GST TECHNICAL TRAINING

UTC CCS TECHNICAL SUPPORT INDIA

1 GST TECHNICAL TRAINING – 2013


Welcome

 Introductions  Operation &


 UTC CCS Technical Commissioning Agenda
Support  Hands On Agenda
 RMA  GST Documentation and
 Hardware Training Downloadable content
Agenda
 Software Training
Agenda
 Handheld Programmer

2 GST TECHNICAL TRAINING – 2013


Introductions

 Who ? ( You and your employer ?)


 Where ? (Are You From ? )
 What ? ( Is your Role and Experience with Regard to Fire
Detection & Alarm System ?)

3 GST TECHNICAL TRAINING – 2013


UTC CCS Technical Support

 India
 Sunil Bhujbal ( GM- Product Solutions & Technical Support )
 sunil.bhujbal@fs.utc.com
 Ph: +91 9769759260
 North
 Kamal Kumar ( Manager Technical Support )
 kamal.kumar@fs.utc.com
 Ph: +91 9873196696
 Pradeep Kumar ( Lead Technical Support )
 pradeep.kumar@fs.utc.com
 Ph: +91 9871126206

4 GST TECHNICAL TRAINING – 2013


 West
 Ashu Shashish ( Lead Technical Support )
 shashish.ashu@fs.utc.com
 Ph: +91 9769686740
 South
 Lakshminarayana Maiya ( Lead Technical Support )
 lakshminarayana.maiya@fs.utc.com
 Ph: +91 9632789492
 Nagaraj Kumbhar ( Lead Technical Support )
 nagaraj.kumbhar@fs.utc.com
 Ph: +91 8884402078

5 GST TECHNICAL TRAINING – 2013


RMA

 Inform your regions UTC Tech Support or Distributor about


the issue
 UTC Technical Support will decide if it is a product fault
 Technical Service Report (TSR) would be prepared by UTC Tech
Support based on data informed by you:
 Site/ Customer Details
 Distributor Contact Details
 Model Number, Serial Number, Date of Production
 Fault Description, Actions & Result
 Distributor will receive the TSR, Fill the RMA Form and send it
to UTC Tech Support
 The RMA request would be sent to Customer Service

6 GST TECHNICAL TRAINING – 2013


 Customer Service will send the Repaired/ Replacement
material to the location mentioned in RMA form
 If the Material Not under Warranty Charges will be informed
 Once the material is received then inform the UTC Tech
Support
 On confirmation faulty material needs to be sent to address
mentioned in RMA form with right packaging

7 GST TECHNICAL TRAINING – 2013


Hardware Training Agenda

 GST FACP
 Intelligent - GST100 , GST 200 , GST M200, GST IFP8 , GST 5000
 Repeaters / Annunciators
 Conventional
 Fire Alarm Field Devices
 Detectors – Intelligent, Conventional , Explosion Proof , Intrinsically
Safe
 Intelligent Modules
 Gas Extinguishing Panel
 Integrated Fire Detection Voice Alarm and Fire Phone System
 Standalone Fire Telephone System

8 GST TECHNICAL TRAINING – 2013


Software Training Agenda

 GST Definition Utility


 GST Graphic Monitor Centre

9 GST TECHNICAL TRAINING – 2013


BREAK !!

10 GST TECHNICAL TRAINING – 2013


Handheld Programmer

 Address
 Parameter / Sensitivity
 Code
 I2C

11 GST TECHNICAL TRAINING – 2013


Operation and Commissioning Agenda

 Check List
 GST 200-2 Operation
 GST 200-2 Commissioning
 GST 5000W Commissioning
 GST IFP8 Operation
 GST IFP8 Commissioning
 Device Types
 C&E equations and NET option
 Interpreting Events / Troubleshooting

12 GST TECHNICAL TRAINING – 2013


Hands On Agenda

 Field Devices Wiring and Addressing


 GST 200 Wiring
 GST 200 Commissioning
 GST GMC (Debug)

13 GST TECHNICAL TRAINING – 2013


GST Documentation and Downloadable content

 http://www.gst.com.cn/en/index.asp

14 GST TECHNICAL TRAINING – 2013


GST HARDWARE

15 GST TECHNICAL TRAINING – 2013


Topics

 GST Intelligent FACP –  Loop Considerations


Overview
 UL Devices
 Features
 Installation – Termination &  Conventional Devices
Wiring  Ex Proof and Intrinsically
 GST M200 Safe
 Network Annunciator &  Gas Extinguishing Panel
Repeaters
 Conventional FACP  Integrated Fire Detection
 GST Network Voice Alarm and Fire
 Intelligent Detectors Phone System
 Intelligent Modules  Standalone Fire
Telephone System
16 GST TECHNICAL TRAINING – 2013
GST Intelligent FACP - Overview
GST GMC GST200-2 GST 852RP GST 8903
Local
Repeater

1.2 Km
GST 100
1.2 Km

RS232
1.2 Km
Class A Global Network of Max. 64 FACP

NRP01
1.2 Km 1.2 Km

GST IFP8
GST 5000 W
17 GST TECHNICAL TRAINING – 2013
REDUNDANCE ACTION IF DETECTOR IN
MAIN CARD LOOP CARD DETECTOR
LEVELS ALARM
Fire alarm OUTPUT IS ON,
sounder internal buzzer
1 FAILS WORKING BLINKING & WORLING give alarm sound, fie LED
indicator on, LCD no
display
DEVICE DOES NOT
HARDWARE ERROR ON
2 WORKING FAILS BLINK, DEVICE DOES
LCD
NOT GIVE ALARM
DETECTOR DOES NOT
detector not blinking, once
BLINK, BUT DEVICE
FAILS BUT alarm the indicator on
PROVIDES LOCAL
3 WORKING PROVIDES digital detector will be
ALARM IE THE LED ON
POWER TO LOOP steady on, panel no
DEVICE IS CONSTANTLY
response
ON
GST UTILIZES BROADCASTING TECHNOLOGY NOT POLLING FOR COMMUNICATION WITH FIELD DEVICES

18 GST TECHNICAL TRAINING – 2013


GST 200-2 Features

 Two Models
 GST200-2/1 – 235 Devices
 GST200-2/2 – 235 +242 = 477 Devices
 Global Network – 32
 P-9940A - RS485 Optional Card Required
 Local Repeater – 10
 RS232 Card – P-9930
 LCD - 8 Lines *18 Characters
 History / Event – 999 No.s
 Max. 30 Virtual Zones with indication Led’s & control Buttons

19 GST TECHNICAL TRAINING – 2013


 Inbuilt PAS Mode – Positive Alarm Sequence [NFPA 72:6.8.1.3]
 PAS MODE
 Fire signal from detector shall be acknowledged at the panel within 15 sec
in order to initiate the alarm investigation phase. Trained personnel shall
have up to 180 sec to investigate.
▫ Fire signal not acknowledged w/in 15 sec – Outputs (Equation) immediately
activated
▫ Panel not reset during the 180 sec – Outputs (Equation) immediately
activated
▫ Second fire signal during the 180 sec – Outputs (Equation) immediately
activated
 Press Evac override PAS
 MCP is exempted (BS5839 P1:2.19)
 21 Ah Battery Capacity

20 GST TECHNICAL TRAINING – 2013


 Optional Fireman’s Control Panel
 Optional Panel Printer/ USB Printer Card
 Devices Debug-Device Status Diagnostic functions
 0 – Polling Command
 0-120 : Device Fault
 450-650 : Device Normal
 900-1200 : Device Alarm
 1- Registration Command – 720 Normal Status
 2- Commissioning Status Command for I-9105R – 680-750
Commissioned
 15 – Start Output of Modules or Start Alarm Led of Devices
 Walk Test Facility / Start and Stop Function /Enable and
Disable function

21 GST TECHNICAL TRAINING – 2013


GST 100 Features

 Single Loop - 120 devices + 8 Sounders


 LCD – 122*32 Dots Lattice
 8 Zone indication - Fire & Fault/Disable
 Programmable via panel keyboard only
 Built-in Panel Printer
 Global Network – 32 : P-9940A & Local Repeater – 64
 No Labeling / Messaging for devices
 7 Ah Battery Capacity
 History - 999 fire + 500 fault
 No Control for intelligent devices

