technical data
technical data
TABLE OF CONTENTS
II Air-cooled selection procedure
Enter indoor unit capacity tables at given indoor and outdoor temperature.
Select the unit that the capacity is the nearest to and higher than the given load.
3
NOTE
1 Individual indoor unit capacity is subject to change by the combination. Actual capacity has to be calculated according to the combination by using
outdoor units capacity table.
Allowable combinations are indicated in indoor unit combination total capacity index table.
In general, oudoor units can be selected as follows though the location of the unit, zoning and usage of the rooms should be considered.
The indoor and outdoor unit combination is determined that the sum of indoor unit capacity index is nearest to and smaller than the capacity index at
100 % combination ratio of each outdoor unit. Up to 32 indoor units can be connected to one outdoor unit. It is recommended to choose a larger
outdoor unit if the installation space is large enough.
If the combination ratio is higher than 100 %, the indoor unit selection will have to be reviewed by using actual capacity of each indoor unit.
Then, correct the indoor unit capacity according to the piping length.
If the corrected capacity is smaller than the load, the size of indoor unit has to be increased. Repeat the same selection procedure.
Room A B C D E F G H
Load (kW) 2.2 2.1 5.5 4.0 3.5 2.6 3.5 4.2
Room A B C D E F G H
Load (kW) 2.2 2.1 5.5 4.0 3.5 2.6 3.5 4.2
Unit size 25 25 63 50 40 32 40 50
Capacity 2.4 2.4 6.1 4.8 3.8 3.1 3.8 4.8
4 Correction factors
3D060819
NOTES
1 These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.
2 With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out.
3 Method of calculating A/C (cooling / heating) capacity:
The maximum A/C capacity of the system will be either the total A/C capacity of the indoor units obtained from capacity characteristics table or the maximum A/C capacity of outdoor
units as mentioned below, wichever smaller.
Calculating A/C capacity of outdoor units
• Condition: Indoor unit combination ratio does not exceed 100%
Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the 100% combination
x Capacity change rate due to piping length to the farthest indoor unit
• Condition: Indoor unit combination ratio exceeds 100%
Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the combination
x Capacity change rate due to piping length to the farthest indoor unit
4 When overall equivalent pipe length is 90m or more, the diameter of the main gas and liquid pipes (outdoor unit-branch sections) must be increased. (Consider the equivalent pipe length of
function unit as 6mm) Overall equivalent pipe length
Diameter of above case
Model gas liquid
RTSYQ10PY1(E) ø 25.4 ❈ ø 12.7 Indoor unit
Outdoor Function Branch
unit unit
❈If available on the site, use this size. Otherwise, not increased.
5 Read cooling/heating capacity rate of change in the above figures based on the following equivalent length.
Overall equivalent length =
(Equivalent length to main pipe) x correction factor + (equivalent length after branching)
Choose a correction factor from the following table.
When cooling capacity is calcurated: gas pipe size
When heating capacity is calcurated: liquid pipe size. Equivalent length Equivalent length
Rate of change correction factor
(object piping) standard size Size increase
Cooling (gas pipe) 1.0 0.5 Indoor unit
Outdoor Gas pipe: size increase
Heating (liquid pipe) 1.0 0.7 liquid pipe: size increase Branch
unit Function
In the above case unit
(Cooling) Overall equivalent length = 80mx0.5+40m=80m
(Heating) Overall equivalent length = 80mx0.2+40m=56m
The rete of change in cooling capacity when Hp=0m is thus approximatly 0.87
heating capacity when Hp=0m is thus approximatly 1.0
EXPLANATION OF SYMBOLS
Hp : Level difference (m) between indoor and outdoor units where indoor unit in inferior position
HM : Level difference (m) between indoor and outdoor units where indoor unit in superior position
L : Equivalent pipe length (m)
α : Rete of change in cooling/heating capacity
[Diameter of the main pipes (standard size)]
Model gas liquid
RTSYQ10PY1 (E) ø 22.2 ø 9.5
[Temper grade and thickness]
Temper grade 0 Type 1/2H Type
Outer diameter ø 9.5 ø 12.7 ø 22.2 ø 25.4
Minimum wall thickness 0.80 0.80 0.80 0.88
3D060820
NOTES
1 These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.
2 With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out.
3 Method of calculating A/C (cooling / heating) capacity:
The maximum A/C capacity of the system will be either the total A/C capacity of the indoor units obtained from capacity characteristics table or the maximum A/C capacity of outdoor
units as mentioned below, wichever smaller.
