Knauf Wetroom Solutions with AQUAPANEL® Technology Inside Knauf Wetroom Solutions with AQUAPANEL® Technology Inside
represent the future of interior wall installation. This unique wall is the ideal solution for architects and planners in multiple
system is based entirely on drywall techniques, which enable applications. The following pages outline how, they include:
far greater flexibility and cost-efficiency than conventional
methods such as brick and block. Architects and contractors Technical construction details, based on standard
around the world are also turning to Knauf Wetroom Solutions construction types in matrix
with AQUAPANEL® Technology Inside for its sustainable Vertical and horizontal cross-sections
qualities and compliance. Test reports for key building physical requirements
(fire, sound, thermal)
The Knauf Wetroom Solutions are suitable for a wide range
of new building applications and thermal or aesthetic Electronic CAD files and sample specification texts can be
renovation projects including offices, hotels, sports facilities, downloaded from www.AQUAPANEL.com
schools, hospitals and residential complexes. Each standard
construction type includes:
Console loads��������������������������������� 32
A better way to build Build interior walls and ceilings
interior walls and ceilings
in wet and humid areas
Knauf Wetroom Solutions with AQUAPANEL® Technology Inside
faster using drylining methods
Knauf Wetroom Solutions with AQUAPANEL® Technology Inside Access Panels��������������������������������� 33
Stability and construction������������������������ 34
Material consumption tables��������������������� 36
Be certain, Be certain,
Fire protection��������������������������������� 38
choose AQUAPANEL® choose AQUAPANEL®
Sound protection������������������������������� 42
See additional documentation for more detailed
System properties������������������������������ 44
information on Knauf Wetroom Solutions
Sample specification��������������������������� 46
Reference of additional documentation������������ 51
3
Knauf Wetroom Solutions with AQUAPANEL®
Technology Inside
Six main types of wall with assorted performance characteristics are available
Shaft walls
To create a drylining wall in front
of an existing brick and block
wall, simply use the single stud
arrangement.
4
Knauf Wetroom Solutions with AQUAPANEL®
Technology Inside
Heavy duty
On its own, the AQUAPANEL® Cement Board Indoor is strong and
rigid and will support up to 50 kg of tiles per square metre of wall.
But with the AQUAPANEL® Traverse, light console loads are borne
securely up to 1.5 kN/m2.
Suspended ceiling
Suspended ceilings ensure that installations are secured. Moreover,
depending on the construction, they can help improve sound and
fire protection of a building.
5
Metal single stud frame wall and plumbing wall
W381 Metal single stud frame wall single stud frame, single-layer planking
stud spacing
600 mm 75 50 12.5 AQUAPANEL
® 42 50 0.70
d
stud spacing
600 mm
D
dh
600 mm
stud spacing
600 mm 100 50 2 x 12.5
AQUAPANEL ® 49 50 0.66
D
stud spacing
600 mm 125 75 2 x 12.5 Cement Board
– 60 0.53
hd d
stud spacing
D
stud spacing
D
d d d h d h dd h d h d d d dh
600 mm
W386-1 Plumbing wall fishplated double stud frame, single-layer planking
stud spacing
600 mm
stud spacing
D
600 mm
230 205 12.5 Indoor
– 2 x 80 0.23
D
stud spacing
600 mm
stud spacing
600 mm
W386-2 Plumbing wall fishplated double stud frame, double-layer planking
stud spacing
d h d h ddh d h d
600 mm
D
stud spacing
600 mm 155 105 2 x 12.5
AQUAPANEL ® > 61 ** 2 x 50 0.35
D D
6
Metal single stud frame wall and plumbing wall
Fire protection
* Mineral wool - layer acc. to EN 13162; 3.1.1, Building material class A, melting point > 1000°C acc. to DIN 4102-17
7
Single stud frame wall, single-layer planking
Wall heights
* See page 34
Profile Stud spacing Max. wall height
Sheet steel thickness 0.6 mm Installation range 1* Installation range 2*
mm m m
Wall heights
* See page 34
Profile Stud spacing Max. wall height
Sheet steel thickness 0.6 mm Installation range 1* Installation range 2*
mm m m
Wall heights
* See page 34
Profile Stud spacing Max. wall height
Sheet steel thickness 0.6 mm Installation range 1* Installation range 2*
mm m m
Knauf profile 2 x CW 50
600 (625) 3.00 2.75
without fire protection requirement
Knauf profile 2 x CW 75
600 (625) 4.50 4.00
without fire protection requirement
Knauf profile 2 x CW 100
600 (625) 5.50 5.00
without fire protection requirement
®
d = 12.5mm Board
300E.g.adhesive
tilehigh
strips
mm application E.g. AQUAPANEL
tile application AQUAPANEL
Cement Board d
Indoor =
E.g. 12.5mm
tile application
300 mm high d =E.g.
®
E.g. tile application Maxi Screw AQUAPANEL
Maxi Screw ®
AQUAPANEL® 12.5mm
tile application ®E.g.® tileAQUAPANEL
application
®
Maxi Screw
300tile
mmapplication
high E.g. flexible tile AQUAPANEL
AQUAPANEL ® Maxi Screw
requirements
adhesive
E.g.E.g.
tileflexible tile
application AQUAPANEL AQUAPANEL ®
Maxi
AQUAPANEL
®Joint Adhesive (PU)
Screw ®
mmmm
adhesive
E.g. flexible tile AQUAPANEL
Joint AQUAPANEL
Adhesive
®
(PU) Maxi® Screw®
to acc. to
mm 600 mm
Joint
® Adhesive (PU)
Maxi Screw
mm
600600
adhesive AQUAPANEL
1650 mm
requirements
Maxi Screw
installation
600
approx.
e.g. Knauf
requirements
approx.
to300
requirements
acc. to
approx.
acc.
approx.
approx.
mmmm
acc.to
Sealing systems,
Unit spacing
Unit spacing acc. to
mmmm
installation
spacing
3001650
750acc.
Knauf
mm
Sealing systems,
installation
Unit spacing
mm
1650
e.g. Knauf
Knauf CW profile Sealing systems, e.g. Wall opening dimenson
installation
Flächendicht
spacing
approx. 1650 mm
1650
Knauf
mm
300300
Sealing systems,
installation
Flächendicht
spacing
1650
e.g. Knauf
300 mm
Sealing systems,
installation
approx. 750 mmapprox.
approx.
e.g. Knauf
Unit
300
Knauf CW profile Sealing strip Flächendicht Wall opening dimenson Board strips
mmmm
Unit
approx.
Sealing strip
Unit
Board
Knauf strips with board strips 12.5 mm
d =® 12.5mm
approx.
10
Plumbing wall – fishplated double stud wall,
double-layer planking
Wall heights
* See page 34
Profile Stud spacing Max. wall height
Sheet steel thickness 0.6 mm Installation range 1* Installation range 2*
mm m m
Knauf profile 2 x CW 50
600 (625) 4.00 3.50
without fire protection requirement
Knauf profile 2 x CW 75
600 (625) 5.40 4.90
without fire protection requirement
Knauf profile 2 x CW 100
600 (625) 7.00 6.50
without fire protection requirement
E.g.high
flexible E.g. AQUAPANEL Maxi
ScrewScrew
® ® tile application
JointMaxi
Adhesive (PU)
®
Cement Board d
Indoor d 300
= mm
12.5mm AQUAPANEL Maxi Screw
AQUAPANEL® E.g.
300tile
300 mmapplication
mm high
high tiletile
E.g.mm adhesive
application AQUAPANEL
AQUAPANEL ®
Maxi Screw
AQUAPANEL
300 high Joint Adhesive ®AQUAPANEL AQUAPANEL
®
®
Maxi Screw
®
E.g. tile
tile application
application AQUAPANEL ® (PU)
600 mm
E.g. flexible
requirements
tile
E.g. adhesive Elastic sealing
AQUAPANEL ® Maxi Screw
compound
mm
flexible
mm
mm mm
E.g.
mm approx.
tile adhesive
adhesive
requirements
tile adhesive
approx. 750 mm 300approx.1650
Sealing systems,
Unit spacing
requirements
600
installation
requirements
approx.
approx. 600
e.g. Knauf
requirements
Flächendicht
acc. to
approx.
mm
approx.1650
Sealing systems,
toto
acc.acc.
approx.1650 mm
Unit spacing
installation
mm
e.g. Knauf
mm
acc.
approx.1650
spacing
Flächendicht
systems,
mm
installation
Unit spacing
spacing
approx.1650
Sealing systems,
mm
spacing
installation
Sealing systems,
300
Flächendicht
e.g. Knauf
installation
750
Flächendicht
Unit
approx.