22 GST TECHNICAL TRAINING – 2013


GST 5000W Features

 Two Models
 GST 5000W/2 – 235*2 = 470 Devices
 GST 5000W/4 – 235*4 = 940 Devices
 Global Network – 32 : P-9941A , Local Repeater – 64
 RS232 Card – P-9931
 LCD - 320×240 dot matrix
 History / Event – 999 No.s
 Max. 60 Virtual Zones with indication Led’s & Activate /Silence
control Buttons
 38 Ah Battery Capacity
 Built-in Panel Printer

23 GST TECHNICAL TRAINING – 2013


 Monitoring Device / Supervisory Data / Device Debug
 4 - immediate start of gas extinguishing devices
 5 - 30 Sec delay start of gas extinguishing devices
 6 - Turn on gas release 24V
 7 - Activate output of modules
 Security and Extinguishing Mode

24 GST TECHNICAL TRAINING – 2013


GST IFP8 Features

 Modular Structure w/ Max 8 Loops – 242*8 = 1936 Devices


 LCD - 15 lines * 40 Characters
 Dual Loop Card – LCIFP8
 Global Network – 64
 P-9945A - RS485 Optional Card Required
 Local Repeater – 64
 P-9946A – RS485 Optional Card Required
 RS232 – P-9935
 Virtual Zones –999/140 zone indication - Fire & Fault/Disable
 Auto Programming Day and Night Mode – Delay Time
 Dirty Detector Reporting
 Supports 10 Loops – Production Date after March 2012

25 GST TECHNICAL TRAINING – 2013


 Duplicate Address Checking and Device Mismatch
 PAS/ Walk Test Facility (w/ silent mode) / Start and Stop
Function /Enable and Disable function
 Edit device details and programmable from keypad
 History / Event – 2000
 Inbuilt Panel Printer
 38 Ah Battery Capacity
 Fault and Supervisory Inputs *
 Optional Fireman’s Control Panel

26 GST TECHNICAL TRAINING – 2013


GST 200-2 Installation – Termination & Wiring

27 GST TECHNICAL TRAINING – 2013


28 GST TECHNICAL TRAINING – 2013
F7.820.828 - GST200-2 TERMINAL LOOP BOARD (LOOP1)

Description Terminal Function


RS-485 XT11, XT12 Passive Repeater
LOOP BUS XT2, XT4 Class A loop, 235 Addressable Devices
FAULT OUTPUT XT8 NC relay 24VDC 1A
Earth X8 Short to detect Earth fault
24 V NC (Mon 4.7k) NO
FIRE ALARM OUTPUT XT5, HL2 24VDC 500 mA(default) Address 242
X5 : Short X5: Cut X5: Cut
X1 : 1-2/4-5 X1: 3-4/5-6 X1: 2-3/5-6
F.P.E. OUTPUT XT6, Hl3 24VDC 500 mA (default) Address 241
Use X6>!X5 & X2>!X1
SOUNDER CIRCUIT OUTPUT XT7, Hl4 24VDC 500 mA(default) Address 240
Use X7>!X5 & X3>!X1

29 GST TECHNICAL TRAINING – 2013


GST 100 Installation – Termination & Wiring

30 GST TECHNICAL TRAINING – 2013


GST 5000W Installation – Termination & Wiring

31 GST TECHNICAL TRAINING – 2013


32 GST TECHNICAL TRAINING – 2013
XS4 XS3 XS2 XS1
 Case 1 : GST 5000 W /2
• XS2 - Dual Loop Card 1 : Address 01
(Ones/Tens)
• XS3 – P-9931 (232)/ P-9941A (485)
 Standalone : P-9931 : Address 03
 Network : P-9941A : Address 02
• XS4 – P-9931 (If Network) : Address 03
 Case 2 : GST 5000 W /4
• XS2 - Same as Case 1
• XS3 – P-9931 / P-9941A : Address 03
• XS4 – Dual Loop Card 2 : Address 02

 XT1 (A&B) – Repeater (passive)


 ZX1 & ZX2 – Loop 1 & 2
 N485 (A1/B1 & A2/B2) - Network
 T485 (A3/B3 & A4/B4) – Loop 3&4

33 GST TECHNICAL TRAINING – 2013


• Wired in Factory
• Troubleshooting
 D1 (+) / D2 (-) : 24V DC
 Z+ / Z- : Loop 1 from Motherboard
Similarly for loops 2,3,4
 Network A/B : Do not use /
Disconnect
 Repeater A/B : Check continuity
with Motherboard
• Networking : motherboard A1/B1 &
A2/B2
• Repeater A/B – Connect with GST 852
RP passive repeater Only

34 GST TECHNICAL TRAINING – 2013


FAULT OUTPUT XT8 NC relay 24VDC
1A
Earth X8 Short to detect
Earth fault

24 V NC (Mon 4.7k) NO

FIRE ALARM OUTPUT XT5, HL2 24VDC 500 mA


Address 242

X5 : Short X5: Cut X5: Cut


X1 : 1-2/4-5 X1: 3-4/5-6 X1: 2-3/5-6
F.P.E. OUTPUT XT6, Hl3 24VDC 500 mA
Address 241
Use X6>!X5 & X2>!X1
SOUNDER CIRCUIT XT7, Hl4 24VDC 500 mA
OUTPUT
Address 240
Use X7>!X5 & X3>!X1

35 GST TECHNICAL TRAINING – 2013


GST IFP8 Installation – Termination & Wiring

36 GST TECHNICAL TRAINING – 2013


XS8
F7.820.1238V2 XS1

NO COM NC
XT18

OUTPUT
FAULT
COM BOARD

REPEATER
B

XT14

B
Output to Repeater or

XS9 XS2 A
Mimic Panel

A
XS15

F2 F1
XT19

BACK
FEED
Fitted
470 ohms
EOL
4.7Kohms

MAIN BOARD

SOUNDER ROUTING
XT13

ALARM

_
O/P EOL
4.7Kohms

+
TO MAINBOARD

+
Sounder with Output Device with
built-in diode fitted diode

OUTPUT TO
XT12
XS10 XS3

_
O/P EOL

+
4.7Kohms

+
+
Sounder with Output Device with
built-in diode fitted diode

OUTPUT
XT11

TO FPE
_
FPE FPE EOL
4.7Kohms

+
+
LOOP BOARD

+
FPE with
fitted diode

XS11 XS4

LOOP 01 LOOP 02 LOOP 03 LOOP 04 LOOP 05 LOOP 06 LOOP 07 LOOP 08 LOOP 09 LOOP 10

I+ I-
XT10

O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O-
A1

O-
Out to next panel A2

LOOP 10
O+
Out to next panel B2
B1

I+ I-

XT10
XT9
Network Terminal - Class A
LOOP BOARD B2 In from next panel B1

I+
+5V GND

I+ I-
XS12 XS5

XT8
In from next panel A1

I-
A2

I+ I-
A

O-
Out to next panel A

XT7

LOOP 10
LOOP BOARD

O+
Out to next panel B
B

I+ I-

XT10
XT6
Network Terminal - Class B

I+
XS13 XS6

I+ I-
No connection

XT5

I-
I+ I-
XT4
LOOP BOARD
Out to first device

O-
I+ I-
Loop Out

XT3

LOOP 01
O+
XS14 XS7

XT1
I+ I-
XT2

I+
Loop In

I+ I-
LOOP BOARD

I-
GND 5V TX RX GND 24V In from last device

XT1
24V

37 GST TECHNICAL TRAINING – 2013


 Possible Combinations:
 8 Loops + Communication + Repeater
 8 Loops + Communication+ Network
 8 Loops + Network + Repeater
 6 Loops + Communication + Network + Repeater
 Com Board (XS8-XS1) – Used only for Repeater/ Mimic Card P-
9946 or Communication Card P-9935 (USB and serial
connection)
 Communication Card P-9935 - Any Loop Board (No USB)
 Network card should be placed to Loop Board 5 (XS10-XS3)
and wired in loop 10 terminal

38 GST TECHNICAL TRAINING – 2013


CARD SUM: 03 LOOP SUM: 04 SUM:0012

**************************
LOOP 1: Loop Card, Devices Sum: 003
LOOP 2: Loop Card, Devices Sum: 003
LOOP 3: Loop Card, Devices Sum: 003
LOOP 4: Loop Card, Devices Sum: 003
LOOP 5: Net Card-01, Net Sum: 02
LOOP 6: CRT CARD -01

Press F1 to print LOOP DEVICES info

Setting the card address- Numbering


sequence, lower card is the recommended
lowest numerical setting. Set dials on the
additional board in ascending order. Each
card must be set at least one higher digit
than the lower card.

