
2
influential factors that normally set a ceiling on the load simultaneous AC-DC system through the same transmission
carrying capability of a particular transmission line [4-5]. The line in [19].
index of stability, in case of a transient fault, is measured in H. Rahman and B. H. Khan [3] presented some numerical
terms of critical clearing time (CCT). The CCT is the simulations for the stability analysis of simultaneous AC-DC
maximum duration to clear the fault for which the system will system considering the faults at different locations of
be stable. transmission line. A comparative analysis between
Yorino et al. [6] proposed a new formulation for transient simultaneous AC-DC system and pure AC system with series
stability analysis for electric power systems. Different from compensation are also presented in the paper. It shows that
existing methods, a minimization problem is formulated for for a transient fault, the magnitude of speed deviation in case
obtaining CCT for transient stability. The method is based on of simultaneous AC-DC system is longer but this speed
the computation of a trajectory on the stability boundary, deviation reduces to zero at a faster rate compared to the pure
which is referred to a critical trajectory in the paper. The HVAC system. Moreover, at the inception of fault the
critical trajectory is defined as the trajectory that starts from a generator real power overshoot is longer and the subsequent
point on a fault-on trajectory at CCT and reaches a critical real power oscillation as well as duration is longer in pure
point of losing synchronism. HVAC system, while this oscillations are subsided much
For transient stability analysis, the direct method requires
faster in case of simultaneous AC-DC system.
less computational time with poor accuracy and the time
K.P. Basu [20] proposed a new technique to improve the
domain simulation method is accurate but time-consuming and
stability of a simultaneous AC-DC system where the system is
thus not suitable for online application. A new hybrid method
for CCT calculation is proposed in [7] with the help of direct no more AC-DC system after clearing the fault until the
method and time domain simulation which can meet the system enters into the normal state. In this technique, AC-DC
requirements of online application. composite system is converted into only a DC system, by
The existing methods of transient stability analysis rely on tripping the AC circuit breakers, just after clearing the fault
time consuming numerical integration of the fault-on and when the system becomes healthy the AC breakers are
dynamics. A novel framework is introduced in [8] to eliminate turned on to revert to a normal simultaneous AC-DC system.
the need for fault-on dynamics simulation in contingency The application of this technique requires special control
screening. mechanism for circuit breakers operation. The numerical
There are some methods to improve the stability and damp analysis of [20] shows that for a transient fault the critical
out oscillations of a power system. Among them flexible AC clearing time varies with the variation of post-fault DC power
transmission system (FACTS) based technology is the flow and maximum rotor angle deviation.
prominent one [9-11]. A comparative analysis is presented in [21] among the
In stability point of view, DC parallel operation with AC various methods of transient stability improvement such as
transmission line is more beneficial than AC-AC parallel static synchronous series compensator (SSSC), static
transmission lines. In case of AC-DC parallel system the DC synchronous compensator (STATCOM) and simultaneous
link power flow is highly controllable because of the converter AC-DC system. The simulation results show that the stability
control system. The effect of controlled DC link on system limit of the simultaneous AC-DC system is the highest
stability and damping depends on system operating conditions compared to all other methods. A comparison of voltage
which are elaborately analyzed in [12-15]. A. E. Hammad [16] stability between a pure AC system and a simultaneous AC-
introduced a generic concept combining transient angle and DC system is shown in [22]. The simulation considers a
voltage stabilities of a parallel AC-DC transmission system. It double circuit transmission lines for both pure AC and
also shows that the short-term overloading capability of simultaneous AC-DC systems. It also shows that the voltage
HVDC converter can be applied for stabilizing the parallel stability limit of a simultaneous AC-DC system is better than
AC-DC system. that of pure AC system.
The simultaneous AC-DC power flow system derives the To date, all the studies conducted on the stability analysis of
benefits of parallel HVDC line without constructing the simultaneous AC-DC power transmission system are based on
separate DC line. In this system of power transmission, numerical simulations. From the numerical results, it is
existing AC line conductors are used to carry AC along with difficult to formulate a generalized comment. To investigate
DC power. H. Rahman and B. H. Khan [2] conducted the the behavior of a system comprehensively an appropriate
numerical analysis for a simultaneous AC-DC transmission mathematical model is necessary.