Calculating A/C capacity of outdoor units
• Condition: Indoor unit combination ratio does not exceed 100%
Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the 100% combination
x Capacity change rate due to piping length to the farthest indoor unit
• Condition: Indoor unit combination ratio exceeds 100%
Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the combination
x Capacity change rate due to piping length to the farthest indoor unit
4 When overall equivalent pipe length is 90m or more, the diameter of the main gas and liquid pipes (outdoor unit-branch sections) must be increased. (Consider the equivalent pipe length of
function unit as 6mm) Overall equivalent pipe length
Diameter of above case
Model gas liquid
RTSYQ14PY1(E) not increased ø 15.9 Indoor unit
Outdoor Function Branch
unit unit
5 Read cooling/heating capacity rate of change in the above figures based on the following equivalent length.
Overall equivalent length =
(Equivalent length to main pipe) x correction factor + (equivalent length after branching)
Choose a correction factor from the following table.
When cooling capacity is calcurated: gas pipe size
When heating capacity is calcurated: liquid pipe size. Equivalent length Equivalent length
Rate of change correction factor
(object piping) standard size Size increase
Cooling (gas pipe) 1.0 / Indoor unit
Outdoor Gas pipe: size increase
Heating (liquid pipe) 1.0 0.3 liquid pipe: size increase Branch
unit Function
In the above case unit
(Cooling) Overall equivalent length = 80mx1.0+40m=120m
(Heating) Overall equivalent length = 80mx0.3+40m=64m
The rete of change in cooling capacity when Hp=0m is thus approximatly 0.88
heating capacity when Hp=0m is thus approximatly 1.0
EXPLANATION OF SYMBOLS
Hp : Level difference (m) between indoor and outdoor units where indoor unit in inferior position
HM : Level difference (m) between indoor and outdoor units where indoor unit in superior position
L : Equivalent pipe length (m)
α : Rete of change in cooling/heating capacity
[Diameter of the main pipes (standard size)]
Model gas liquid
RTSYQ14PY1 (E) ø 28.6 ø 12.7
[Temper grade and thickness]
Temper grade 0 Type 1/2H Type
Outer diameter ø 12.7 ø 15.9 ø 28.6
Minimum wall thickness 0.80 0.99 0.99
3D060821
NOTES
1 These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.
2 With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out.
3 Method of calculating A/C (cooling / heating) capacity:
The maximum A/C capacity of the system will be either the total A/C capacity of the indoor units obtained from capacity characteristics table or the maximum A/C capacity of outdoor
units as mentioned below, wichever smaller.
Calculating A/C capacity of outdoor units
• Condition: Indoor unit combination ratio does not exceed 100%
Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the 100% combination
x Capacity change rate due to piping length to the farthest indoor unit
• Condition: Indoor unit combination ratio exceeds 100%
Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the combination
x Capacity change rate due to piping length to the farthest indoor unit
4 When overall equivalent pipe length is 90m or more, the diameter of the main gas and liquid pipes (outdoor unit-branch sections) must be increased. (Consider the equivalent pipe length of
function unit as 6m) Overall equivalent pipe length
Diameter of above case
Model gas liquid
RTSYQ16PY1(E) ø 31.8 ❈ ø 15.9 Indoor unit
Outdoor Function Branch
unit unit
❈If available on the site, use this size. Otherwise, not increased.
5 Read cooling/heating capacity rate of change in the above figures based on the following equivalent length.
Overall equivalent length =
(Equivalent length to main pipe) x correction factor + (equivalent length after branching)
Choose a correction factor from the following table.
When cooling capacity is calcurated: gas pipe size
When heating capacity is calcurated: liquid pipe size. Equivalent length Equivalent length
Rate of change correction factor
(object piping) standard size Size increase
Cooling (gas pipe) 1.0 0.5 Indoor unit
Outdoor Gas pipe: size increase
Heating (liquid pipe) 1.0 0.3 liquid pipe: size increase Branch
unit Function
In the above case unit
(Cooling) Overall equivalent length = 80mx0.5+40m=80m
(Heating) Overall equivalent length = 80mx0.3+40m=64m
The rete of change in cooling capacity when Hp=0m is thus approximatly 0.88
heating capacity when Hp=0m is thus approximatly 1.0
EXPLANATION OF SYMBOLS
Hp : Level difference (m) between indoor and outdoor units where indoor unit in inferior position
HM : Level difference (m) between indoor and outdoor units where indoor unit in superior position
L : Equivalent pipe length (m)
α : Rete of change in cooling/heating capacity
[Diameter of the main pipes (standard size)]
Model gas liquid
RTSYQ16PY1 (E) ø 28.6 ø 12.7
[Temper grade and thickness]
Temper grade 0 Type 1/2H Type
Outer diameter ø 12.7 ø 15.9 ø 28.6 ø 31.8
Minimum wall thickness 0.80 0.99 0.99 1.10
3D060822
NOTES
1 These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.
2 With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out.
3 Method of calculating A/C (cooling / heating) capacity:
The maximum A/C capacity of the system will be either the total A/C capacity of the indoor units obtained from capacity characteristics table or the maximum A/C capacity of outdoor
units as mentioned below, wichever smaller.