39 GST TECHNICAL TRAINING – 2013


Class A Network

40 GST TECHNICAL TRAINING – 2013


GST M200
UL864 Compliant

 Max 2 Loops- Each Loop Supports 242 Devices


 GST M200 & GST M200-2
 Max Loop Distance – 4000 ft or 1219 m
 Network of 32 Panels with 30 Virtual Zones
 Duplicate device address and device type mismatch
 Walk Test - silent or audible
 PAS (NFPA72 compliant)
 Auto silence timer option per NAC. The time duration is
5minutes.
 Fully programmable from local keypad and from a pc

41 GST TECHNICAL TRAINING – 2013


 Supports P-9930 Modbus and Passive Local Repeater
GST852RP
 Does not Support
 NRP01 active Network panel
 GST303/306 gas extinguishing system
 LCD - 128*64 dots
 History - 1,000 events
 Optional Printer

42 GST TECHNICAL TRAINING – 2013


Network Annunciator & Repeaters

 Types
 Global / Local
 Passive/ Active
 NRP01
 Active Global Network Annunciator
 GST 852RP
 Passive Local Repeater
 Only Fire events
 GST 8903
 Mimic Panel / Local
 Max. 64 Modules with 100 LED per module

43 GST TECHNICAL TRAINING – 2013


Conventional FACP

 GST 102A – 2 Zones, 2 Sounder O/p


 GST 104A/108A/116A – 4/8/16 Zones , 4 Sounder O/p
 Maximum Devices in a zone
 25 detectors – EOL
 1 + IN , 2 + OUT , 3 – IN/OUT
 MCP should be ahead of detectors in the zone
 15 detectors – AEOL
 Without P-9907 AEOL Base
▫ Diode Between 1&2 / End with 2&3 of P-9907 AEOL
 With P-9907 AEOL Base
▫ End With 1&3 of P-9907 AEOL
 Total number shall not exceed 32 . Eg. MCP=32-Detectors

44 GST TECHNICAL TRAINING – 2013


Fault O/p NC

Alarm O/p NO
Zone I/p 4.7K
Ohms
470 Ohms

45 GST TECHNICAL TRAINING – 2013


46 GST TECHNICAL TRAINING – 2013
 Three access levels settable via a key switch and an internal
switch
 Level 1 : SW2- 1 Off & Control Enable Off
 Level 2 : SW2 -1 Off & Control Enable On
 Level 3 : SW2 -1 On
 Resetting to Default
 What is default Status
 Alarm from any zone will activate all sounders without any delay
 There is no disabled zone or output.
 Enter Access Level 3
 Press and hold Output Program for more than 2 seconds, and the
system will enter default state with 1s sound indication.
 Exit Access Level 3.

47 GST TECHNICAL TRAINING – 2013


 Test and disable functions
 Day/night mode settable & Delay modes
 Repeater panel interface for fire alarm indication of multiple
zones
 External I/p - RESET, SILENCE, EVAC and forced Night Mode.
 Alarm output & Fault output
 4 sounder outputs can be programmed to correspond a zone
 RB116 - dry contact fire alarm output & fault output for each
Zone

48 GST TECHNICAL TRAINING – 2013


GST Network

 Copper
+ Fibre +
 Fiber Optic
P-9945A + FIB485S01 x2 (Class A) P-9940A + FIB485S01 x2 (Class A)
 Copper/ Fiber

 TCP /IP + TCP/IP +


P-9935(TCP/IP)+NPort NPort + P-9930(TCP/IP)

 CAN Bus
 P-9965 GSTIFP8
 P-9960 GST200

49 GST TECHNICAL TRAINING – 2013


Intelligent Detectors

 Removable innovative sensing chamber


 History : 14 events
 Wiring
 1&3 : Loop connection (non-polarized)
 2 : Positive terminal of remote indicator
 4 : Negative terminal of remote indicator
 I-9103 - Fixed temp @ 58 °C “OR” Rate of rise 3 °C/min
 DI-9103 - 3 levels @ 58°C,66°C,74°C / Rate of rise 5°C/min
 A1R - fixed temperature or rate of rise will cause alarm
 A2S - The temperature must be above the fixed alarm temperature
and rate of rise meets requirement will cause alarm

50 GST TECHNICAL TRAINING – 2013


 Sensitivity: 0.10dB/m to 0.56dB/m-3 levels
 Each detector adjusts its reference value every 3 minutes and
can adjust up or down with a changing environment.
 70 % Dirty – Maintenance
 Detecting range recommended: 30 Sq.m for normal area; and
20 Sq.m for high risk
Sensor Output

GST DETECTOR OBSCURATION CALCULATION


PERCENTAGE TO COEFFICIANT
Real-Time Analog Value
D(%Obs)= 0.73 :-----> m(db/m)= 0.10
Initial Reference Value COEFFICIANT TO PERCENTAGE
% Obscuration/Ft m(db/m)= 0.10 :-----> D(%Obs)= 0.73

51 GST TECHNICAL TRAINING – 2013


 I-series Models *I-9101 LPCB very soon!!
 I-9101 – Photo and Heat Detector
 I-9102 – Photo/ Optical Detector
 I-9103 – Fixed and Rate of Rise Detector
 I-9104 – Ultraviolet Flame Detector
 DZ-03 – I series Base
 C-9314 – Remote Indicator
 I-9314 – Door Lamp or addressable
remote indicator
 C-9504 – Base Mount Isolator
 I-9603 – CO Detector

52 GST TECHNICAL TRAINING – 2013


 I-9105R (8-100m) Reflective Beam Smoke Detector
 Wiring To Be Glued

 D1,D2 – 24 V Power Mounting Direction Adjusting Wheel


 Z1,Z2 – Intelligent Loop Comm
Rotary
 K11,K12 – Fire O/p Rack

K21,K22 – Fault O/p


Flexible Cable

 Red Flashing – Normal Reed Switch

 Sensitivity : Level 1: 1.61dB , Level 2: 2.31dB


To Be Glued

 I-9602 – LPG, Natural & Coal Gas Types


 Built-in relay contacts - Gas Valves
 Built-in sounder with 2 stage alarm
 Manual reset and control (on/off) of relay contacts

53 GST TECHNICAL TRAINING – 2013


 DI-Series Models
 DI-9101 – Photo and Heat Detector
 DI-9102 – Photo/ Optical Detector
 DI-9103 – Fixed and Rate of Rise Detector
 DI-9104 – UV flame Detector
 DB-01 – I series Base
 C-9314 – Remote Indicator
 DC-9504 – Base Mount Isolator

54 GST TECHNICAL TRAINING – 2013


Intelligent Modules

 Intelligent Manual Call Point – DI-9204


 Semi-flush or Surface mounted
 Re-settable (non-breaking glass)
 LED indicator – flashes every 3 sec
 Optional
 Flipping plastic cover (C-92FC)
 Weatherproof box (D-92WPB)
 BackBox Surface mount
 Wiring : Z1 +, Z2 -

55 GST TECHNICAL TRAINING – 2013


 Input Modules
 I-9300
 Input - I1 & G
 Loop - Z1 +, Z2 –

 Input / Output
Module
 DI-9301
 Input same as I-
9300
 Loop Powered for
driving Ouput