Sealing strip
mm
750750
Knauf
ElasticUW profile Vertical truss reinforcement Knauf d = 12.5mm
approx.
Details AQUAPANEL
AQUAPANEL ® ®
AQUAPANEL
Cement
CementBoardBoard AQUAPANEL ® ®
Indoor
Indoor Cement
CementBoard
Board
Insulating
Insulatingwool
AQUAPANEL ®®wool
® Indoor
Indoor
AQUAPANEL
AQUAPANEL
AQUAPANEL
AQUAPANEL
®
Insulating
Knauf
Knauf
Cement
Cement UWUW
Board
Board
®®
profile
profile Insulatingwool
AQUAPANEL
AQUAPANEL
AQUAPANEL ®wool
®® ®
Cement
Cement
Cement Board
Board
Board AQUAPANEL
AQUAPANEL
Cement Board
®®
Indoor
Indoor
Indoor Cement
Cement
Cement
Cement Board
Board
Board
Board
Indoor
Tommy
Tommybar
Indoor
Insulating barplug
wool plug Knauf
Knauf
Indoor UWUW profile
profile
Insulating
Insulating
Insulating wool
woolwool Indoor
Indoor
Indoor
Indoor
Insulating
Sealing
Sealing
Knauf strip
UW wool
strip
profile Insulating
Elastic wool
Elastic wool
Insulating
Insulatingwool
wool
Knauf
Knauf
Knauf UW UW profile
UW profile
Knauf profile Insulating
Insulating wool
ElasticUW profile
Elastic sealing
sealingcompound
compound
Tommy
Tommy
Tommy
sealing
sealing bar
bar
bar plug
plug
compoundplug
compound Knauf
Knauf
KnaufUWUW
UW profile
profile
profile
Tommy
Tommy bar plug
bar plug Knauf UW
Knauf UWprofile
profile
Sealing
Sealing
Sealing strip
strip
strip Elastic
Elastic
Elastic
Sealing strip
Sealing strip Elastic
Elastic
Elastic
Elastic sealing
sealing
sealing compound
compound
compound
Elastic
Elastic
Elastic sealing compound
sealing compound
sealing
sealing
sealing compound
compound
compound
sealing compound
sealing compound
AQUAPANEL
AQUAPANELCement
® ®
CementBoard
BoardFloor
Floor
AQUAPANEL
AQUAPANEL
AQUAPANEL
®
CementBoard
®® Cement Board
®® Cement
® Floor
Floor
Board Floor
AQUAPANEL
AQUAPANEL Cement Board
Cement Floor
Board Floor
AQUAPANEL
AQUAPANEL ® ® AQUAPANEL
AQUAPANEL ® ®
AQUAPANEL
AQUAPANEL Cement
® ®
CementBoard
BoardFloor
Floor
AQUAPANEL
AQUAPANEL
®
CementBoard
®® Cement
AQUAPANEL Board
®® Cement
® Floor
Floor
Board Floor
AQUAPANEL Cement
AQUAPANEL Board
Cement Floor
Board Floor
W386-VU2 Connection on wet screed W386-VU3 Connection to unfinished floor
Sealing
Sealingstrip Sealing
Sealingstrip
520aaaaaa ≤20 a
strip
520aaaaaa ≤20 a
strip
20 a
20 a
a a mm
a a mm
mm
mm
AQUAPANEL
AQUAPANEL ® ®
AQUAPANEL
AQUAPANEL ® ®
≤ a ≤
≤ a ≤
Cement
CementBoardBoard Cement
CementBoardBoard
Sealing
Sealing
Sealing
Indoor
Indoor strip
strip
strip
strips
strips Sealing
Sealing
Sealing
Indoor
Indoor strip
strip
strip
strips
strips
Sealing
Sealingstrip
strip Sealing
Sealingstrip
strip
5mm
5mm
mm
mm
mm
mm
≤20
a20aaaaa++amm
≤20
a20 aaa+mm
Knauf
Knauf
AQUAPANELUWUWprofile
®®profile Knauf
Knauf
AQUAPANELUWUWprofile
®®profile
20
20
® ®
mm
mm
≥a aa≤20
≥a aa≤20
AQUAPANEL AQUAPANEL
20
20
AQUAPANEL ®
AQUAPANEL ®
≤≤
≤≤
AQUAPANEL
AQUAPANEL ®® AQUAPANEL
AQUAPANEL ®®
mm mm mm
mm mm mm
mm
mm
Cement
Tommy
Tommy Board
barbarplug
plug Cement
Tommy
Tommy Board
barbarplug
plug
a
Cement
Cement
Cement Board
Board
Board Cement
Cement
Cement Board
Board
Board
Indoor strips Indoor strips
a
Indoor strips
AQUAPANEL
AQUAPANEL
Indoor strips ® ®
Indoor
Indoor strips
strips
a
Indoor
Indoorstrips
strips Indoor strips
AQUAPANEL
Indoor strips
a++555mm
++55 mm
AQUAPANEL ® ®
aa++55 20
aa++55 20
Knauf
Cement
Knauf
Knauf UW
Cement
UW UW profile
Board
Board
profile
profile Indoor
Indoor Knauf
KnaufKnauf UW
UW UW profile
profile
profile
5
Knauf
Tommy UW
bar profile
plug Cement
Knauf
Cement
Tommy Board
UW
bar profile
Board
plug Indoor
Indoor
amm
amm
mm
mm
Insulating wool
+
Insulating
Tommy bar wool
plug Tommy bar plug
amm
amm
mm
Tommy
Tommy barbar
plugplug Tommy
Insulatingbar
Insulating
Tommy plug
wool
barwool
plug
+
aAQUAPANEL
=
a =10-20
AQUAPANEL10-20mm
AQUAPANEL
AQUAPANEL
®® ®
®mm
aAQUAPANEL
=
a =10-20
AQUAPANEL 10-20mm®mm
®
® ®
AQUAPANEL
Cement Board
®®
Indoor AQUAPANEL
AQUAPANEL
AQUAPANEL ®®
Cement
Cement
Cement Board
Board
Board
Cement Board Indoor
IndoorIndoor
Indoor Cement
Cement
Cement Board
Board
Board Indoor
Indoor
Indoor
Insulating
Insulating
Insulating wool
wool
wool Cement
Cement
Insulating Board
Board
woolIndoorIndoor
Insulating wool
Insulating wool Insulating
Insulating
Insulating wool
woolwool
aa=a=10-20
10-20 mm
mm Insulating wool
=
a =a10-2010-20 mm
mmmm a = 10-20 mm
= 10-20 aa==aa10-20
10-20
=
= 10-20
10-20 mm
mm mm
mm
Joint
Jointprofile
profile ≥ ≥a a a a ≥ ≥a a aa
e.g.
