Sunteți pe pagina 1din 2

F 3236 (0145) Data Sheet

F 3236
F 3236: 16-channel input module,
safety-related
for 1-signals or sensors
with safety isolation
Safety-related, requirement class RC 1...6

Block diagram

Front cable plug

The module is automatically fully tested during operation for safety-related


errors. The essential test procedures are:
– Cross-talking of the inputs with walking-zero
– Functions of the filter capacitors
– Function of the module
The LEDs of the cable plug are not tested.

Inputs 1-signal, 6 mA (incl. cable plug)


or mechanical contact 24 V
Switching time typ. 8 ms
Space requirement 4 TE
Operating data 5 V DC: 120 mA
24 V DC: 200 mA

All rights reserved. The technology is subject to changes without notice: 1/2
HIMA Paul Hildebrandt GmbH + Co KG, Postfach 1261, 68777 Brühl
F 3236 (0145)

Channel Connection Colour


1 d2 WH
2 d4 BN
3 d6 GN
4 d8 YE
5 d10 GY
6 d12 PK
7 d14 BU Cable
8 d16 RD LiYY 16 x 0.25 mm2
9 d18 BK
10 d20 VT
11 d22 WHBN
12 d24 WHGN
13 d26 WHYE
q = 1 mm2
14 d28 WHGY
l = 750 mm
15 d30 WHPK
16 d32 WHBU
L– z2 BK Flat pin plug
L+ z12 RD 2.8 x 0.8 mm2
Screen z4 YEGN
z6 YEGN Flat pin plug 6.3 x 0.8 mm, to be connected to the earth
bar under the slot
q = 1 mm2
l = 120 mm

Lead marking of the cable plug


Z 7116 / 3236 / C..

Test plug diagram Z 7201 / 3236

2/2

S-ar putea să vă placă și