56 GST TECHNICAL TRAINING – 2013


 Dual Address I/O Module
 I-9303
 External 24 V for driving
output

 Multi-Chanel 16 I/p & 2 O/p


 DI-9309
 3-18 consecutive addresses

57 GST TECHNICAL TRAINING – 2013


 Addressable Sounder Circuit Module
 I-9308
 Isolator Module
 C-9503
 Non Addressable

 Addressable Zone
Monitor Module
 I-9319

58 GST TECHNICAL TRAINING – 2013


 Single Output Module
Z1
Z2

 DI-9302
Z1 Z2

 Loop Powered N L COM NO

 Drive a smoke Vent or fire damper 220V AC

 Addressable Sounder/ Hooter Electrical Tripping Device

 I-9404 - 50mA
 Multiple Tones
 Loop Powered (optional)
 Addressable Sounder and Strobe
 I-9403 - 35mA
 Deep Base – C-94DB

59 GST TECHNICAL TRAINING – 2013


 Addressable Loop powered Sounder/ Strobe
 I-9407
 Provide two tones
 Ultra-high brightness (UHB) red LEDs
 Addressable Flashing Beacon Base
 I-9406 (DZ-03)
 DI-9406 (DB-01))
 Addressable Base Mount Sounder
 I-9402
 DI-9405

60 GST TECHNICAL TRAINING – 2013


 Addressable Sounder Beacon
 I-9301
 84dBA @3 meters
 Beacon Frequency: 20~180 times
 External Power Consumption: 160 mA
 Loop Splitter
 P-9902 (Installed inside panel , Takes one address)
 Connect a T-Tap in Class B / Style 4 Signaling Line Circuit
 Loop Relay Cable Length ≤1000m

 P-9903 (Output side is Class B)

Z1IN Z2IN

Z1o Z2o
P-9903
LOOP
24VIN 24VIN

 Loop length extends 1Km +24V


GND
Loop Device Loop Device

 Current sink of the devices in loop exceeds 300mA

61 GST TECHNICAL TRAINING – 2013


Loop Considerations

 Consider 20% spare addresses per loop for future expansion within
the loop
 Using 1.0mm²-800M-Full Load / Using 1.5mm²-1.0Km-Full Load
 Loop factor:
 I-9402 = 30 per loop
 I-9406 = 30 per loop or (Power Save Mode 80 devices)
 I-9407 = 25 per loop
 I-9300 = 100 per loop
 DI-9301 = 50 per loop
 C-9503 = 10 per loop
 C-9504 = 20 per loop
 Loop Voltage 21-27 V, 300 mA
 Class B – short In out terminals

62 GST TECHNICAL TRAINING – 2013


UL Devices

 Models
 I-9102UL / C-9102UL
 I-9103UL / C-9103UL
 DI-M9204 / DC-M9204
 DZ-03UL
 C-M9503UL
 I-M9300
 I-M9301

63 GST TECHNICAL TRAINING – 2013


Conventional Devices

 D Series
 DB-01D (DP-9907 AEOL) / DB-01 without EOLR
 DC-9101 / DC-9102/ DC-9103
 C Series
 DZ-03D (P-9907 AEOL) / DZ-03
 C-9101 / C-9102 / C-9103 / C-9104
 4 Wire Conventional Optical Detector, 12-28VDC Power, N/O
Relay Output R6601 / R6602
 Standalone Detector - S-9102
 Local Buzzer Alarm, Manual Test Button, Optional Network Function,
9V Battery for Operation of 1 Year

64 GST TECHNICAL TRAINING – 2013


 C-9602LW-NG (LPG/CG) Gas Detector
 220VAC Powered, with Local Buzzer Alarm and Relay Output
 DC-9204
 Conventional Base Mount Sounder
 C-9402 / C-9403 Conventional Combined Sounder and Strobe,
(Certificated by LPCB)
 Electronic 24 VDC Bell
 C-9410 /C-9411

65 GST TECHNICAL TRAINING – 2013


Explosion Proof & Intrinsically Safe

 Explosion proof
 Contain a flash or explosion
 Made of cast aluminum or stainless steel
 Intrinsically safe
 Not cause any sparking or arcing
 Cannot store sufficient energy to ignite a flammable gas or vapor
 Cannot produce a surface temperature high enough to cause ignition
 Such a design need not be explosion proof
 Zener Barrier
 GST-AS-200 - polarised zener barrier w/ earth
 Limiting the energy - Max output current 93mA

66 GST TECHNICAL TRAINING – 2013


 Addressable zone Interface with Zener barrier
 I-9332 – 4-5 Det Max
 Addressable Sounder interface with Zener Barrier
 I-9333 – 1 Sounder Max
 Ex / Intrinsic Devices
Fire LED
 DC-9101 Ex Detection
 D-9107RExd Window
Fault LED
 D-9105RExd
 C-9201Ex
 C-9403EX Cable Junction
Cap
 C-9404EX
 DC-9204EXd
 DB-01EX

67 GST TECHNICAL TRAINING – 2013


Gas Extinguishing Panel

 Addressable
 GST-303/6

 Conventional
 GST-301

68 GST TECHNICAL TRAINING – 2013


Integrated Fire Detection Voice Alarm and Fire
Phone System
 P-9935EVAX IFP8 VT – Note: please check the slot limitations
 Audio part / IN FACP
 GST-MP16X – 1 No.s
 GST-MFA – 1 No.s
 GST-SLC-A – Provide 16 zones So 2 No.s for 20 zones
 Field Amplifier supervised by IFP8VT
 GST-DP – max 8 speaker zones and 16 fire phone ckts – 3No.s
 GST-100E-A – 100 watt Max. 2 No.s in GST-DP for 200 Watt – 6No.s
 FP02 - required for 2nd, 3rd & 4th GST-FPI - NR
 GST-FPI – provides 4 fire phone ckts – 1No.s
 XFMR – 1 No.s

69 GST TECHNICAL TRAINING – 2013


 Speaker
 SSPKCPR
 Red Ceiling or Wall Mounting 6.1” Square X 1.88” Deep, Mounting to a
standard 4”
 Square X 2- 1/8" Deep Back Box • High Quality dBA Output (Intelligible) •
Frequency
 Range 400-4000Hz • Power Taps: 1/8W, 1/4W, 1/2W, 1W, 2W, 4W •
Speaker
 Voltage 25 or 70.7 VRMS Standard, Field Selectable UL Listed.
 Fire Phone :
 GX-FJ – Installed at Field
 GX-FH – Would be less than GX-FJ

70 GST TECHNICAL TRAINING – 2013


Description Unit Qty MODEL REMARKS
Main FACP No. 1 GSTIFP8-VT
Max 3 LCIFP8
No. 1 P-9945A
No. 1 P-9935
Integrated with Main FACP No. 1 P-9935EVAX For Connecting GST-MP16X
No. 1 GST-MP16X 16 Zone Integrated Voice Alarm & Fire Telephone
No. 1 GST-MFA Master Fire Phone Assembly, Includes
No. 1 GST-SLC-A 16 Zone Switch Assembly includes Plate
No. 9 GST-DP Addressable Distributed Panel
Field Amplifiers
No. 9 GVX100E 200 Watt Considered per amplifier with 6 speaker ckt
No. 0 FP02 Interface for FPI
DP Fire Phone Interface, provide 4 Fire Phone Circuits Class
No. 9 GST-FPI
B
No. 9 XFMR Transformer kit
2 way communication Fire
No. GX-FJ max 48 addressable telephone zones available
Fighter's Telephone
2 way communication Fire
No. GX-FH
Fighter's Handset.
Speaker No. SSPKCPR

71 GST TECHNICAL TRAINING – 2013


Standalone Fire Telephone System

 Model
 FT8WN – 8 zone networkable / FT24N – 24 zone networkable
 Field Devices
 P-9911(S) Speaker Fire Telephone Station
 P-9911(F) Fixed Fire Telephone Handset
 P-9911(J) Fire Telephone Jack Socket
 P-9911(M) Fire Telephone Mobile Handset (Red)