Calculating A/C capacity of outdoor units
• Condition: Indoor unit combination ratio does not exceed 100%
Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the 100% combination
x Capacity change rate due to piping length to the farthest indoor unit
• Condition: Indoor unit combination ratio exceeds 100%
Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristic table at the combination
x Capacity change rate due to piping length to the farthest indoor unit
4 When overall equivalent pipe length is 90m or more, the diameter of the main gas and liquid pipes (outdoor unit-branch sections) must be increased. (Consider the equivalent pipe length of
function unit as 6m) Overall equivalent pipe length
Outdoor
Diameter of above case unit
EXPLANATION OF SYMBOLS
Hp : Level difference (m) between indoor and outdoor units where indoor unit in inferior position
HM : Level difference (m) between indoor and outdoor units where indoor unit in superior position
L : Equivalent pipe length (m)
α : Rete of change in cooling/heating capacity
[Diameter of the main pipes (standard size)]
Model gas liquid
RTSYQ20PY1 (E) ø 28.6 ø 15.9
[Temper grade and thickness]
Temper grade 0 Type 1/2H Type
Outer diameter ø 15.9 ø 19.1 ø 28.6 ø 31.8
Minimum wall thickness 0.99 0.80 0.99 1.10
RTSYQ-P
3
INTEGRATED HEATING CAPACITY COEFFICIENT
The heating capacity tables do not take account of the reduction in capacity, when frost has accumulated or while the defrosting operation is in progress.
The capacity values, which take these factors into account, in other words, the integrated heating capacity values, can be calculated as follows:
Formula:
Integrated heating capacity = A
Value given in table of capacity characteristics = B
Integrated correction factor for frost accumulation = C
A=BxC
Outdoor Temperature° CDB (° CWB) -7 (-7.6) or less -5 (-5.6) -3 (-3.7) 0 (-0.7) 3 (2.2) 5 7 (6.0)
Correction factor defrost 0.95 0.93 0.88 0.85 0.86 0.90 1.00
0 Time
1 cycle
3TW27232-7
NOTE
1 The figure shows that the integrated heating capacity expresses the integrated capacity for a single cycle (from defrost operation to defrost
operation) in terms of time.
Please note that, when there is an accumulation of snow against the outside surface of the outdoor unit heat exchanger, there will always be a
temporary reduction in capacity, although this will of course vary in degree in accordance with a number of other factors, such as the outdoor
temperature (°CDB), relative humidity (RH) and the amount of frosting which occurs.
Liquid side junction Discharge gas side junction Suction gas side junction