e.g.Migua
Migua
AQUAPANEL
AQUAPANEL ® ® Knauf
Knauf CWCWprofile
profile AQUAPANEL
AQUAPANEL ® ®
Cement
CementBoard
BoardIndoor
Indoor Knauf
KnaufCW
CWprofile
profile 75x50
75x50 Cement
CementBoard BoardIndoor
Indoor
Knauf
Knauf CWCWprofile
profile
AQUAPANEL ® 100x50
100x50 Knauf
Knauf CW
CW profile
profile AQUAPANEL ®
AQUAPANEL
AQUAPANEL ®® ®
AQUAPANEL
AQUAPANEL
®
® Knauf CW profile Knauf
Knauf
KnaufCW CW
CW profile
profile a=
AQUAPANELa =10-20
AQUAPANEL
profile AQUAPANEL ®® mm
10-20 ® mm
Cement
Cement Board
Board Indoor
Indoor Knauf
Knauf CW
Knauf
CW CWprofile
profile
profile 75x50
75x50
75x50 AQUAPANEL
Cement Board
®®
Indoor
Cement
Cement Board
Board
Cement Indoor
Indoor
Board Indoor Knauf CW profile Knauf 75x50
CW 75x50
profile Cement
Cement
Cement
Cement Board
Board
Board Indoor
Indoor
Indoor
Board Indoor
Knauf
Knauf
Knauf CW
CW CW profile
profile
profile
Knauf CW profile
100x50
100x50
100x50
W386-BFU2 Expansion joint with joint profile 100x50
100x50
W381-BFU1 Expansion joint EI 30 a = 10-20 mm
aa==aa10-20
10-20
=
= 10-20 mm
mm
10-20 mm
mm
12
Coatings and facings, door openings
13
Profile extension, details for wet rooms
Knauf Knauf
Knauf Knauf Knauf Knauf CW Knauf
profile 2 Knauf CW profile 2 Knauf CW profile 2
CW profile 2 CW CW
profile 2 2
profile CW profileCW
2 profile
or2Knauf UA
CWprofile 22
profile or Knauf UA profile 2or Knauf UA profile 2
o
o
o
Knauf Knauf
Knauf Knauf Knauf Knauf Knauf Knauf Knauf
CW profile 1 CW profile 1 1
CW profile CW profile 1 profile
CW
Knauf
CW1 profileCW
1 orprofile 1 CW profile 1 or KnaufCW profile 1 or
Knauf CW profile 2
CW profile 2 Knauf UA profile 1 2
CW profile Knauf UA profileor1Knauf
Knauf UA profile
UA profile 2 1
Additional Additional
Knauf CW profile Knauf UW profile
Installation aid
o
o
Knauf profile overlap (in cm)
ivet, crimp or bolt
R
o
AQUAPANEL® AQUAPANEL ®
AQUAPANEL® CW / UA
the profiles in the lining
Ceramic Ceramic lining Ceramic Cement
lining Board Indoor Cement Board Indoor
Cement
50 Board Indoor75 100
overlap area Crimping tool
AQUAPANEL® AQUAPANEL® AQUAPANEL®
Pipe feedthrough with Pipe feedthrough with
Pipe feedthrough with
o
o
Board Primer Board Primer Board
cmPrimer cm cm
bolted connection bolted connection bolted connection
Sealing strip Sealing strip Sealing
≤ 25 strip ≤ 35 ≤ 50
Knauf Knauf Knauf
CW profile 1 CW profile 1 CW profile 1 or
Knauf UA profile 1
Sealing tape,
Sealing if necessary permanentlySealing if necessary
Sealing if necessary Sealing if necessary Sealing if necessary Sealing if necessary
elastic joint
(e.g. Knauf all-over seal) (e.g. Knauf all-over seal)
(e.g. Knauf all-over seal) (e.g. Knauf all-over seal) (e.g. Knauf all-over seal)
(e.g. Knauf all-over seal)
Sealing e.g. Knauf
AQUAPANEL® AQUAPANEL® AQUAPANEL® sealing stripAQUAPANEL
laid
in Knauf sealing system
®
AQUAPANEL® AQUAPANEL®
Cement Board Indoor Cement Board Indoor
Cement Board Indoor Cement Board Indoor Cement Board Indoor
Cement Board Indoor
Sealing strip Sealing strip Sealing strip Sealing strip Sealing strip Sealing strip
14
Crimping
Crimping tool tool
o o
o o
o
o
o
o
Profile extension, detailsKnauf
forKnauf
wet rooms
Knauf Knauf Knauf Knauf
CWKnauf CW
profile 1 profile 1
Knauf CWKnauf CW
profile 1 profile 1
Knauf CWKnauf CW
profile 1 orprofile 1 or
Knauf
CW profile
CW profile 1 1 CW profile
CW profile 1 1 Knauf
CWUA Knauf
profile
CW
profile 1 UA
or1 profile
profile 1 or 1
Knauf
Knauf UA UA profile
profile 1 1
AQUAPANEL AQUAPANEL
® ®
Ceramic lining
Ceramic lining Cement Cement
Board ® Board
Indoor ® Indoor
AQUAPANEL
AQUAPANEL
CeramicCeramic
lining lining AQUAPANEL
Cement AQUAPANEL
®
Cement
®
Board Indoor
Board Indoor
Pipe feedthrough
Pipe feedthrough with with Board Board
Primer Primer
bolted bolted
connection connection AQUAPANEL
AQUAPANEL ® ®
Pipe feedthrough
Pipe feedthrough with with Board Primer
Board Primer
bolted bolted connection
connection Sealing strip
Sealing strip
SealingSealing
strip strip
Sealing tape,
Sealing tape,
Sealingpermanently
permanently Sealing
tape, tape,
elastic elastic
joint joint
permanently
permanently
elastic
Sealing elastic
Knaufjoint
joint
Sealing
e.g. e.g. Knauf
sealing
Sealingsealing
strip laid
Sealing
e.g. strip laid
e.g. Knauf
Knauf
in Knauf
sealingin Knauf
sealing
sealing
strip sealing
system
strip
laid laidsystem
in Knaufin sealing
Knauf sealing
systemsystem
Sealing if Sealing
necessary if necessary Sealing if Sealing
necessary if necessary
Knauf(e.g.
(e.g.SealingSealingKnauf
ifall-over
necessary all-over seal)
if seal)
necessary Knauf(e.g.
(e.g.Sealing Knauf
ifall-over
Sealing all-over seal)
if seal)
necessary necessary
(e.g.
(e.g. Knauf Knauf all-over seal)
® all-over ®seal)
(e.g.
(e.g. Knauf Knauf all-over seal)
® all-over ®seal)
AQUAPANEL AQUAPANEL AQUAPANEL AQUAPANEL
Cement Cement
Board ® Board
Indoor
AQUAPANEL
AQUAPANEL ® Indoor Cement Cement
Board ® Board
Indoor
AQUAPANEL
AQUAPANEL ® Indoor
Cement Cement
Board
Sealing
Sealing strip Board
Indoor
strip Indoor Cement Cement
Board
Sealing
Sealing strip Board
Indoor
strip Indoor
SealingSealing
strip strip SealingSealing
strip strip
Permanently
Permanently elastic joint
elastic joint Permanently
Permanently elastic joint
elastic joint
Permanently
Permanently elastic elastic
joint joint Permanently
Permanently elastic elastic
joint joint
W382-ZH3 Bathtube connection (double-layer planking) W 382-ZH4 Bathtube connection (single-layer planking)
When constructing wet and damp rooms, it is essential to pay attention The procedure is done in two stages:
to the watertightness of the construction. • After panelling and
• After tiling
Installation passages as well as all joints and corners must be closed
with permanently flexible, fungicidal joint mastic. Open board edges must be primed before injection to enhance
adhesion of the joint mastic.
Passages for pipes or fittings must be made approx. 10 mm bigger
than the relevant built-in installation. The gap between the sanitary The transfer of impact sound via sanitary items on the partitions must
items and the tiles (approx. 5 mm) must be closed with permanently be kept as low as possible. Therefore, an insulation strip e.g. felt must
flexible fungicidal joint mastic. be placed between the sanitary items and the panels.
Shower areas, bathrooms, kitchens, toilets in private households as well Sealing of areas where walls meet or walls and floors meet; sealing of any
as sanitary areas in hotel rooms cut-outs for pipes etc., if applicable.
Damp rooms and wet rooms such as public showers, sanitary areas in Sealing of areas where walls meet or walls and floors meet; sealing of any
public and commercial sectors, as well as commercial kitchens, dairies and cut-outs for pipes etc., if applicable. In addition, sealing of the entire surface
breweries, having limited chemical contamination and under high load. of the AQUAPANEL® Cement Board is necessary.
15
Curved wall constructions
radiusradius
12.5 ≥ 1000 ≥ 3000
d d Unwound length L
face side d face side
radius
radius
radius
Details
face side d face side d face side face side
Knauf UW profile
Knauf UW profile Note:
AQUAPANEL® Cement Board Indoor should be given its bent
Knauf stud profile
shape when dry before installation. Small cracks may appear on
Knauf stud profile
Knauf UW profileKnauf UW the surface of the board during shaping. This does not represent
AQUAPANEL® profile
Cement Board® Indoor a loss of strength nor function.
AQUAPANEL
Cement
Knauf stud Knauf
profile Board
Sinus Indoor
profile Pay attention to the specifications of the relevant Knauf detail
Knauf stud profile
Knauf Sinus profile sheets when installing Knauf boards as an inner lining.