system considering only the transmission line disregarding the In this paper, a mathematical model of a simultaneous AC-
whole system. A feasibility study is performed for small DC transmission system is presented. The model is developed
power tapping from simultaneous AC-DC transmission line in based on the principle of equal area criterion [23]. The main
[17]. Babu et al. [18 ] have studied two control modes such as advantage of the model is that it avoids the trial and error
independent control and coordinated control of AC and DC approach for the stability analysis by incorporating a solution
power transmission to maintain the thermal limit line current technique of an integral component of the model. It is
in case of simultaneous AC-DC system. A comparison of validated by comparing its results with the published one and
power flow is shown among pure AC, HVDC and also with those obtained through circuit simulation using
standard software. The model is also applied to a realistic
0885-8950 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2017.2781905, IEEE
Transactions on Power Systems
3
δcr = [ −2 − ] (3)
! "#
Tcr = (4)
Where, Fig. 3. Simultaneous AC and DC power flow curve
0885-8950 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2017.2781905, IEEE
Transactions on Power Systems
4
During the pre-fault steady state condition, the mechanical δm = Maximum rotor angle
power input is equal to the electrical power consumption if the
losses are neglected. That is Fig. 3 shows that the DC power flow at the post fault
condition is higher than the steady state DC power. In terms of
Pac + Pdc = Pm (5)
stability, the simultaneous AC-DC transmission system is
Where, advantageous over pure AC system as it can exploit the
Pac = steady state AC power flow overloading feature of the converter system. Note that,
Pdc = steady state DC power flow converters can be overloaded up to 50% of their rated
Pm = Mechanical power or shaft power capacities [16] for a shorter duration. If the converters are
operated at overloaded condition, the post fault DC power,
In Fig. 3, Pm1 and Pm2 are two mechanical power inputs and PDCpf , can be determined by multiplying the converter rated
these are represented by two horizontal lines. That is, Pm1 and capacity with a factor greater than unity. For example, if the
Pm2 remain constant and the summation of Pm1 and Pm2 is converters are over loaded by 20% the multiplying factor
equal to Pm. During pre-fault steady state condition, Pm1 and
The critical clearing angle, ,- , corresponding critical
would be 1.2.
Pm2 are equal to Pac and Pdc, respectively.
During the fault condition the transmission line does not clearing time, and the maximum rotor angle, , of (7) will be
transmit any power. That is, the electrical power consumption affected due to the increased DC power flow during post-fault
condition. That is, ,- and
is zero. However, during this period mechanical system
can be increased in the
continues to produce energy and due to this mechanical energy
simultaneous AC-DC system by exploiting the overloading
generation during the fault the whole system may be unstable.
To attain a stable condition, after clearing the fault the feature of the converter. For different values of the additional
electrical system must consume an additional amount of DC power flow, 0 = , ,- and are illustrated in Fig. 4.
energy which is equal to the mechanical energy generation For comparison, the power flow curve of pure AC system is
during the fault. That is, for the stability of the system also depicted in the same figure.
The figure clearly shows that with the increased 0 = the
,- increases providing large time for fault clearance. Note
Mechanical energy Additional electrical energy
generation during the = consumption right after that at the rotor attains the synchronous speed and for any
fault clearing the fault.
value greater than that the rotor starts to accelerate.
Where,
Pcomb = Total combined steady state power flow in a
simultaneous AC-DC system
PDCpf = Post fault DC power flow
Pacm = Maximum value of AC Power flow in
simultaneous AC-DC system
(b) Power flow curve for simultaneous AC-DC system
δac = Rotor angle at steady state condition when 0 = <
δCR = Critical clearing angle for simultaneous AC-DC
different values of 0 = : (a) for AC power only (b) when 0 = <
Fig. 4. Power flow curve for pure AC and simultaneous AC-DC system for
system
0885-8950 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2017.2781905, IEEE
Transactions on Power Systems
5
Solving the integral part and rearranging the terms, (7) can be
when 0 = >
(d) Power flow curve for simultaneous AC-DC system
Fig. 5. Area calculation under the AC curve in AC-DC system
− ∅ B 0 = < of Ψ and
simultaneous AC-DC system, may be expressed in terms
= @ B 0 = = C 8
as
+ ∅* B 0 = > =Ψ 14
where Now, the value of must be such that the area ABCD of
∅1 = sin −1
9
G
F H
J Fig. 5, the product of and (δm - δCR), is equal to the area
H I
∅* = − sin F J 10
"L under the AC curve between δCR and δm . That is
"LM8
0 =.