72 GST TECHNICAL TRAINING – 2013


Control Room 2 core panel to panel networking Remote substation

PS PS

Each zone - 2 core Twisted Pair, Max impedance of 20 Ohms


for each zone with 10 KOhm EOLR. For ex. 1.5 sqmm polycab
cable with resistance of 13Ohm/Km is used then approx
900m cable can be laid for each zone

P-9911S PTT outstation


Speaker Telephone
1200 Meters

FT8WN- 8 Zone Emergency Telephone system , Networkable to 8 panels


73 GST TECHNICAL TRAINING – 2013
 Call Functions
 Call divert to the main panel after 12 sec.
 Operator can select single or group call
 Operator can ring outstations and fixed
handsets
 Operator can call the other panel
 Considerations
 No. of telephone per zone – 5
 Wiring – Twisted Pair, Max impedance of 20
Ohms for each zone with 10 KOhm EOLR.
 For ex. 1.5 sqmm polycab cable with resistance
of 13Ohm/Km is used then approx 900m cable
can be laid for each zone.
 Frequency Range – 300-3400Khz

74 GST TECHNICAL TRAINING – 2013


GST SOFTWARE

Live Demonstration

75 GST TECHNICAL TRAINING – 2013


Topics

 GST Definition Utility  GST GMC


 GST DEF 2.18  GST GMC 2.1
 Installation  Installation
 Driver / Connection  Registration / Debug
 Zones Configuration  Configuring
 Device Tree  Design Maps
 Backup / Restore  Client
 C&E
 History Logs

76 GST TECHNICAL TRAINING – 2013


BREAK!!

77 GST TECHNICAL TRAINING – 2013


HANDHELD PROGRAMMER

P-9910B

78 GST TECHNICAL TRAINING – 2013


Topics

 Check Parameter
 Address
 Parameter / Sensitivity
 Code
 I2C

79 GST TECHNICAL TRAINING – 2013


Check Parameter

 Turn On (Press Reset if in Sleep


Mode)
 Press “Clear”
 Press “Test”
 Press “UP” …

 Detector & Input Module  Sounders


 Address  Address
 Sensitivity/Parameter  Sensitivity/Parameter
 Device Type  Factory
 Factory code  Device Code (For Sounder)

80 GST TECHNICAL TRAINING – 2013


 I-9403 - CODE & ADDRESS  I-9300 INPUT
 Test - Address  Test - Address
 0 -up  4 - PARAMETER - NO INPUT
 24-up  18 - TYPE
 27 code  13
 I-9103  I-9301 I/O MODULE
 Test – Address  Test - Address
 1 –SENSITIVITY - HIGHEST  4- PARAMETER - N O INPUT
 2 Type R+F HEAT  13 - TYPE
 2  13
 I-9102  DI-9204 PULL
 Test - Address  Test - Address
 1- SENSITIVITY - HIGHEST  4- PARAMETER - NO INPUT
 3 Type Optical  11 – TYPE - MCP
 44  0

81 GST TECHNICAL TRAINING – 2013


Address

 Turn On (Press Reset if in Sleep Mode)


 Press “Clear”
 Enter “Valid” Address
 Press “Program” – Confirm by “P”
 Press “Clear”
 Press “Test” - Verify

82 GST TECHNICAL TRAINING – 2013


Parameter / Sensitivity

 Turn On (Press Reset if in Sleep Mode)


 Press “Clear”
 Enter “456”
 Press “Clear”
 Press “Function” + “3” – Confirm by “-”
 Enter “Valid” Sensitivity / Parameter
 Press “Program” – Confirm by “P”
 Press “Clear”
 Press “Test”
 Press “UP” – Verify

83 GST TECHNICAL TRAINING – 2013


 Sensitivity Level I-9101, I-9102, I-9103, and I-9104
 Level 1 highest sensitivity (Default Setting); Level 2 Standard sensitivity
Level 3 Lowest Sensitivity
 (Optical Smoke: L1-0.10dB/m, L2-0.33dB/m, L3-0.56dB/m)
 (Fixed Temp: L1-54°C, L2-62°C, L3-70°C)
 (Flame: L1-25metres, L2-17metres, L3-12metres)
 Input module I-9300, I-9301, DI-9301, I-9303 (Refer
Datasheet)
 Parameter 4 Normally Open Input (Default Setting)
 Parameter 7 Normally Close Input
 Parameter 1 Cable monitoring only for I-9300
 Parameter 3 Feedback signal - I-9301 (PLANT condition)

84 GST TECHNICAL TRAINING – 2013


 Remote Indicator I-9314
 Parameter 20: Operates on its duplicate address
 Parameter 21: One address
 I-9406 Sounder Strobe Base
 Parameter 1 One Address – 1 to 16 tones (Default Setting)
 Parameter 2 Two addresses (17 to 32 tones)
 Parameter 3 Two addresses (33 to 48 tones)

85 GST TECHNICAL TRAINING – 2013


Code

 Turn On (Press Reset if in Sleep Mode)


 Press “Clear”
 Enter “456”
 Press “Clear”
 Press “Function” + “4” – Confirm by “-”
 Enter “Valid” Code
 Press “Program” – Confirm by “P”
 Press “Clear”
 Press “Test”
 Press “UP”*3 – Verify

86 GST TECHNICAL TRAINING – 2013


 I-9103/ DI-9103 Heat Detector
 Code 2 Dual Function, Fixed and Rate of Rise Temperature (Default Setting)
 Code 4 Fixed Temperature Function
 I-9402 Sounder Base
 Code 100 Operates on its Duplicate Address
 Code 101 Evacuate Tone, One Address (Default Setting)
 Code 102 Alert and Evacuate, 2 Address:1st -Alert: 2nd –Evacuate Tone
 I-9403/ I-9404 Sounder Strobe
 Code 27 Evacuate Tone, One Address (Default Setting)
 Code 121 Alert and Evacuate Tone, 2 Address:1st -Alert: 2nd –Evacuate Tone
 I-9308 Sounder Driver Module
 Code 1 Evacuate Tone, One Address (Default Setting) for C-9403/04
 Code 2 Alert and Evacuate Tones, 2 Addresses for C-9402
 Code 3 Evacuate Tones, One Address for C-9402
 Code 4 Alert and Evacuate Tones, 2 Addresses for C-9403/04

87 GST TECHNICAL TRAINING – 2013


I2C

 Beam Detector and Mimic Panel utilizes I2C based connection


 Addressing of Beam
 Turn on, press the “2,5,9” then the “Function”,
 Input the new address and then press the “Program”
 Shifting Sensitivity of Beam
 Turn on, press the “2,5,9” then the “Function” and press “Clear”
 Press “4,5,6” then “Clear”
 Press “Function” then “3” (display show ‘-‘ dash)
 Enter sensitivity , then the “Program”
 Exit I2C
 Press the “2,5,9” then the “Function”

88 GST TECHNICAL TRAINING – 2013


 Changing Device Code of Beam
 Turn on, press the “2,5,9” then the “Function” and then press the
“Clear”
 Press the “Function” then “4” then press the “4,5,6” and “Clear”
 Press “Function” then “4” (display show ‘-‘ dash)
 Enter device code and then “Program”
 I-9105R Code
 52 Detection Distance between 40 to 100 m (Default Setting)
 51 Detection Distance between 8 to 40 m
 I-9105 Sensitivity
 2 means sensitivity 1 or 3 means sensitivity 2) (Level 1:1.61dB/m and
Level 2:2.31dB/n)

89 GST TECHNICAL TRAINING – 2013


OPERATION & COMMISSIONING

GST 200-2, 5000w, IFP8

90 GST TECHNICAL TRAINING – 2013


Topics

 Check List
 GST 200-2 Operation
 GST 200-2 Commissioning
 GST 5000W Commissioning
 GST IFP Operation
 GST IFP8 Commissioning
 Device Types
 C&E equations and NET option
 Interpreting Events / Troubleshooting