AQUAPANEL ®
AQUAPANEL AQUAPANEL
® ®
Unit spacing of the upright sections: < 300 mm (outer radius)
Cement Board Indoor
Cement Cement
Board Board
Indoor Indoor
AQUAPANEL®
Knauf Sinus
Cementprofile
Board Indoor
Knauf Sinus profiler of curved wall
Radius
Radius r of curved wall
AQUAPANEL AQUAPANEL®
®
AQUAPANEL®
Cement Board® Indoor
AQUAPANEL
Cement Board Indoor
AQUAPANEL® AQUAPANEL®
Cement Board Indoor
Cement Board Indoor
Design with 900 mm wide boards for r ≥ 3.0 m Design with 300 mm wide boards for r ≥ 1.0 m
16
Load fastening
Note:
Load Load Load Load Load Load Load Load Load Light objects e.g. pictures can be fastened with X-hooks.
5 kg 5 kg 5 kg 10 kg 10 kg 10 kg 15 kg 15 kg 15 kg Load Load
Load Load Load
Load
5 kg Load 10 kgLoad 15 kgLoad
Load Load 5 kg 5 kg Load 10 kg 10 kg 15 kg 15 kg
5 kg 10 kg 15 kg
Other bracket loads up to 0.7 kN/m (plug) Plug load, tensile and shearing load Load Load
Load
5 kg
Thickness 10Plastic
kg cavity fixing plug 15 kg
Wall cabinets
cabinets
Wall cabinets of facing Ø8 mm Ø10 mm
Plastic cavity fixing plugs
PlasticPlastic
cavity cavity
fixing plugs
fixing plugs Wall cabinets
Wall cabinets
Wall cabinets mm kg kg
1 x 12.5 30 40
≥ 30 cm
Cabinet height
height
cm
Cabinet height
≥ 30 cm
≥ 30 cm
≥ 30
≥ 30 cm
th Cabinet
abinet widthepwidth
th
ep t de
d d screw M5 or M6 Hartmut
Cabinet height
a a Cabinet e kg kg
C CCabinet width pth inted et d
t de Metal cavity fixing plugs Cbainbe i n
e Ca b 30 60
bin Ca
Ca th
Cabinet width
50 ep 110
e td
Heavy bracket loads up to 1.5 kN/m (trusses, crossbeams) bin
Ca
Note:
Bracket loads over 0.7 kN/m According to DIN 18183, single-layer walls may be loaded at any point by bracket loads up to
Bracket loads over
to 1.5Bracket
kN/m loads0.7
wall kN/m
over
length 0.7
arekN/m
to
/m tobe
1.5installed
kN/m 0.7 kN/m wall length taking into account the leverage (cabinet height > 30 cm) and eccentricity
to 1.5 wall
kN/m
ontolength
wall are to are to
length
the substructure
re to bevia
installed onto
be installed
main the substructure
ontocrossbeams.
trusses and the substructure (cabinet width < 60 cm). Fastening distance of the plugs is > 75 cm.
tructure via mainviatrusses and crossbeams.
main trusses and crossbeams.
beams. The bracket loads must be fastened with at least 2 cavity fixing plugs of plastic or metal, e.g. Tox
Bracket loads over 0.7 kN/m
to 1.5 kN/m wall length are to Universal, Fischer Universal, Molly Schraubanker.
be installed onto the substructure
via main trusses and crossbeams.
Diagram 1 Diagram 2
binet weight Permissible bracket loads up Max.
weight to 0.4 permissible
kN/mMax.
wall length
Max.applicable for
permissible
permissible
cabinet weigth the system:
cabinet W38weigth
cabinet
weigth I Permissible bracket loads up to 0.7 kN/m wall length applicable for system: W38 I
(kg)
Max.(kg) (kg)cabinet
permissible weight Max. permissible cabinet weigth
Max.
(kg)permissible cabinet
Max. permissible weightweight
cabinet CabinetCabinet
Cabinet width width width Max.
(kg)permissible cabinet
Max. permissible weigthweigth
cabinet
ssible cabinet weight
Cabinet width Cabinet
Cabinet width width
(kg) (kg) Max. permissible cabinet weigth
(cm) (cm) (cm)
(kg) (kg)
(cm) (kg) Cabinet width
(cm) (cm)
>2 >2120 >2 120 120 Cabinet width Cabinet width
Cabinet width
(cm)
fastening fastening fastening Cabinet width
Cabinet width >2 Cabinet width (cm) (cm)
120 point 110 (cm) 120
Cabinet
point 120 point width
110 110 Max. permissible cabinet (cm)weight
(cm)>2fastening
>2 120 120 (cm) Max. permissible cabinet weigth
120(cm) >2 100 (kg)120 (kg)
110 fastening
pointfastening110
110 100 110
100fastening
point point 110 110 Cabinet
100 90 90 point 90 110 100
100 100 Cabinet width
90 80 80 120 100 120 120 100 120 100
90 (cm) >2
>2 90 80 90 120
>2fastening
>2 90 90 fastening 120
80 70 70 70 110 90 100 100 100
80 110 120 120
fastening 80 80 point
point2fastening 2 80 2 60 100 80
80 120
100
point point 70 60 60 8070 100
fastening 70 fastening
70 fastening 80 2 80 70 70 100 100
60
120 50 point 50 50 90 70 2 fastening 60 100 90
120 point
120 60 point60 >2 2 2 60 60 80
40 80 60 60 fastening 60 80 80
100 100 50 100
50 40 40fastening
fastening 120 pointfastening
60 50
80 80
80 50 120 120point point 50 50
point 60
80 2 80 40 30 30point30 70 50 100 4040 70 60 60
60 2 fastening
260 60 40 120
40 100 100
80
40 40 40 40 60 2
30 20 100 20 20 60 40 30 60 40
40 fastening
pointfastening
40 40 30
30 80 80 30 30
60 fastening 40 40
point point 20 10 80 10 10 50 30 60 60 20 40 point 50
20 20 60 40 20 120
20
10 40 40 10
10 10 40 2 40 20 10 100 10 40
0 5030 40 604050 50
60 60 fastening
10 20 10303010 10
20 4020 30 5030 40 6040 50 50
60 60 80 30
(cm) 10 point20 Cabinet30Cabinet 40 depth 50 (cm)60 60 10 20 3020 40 50 60
10Cabinet
20 depth
10 2030(cm)
20depth
40 (cm)
30 4050 50 60 60 40 10 20
10 30
20 3040 40 50 50 60 60
10 20 30 40 50 Cabinet depth (cm) 10
60 10 20 30 40 50 Cabinet depth (cm) 10
60
Cabinet depth depth
Cabinet (cm) (cm) Cabinet depth depth
Cabinet (cm) (cm)
net depth (cm) Cabinet depth (cm)
10 20 30 40 50 60 10 20 30 40 50
Example: Cabinet depth 30 cm, cabinet width 80 cm. Example: Cabinet depth 45 cm, cabinet width 80 cm.
Cabinet depth (cm) Cabinet depth (cm)
In the diagram, trace a line vertically upwards at cabinet depth 30 cm (1) to the line for In the diagram, trace a line vertically upwards at cabinet depth 45 cm (1) to the line for
cabinet width 80 cm (2), and at this intersection horizontally to the left. Read (3): 50 kg cabinet width 80 cm (2), and at this intersection horizontally to the left. Read (3): 65 kg
is the maximum permissible cabinet weight for this cabinet dimension. is the maximum permissible cabinet weight for this cabinet dimension.