KHRP22M64T8
I.D. J12.70
3
I.D. J10 I.D. J31.80
I.D. J15.90 I.D. J19.10 I.D. J38.10 I.D. J31.80
I.D. J9.52 I.D. J15.90
I.D. J15.90 I.D. J25.40
I.D. J12.70 I.D. J19.10
I.D. J25.40
I.D. J31.80
KHRP22M75T8
I.D. J38.10
I.D. J15.90 I.D. J12.70
I.D. J19.10
I.D. J38.10
I.D. J15.90 I.D. J19.10
I.D. J19.10 I.D. J22.20 I.D. J44.50
I.D. J19.10
I.D. J12.70 I.D. J9.52 I.D. J22.20
I.D. J19.10
I.D. J19.10
I.D. J12.70 I.D. J9.52 I.D. J25.40 I.D. J22.20
I.D. J9.52
I.D. J9.52 I.D. J6.35 I.D. J15.90 I.D. J12.70
I.D. J31.80
I.D. J15.90 I.D. J19.10 I.D. J38.10 I.D. J31.80
I.D. J19.10 I.D. J22.20
I.D. J15.90
I.D. J12.70 I.D. J25.40 I.D. J19.10
I.D. J15.90
I.D. J15.90
KHRP23M33T8
I.D. J15.90
KHRP23M64T8
I.D. J15.90 I.D. J25.40 I.D. J19.10 I.D. J28.60 I.D. J25.40
I.D. J12.70
I.D. J25.40
I.D. J31.80
KHRP23M75T8
I.D. J15.90
I.D. J25.40 I.D. J19.10 I.D. J38.10
I.D. J15.90 I.D. J12.70
I.D. J19.10
I.D. J6.35
KHRQ23M20T8
I.D. J15.90
KHRQ23M64T8
I.D. J15.90
KHRQ23M75T8
I.D. J28.60
I.D. J15.90 I.D. J25.40 I.D. J19.10 I.D. J25.40
I.D. J12.70
I.D. J19.10
I.D. J19.10
I.D. J12.70
I.D. J9.52
Closed pipes
O.D. J15.90
O.D. J19.10
1TW25799-4C
I.D. J6.35 (6x) I.D. J15.90 I.D. J15.90 (2x) I.D. J12.70 (5x)
I.D. J6.35 (2x) I.D. J9.52 (6x) I.D. J19.10
I.D. J15.90
I.D. J15.90 I.D. J19.10
3
I.D. J15.90 I.D. J22.20
I.D. J31.80
KHRQ22M75H8
I.D. J31.80
I.D. J19.10
I.D. J15.90 I.D. J22
I.D. J9.52 (3x) I.D. J9.52 (3x) I.D. J12.70 (3x) I.D. J19.10 (3x) I.D. J12.70 (3x) I.D. J12.70 (3x)
I.D. J15.90 (3x) I.D. J15.90 (3x)
I.D. J9.52 (2x)
KHRQ23M64H8
I.D. J15.90
I.D. J9.52 (3x) I.D. J19.10 (2x)
I.D. J28.60 I.D. J15.90
I.D. J15.90
I.D. J9.52 (3x) I.D. J19.10 (2x)
I.D. J28.60 I.D. J15.90
I.D. J9.52 I.D. J12.70 I.D. J9.52 (3x) I.D. J12.70 (3x)
KHRQ127H8
I.D. J19.10
I.D. J15.90 I.D. J15.90
I.D. J9.52 (3x)
I.D. J12.70
I.D. J15.90
I.D. J9.52 (3x)
O.D. J15.90 I.D. J12.70 O.D. J19.10 I.D. J22.20 I.D. J22.20 I.D. J25.40
I.D. J9.52 O.D. J19.10
O.D. J15.90 I.D. J15.90 O.D. J25.4 I.D. J19.10 I.D. J15.90 I.D. J12.70
I.D. J12.70 O.D. J19.10 I.D. J12.70
I.D. J28.60
O.D. J22.20
O.D. J9.52 I.D. J12.70 O.D. J12.70 I.D. J15.90
O.D. J6.35 I.D. J9.52 I.D. J12.70 O.D. J12.70 I.D. J19.10
O.D. J9.52
1TW25799-4C
12
4
Gas-side junction Liquid-side junction Reducers Insulation tube
for gas pipe for liquid pipe for gas pipe for liquid pipe
OD Ø38.1 OD Ø15.9
OD Ø15.9
OD Ø25.4
ID Ø15.9 ID Ø12.7
BHFQ22P1007
ID Ø28.6
ID Ø25.4 ID Ø19.1 ID Ø9.5 OD Ø31.8 OD Ø31.8 OD Ø31.8
OD Ø12.7
ID Ø22.2
OD Ø25.4
ID Ø19.1
ID Ø19.1
ID Ø22.2 ID Ø28.6
ID Ø22.2
ID Ø25.4 OD Ø38.1
ID Ø28.6 ID Ø19.1 ID Ø15.9 ID Ø25.4