91 GST TECHNICAL TRAINING – 2013


Check List

 Maintain a list of device and detectors on a sheet with Address


provided. Use stickers available on field device.
 Check the continuity of loop.
 Measure the resistance between each conductor and earth ground.
The circuit resistance between a conductors and earth ground
should be infinite.
 Check for short between two conductors
 Maintain a list of device and detectors on a sheet with Address
provided. Use stickers available on field device.
 Connect other wiring like NAC’S, Annunciator, battery etc
 RS232 card, P-9910B Handheld tool
 A laptop installed with GST Def Utility Software
 Laptop should have Native / Virtual RS232 port and USB Ports
 Factory Passwords

92 GST TECHNICAL TRAINING – 2013


GST 200-2 Operation

93 GST TECHNICAL TRAINING – 2013


 SYSTEM [Manager Password Required]
 Time/Date
 Password Change
 Operator Password (8 digits) – 8 times1 Default
 Manager Password (8 digits) - 8 times1 Default
 Super Password – 24220011 – Cannot be Changed
 Network Setup – Check Address Important
 Net Local Address (1-32 address)
 Net Event Display
▫ Disable
▫ Enable

94 GST TECHNICAL TRAINING – 2013


 Zone Start Number
 If Total zones are less than 60 zones create the same zones in all panels.
Like 1-5 for first Panel, 6-10 for Second and so on..
 IFP8 has 999 zones so there is no problem but make sure it does not
conflict
 Zone start number 61,then the real zone1\2\3 of GST200 will show
61/62/63
 Customize
 Output Set-up
▫ Default Output: Device type 13 Sounder activate at alarm in the same zone
▫ C&E Output: The system output will be based on the configured C&E equation
 PAS Delay (000-180 second)*
 Re-Sound Configurations
▫ Another Zone
▫ Self Zone

95 GST TECHNICAL TRAINING – 2013


 Initialize System
 Set the system Main Board into factory setting (Commissioning Password)
 Steps
▫ Press “LOCK” then ENTER
▫ Press “ SYSTEM” then input password 24220011
▫ Press number “6” – Initialize System then
▫ Press number “2” System Initialize
▫ Input password “19491030”
 Disable Battery Impedance
 Devices debug

96 GST TECHNICAL TRAINING – 2013


 MODE [Operator password required]
 1 LCD Contrast : (0-100)
 Display Mode
 Zone Mode : by zone detail
 Loop Mode : by point device detail
 Print Mode
 Disable
 Only Fire : Automatic print on fire event
 All History: Pressing PRINT when viewing history records can print out the
messages being viewed

97 GST TECHNICAL TRAINING – 2013


 PAS Setup * (Positive Alarm Sequence)
 Disable
 Enable
▫ Pre-alarm Window: pre-programmed15 seconds. A distinctive pre-alarm
indication shall be displayed.
▫ Alarm Verification window: programmable from 0 to 180 seconds. The system
shall response to a second alarm from any device as the system alarm
 Start Devices (manually start)
 ZONE(3)_ADDRESS(3)_DEVICE TYPE(2) – 8 Digits
▫ 001***13- Sounder
 Stop Devices (manually stop)

98 GST TECHNICAL TRAINING – 2013


 TEST [Operator Password required]
 Display Test - check the LED and LCD
 Each Zone In Test
 Stop a Zone Test
 Stop All Zones Test

TEST MODE LED ON ZONE LED YELLOW

99 GST TECHNICAL TRAINING – 2013


 ENABLE/DISABLE [Operator Password Required]
 Disable Devices
 Each Zone Fully
 Individual Point
 All Loop Sounder
 Use Device Code
 Enable Devices
 Each Zone Fully
 Individual Point
 All Loop Sounder
 Use Device Code
Note :
 Address - Loop: 1 Point : 001
 Device Code - 00112503 Optical

100 GST TECHNICAL TRAINING – 2013


 Dis/En-able Output
 Sounder Circuit
 F.P.E Output
 Dis/En-able Delays:
 Disable
 Enable-The Panel will delay the output base on the configured C&E
equation
 Delete Net Disable

101 GST TECHNICAL TRAINING – 2013


 Browse
 Loop Devices:
 View number of devices per loop
 Detailed provided with each device
 Zone Devices: Total Input devices per zone
 Group Device: Total number of Output devices per zone
 In Test Mode Zones
 COM Devices: View the number of Control Panel and Repeater panel
connected in the system
 Access: Control switch and zone indicator detailed.
 Browsing C&E: Sequence of operation detailed

102 GST TECHNICAL TRAINING – 2013


GST 200-2 Commissioning

 Auto Learn / Registration


 Press “System” Enter the password “24220011” & Press “Enter”
 Press “SK1 button” behind the door
 (Note: procedure should be done within 25 seconds otherwise the control
panel will initialize the normal panel reset)
 After the registration HL1 on RS232 board will be flashing strong
 Check the number of devices registered. (Browse > Loop
Devices)

103 GST TECHNICAL TRAINING – 2013


 Connect the PC to Panel
 Upload – Retrieve the information from panel
 Check the devices which get “True”
 If any devices not registered check the issue on field
 Software Configuration
 Provide Label – Just Location
 Assign device types via software
 Create Zone and assign them
 Create C&E if required
 Connect the PC to Panel
 Download – Send the data to panel

104 GST TECHNICAL TRAINING – 2013


GST 5000W Commissioning

CONNECT THE LOOP & By default the Panel is in


POWER UP THE PANEL Commissioning mode

SELECT : SYSTEM > 3 WORKING RESTART PANEL OR PRESS TEST


COMMISSIONING MODE NO STATE SETUP > 2 COMMISSION BUTTON (SELF TEST) – CALLED
? MODE MANUAL REGISTRATION

YES

AUTOMATIC REGISTRATION
BROWSE DEVICES DEFAULT
OF DEVICES
: NO PASSWORD

UPLOAD DATABASE
CHECK CABLE , DUAL
FROM PANEL TO YES IF DEVICES AS NO ADDRESSING AND REGISTER
GST DEF USING P- EXPECTED? AGAIN
9931

LABEL / ZONES / EQUATION SET THE WORKING STATE AS


DOWNLOAD TO PANEL MONITORING MODE

105 GST TECHNICAL TRAINING – 2013


GST IFP8 Operation

106 GST TECHNICAL TRAINING – 2013


*SYSTEM SETUP*

 System Setup > Programming ********************************


1.PROGRAMMING

 DEVICE SET-UP 2. LOCAL OUTPUT SET-UP


3. WORKING STATE SET UP
4. COMMISSIONING
 Zone: Zone assignment FAR: OK FPE: OK OTS: OK 13:01:06

 Device Type: Selection of device type.


 Attribute: Detector sensitivity/For output signal - 0-on/off ; 1-continoues
 Location: Device location information , max 40 characters

*DEVICE SETUP*

Loop: 01 Address(1-242) : 001


********************************
ZONE (I-999) : 001
DEVICE TYPE: 03- Optical Smoke
ATTRIBUTE (1-6) : 6
TEXT (40 Byte) :
MANAGER ROOM

FAR: OK FPE: OK OTS: OK 13:01:08

107 GST TECHNICAL TRAINING – 2013


 ZONE SET-UP
 Dependency Mode:
▫ 0-Off: Panel display Fire immediately- No Pre-alarm feature
▫ 1-Type A: Enable Pre-alarm/ The system shall response to a second alarm
from any device in the same zone as the system alarm
▫ 2-Type B: Enable Pre-alarm/ The system shall response to a second alarm
from any device in the same or other zone as the system alarm
 Zone Sounder Mode
▫ 0-Sound By Zone Fire *ZONE SETUP*

ZONE (1-999) : 001


▫ 1-On E&C *****************************
DEPENDENCY TYPE (0-2) : 0-OFF
SOUNDER MODE (0-1) : 1-ON C&E
RESOUND MODE (0-1) : 1- Resound by New Fire
ZONE LED (1-140) : 001
TEXT (40 Byte) :
GROUND FLOOR
FAR: OK FPE: OK OTS: OK 13:01:08