17
Partitions with mixed panelling
Abbreviations
600/625 mm
W Wall thickness (mm)
d Total thickness of the panelling Mixed construction F30
A Thickness of insulation layer (mm) 1 x 12.5 mm AQUAPANEL®
h Profile bridge height (mm) Cement Board Indoor +
1 x 12.5 mm GKF*
Description of material
1 AQUAPANEL® Cement
Board Indoor
2 Insulation material 600/625 mm
3 C wall profile
4 AQUAPANEL® Maxi Screw Mixed construction F90
4 a Quick-build screw 3.5 x 25 mm 1 x 12.5 mm AQUAPANEL®
6 Insulation strips e.g. sealing Cement Board Indoor +
tape/partition wall kit 1 x 12.5 mm GKF both sides*
7 Glued joint with AQUAPANEL®
Joint Adhesive (PU)
9 Permanently flexible sealant
14 a Knauf fire protection plate GKF, 600/625 mm
12.5 mm
Mixed construction F90
2 x 12.5 mm AQUAPANEL®
Cement Board Indoor +
2 x 12.5 mm GKF*
Physical properties
AQUAPANEL® Cement Board Wall thickn ess Mineral wool (A1, Fire resistance class Sound insulation Rw, RdB
Profile
Indoor (mm) Melting point >1000ºC) Test certificate (*) Test certificate
Thickness Gross density
(mm) (kg/m3)
CW 50/06 75 50 22 - 44 420001276-4
40 40 F30 P-3239-5122
CW 75/06 100 -
1 x 12.5 mm AQUAPANEL® Cement Board 60 25 F30 P-3239-5122
Indoor + 1 x 12.5 mm GKF 40 40 F30 P-3239-5122 -
CW 100/06 125 60 25 F30 P-3239-5122 -
80 14 - 45 420001590-3
CW 50/06 100 50 22 - 51 420001276-5
2 x 12.5 mm AQUAPANEL® Cement Board CW 75/06 125 60 25 F90 P-3243-5162 -
Indoor + 2 x 12.5 mm GKF 60 25 F90 P-3243-5162 -
CW 100/06 150
80 14 - 50 420001590-4
CW 75/06 125 60 25 F90 P-3243-5162 -
CW 100/06 150 60 25 F90 P-3243-5162 -
1 x 12.5 mm AQUAPANEL® Cement Board
80 Partition felt - 51 420001590-5
Indoor + 1 x 12.5 mm GKF on both sides
Noise control 150 2 x 40 100 F90 P-3243-5162 54 0065.05-P244
profile
18
Partitions with mixed panelling
Maximum wall height for wall with mixed panelling in m (including tiles)
AQUAPANEL® Cement Board Indoor +
without fire protection requirement
12.5 mm GKF
1 x 12.5 2 x 12.5 1 x 12.5 2 x 12.5
Installation range 1 Installation range 2
1) CW-profile 50/0.6 3.00 4.00 2.75 3.50
2) CW-profile 75/0.6 4.50 5.50 3.75 5.00
3) CW-profile 100/0.6 5.00 6.50 4.25 5.75
Special notes
When building the metal framework, follow the standard guidelines supplied by Knauf. Connection to solid walls
In rooms with continuous high levels of damp or chemical contamination such as commercial kitchens,
swimming pools, saunas or chemical laboratories, use profiles with increased corrosion protection.
Non-load-bearing partition walls should have expansion joints at least every 7.2/7.5 metres.
A further improvement in the sound reduction level of 1 to 3 dB can be achieved through using special
sound insulation profiles, e.g. Knauf MV profile.
The stated construction physical characteristics, static and construction properties can only be Corner formation and wall connection
achieved when exclusive use is made of recommended products.
To fasten other console loads such as sanitary items, separate measures are required.
19
Independent wall linings/shaft walls
600/625 mm
EI30 wall lining, double layer of panelling, horizontal section EI30 wall lining, vertical section
20
Independent wall linings/shaft walls
Special notes
Tiled walls with A
QUAPANEL® Cement Board Indoor and in-built
alutop-inspection openings are tested for impermeability.
600/625 mm
Wall lining, single layer of panelling, horizontal section Connection to solid walls
Physical properties
Wall Fire resistance class
Aquapanel® Cement Board Indoor Profile Mineral wool (A1 or A2) Rw, R dB
thickness Test certificate
(mm) Thickness (mm) Gross density (kg/m3)
2 x 12.5 mm single side CW 75/0.6 100 - - EI30 P-3029/2722 TM -
21
Directly fastened wall linings
Special notes
With continuous directly fastened wall linings
there is no limitation in construction height.
600/625 mm
600/625 mm
22
Independent wall linings/shaft walls
Description of material
1 AQUAPANEL® Cement Board Indoor
2 Insulation material
4 AQUAPANEL® Maxi Screw
5 Approved fixing method
7 Glued joint with AQUAPANEL®
Joint Adhesive (PU)
9 Permanently flexible sealant
12 UW-profile
18 Alignable acoustical mounting,
Hat profile e.g. Knauf 98/15/06
or direct hanger
19 Wooden batten b = ≥ 50 mm
Outer corner
Material
AQUAPANEL® Cement Board Indoor 1 m2
AQUAPANEL® Maxi Screws 15 pieces
AQUAPANEL® Joint Adhesive (PU) 50 ml
AQUAPANEL Board Primer
®
approx. 50 g
Insulation material 0.90 m2
Permanently flexible sealant
23
Partition wall, timber framing
Abbreviations
600/625 mm
W Wall thickness (mm)
d Thickness of the AQUAPANEL®
Cement Board Indoor panel
D/A Thickness of insulation layer (mm)
b/h Cross-section of the timber framing
(mm/mm)
HS Half width of panel (mm)
Description of material
1 AQUAPANEL® Cement Board Indoor Wooden stud frame, single-layer panelling, horizontal section
2 Insulation material
3 Supporting and foundation battens, 600/625 mm
softwood grade S10
4 AQUAPANEL® Maxi Screws, clips
or wood screws
5 Galvanized woodscrews 8 x 100 mm
with plastic pins 10 x 40 mm
6 Insulation strips e.g. sealing
tape/partition wall kit
7 Glued joint with AQUAPANEL®
Joint Adhesive (PU) Wooden stud frame, double-layer panelling, horizontal section
8 Woodscrews 6 x 100 mm
9 Permanently flexible sealant
Physical properties
Aquapanel® Cement Board Indoor Profile Wall thick Mineral wool (A1, Fire resistance class Sound insulation Rw, RdB
ness (mm) Melting point >1000ºC) Test certificate Test certificate
Thickness Gross density
(mm) (kg/m3)
1 x 12.5 mm per wall side HS 60/60 85 85 85 EI60 3032/2752 36(*) 420001590-6
24
Partition wall, timber framing
Particularly suitable for housing construction and for wooden stud structures
For connection to floors and ceilings and for studs, Clamp type:
use flat, warp-free grade S10 wood with a moisture Haubold SD 9150 CRF
content of less than 20%. (Ø 2.0 mm, L = 50 mm) oder Bühnen
Q 21 BAB/LQ21 BLB (Ø 1.8 mm, L = 50 mm),
Installing the connection timbers Minimum edge distance of 30 mm
The connection timbers are fastened with at least one
6 mm diameter woodscrew per metre wall length or Clamping device:
an equivalent, approved anchoring device. Haubold PN 9180 XII
or Bühnen SQ S 55
For side fastening of walls to wooden components,
we recommend two 12 mm diameter woodscrews. Screwnail type:
The wall lengths must not exceed 5000 mm. Haubold RNC-S 28/45 RF
(Ø 2.8 mm, L = 45 mm, Torx 15),
When installing the AQUAPANEL® Cement Board Minimum edge distance of 20 mm
Indoor panels on the timber frame, follow the
instructions for screwing and glueing given on page 9. Nail device:
Haubold RNC 65 S/ W I
When fastening the AQUAPANEL® Cement Board
Indoor panels, galvanized or rust-free clips or screw- Fastening distances from
nails can be used as an alternative to the A
QUAPANEL® each other:
Maxi Screw. For wood screws, minimum b/h Board edge: 150 mm
measurements of 80/60 must be selected. Board centre: 75 mm
Single Double
Material
layer layer
Square timber 80/60 2.7 lfm 2.7 lfm
Sealing tape/partition wall kit 0.7 lfm 0.7 lfm
Vertical section
Wood screws 8 x 100 mm plus peg 1.6 pieces 1.6 pieces
AQUAPANEL® Cement Board Indoor 2 m2 4 m2
AQUAPANEL Maxi Screws or
®
30 pieces 60 pieces
clips or wood screws 52 pieces 104 pieces
AQUAPANEL® Joint Adhesive (PU) 100 ml 200 ml
AQUAPANEL® Board Primer approx. 100 g approx. 100 g
Insulation material 1m 2
1 m2
Permanently flexible sealant
Special notes
For all walls with wooden frameworks we recommend adhering to national regulations. Table 1, DIN 4103,
part, 4, page 3, line 2 can be used to determine approved wall heights. The penetration depth of the screws Wall connection
in a wooden framework is 5 times the shank diameter, but not less than 24 mm. Non-load-bearing partition
walls should have expansion joints at least every 7.2/7.5 metres. Building expansion joints must also be
applied. The stated construction physical characteristics, static and construction properties can only be
achieved when exclusive use is made of recommended products.