sin ;
7
Area ABCD = Q7 8
of (9) and (10) is the difference between and
9:
(15)
= sin − 0 =
That is
= sin − − 0 =
Using the steady value the integral component of (7) or
= − = 11
(15) may be written as
0
78
0 = = 0,12 − = 12 3 sin ; = − 16
The additional DC power of (11) may be expressed as
,-
79:
0885-8950 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2017.2781905, IEEE
Transactions on Power Systems
6
4_ −
],- = ^ 21
,-
That is, (7) may be expressed as
`a . /
. / − = 0,12 − ,-
+ − ,- 17 Combining (4), (20) and (21) the expression of the critical
clearing time of simultaneous AC-DC system, TCR , can be
To determine the empirical values of Ψ several power expressed in terms of the critical clearing time of pure AC
system, Tcr , as
values of Ψ is determined for each system. The average −
systems are considered. Using the trial and error approach the
],- = ] % ^b1 − cd e 22
. / \
values of Ψ of all the systems, for a particular DC voltage Z 0,12 + [ % − . /
mix and for a particular torque angle, are presented in Table
voltage mix the values of Ψ for different power system lie in a ],- = & ] % 23
A1 of Appendix-A. Tables A2 and A3 show that for the same
& = d1 − eF J #
"Mf8g 78 7LM "
Z"h9ij k "LM8 [ 7Ml 7m "Mf8g
DC voltage mix or angle are different the values of Ψ are
to each other, respectively. However, when the percentage of
distinctly different. Using the average values of Ψ from the Equation (23) shows that the critical clearing time of
Table A1 a generalized expression of Ψ in terms of percentage
AC system if the value of & is greater than unity.
simultaneous AC-DC system will be higher than that of pure
of DC voltage mix and torque angle is developed through
curve fitting technique of MATLAB. The expression is Note that, if the rise time delay is considered for the post
fault DC power flow, just after clearing the fault, from its zero
− 0.2912 X + 0.9738 18
from ,- to
−
will be a bit lower than the area given by
0,12 ,- and the magnitude of decrease in area
Where, δ is the torque angle of the generating unit and k is depends on converter characteristics and its reactive power
the percentage of DC voltage mix. The expression of k may be
management system.
presented as
Y=
X = 19
III. MODEL VALIDATION
∅
This section presents the validation of the proposed model.
. /
be written as [20] considers (i) 50% DC voltage mix, (ii) Steady state power
,- = − − 20
flow of 0.9 pu with a transmission angle of 800, and (iii) a 3-
Z 0,12 + [ phase to ground fault at the load terminal of the sending end
The expression for the critical clearing time of the bus. The simulation also considers that during post fault
condition only the DC power is allowed to flow and the AC
simultaneous AC-DC system, TCR, can be written by just
breakers are on when the system becomes stable.
replacing \ by . / in (4) as
0885-8950 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2017.2781905, IEEE
Transactions on Power Systems
7
0885-8950 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2017.2781905, IEEE
Transactions on Power Systems
8
0885-8950 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2017.2781905, IEEE
Transactions on Power Systems
9
Vdc mix(%)
V. CONCLUSION
10 20 30 40 50
Conventional approaches have limited scope to improve the Angle(degree)
stability of the existing AC transmission system. Therefore, 20 0.848 0.78 0.69 0.662 0.642
the researchers are putting emphasis on the simultaneous AC- 35 0.844 0.766 0.664 0.634 0.61
DC transmission system. Simulation results show that 50 0.854 0.734 0.632 0.602 0.572
significant increment in transient stability can be achieved by 65 0.83 0.706 0.594 0.558 0.528
transmitting AC and DC power simultaneously through the
VALUES OF U FOR DIFFERENT DC VOLTAGE MIX WITH 350 TRANSMISSION
existing AC line. This paper presents an analytical model of a TABLE A2
simultaneous AC-DC power transmission system with a view ANGLE
to facilitate a comprehensive and generalized analysis for the
transient stability of such a transmission system. By using the % of Vdc System-1 System-2 System-3 System-4 System-5 average
developed expression it can easily be determined which 10 0.86 0.85 0.84 0.84 0.84 0.844
parameter of the system impacts how much on the 20 0.8 0.78 0.76 0.76 0.74 0.766
improvement of stability. 30 0.71 0.67 0.65 0.65 0.64 0.664
The stability analysis of simultaneous AC-DC system is 40 0.66 0.64 0.63 0.62 0.61 0.634
generally based on either numerical iterative technique or time 50 0.64 0.61 0.61 0.6 0.59 0.61
domain circuit simulation both of which are time consuming.