108 GST TECHNICAL TRAINING – 2013


 Zone Resound Mode
▫ 0-No Resound: Sounder will not alarm if
new fire from the other zone after being
silenced
▫ 1-Resound by New Fire: Sounder will alarm if new fire from other zone after
being silenced
 Zone LED: 1-140 LED
 TEXT: Up to 40 characters
 COMMUNICATION SET UP
 DAY/NIGTH TIME SETUP
 MODIFY PASSWORD SETUP
 C&E EQUATION SETUP
 DEVICE TYPE SETUP

109 GST TECHNICAL TRAINING – 2013


*SYSTEM SETUP*

 System Setup > Commissioning ********************************


1.PROGRAMMING

 DEVICE LEARN 2. LOCAL OUTPUT SET-UP


3. WORKING STATE SET UP
4. COMMISSIONING
 DUPLICATED ADDRESS CHECK FAR: OK FPE: OK OTS: OK 13:01:06

 Panel must be set to “Commissioning Mode”


 The system must initialize to “Digital Mode”
 To find out the duplicated address:
▫ User Setup→1 Browse→4 Browse Duplicated Address
 Enter the loop which have duplicated addresses to view the addresses
DUPLICATED ADDRESS CHECKING CARD SUM: 03 LOOP SUM: 04 SUM:0012
Please wait……
Press [Cancel] to Exit! ********************************
LOOP 1: Loop Card, Dupli. Add. Sum : 000
LOOP 2: Loop Card, Dupli. Add. Sum : 001
FAR: OK FPE: OK OTS: OK 13:01:07 LOOP 3: Loop Card, Dupli. Add. Sum : 000
LOOP 4: Loop Card, Dupli. Add. Sum : 000
LOOP 5: Net Card-01, Net Sum: 02
DUPLICATED ADDRESS CHECKE OK LOOP 6: CRT CARD -01
Duplicated Address Sum: 001
→F1 to print LOOP DEVICES info
→F2 –Found devices F3- Missed devices

FAR: OK FPE: OK OTS: OK 13:01:07 FAR: OK FPE: OK OTS: OK 13:14:15

110 GST TECHNICAL TRAINING – 2013


 MODIFY ADDRESS *MODIFY ADDRESS*

Loop: 01 Address(1-242) : 001


 The panel must be set to “Commissioning ********************************
Mode” USER CODE : 00100115
SERIAL NO.: 0000BB40
 To change the address NEW CODE: 002

▫ Enter the loop number and address you


wish to change
▫ Type the new address into “NEW CODE” FAR: OK FPE: OK OTS: OK 13:01:08

then Enter
*MODIFY DEVICE SENSITIVITY*
 MODIFY DEVICE SENSITIVITY Loop: 01 Address(1-242) : 001
 3 LEVELS OF SENSITIVITY ********************************

▫ LEVEL 1: HIGHEST SENSITIVITY USER CODE : 00100115


DEVICE TYPE: MULTISENSOR
▫ LEVEL 2: STANDARD SENSITIVITY SENSITIVITY: 1- SENSITIVITY 1
NEW SENSITIVITY: 0

▫ LEVEL 3: LOWEST SENSITIVITY


▫ LEVEL 4/5/6: FOR FUTURE USE
FAR: OK FPE: OK OTS: OK 13:01:08

111 GST TECHNICAL TRAINING – 2013


 COMMISSION IN ANALOG MODE
 Normal Status: Range 450 to 650
 Alarm Status : Range 900 to 1200
 Fault Status : Range 1 to 120
 COMMISSION IN DIGITAL MODE – Future Use
 SYSTEM INITIALIZATION
 Detector : Indicate the current mode
Detector: Analog Mode
 Digital mode : to have access in the following Press [1] Initialize detector in digital mode
▫ Duplicated Address Check Press [2] Initialize detector in analog mode
Press [3] To Initialize the system
▫ Modify Address Press [4] To disable the battery resistance
Press [5] To hide sounder plant item

▫ Modify Device Sensitivity FAR: OK FPE: OK OTS: OK 13:01:07

 Analog mode: Default mode and must be used as the


working mode

112 GST TECHNICAL TRAINING – 2013


 Initialize System: To reset the main control card – this will delete the
configuration of Zone LED, Equation and Device type list
▫ Use Password “20080512”
Warning!! Make sure you have the back up data base
 Hide Sounder Plant Item – if you wish not to shown the active sounders

113 GST TECHNICAL TRAINING – 2013


*USER SETUP*

 User Setup > Browse ********************************


1.BROWSE
 Browse Devices: Number of devices per loop 2. CLOCK
3. PRINTER SETUP
4. DELAY MODE
 Browse Zones: Total I/P devices per zone 5. ACKNOWLEDGE TIMER
6. TEST SETUP

 Browse Groups: Total O/p devices per Zone 7. START/STOP DEVICE


8. DISABLE/ENABLE

 Browse Duplicated Address


 Browse Panel Status: Panel configuration and version
 Browse C&E Equation *BROWSE*

 History LOG ********************************


1.BROWSE DEVICES
 Fire History 2 BROWSE ZONES
3.BROWSE GROUPS
4.BROWSE DUPLICATED ADDRESS
 Common History 5.BROWSE PANEL STATUS
6.BROWSE C&E EQUATION
 Initialization 7. HISTORY LOG

FAR: OK FPE: OK OTS: OK 13:01:07

114 GST TECHNICAL TRAINING – 2013


*USER SETUP*

 User Setup > Delay Mode ********************************


1.BROWSE
 Commission or Monitor Mode 2. CLOCK
3. PRINTER SETUP
4. DELAY MODE
 Disable - No output delay 5. ACKNOWLEDGE TIMER
6. TEST SETUP

 Enable - Enable the Equations delay time 7. START/STOP DEVICE


8. DISABLE/ENABLE

 Note: The Delay Mode LED will turn ON

 Enabling the delay outputs based on C&E equation:


 Enable the delay command form DELAY MODE SETUP
 Configured the system “DAY TIME” form DAY/NIGTH SETUP
 Configured the zone mode parameter into 1- on C&E from the ZONE
SETUP

115 GST TECHNICAL TRAINING – 2013


*USER SETUP*

 User Setup > Acknowledge Timer ********************************


1.BROWSE
 EN54 P2-7.12 2. CLOCK
3. PRINTER SETUP
 PAS Day Mode 4. DELAY MODE
5. ACKNOWLEDGE TIMER
6. TEST SETUP
 Pre-alarm Window - 1 sec. to 30 min. 7. START/STOP DEVICE
8. DISABLE/ENABLE
 Alarm Verification window - 1 sec. to 30 min.
 PAS Night Mode (Default setting)
 Pre-alarm Window
▫ Type A - Auto-reset the Alarm in the Panel after 30
min
▫ Type B - Auto-reset the Alarm in the Panel after 5 *ACKNOWLEDGE TIMER*

min ********************************
1.Please input the Pre-Alarm ACK time:
 Type A - Activate when second alarm in same Phase 1 (Default 30S) : [00] M - [30] S
2.Please input the Pre-Alarm Verify time:
zone Phase 2 (Default 2M) : [02] M - [00] S

 Type B - Activate when second alarm in any zone

116 GST TECHNICAL TRAINING – 2013


*USER SETUP*

 User Setup > Test Setup ********************************


1.BROWSE
 Commission or Monitor Mode 2. CLOCK
3. PRINTER SETUP
4. DELAY MODE
 Setup Test Zone 5. ACKNOWLEDGE TIMER
6. TEST SETUP
 Input test zone : (1-999) 7. START/STOP DEVICE
8. DISABLE/ENABLE

 Input test mode : (0-1)


▫ 0-Without sounder
▫ 1-With sounder – Automatic Stop after 10
*TEST SETUP*
seconds
********************************
1.LED BUZZER TEST
2 LOCAL OUTPUT TEST
3. SETUP TEST ZONE
4. CANCEL TEST ZONE

