Sunteți pe pagina 1din 1

TITLE Document Ref:T-235-07-08

ARBL SIZING CALCULATION SHEET Pg. : 1 of : 1


SIZING AS PER IEEE 485 Pg . Rev. : 00 Date : 30/5/09

Load in KVA 192.5 KVA


End Cell Voltage 1.75 V
Design Factor 1
Ageing Factor 1.25

Inverter Efficiency 0.96


Power Factor 1
Backup time 15 min
DC Voltage 480 V
o
Temperature 27 C
Temp corr. Factor * 1
K-factor* 1.00
No of cells 240 No's
Proprietary Material of M/s. AMARA RAJA GROUP OF COMPANIES, Thirupati.
All rights are reserved . No copying permitted. Unauthorized use prohibited.

Load in KVA x 1000 x Power Factor


Load Current = = 477.43 Amps
No.of cells x ECV x Invertor Efficiency

Ah Capacity considering
= Load current x K-Factor x Aging factor x Temperature Factor x Design Factor = 596.79 Ah
Various factors

Recommended Ah is 600 Ah

From the manufacturers catalogue,type F 600 P is recommended with 600 Ah at 1.75 ECV
*Temperature Factor and K-Factor cosidered as per manufacturer's catalogue

APPROVED BY: PREPARED BY : Sterling And Wilson