But, the model presented in this paper avoids the iterative
0885-8950 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2017.2781905, IEEE
Transactions on Power Systems
10
06 DC system DC system rated voltage 141kV. Fig. C. MATLAB simulink circuit model for simultaneous AC-DC system
APPENDIX-D
Montana 500kV transmission system transmits power from
the East (Colstrip) to west (Taft). The eastern Montana
APPENDIX-C
generation system has four coal-fired thermal units of a total
The parameters of different components of the power system capacity of 2272MW [1]. For the application of the proposed
considered for the validation of the proposed model through model only 500kV double circuit transmission line from
circuit simulation are presented in Table C. Fig. C represents Colstrip to Taft, excluding other portion of the power system,
the circuit model with MTLAB simulink for the simultaneous is considered. Colstrip with the generation capacity of
AC-DC transmission system. 2272MW of an equivalent single machine and Taft are
considered as a generator and infinite bus, respectively. The
simulation also does not consider Broadview and Garrison
buses in between Colstrip and Taft. The parameters of
different components of this system are presented in Table D.
0885-8950 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2017.2781905, IEEE
Transactions on Power Systems
11
TABLE D REFERENCES
PARAMETERS OF THE DIFFERENT COMPONENTS OF MONTANA 500KV
TRANSMISSION SYSTEM [1] D. N. Kosterev, W. A. Mittelstadt, R. R. Mohler and W. J. Kolodziej,
Sl. No. Component Parameter “An Application Study for Sizing and Rating Controlled and
(i) x = j253.21 Ω/phase/ckt Conventional Series Compensation,” IEEE Transactions on Power
(iii) Double ckt Delivery, Vol. 11, No. 2, April 1996.
(iv) Three phase [2] H. Rahman , and B. H. Khan, “Power Upgrading of Transmission Line
01 Line (v) 60Hz by combining AC-DC Transmission,” IEEE Transactions on Power
(vi) 804km Systems, Vol. 22 ,No. 1, February 2007.
(vii)500kV
[3] H. Rahman, and B. H. Khan, “Stability Improvement of Power System
(viii) Thermal limit current = 3kA by Simultaneous AC–DC Power Transmission,” Electric Power System
358*2, 778*2(MW) Research, Vol. 78, No. 4, pp. 756-764, Apr. 2008.
02 Generator
24kV,Reactance = 0.3pu, H=3.5 s. [4] R. D. Dunlop, R. Gutman, and P.P. Marchenko, “Analytical
Generator development of Loadability Characteristics for EHV and UHV
03 24/230kV, Leakage reactance = 0.15pu. Transmission Line,” IEEE Transactions on Power Apparatus and
Transformer
∆-Y, 230/500kV, leakage reactance = 0.1pu. (pure Systems, Vol. PAS-98, No. 2 March/April 1979.
Transformer (At AC) [5] P. Kundur, Power System Stability and control, New York: McGraw-
04 the sending end Hill, Inc, 1994.
of the line): ∆-Z, 230/253kV, Leakage reactance = 0.1pu. (AC- [6] N. Yorino, A. Priyadi, H. Kakui, and M. Takeshita, “ A New Method
DC)
Transformer (At for Obtaining Critical Clearing Time for Transient Stability,” IEEE
Z-∆ 253/500kV, Leakage reactance= 0.1pu, (AC- Transactions on Power Systems, Vol. 25, No. 3, August 2010.
05 the receiving end
DC)
of the line): [7] L. Y. Ren, F. Tian, J. F. Yan, Z. H. Yu, F. Su, and T. Wu, “ Online
DC system rated voltage and current are Application and Fast Solving Method for Critical Clearing Time of
06 DC system
202kVand 9kA, respectively. Three-Phase Short Circuit in Power System,” International Journal of
Smart Grid and Clean Energy, Vol. 2, No. 1, January 2013.
APPENDIX -E [8] T. L. Vu, S. A. Araifi, M. S. Elmoursi, and K. Turitsyn, “ Toward
Simulation-free Estimation of Critical Clearing Time,” IEEE
Transactions on Power Systems, Vol. 31, No. 6, November 2016.
[9] D. N. Kosterev, W. J. Kolodziej, R. R. Mohler and W. A. Mittelstadt,
“Robust Transient Stability Control Using Thyristor-Controlled Series
Compensation,” in Proceedings of the 4th IEEE Conference on Control
Applications, Sep. 1995, pp. 215-220 (1995).
[10] N. Johansson, L. Angquist, and H. P. Nee, “An Adaptive Controller for
Power System Stability Improvement and Power Flow Control by
Means of a Thyristor Switched Series Capacitor (TSSC),” IEEE
Transactions on Power Systems, Vol. 25, No.1, pp. 381-391, Nov. 2010.
[11] T. F. Orchi, H. R. Pota, and M. J. Hossain, “Stability Improvement of
Wind Farms Using Shunt and Series Compensation,” in 22nd
(a) Australasian Universities Power Engineering Conference(AUPEC), Sep.
2012, pp. 1-6 (2012).