ID Ø31.8 ID Ø31.8
ID Ø22.2 ID Ø19.1 ID Ø28.6 OD Ø31.8
OD Ø28.6
ID Ø28.6
OD Ø31.8 OD Ø12.7
(2x) (2x) OD Ø12.7
ID Ø28.6 ID Ø22.2 ID Ø9.5
OD Ø25.4 ID Ø41.3 ID Ø9.5
BHFQ22P1517
ID Ø25.4 ID Ø12.7
ID Ø25.4 ID Ø15.9 ID Ø12.7 ID Ø15.9
• Air-cooled selection procedure
OD Ø31.8 OD Ø15.9
OD Ø15.9 OD Ø19.1
ID Ø28.6 ID Ø28.6 ID Ø15.9 ID Ø12.7 OD Ø25.4 OD Ø25.4
ID Ø19.1 ID Ø9.5 OD Ø38.1
ID Ø31.8 ID Ø25.4
OD Ø28.6
ID Ø22.2
(2x) OD Ø19.1 (2x) (2x) (2x) (2x)
ID Ø19.1
13
3
3
14
4
Reducers Insulation tube
Gas side junction Discharge gas side junction Liquid side junction Joint for pressure For pressure
For gas pipe For discharge gas pipe For liquid pipe For gas pipe For liquid pipe
equalization pipe equalization pipe
I.D. J19.1
I.D. J19.1
I.D. J22.2
I.D. J22.2
I.D. J25.4 I.D. J25.4
I.D. J25.4
I.D. J25.4 I.D. J15.9 I.D. J28.6 I.D. J25.4 I.D. J19.1
I.D. J28.6
I.D. J9.5
I.D. J22.2
O.D. J25.4 O.D. J25.4 I.D. J12.7
I.D. J15.9
I.D. J28.6 I.D. J28.6 I.D. J19.1 O.D. J12.7 O.D. J25.4
I.D. J31.8 I.D. J25.4 I.D. J22.2 O.D. J9.5
BHFQ23P907
I.D. J28.6 I.D. J28.6
I.D. J22.2 O.D. J15.9
I.D. J25.4 I.D. J25.4
I.D. J19.1
I.D. J22.2 I.D. J34.9
I.D. J22.2
I.D. J19.1
O.D. J25.4
O.D. J31.8
I.D. J28.6 I.D. J28.6 I.D. J28.6 I.D. J19.1 I.D. J15.9 I.D. J28.6
I.D. J31.8 I.D. J31.8 I.D. J25.4 I.D. J22.2 I.D. J19.1
I.D. J22.2
BHFQ23P1357
I.D. J19.1 O.D. J25.4
• Air-cooled selection procedure
I.D. J9.5
I.D. J25.4
I.D. J12.7
O.D. J25.4
I.D. J34.9
I.D. J19.1 O.D. J15.9
I.D. J22.2
I.D. J25.4
I.D. J25.4 I.D. J25.4
I.D. J15.9
I.D. J28.6
I.D. J19.1 I.D. J19.1
O.D. J25.4
O.D. J38.1
2TW29119-1
• Air-cooled selection procedure
3
I.D. J20
I.D. J12 I.D. J20 I.D. J22
I.D. J10
I.D. J20
I.D. J12 I.D. J26 I.D. J22
I.D. J10
I.D. J10
I.D. J10 I.D. J6 I.D. J16 I.D. J12
KHRQM22M64T8
I.D. J32
I.D. J16 I.D. J38
I.D. J20 I.D. J32
I.D. J20 I.D. J22
I.D. J16
I.D. J12 I.D. J26 I.D. J20
I.D. J16
KHRQM23M20T8
I.D. J20
I.D. J12 I.D. J10
Closed pipes
O.D. J6 I.D. J10 O.D. J12
1TW29479-1
3 I.D. J6 (2x)
I.D. J6 (6x)
I.D. J16
I.D. J26
I.D. J22
I.D. J32
I.D. J32
I.D. J10 (3x) I.D. J10 (3x) I.D. J12 (3x) I.D. J20 (3x) I.D. J12 (3x) I.D. J12 (3x)
I.D. J16 (3x) I.D. J16 (3x)
I.D. J12 (3x) I.D. J10 (2x) I.D. J12 (2x)
I.D. J6 (2x) I.D. J6 (6x) I.D. J26
I.D. J10 (6x) I.D. J16 (3x)
I.D. J26 I.D. J28
I.D. J16 I.D. J16 I.D. J22
I.D. J16
I.D. J10 (3x)
I.D. J16
I.D. J6 (3x)
I.D. J20 (2x)
I.D. J26
I.D. J10 I.D. J12 I.D. J10 (3x) I.D. J12 (3x)
KHRQM127H8
I.D. J20
I.D. J16 I.D. J16
I.D. J10 (3x) I.D. J12
I.D. J6 (3x)
I.D. J6 (3x)
O.D. J16 I.D. J12 I.D. J10 I.D. J20 I.D. J22 O.D. J20 I.D. J22 I.D. J26