T connection of two partition walls, variant 1 T connection of two partition walls, variant 2 Corner formation
25
Suspended ceiling with metal framing
Fire resistance period during fire load from the room side: EI30
Fire grading period during fire load from the room side
Fire resistance class
Layer Mineral wool (A1, Melting point >1000ºC)
Test certificate
Minimum
Thickness (mm) Gross density (kg/m3)
EI30 3461/7923-Mer
1) 1 x 12.5 mm AQUAPANEL® Cement Board Indoor
- - EI30 3461/7923-Mer
+ 1 x 12.5 mm GKF
EI30 3461/7923-Mer
2) 2 x 12.5 mm AQUAPANEL® Cement Board Indoor 2 x 40 50 EI30 c. Pr-02-02.092
26
Suspended ceiling with metal framing
Connection to solid walls for suspended ceilings Connection to light partition walls for suspended
with fire protection requirements ceilings without fire protection requirements
Special notes
• The framework of suspended ceilings is constructed in accordance • In rooms with continuous high levels of damp or chemical contamination
with EN 13964. such as commercial kitchens, swimming pools, saunas or chemical
• Built-in units such as lamps and ventilation extractors may load the laboratories, use profiles with increased corrosion protection.
framework in terms of its bearing capability. • A load case of internal pressure is not taken into account in the above
• Large loads must be attached to separate suspensions. construction information.
• Suspended ceilings with fire protection requirements may not be • The ceiling void must remain free from condensation.
stressed with extra loads.
27
Suspended ceiling with timber framing
28
Suspended ceiling with timber framing
Abbreviations •A
load case of internal pressure
a Distance (mm) of direct hanger is not taken into account in the
b Distance (mm) of the batten above construction information.
framework 40/60
c Distance (mm) of the lath The stated construction physical
framework 40/60 Connection to solid walls characteristics, static and
construction properties can only
be achieved when exclusive use is
made of recommended products.
Direct fastening under wooden ceilings Expansion joint for ceilings without fire
protection requirements
29
Moisture protection
CERTIFIKATE
AQUAPANEL® Cement Board Indoor is resistant to mould growth and is Due to excellent test results we are pleased to grant
This was confirmed by the Institute for Building Biology in Rosenheim. AQUAPANEL Cement Board
Indoor, Outdoor, Floor
Warranty
____________________________
The Warranty has been granted for a period of 2 years. Before the expiration renewed tests have to be applied for and carried out in
the interest of the consumer.
IBR Institut für Baubiologie Rosenheim GmbH D-83022 Rosenheim Heilig-Geist-Str. 54 Tel. +49(0)8031 3675-0 Fax -3675-30
Executive Director Reimut Hentschel HRB Traunstein 5362 Ust-IdNr. DE 131182830
info@baubiologie-ibr.de www.baubiologie-ibr.de
30
31
Permitted console loads
32
Access Doors
WARNING:
The screw length depends on the panel. At least 3 screws for each side
of the frame. Maximum distance of 150 mm between screws. There
should be no joins in the panels near the access panel. In the case of
wall-mounted access panels allow clearance of ≥ 50 mm at the top
third of the panel for opening.
33
Stability and construction
Installation range I
Areas less frequented by people as are assumed in e.g. flats, hotel
rooms, offices or wards and similarly used rooms including corridors.
Installation range II
Areas highly frequented by people as are assumed in e.g. larger
meeting rooms, lecture theatres, exhibition and retail spaces and
similarly used rooms. Additionally, rooms with a height difference
of the floors of 1 m or more are categorised in installation range II.
Maximal wall height h for installation range II of shaft walls, free-standing facings and partition walls with separated double stud frames:
with Knauf Gypsum Boards: 12.5 mm and 15 mm thick according to DIN 18180 (unit of h in m)
34
Stability and construction
Maximal wall height h of shaft walls, free-standing facings and partition walls with separated double stud frames:
with Knauf Gypsum Boards 20 mm and 25 mm thick according to DIN 18180 (unit of h in m):
Board thickness in mm
Metal stud frame (d = 0.6 mm) Distance between centres in mm
2 x20 2x25
1000 (2.70)/- (3.10)/-
625 (3.55)/2.80 4.00
CW 50 417 4.00 4.00
312.5 4.00 4.05
156.3 4.80 5.40
1000 3.95 4.00
625 4.00 4.05
CW 75 417 4.55 4.95
312.5 5.20 5.70
156.3 6.85 7.50
1000 4.00 4.10
625 5.00 5.40
CW 100 417 6.10 6.55
312.5 6.90 7.45
156.3 8.90 9.50
1000 4.95 5.25
625 6.40 6.85
CW 125 417 7.70 8.20
312.5 8.60 9.15
156.3 10.65 11.15
1000 6.15 6.50
625 7.85 8.30
CW 150 417 9.20 9.70
312.5 10.10 10.60
156.3 12.00 12.00
( ) value for installation range I
35
Material requirements
Note:
Data is without sound or fire protection requirements.
Data applies for complete construction with facing and coating on both sides.
AQUAPANEL® Board Primer should be deluted at a ratio of 1:2 (concentrate/water) before use.
The consumption data above relates to the amount of concentrate.
AQUAPANEL® Joint Filler & Skim Coating - white is processed with a nominal layer thickness of 4 mm.
The consumption data above relates to d = 4 mm.
36
Basis for calculation
Material consumption
Facing and coatings Description Unit Quantity / m2
AQUAPANEL® Cement Board Indoor single, single-layer sheeting m2 1.0
AQUAPANEL Maxi Srew (SN, SB)
®
unit spacing of posts = 600 or 625 mm pieces 15
AQUAPANEL Joint Adhesive (PU)
®
1 cartridge for 6.5 m 2
ml 50
AQUAPANEL® Board Primer Concentrate diluted 1:2 g 50
AQUAPANEL® Joint Filler & Skim Coating – white dry, thickness of 4 mm kg 3.5
AQUAPANEL Reinforcing Mesh
®
m 2
1.1
AQUAPANEL® Q4 Finish per mm thickness kg 1.7
Installation times
Per m2 Per m2
Facing and coatings
manual processing mechanical processing
AQUAPANEL® Cement Board Indoor
AQUAPANEL® Maxi Srews (SN, SB) 15 minutes -
AQUAPANEL Joint Adhesive (PU)
®
Corrosion protection
Humid and warm air can cause damage and corrosion to metal load class C. Special measures have to be taken for load class D
substructures. Care must be taken to ensure adequate corrosion depending on use and corrosive contamination. National standards
protection of the metal furring and connectors, particularly in humid and regulations may specify stricter requirements on corrosion
indoor areas such as swimming pools, public showers or canteens, etc. protection and must be followed (e.g. DIN 18168).
EN 13964 can be regarded as being decisive for corrosion protection.
Necessary corrosion protection class is to be specified by the planning
According to EN 13964, metal profiles Z 100 (zinc coating 100 g/m2) office and thus taken into account during all further planning, specifica-
with an additional organic coating of 20 μm per side are necessary for tion and application.
37
Fire protection
Fire protection
‘The protection of people and property from fire is the essential aim of Before the formation of the European community, the tests took place
fire protection.’ according to national standards, e.g. according to DIN 4102. This
brochure also contains constructions whose behaviour in case of fire
Preventative structural fire protection has to meet the following planning is proven according to DIN 4102.
and construction requirements:
– Fire risk is reduced if as many non-flammable building materials as The fire resistance tests according to European standards are conducted
possible are used. to EN 1364 for non-load bearing components and to EN 1365 for
– In the event of a fire, people within the building must be able to load-bearing ones, in each case following EN 1363.
leave the building safely.
– The construction must be such that it remains stable sufficiently long The fire resistance time of the tested AQUAPANEL® Cement Board
in the event of fire, and prevents spread of fire and smoke to other Indoor constructions extends, according to the type of construction, up
buildings or other parts of the building for long enough. to a maximum of 120 minutes and is indicated by a precise fire
resistance classification for each component. Based on the classifica-
From these requirements comes the need to research building materials tion designation, you can recognise whether the test was carried out
and components both structurally and technically for their applicable fire according to national DIN 4102 or European standard. National tests
behaviour and ability to protect against fire. Each building material is use designations F or particularly W for non load-bearing external
given a building material classification according to how it behaves during walls. The European standard uses different designations. The most
a fire. AQUAPANEL® Cement Board Indoor is classified as “non-combusti- important designations for the description of the performance criteria
ble”, building material class A1 in accordance with EN 13501. are given below, together with their meanings.