[12] T. Machida, “Improving Transient Stability of AC System by Joint
Usage of DC System,” IEEE Transactions on Power Apparatus and
Systems, Vol. PAS-85, No. 3 March 1966.
[13] P. K. Dash, B. Puthal, O. P. Malik, and G. S. Hope, “Transient Stability
and Optimal Control of Parallel A.C.-D.C. Power System,” IEEE
Transactions on Power Apparatus and Systems, Vol. PAS-95, No. 3
May/June 1976.
[14] N. A. Vovos, and G. D. Galanos, “Transient Stability of AC-DC
Systems,” IEEE Transactions on Power Apparatus and Systems, Vol.
PAS-98, No. 4 July/August 1979.
[15] M. A. Pai, K. R. Padiyar, and C. Radhakrishna, “Transient Stability
(b) Analysis of Multi-Machine AC/DC power systems Via Energy Function
Method,” IEEE Transactions on Power Apparatus and Systems, Vol.
PAS-100, No.12 December 1981.
[16] A. E. Hammad, “Stability and Control of HVDC and AC Transmissions
in Parallel,” IEEE Transactions on Power Delivery, Vol. 14, No.4,
October 1999.
[17] H. Rahman and B. H. Khan, “Possibility of Power Tapping From
Composite AC–DC Power Transmission Lines,” IEEE Transactions on
Power Delivery, Vol. 23, No. 3, July 2008.
[18] P. V. K. Babu, P. B. Prasad, and M. P. Lalitha, “Power Upgrading of
Transmission Line by Combining AC–DC Transmission,” International
Journal of Engineering Research and Applications (IJERA), Vol. 2, No.
6, pp. 1699-1704, Nov./Dec. 2012.
(c) [19] B. G. Sherkhane and M. R. Bachawad, “Improvement in Power
Transmission Capacity by Simultaneous AC-DC Transmission,” The
Fig. E: Rotor angle transient response of Montana 500kV transmission International Journal of Engineering and Science (IJES), Vol. 4, No. 5,
system for different values of steady state angle: (a) for 30 degree , (b) pp. 22-31, May 2015.
for 50 degree, (c) for 70 degree
0885-8950 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2017.2781905, IEEE
Transactions on Power Systems
12
[20] K. P. Basu, “Stability Enhancement of Power System by Controlling serving as a faculty member in the Department of Electrical
HVDC Power Flow through the Same AC Transmission Line,” in 2009 and Electronic Engineering of Ahsanullah University of
IEEE Symposium on Industrial Electronics and Application (ISIEA
Science and Technology, Dhaka, Bangladesh. His research
2009), October 4-6, 2009, Kuala Lumpur, Malaysia.
[21] K. P. Basu, and M. H. Neem, “Stability Enhancement of Power System
interests include HVDC, power system stability and renewable
by Simultaneous AC-DC Power transmission,” IEICE Electronics energy.
Express, Vol. 6, No. 12, pp. 818-823, June 2009. Q. Ahsan was born in Bangladesh in 1951. He graduated
[22] A. D. Diwan, and P. Khurana, “ Comparative Analysis of Voltage from Bangladesh University of Engineering and Technology
Stability Between AC Transmission and Hybrid AC-DC Transmission (BUET), Dhaka in 1975. Dr. Ahsan did his M. Sc.
Systems,” International Journal of Engineering Research and
Technology (IJERT), Vol. 3, No. 2, February 2014. Engineering from the same university in 1980 and Ph. D from
[23] J. J. Grainger, and W. D. Stevention Jr., Power System Analysis, the University of Ottawa, Canada in 1984.
McGraw-Hill, International Edition, New York, 1994. Dr. Ahsan joined in the Department of Electrical and
Electronic Engineering of BUET as a lecturer in 1976 and he
Mohammad Tawhidul Alam was born in Bangladesh in became a full professor in 1988. He has worked as a visiting
1977. He received B.Sc. (Engg.) degree from Dhaka faculty in a number of Universities at home and abroad. Dr.
University of Engineering and Technology (DUET) in 2002, Ahsan has also worked as a consultant of many important
and M.Sc. (Engg.) degree from Bangladesh University of national and international projects.
Engineering and Technology(BUET) in 2008. He obtained his He has published around 90 technical papers in the reputed
Ph.D. degree in 2016 in the department of Electrical and national and international journals and conferences. He is the
Electronic Engineering at Bangladesh University of author of couple of books and a chapter of a book. He is the
Engineering and Technology, Dhaka, Bangladesh. recipient of a number of awards.
Dr. Alam served as a lecturer at Bangladesh College of
Leather Technology from 2003 to 2008. Currently, he is
0885-8950 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.