O.D. J26 I.D. J28 I.D. J26 I.D. J28 I.D. J32 O.D. J32 I.D. J38
O.D. J10 I.D. J6 I.D. J12 I.D. J10 O.D. J12 I.D. J10 I.D. J6
Reducers - Expanders
O.D. J16 I.D. J12 I.D. J20 I.D. J16 I.D. J12 O.D. J26 I.D. J20 I.D. J16 I.D. J12
O.D. J16 I.D. J20 I.D. J32 I.D. J35 I.D. J42
O.D. J10 I.D. J12
O.D. J22 I.D. J28 I.D. J12 I.D. J16 O.D. J6 I.D. J10
1TW29479-1
BHFQM22P1007A
I.D. J10 O.D. J32 O.D. J32 O.D. J12
I.D. J22
I.D. J28 I.D. J16
O.D. J15.9
O.D. J28.6
O.D. J26
I.D. J22
I.D. J22
I.D. J26 I.D. J32
I.D. J26
I.D. J28 I.D. J20 I.D. J16 I.D. J12
O.D. J28 I.D. J22
I.D. J32 I.D. J22 I.D. J20 I.D. J28 O.D. J32
O.D. J28 O.D. J12 O.D. J12.7
O.D. J32 O.D. J22.2 O.D. J32
O.D. J12
BHFQM22P1517A
I.D. J26 I.D. J16 I.D. J16
• Air-cooled selection procedure
I.D. J28
O.D. J32 O.D. J15.9
O.D. J28.6 O.D. J16 O.D. J16
I.D. J28 I.D. J16 I.D. J12 O.D. J26 O.D. J20
I.D. J28 O.D. J28
I.D. J26 I.D. J20 I.D. J10 O.D. J38
I.D. J32
I.D. J22
I.D. J20 O.D. J20
17
3
3
18
4
Reducers - Expanders
Suction gas side junction Discharge gas side junction Liquid side junction Parts for oil pipe
For suction gas pipe For discharge gas pipe For liquid pipe
I.D. J15.90
I.D. J19.10 O.D. J25.40
I.D. J22.20
I.D. J15.90
I.D. J25.40
I.D. J19.10 I.D. J25.40
I.D. J25.40
I.D. J22.20 I.D. J28.60
I.D. J10
I.D. J32 I.D. J12
I.D. J20 I.D. J22.20
I.D. J28 O.D. J25.40
I.D. J22 I.D. J22 I.D. J19.10
I.D. J22 I.D. J16 I.D. J22 I.D. J15.90
I.D. J20 I.D. J10 I.D. J20 O.D. J15.90
I.D. J26 I.D. J20 I.D. J35 O.D. J32 I.D. J16
I.D. J16 I.D. J12
BHFQM23M907A
I.D. J28 I.D. J22
I.D. J28
I.D. J26
I.D. J22
I.D. J20
I.D. J22
I.D. J16
I.D. J20
I.D. J16
I.D. J32
I.D. J22
I.D. J26 I.D. J22 I.D. J20
I.D. J32 I.D. J20 I.D. J16
I.D. J28 I.D. J28
I.D. J32 I.D. J38 I.D. J10
I.D. J28
I.D. J35 O.D. J32 I.D. J12
Refnet pipe systems
I.D. J22.20
I.D. J25.40 O.D. J15.90
I.D. J22 I.D. J19.10 Reducer
I.D. J25.40 I.D. J20
I.D. J15.90
BHFQM23M1357A
I.D. J32
I.D. J20 I.D. J6
I.D. J22 I.D. J28
I.D. J22 I.D. J10 I.D. J42 O.D. J38
I.D. J20
I.D. J26 I.D. J20 I.D. J12
I.D. J16
I.D. J28 O.D. J6.35
I.D. J22 I.D. J22
• Air-cooled selection procedure
19
3
• Air-cooled selection procedure
Simultaneous
Indoor unit
Indoor unit
Cooling only
Distribution by REFNET joints
Cooling only
Cooling only
Simultaneous
control of
Cooling only Cooling only
cooling/heating
Can be added
Indoor unit
Indoor unit
REFNET header (8 branch fitting) REFNET header (8 branch fitting)
Can be added
(*1) “ ” Indicate the Outdoor unit multi Function unit Function unit Function unit
Outdoor unit : Outdoor unit : Outdoor unit
connection piping kit.