The behaviour of AQUAPANEL® Cement Board Indoor constructions in The following table shows the allocation of the fire grading periods
the event of a fire has been proven by extensive fire tests. according to DIN and EN.
Testing and classification must also only be carried out on one side. Independent of the test/tests performed, the classifications are described as follows:
i -> o, when the intention is to classify from inside to outside;
i <- o, when the intention is to classify from outside to inside;
i <-> o, when the intention is to classify from inside to outside and from outside to inside.
According to EN, the description of fire resistance is described by the following performance criteria:
38
Fire protection
Single stud
Fire Wall
Profile Measurements from inside to outside Insulation System properties
resistance thickness
Sound
Weight Approv. sound
Approval No Fire insulation dB
(kg/m²) insulation*
Rw,P (Rw,R)
40 mm 420001590-9 +
PB 3031/2742 CW 75 GKF 12.5 + CW75 + OD 12.5 100 mm 28.6 EI 30 50 (48)
(40 kg/m³) insulation
Timber stud 40 mm
PB 3032/2752 ID 12.5 + HS 60 + OD 12.5 85 mm 34.8 EI 60 N/A -
60/60 (40 kg/m³)
60 mm
PB 3220/5032 CW 75 ID 12.5 + CW 75 + OD 12.5 100 mm 33.6 EI 30 N/A -
(30 kg/m³)
60 mm
PB 3973/1183 CW 75 2x GKF12.5 + CW 75 + 12.5 OD 112.5 mm 40.2 EI 60 420001276-8 48 (46)
(50kg/m³)
80 mm
PB 3321/2155 CW 100 2x ID 12.5 + CW 100 + 2x OD 12.5 150 mm 65.3 EI 120 N/A -
(30kg/m³)
PB 3258/1525 CW 50 ID 12.5 + CW 50 + OD 12.5 75 mm none 31.7 EI 30 N/A -
60 mm
PB 3015/2882 CW 75 2x ID 12.5 + CW 75 + 2x OD 12.5 125 mm 65.8 EI 120 N/A -
(50 kg/m³)
PB 3672/6696 CW 50 2x ID 12.5 + CW 50 + 2x OD 12.5 100 mm none 62.7 EI 90 N/A -
PB 3054/119/09 CW 50 ID 12.5 + CW 50 + OD 12.5 75 mm none 31.7 EI 30 N/A -
CW 50 ID 12.5 + CW 50 + OD 12.5 75 mm none 31.7 N/A -
CW 75 ID 12.5 + CW 75 + OD 12.5 100 mm none 31.8 N/A -
CW 100 ID 12.5 + CW 100 + OD 12.5 125 mm none 31.9 N/A -
420001276-7 +
CW 50 GKFi 12.5 + CW 50 + OD 12.5 75 mm none 26.9 45 (43)
insulation
AC3-D2-05-XVI +
CW 75 GKFi 12.5 + CW 75 + OD 12.5 100 mm none 27 50 (48)
insulation
abP 3239/5122 EI 30
420001590-9 +
CW 100 GKFi 12.5 + CW 100 + OD 12.5 125 mm none 27.1 50 (48)
insulation
420001276-7 +
CW 50 GKBi 12.5 + CW 50 + OD 12.5 75 mm none 26 45 (43)
insulation
AC3-D2-05-XVI +
CW 75 GKBi 12.5 + CW 75 + OD 12.5 100 mm none 26.1 50 (48)
insulation
420001590-9 +
CW 100 GKBi 12.5 + CW 100 + OD 12.5 125 mm none 26.2 50 (48)
insulation
CW 50 2xID 12.5 + CW 50 + 2xOD 12.5 100 mm none 62.7 N/A -
CW 75 2xID 12.5 + CW 75 + 2xOD 12.5 125 mm none 62.8 N/A -
CW 100 2xID 12.5 + CW 100 + 2xOD 12.5 150 mm none 62.9 N/A -
CW 50 ID 12.5 + GKF 12.5 + CW 50 + GKF 12.5 + OD 12.5 100 mm none 52.1 N/A -
CW 75 ID 12.5 + GKF 12.5 + CW 75 + GKF 12.5 + OD 12.5 125 mm none 52.2 N/A -
CW 100 ID 12.5 + GKF 12.5 + CW 100 + GKF 12.5 + OD 12.5 150 mm none 52.3 N/A -
420001276-8 +
CW 50 2x GKF 12.5 + CW 50 + 2x OD 12.5 100 mm none 53.1 48 (46)
insulation
AC3-D2-05-XVI +
abP 3243/5162 CW 75 2x GKF 12.5 + CW 75 + 2x OD 12.5 125 mm none 53.2 F 90-A 50 (48)
insulation
AC3-D2-05-XIX +
CW 100 2x GKF 12.5 + CW 100 + 2x OD 12.5 150 mm none 53.3 50 (48)
insulation
CW 50 2x GKF 12.5 + CW 50 + GKF 12.5 + OD 12.5 100 mm none 47.3 N/A -
CW 75 2x GKF 12.5 + CW 75 + GKF 12.5 + OD 12.5 125 mm none 47.4 N/A -
CW 100 2x GKF 12.5 + CW 100 + GKF 12.5 + OD 12.5 150 mm none 47.5 N/A -
CW 50 ID 12.5 + GKF 12.5 + CW 50 + 2x OD 12.5 100 mm none 57.9 N/A -
CW 75 ID 12.5 + GKF 12.5 + CW 75 + 2x OD 12.5 125 mm none 58 N/A -
CW 100 ID 12.5 + GKF 12.5 + CW 100 + 2x OD 12.5 150 mm none 58.1 N/A -
* To reach the appropriate sound insulation an additional or different insulation may be necessary
39
Fire protection
Single stud
Fire resistance Profile Measurements from inside to outside Wall thickness Insulation System properties
Weight Approv. sound Sound insulation
Approval No Fire
(kg/m²) winsulation* dB R w,P (Rw,R)
60 mm
CW 75 2x ID + CW 75 + 2x OD 125 mm 65.8 N/A -
(50kg/m³)
abP 3244/5172 F 120-A
60 mm
CW 100 2x ID 12.5 + CW 100 + 2x OD 12.5 150 mm 65.9 N/A -
(50 kg/m³)
60 mm
(25kg/m³)
CW 50 1x ID 12.5 + CW 50 + 1x OD 12.5 75 mm or MW 33.3 N/A -
40 mm
(40 kg/m³)
60 mm
(25kg/m³)
P 3649/9454 CW 75 1x ID 12.5 + CW 75 + 1x OD 12.5 100 mm or MW 33.4 F 30-A N/A -
40 mm
(40 kg/m³)
60 mm
(25kg/m³)
CW 100 1x ID 12.5 + CW 100 + 1x OD 12.5 125 mm or MW 33.5 N/A -
40 mm
(40 kg/m³)
40
Fire protection
Double stud
Fire resistance Profile Measurements from inside to outside Wall thickness Insulation System properties
Weight Approv. sound Sound insulation
Approval No Fire
(kg/m²) insulation* dB Rw,P (Rw,R)
2x ID 12.5 + CW 50 + e = 50 mm + CW 50 + 60 mm
CW 50 200 mm 65.2 N/A -
2x OD 12.5 (30 kg/m³)
60 mm
CW 75 2x ID 12.5 + CW 75 + CW 75 + 2x OD 12.5 200 mm 65.4 N/A -
(30 kg/m³)
60 mm
CW 100 2x ID 12.5 + CW 100 + CW 100 + 2x OD 12.5 250 mm 65.6 N/A -
(30 kg/m³)
1xID 12.5 + 1x GKF 12.5 + CW 50 + e = 50 60 mm
CW 50 200 mm 58.6 N/A -
mm + CW 50 + 2x OD 12.5 (30 kg/m³)
1xID 12.5 + 1x GKF 12.5 + CW 75 + CW 75 + 60 mm
CW 75 200 mm 60.6 N/A -
2x OD 12.5 (30 kg/m³)
1xID 12.5 + 1x GKF 12.5 + CW 100 + CW 100 60 mm
CW 100 250 mm 60.8 N/A -
+ 2x OD 12.5 (30 kg/m³)
P 3650/9464 F 90-A
2x GKF 12.5 + CW 50 + e = 50 mm + CW 50 + 60 mm
CW 50 200 mm 55.6 AC3-D2-05 XVIII 62 (60)
CW 50 + 2x OD 12.5 (30 kg/m³)
60 mm
CW 75 2x GKF 12.5 + CW 75 + CW 75 + 2x OD 12.5 200 mm 55.8 AC3-D2-05 XVII 58 (56)
(30 kg/m³)
2x GKF 12.5 + CW 100 + CW 100 + 2x OD 60 mm
CW 100 250 mm 56 N/A -
12.5 (30 kg/m³)
2x GKF 12.5 + CW 50 + e = 50 mm + CW 50 + 60 mm
CW 50 200 mm 49.8 N/A -
1x GKF 12.5 + 1x OD 12.5 (30 kg/m³)
2x GKF 12.5 + CW 75 + CW 75 + 1x GKF 12.5 60 mm
CW 75 200 mm 50 N/A -
+ 1x OD 12.5 (30 kg/m³)
2x GKF 12.5 + CW 100 + CW 100 + 1x GKF 60 mm
CW 100 250 mm 50.2 N/A -
12.5 + 1x OD 12.5 (30 kg/m³)
41