FAR: OK FPE: OK OTS: OK 13:01:07

117 GST TECHNICAL TRAINING – 2013


GST IFP8 Commissioning

 Auto Learn / Registration


 The control panel is set in COMMISIONING MODE by default, once it is
powered ON, the system immediately after the start-up will
automatically initialize the REGISTRATION process.
 If the system set to MONITORING MODE change the setting by
 (System Setup→ 3 Working State Set-up→ select 1 Commissioning State)

Device Learn)
X

FIRE CONTROL PANEL IFP8

Wed 13 Jan 2012

Panel Healthy

FAR: OK FPE: OK OTS: OK 13:14:15

118 GST TECHNICAL TRAINING – 2013


 Check the Registered devices
 Press “User Setup”, No password (Default password) then press Enter
 Press “Browse Devices”
 Select the loop number using UP/Down arrow and then press Enter
CARD SUM: 03 LOOP SUM: 04 SUM:0012 Loop01: Loop Card, Devices SUM:003

******************************** ********************************
LOOP 1: Loop Card, Devices Sum: 003 D001 Group 001 Loop 1 Lift
LOOP 2: Loop Card, Devices Sum: 003 Mechanical Room
LOOP 3: Loop Card, Devices Sum: 003 D002 Zone-001 Loop 1 Optical Smoke
LOOP 4: Loop Card, Devices Sum: 003 Manager Room
LOOP 5: Net Card-01, Net Sum: 02 D003 Zone-001 Loop 1 Optical Smoke
LOOP 6: CRT CARD -01 Secretary Room
D004 Zone-001 Loop 1 Heat Detector
→F1 to print LOOP DEVICES info Pantry
→F2 –Found devices F3- Missed devices

FAR: OK FPE: OK OTS: OK 13:14:15 FAR: OK FPE: OK OTS: OK 13:14:15

119 GST TECHNICAL TRAINING – 2013


 Registration of RS232 download card (Hardware)
 Identify the loop number of the P-9935 card by pressing “User Set-up”
 Select 1 Browse Devices
 Press “System Setup” (No password) Press “Enter”
 Press “1 Programming” and then “3 Communication Set-up”
 Press “1 Monitor Interface”
▫ Please input loop number: (1:10)
▫ Please input panel address: (1-32)

120 GST TECHNICAL TRAINING – 2013


 Connect the PC to Panel
 Upload – Retrieve the information from panel
 Check the devices which get “True”
 If any devices not registered check the issue on field
 Software Configuration
 Provide Label – Just Location
 Assign device types via software
 Create Zone and assign them
 Create C&E if required
 Connect the PC to Panel
 Download – Send the data to panel

121 GST TECHNICAL TRAINING – 2013


 Zone Mode:
 0-Off: Panel display Fire immediately- No Pre-alarm feature
 1-Type A
 2-Type B
 Zone Sounder Mode
 0-Sound By Zone Fire
 1-On E&C
 Zone Resound Mode
 0-No Resound: Sounder will not alarm if new fire from the other zone
after being silenced
 1-Resound by New Fire
 Zone LED: 1-140 LED

122 GST TECHNICAL TRAINING – 2013


 Define net units on IFP8
 SYSTEM SETUP > Device setup OR via Software
 Scenario
▫ 1 loop card, card 1, loop address is 1and 2.
▫ 1 network card, card 2, loop address is 3
▫ 1 download card, card 3, loop address is 4.
 LOOP 3
▫ Address 1, 255001 net unit, IFP8 panel
▫ Address2 , 255002,net unit ,NRP01
 The zone should be 255, device type should be 39(Net unit).

123 GST TECHNICAL TRAINING – 2013


Device Types

 GST 200-2  IFP8

Device Type Type Description Device Type Type Description


1-11 FIRE 1-11 FIRE
12-30 ACTION 12-30 ACTION
13 SOUNDER 13 SOUNDER
31-40 FAULT
41-50 SUPERVISORY
51-65 ACTION
66-99 PANEL

124 GST TECHNICAL TRAINING – 2013


C&E equations and NET option

 GST 200-2
 G/S60 242 99 = G/S60 242 99
99
 Zone Address Device Type Zone Address Device
Type Delay
 Cause
 G01 020 03 - Address 20 Optical smoke in Zone 1 (By Point)
 S02 001 11 - At least 1 (Amount) MCP regardless of address in Zone 2 (By
Zone)
 S** 002 02 - 2(Amount) Heat det. should alarm at same time in the entire area
(Global)
 Effect
 S**001 31 12 meaning latch all lift module after (10 Times!!) 2 minutes –
regardless of quantity.
 Sample
 S01 001 11 + S01 00103 + S0100103 = S0100113 00 S**00113 06

125 GST TECHNICAL TRAINING – 2013


 IFP8
 Cause
 001 020 0 - Address 20 Optical smoke in Zone 1 (By Point)
 001 *** 03 - At least 1(any address) Optical smoke in Zone 1 (By Zone)
 *** *** 02 - At least 1(any address) Heat det. in the entire area (Global)
 Effect
 XXX XXX 13 03 means sounder global alarm after 30 seconds (Global)
 Sample
 001 *** 11 + 001 *** 03 + 001 *** 02 = 001*** 13 00, *** *** 13 06
 Note:
 Logic: AND Logic (x), OR Logic (+)
 Fuzzy Logic: Asterisk (* value 1-9)
 Net Option – In Software is used for inter-panel C&E

126 GST TECHNICAL TRAINING – 2013


Interpreting Events / Troubleshooting

 GST200-2
 Loop SW – loop wiring problem, check the following (open circuit,
short circuit between cores, cores toscreen or cores to building earth.)
and make sure the loop is not exceed to 1.2Km.
 CRT Fault – Download card is not communicating with the computer,
turn-off the panel and removed the card after commissioned the
system.
 System cannot register the device/s
 Check the panel if it set to Commissioning Mode
 If the cable exceed to 1.2Km the succeeding devices will not register
(Loop In is the standby voltage)
 Check the device wiring and terminal polarity
 Check the address on the device

127 GST TECHNICAL TRAINING – 2013


 GST IFP8
 ZoneDir - Zone indication board fault, not able to communicate with
main board
 Battery fault or low voltage (not able to charge)
 Ground fault - loop grounding
 Loop Short - Loop cable short circuit
 Loop Board - Loop card fault
 Power Board / Power Box - Internal psu to Panel communication fault,
either cause by loose connection or internal PSU fault
 BAT Resistance - Battery internal resistance value high nearly damage
or not proper connect

128 GST TECHNICAL TRAINING – 2013


IFP8 GST200-2
001:23-JAN 14 :15 group00 sum 004 control panel
internal info 001 of 007 fault
z000 n2 - n001 loopsw
00123- JAN 12.11 L03 D003 LOOP SW PANEL -01 loop-03 fault
00423-JAN 12.22 L00 D00 BATTERY z000 n2 - n001 battery fault
002:23-JAN 14:15 group003 sum002 /008 Ist floor
001:23 jan 14:15 l03 d047 SOUNDER STROBE LIFT z003 n2 - n047 VA.Module Lift
LOBBY Lobby
002:23 - jan 14:15 l03 d054 SOUNDER STROBE CMD z003 n2 - n054 VA.Module CMD
CABIN CABIN
001:27 JAN ZONE 001 SUM 001 / 096 BASEMENT
001:27 JAN L01 D002 PS AC DEPT CABIN Z001 N2 - N002 PS AC DEPT CABIN
ZONE SUM 001 NET 07 FLOOR 001 of 001 FAULT
ZONE 009 SUM 001 NETD008 PASSAGE FIRE Z009 l1 - N008 PHS PASSAGE FIRE
129 GST TECHNICAL TRAINING – 2013
HANDS ON

Commission GST 200-2 DEMO PANEL

130 GST TECHNICAL TRAINING – 2013


Topics

 Field Devices Wiring and Addressing


 GST 200 Wiring
 GST 200 Commissioning
 GST GMC (Debug)

131 GST TECHNICAL TRAINING – 2013


Thank You