H4
H4
H4
(*2) In case of multi outdoor system, re-read “
outdoor unit” to “Outdoor unit multi connection
REFNET joint
VRV®III-C
H1
H1
H1
c d e f g h c
REFNET
header k
A B C D E F G
H2
i j k m n p q 7 8 c d e f g h i j
H2
d e f g h i
1 2 3 4 5 6 7 1 2 3 4 5 6 1 2 3 4 5 6 7
8 8
H2
Outdoor unit Function unit Outdoor unit Function unit : Outdoor unit Function unit
H3
H3
Refrigerant pipe selection
H3
H4
H4
H4
REFNET joint
r r
• Air-cooled selection procedure
a a (A, B) r a
b REFNET joint b j b
REFNET header
Multi s (A~G) s s
A B
outdoor
H1
system c d e f g h c
H1
H1
REFNET
header k
A B C D E F G
i j k m n p q 7 8
H2
H2
d e f g h i c d e f g h i j
1 2 3 4 5 6 7 1 2 3 4 5 6 1 2 3 4 5 6 7
Actual pipe Pipe length between outdoor unit (*2) and indoor unit < 165m
length Example 8 : a + b + c + d + e + f + g + h + q < 165m Example 6 : a + b + c + i < 165m, 8 : a + b + j + < 165m Example 8 : a + b + j < 165m
Between outdoor unit (*2) Equivalent Equvalent pipe length between outdoor unit (*2) and indoor unit < 190m (Note 1)
Maximum and indoor unit length (Assume eqivalent pipe length of REFNET joint to be 0.5m, that of REFNET header to be 1m, that of function unit to be 6m for calculation purposes)
allowable Total extention length Total piping length from outdoor unit (*2) to all indoor unit < 500m
length
Between outdoor unit and function unit Actual and Actual pipe length from outdoor unit to function unit, that from first outdoor unit multi connection piping kit to outdoor unit < 10m Function unit
Between outdoor unit and outdoor unit equivalent Equivalent pipe length from outdoor unit to function unit, that from first outdoor unit multi connection piping kit to outdoor unit < 13m : Outdoor unit
length a < 10m
Multi connection piping kit
Between outdoor and indoor units (Equivalent length < 13m)
Difference in height Difference in height between outdoor unit and indoor unit (H1) < 50m (Max 40m if the outdoor unit is below)
Allowable r < 10m
Between indoor and indoor units Difference in height Difference in height between indoor units (H2) < 15m (Equivalent length < 13m)
height
Difference in height s r a s < 10m
difference Between outdoor and outdoor units Difference in height between outdoor units(H3) < 5m
Between outdoor unit and function unit Difference in height Difference in height between outdoor unit and function unit (H4) < 1m (Equivalent length < 13m)
Actual Pipe Actual pipe length from first refrigerant branch kit (either REFNET joint or REFNET header) to indoor unit < 40m (Note2)
Allowable length after the branch Length Example 8 : c + d + e + f + g + h + q < Example 6 : c + i < 40m ,8 :j+ < 40m Example 8 : j < 40m
21
3
3
22
6
6-1
Outdoor unit multi connection piping kit How to select the REFNET joint How to select the REFNET header
• When using REFNET joint at the first branch counted from the outdoor unit side,choose from • Choose from the following table in accordance with the total capacity index of all the
and Refrigerant branch kit selection the following table in accordance with the outdoor system capacity type. (Example : REFNET indoor units connected below the REFNET header.
joint A) • 250 type indoor unit can not be connected below the REFNET header.
Outdoor system capacity type Refrigerant branch kit name Indoor unit total capacity index Refrigerant branch kit name
•Refrigerant branch kits can only be used with R410A. 10HP type KHRP26A33T x < 200 KHRP26M22H or KHRP26A33H
•When multi outdoor system are installed, be sure to 14~20HP type KHRP26A72T 200 < x < 290 KHRP26M33H
use the special seperately sold Outdoor unit multi
290 < x <640 KHRP26M72H
connection piping kit. (BHFP30A56) • Choose the REFNET joints other than the first branch from the following table in accordance
(For how to select the proper kit, follow the table at 640 < x KHRP26M73H + KHRP26M73HP
with the total capacity index of all the indoor units connected below the REFNET joint.
right.)
VRV®III-C
Indoor unit total capacity index Refrigerant branch kit name How to select the outdoor unit multi connection piping kit
x < 200 KHRP26A22T (This is required when the system is multi outdoor unit system.)
• Choose from the following table in accordance with the number of outdoor units.
200 < x < 290 KHRP26A33T
290 < x <640 KHRP26A72T Number of outdoor unit Connecting piping kit name
2 units BHFP30AP56
Example for indoor units Example REFNET joint B : Indoor units 7 + 8 Example REFNET header :
Example REFNET joint C : Indoor units 3 + 4 + 5 + 6 + 7 + 8
connected downstream Example REFNET header : Indoor units 1 + 2 + 3 + 4 + 5 + 6 Indoor units 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8
Pipe size selection Piping between outdoor unit (*2) and refrigerant branch kit (part A) Piping between refrigerant branch kits
• Choose from the following table in accordance with the outdoor unit system capacity type. • Choose from the following table in accordance with the total capacity type of all the
(Unit:mm) indoor units connected downstream.
The thickness of the pipes in the table shows the Outdoor system Piping size (O. D.) • Do not let the connection piping exceed the main refrigerant piping size (Part A). If
requirements of Japanease High Pressure Gas capacity type
the piping size selected from the following table exceeds the piping size of part A,
Gas pipe Liquid pipe
Controll low. (As of Jan.2003) decide the piping size in either of the following methods.
the thickness and material shall be selected in 10HP type Ø22.2 Ø9.5 (1)Reduce the size of the connection piping to the piping size of part A.
accordance with local code. 14, 16HP type Ø12.7 (2)Replace the piping of part A with piping that is a size larger (see the table in Note
Refrigerant pipe selection
Ø28.6
20HP type Ø15.9 1) so that it will be the same as the size of the connection piping.
In case of single outdoor unit system (Unit:mm)
• Air-cooled selection procedure
Example for refrigerant branch using REFNET joint and REFNET header for the systems and each pipe length as shown below.
System: RTSYQ20PY1
Independant outdoor unit: RTSQ8PY1, RTSQ12PY1 a : φ15.9 × 10m e : φ6.4 × 10m i : φ6.4 × 10m r : φ12.7 × 5m
Function unit: BTSQ20PY1 b : φ15.9 × 30m f : φ6.4 × 20m j : φ9.5 × 20m s : φ9.5 × 10m
c : φ12.7 × 20m g : φ6.4 × 20m k : φ9.5 × 10m
d : φ6.4 × 10m h : φ6.4 × 10m : φ9.5 × 10m
φ12.7 → φ15.9
on right) must be increased according to the right table. RTSYQ16 type Indoor Indoor
φ28.6 → φ31.8 (*)
RTSYQ20 type φ15.9 → φ19.1 unit unit
*If available on the site , use this size.
Main pipes Main pipes
Otherwise, it can not be increased.
Inclease gas and liquid pipe Inclease gas and liquid pipe
size both. size both.
: In case of single outdoor unit system : In case of multi outdoor unit system
Note 2. Allowable length after the first refrigerant branch kit to indoor units is 40m or less, however it can be extended up to 90m if all the following conditions are satisfied.
1. It is necessary to increase the pipe size between the first branch kit and the final 8 c + d + e + f + g + h + q ≤ 90 m : Increase the pipe size as follows.
branch kit. (Reducers must be procured on site) However, the pipes that are same
Increase the pipe size of c, d, e , f ,g, h
pipe size with main pipe must not be increased. φ 9.5 → φ12.7 φ15.9 → φ19.1 φ22.2 → φ25.4* φ34.9 → φ38.1*
φ12.7 → φ15.9 φ19.1 → φ22.2 φ28.6 → φ31.8*
2. For calculation of Total extension length, the actual length of above pipes must be : Outdoor unit : Function unit :REFNET joint
doubled. (except main pipe and the pipes are not increased).
a+b+c×2+d×2+e×2+f×2+g×2
+ h × 2 + i + j + k + + m + n + p + q ≤ 500 m (A~G)
a
3. Indoor unit to the nearest branch kit < 40m i, j....... p, q ≤ 40 m b c d e f g h
A B C D E F G q
4. The difference between The farthest indoor unit 8 i j k m n p
[Outdoor unit to the farthest indoor unit] and [Outdoor unit to the nearest indoor 1 2 3 4 5 6 7
The nearest indoor unit 1
unit] < 40m
( a + b + c + d + e + f + g + h + q ) - ( a + b + i ) ≤ 40 m Indoor unit ( 1 - 8 ) 8
*If available on the site , use this size. Otherwise it can not be increased.
23
3
• Air-cooled selection procedure
3
Ø 15.9 O 0.99
Ø 19.1 1/2H 0.8
Ø 22.2 1/2H 0.8
Ø 25.4 1/2H 0.88
Ø 28.6 1/2H 0.99
Ø 31.8 1/2H 1.10
Ø 34.9 1/2H 1.21
Ø 38.1 1/2H 1.32
Ø 41.3 1/2H 1.43
O : annealed
1/2H : half-hard
For half hard pipes the maximum allowed tensile stress is 61 N/mm2. For this reason the 0.2% proof strength
of the half hard pipe shall be minimum 61 N/mm2.
The bending radius is more than or equal to 3 times the diameter of the pipe.