Sound protection
Single stud
Test report Substructure Type of board inside Type of board outside Insulation Thickness Sound re-duction [dB]
420001276-1 CW 50 1x Indoor 1x Indoor Mineral fibre 50 mm (22kg/m³) 75 mm R w,P = 44
42001276-2 CW 50 2x Indoor 2x Indoor Mineral fibre 50 mm (22kg/m³) 100 mm R w,P = 51
420001061-1 CW 75 1x Indoor 1x Indoor Mineral fibre 40 mm (40kg/m³) 100 mm R w,P = 43
420001061-2 CW 75 2x Indoor 2x Indoor Mineral fibre 40 mm (40kg/m³) 125 mm R w,P = 49
22019604 MC 70 2x Indoor 2x Indoor Mineral fibre 75 mm (30kg/m³) 120 mm R w,P = 50
22019603 MC 70 Indoor Indoor Mineral fibre 75 mm (30kg/m³) 95 mm R w,P = 45
2x Indoor 2x Indoor
22019605 MC 70 Mineral fibre 75 mm (30kg/m³) 118 mm R w,P = 52
incl. Plaster system incl. Plaster system
420001590-1 CW 100 1x Indoor 1x Indoor Mineral fibre 80 mm (14kg/m³) 125 mm R w,P = 46
420001590-2 CW 100 2x Indoor 2x Indoor Mineral fibre 80 mm (14kg/m³) 150 mm R w,P = 51
420001590-8 CW 100 Magnum 2x Indoor 2x Indoor Mineral fibre 80 mm (14kg/m³) 150 mm R w,P = 53
420001590-6 Timber 60/60 1x Indoor 1x Indoor Mineral fibre 40 mm (14kg/m³) 85 mm R w,P = 38
420001590-7 Timber 60/60 2x Indoor 2x Indoor Mineral fibre 40 mm (14kg/m³) 110 mm R w,P = 44
420001276-4 CW 50 1x Indoor 1x GKF 12,5 mm Mineral fibre 50 mm (22kg/m³) 75 mm R w,P = 46
420001276-5 CW 50 2x Indoor 2x GKF 12,5 mm Mineral fibre 50 mm (22kg/m³) 100 mm R w,P = 53
420001590-3 CW 100 1x Indoor 1x GKF 12,5 mm Mineral fibre 80 mm (14kg/m³) 125 mm R w,P = 47
420001590-5 CW 100 1x Indoor + 1x GKF 1x Indoor + 1x GKF 12,5 mm Mineral fibre 80 mm (14kg/m³) 150 mm R w,P = 53
0065.05 - P 244 CW 100 Magnum 1x Indoor + 1x GKF 1x Indoor + 1x GKF 12,5 mm MW 2x40 mm (100kg/m³) 150 mm R w,P = 56
420001590-4 CW 100 2x Indoor 2x GKF 12,5 mm Mineral fibre 80 mm (14kg/m³) 150 mm R w,P = 52
Double stud
Test report Substructure Type of board inside Type of board outside Insulation Thickness Sound re-duction [dB]
420001276-3 2x CW 50 1x Indoor 1x Indoor Mineral fibre 2x50mm (22kg/m³) 245 mm R w,P = 53
0066.05 - P 244 2x CW 50 1x Indoor 1x Indoor Mineral fibre 2x40 mm (100kg/m³) 130 mm R w,P = 56
0067.05 - P 244 2x CW 50 2x Indoor 2x Indoor Mineral fibre 2x40 mm (100kg/m³) 155 mm R w,P = 63
2x GKB 12,5 mm
22019606 2x MC 48 2x GKB 12,5 mm 2x Mineral fibre 50 mm (30kg/m³) 159 mm R w,P = 58
+ Indoor intermediate
2x GKB 12,5 mm 2x GKB 12,5 mm
22019607 2x MC 48 2x Mineral fibre 50 mm (30kg/m³) 159 mm R w,P = 57
+ Indoor intermediate + Electrical installation
42
System properties
Single stud
Impact resistance
Report no. 220004884 Impact tests of AQUAPANEL ® Cement Board Indoor (according to BS 8200)
Impact tests of AQUAPANEL ® Cement Board Indoor
Testing of AQUAPANEL® Cement Board Indoor (according to ASTM Standard C 1325-04)
(according to BS 8200)
Testing of AQUAPANEL ® Cement Board Indoor
Certified hygrothermal behaviour of AQUAPANEL Cement Board Indoor of Scientific Centre for Building Techniques, France (CSTB)
(according to ASTM Standard C 1325-04)
In case of fire resistance the dimension of the wall (thickness) or the dimension of single wall
Weight of components kg/m Board type kg/m²
components could always be increased. Further the dry density of the insulation can be increased
CW 50 0.70 GKB 12.5 mm 9.3
(acc. EN1364-1). In case of sound insulation note the following: an increased wall thickness (with
increased dimensions of the wall components) always benefits the system (excluding an increased CW 75 0.80 GKF 12.5 mm 10.2
material thickness of the stud). A flow resistance of >= 5 for the insulation material is always a CW 100 0.90 GKF 15 mm 13.3
benefit for the system in case of sound issues. An increased dry density of the insulation could CW 125 0.95
downgrade the sound performance of the system.
CW 150 1.00
43
System properties
Physical properties
According to ETA-07/0173
Min. bending radius for 900/1200 mm wide board (m) 3
Min. bending radius for 300 mm wide strip (m) 1
Dry bulk density (kg/m3) according to EN 12467 approx. 1050
Bending strength (MPa) according to EN 12467 8.75
Tensile strength perpendicular to the plane of the board (N/mm ) according to EN 319
2
0.49
Shearing strength (N) according to EN 696
pH-value 12
Thermal conductivity (W/mK) according to EN ISO 10456 0.35
Thermal expansion (10 K)
-6
7
Water vapour diffusion resistance μ (-) according to EN ISO 12572 50
Length variation 65% - 85% humidity (mm/m) according to EN 318 0.25
Thickness variation 65% - 85% humidity (%) according to EN 318 0.1
Building material class according to EN 13501 A1, non-combustible
Physical properties
Board type acc. EN 520 A
Physical properties
Board type acc. EN 520 H2
Fireboard
Physical properties
Density (kg/m³) ≥ 780
Min. bending radius (m) 4 - 50
Bending tensile strength (Fireboard 20 mm) (N/mm²) parallell: approx. 4.9
perpendicular: approx. 1.8
Water vapour diffusion coefficient acc. EN 12524, Table 1 (μ) 10
Thermal conductivity acc. EN 12524, Table 1 (λ ) (W/mK) 0.25
Building material class acc. EN 13501 A1, non-combustible
Massivbauplatte
Physical properties
Board type acc. EN 520 DF / DFH2
Building material class acc. EN 13501 A2
44
System properties
Physical properties
Board type acc. EN 520 DFH2IR
Characteristic compressive strength perpendicular (N/mm²) approx. 10
Bending E-Modulus (N/mm²) approx. 3500
Building material class acc. EN 13501 A2-s1,d0 (B)
Silentboard
Physical properties
Board type acc. EN 520 DF
Building material class acc. EN 13501 A2
Profiles
Physical properties
acc. to DIN 18182-1. Accessories for use with gypsum plasterboards — Part 1: Steel plate sections
Insulation
Physical properties
acc. to EN 13162. Thermal insulation products for buildings - Factory made mineral wool (MW) products
45
Sample specification
m² Corrosion-resistant substructure
Build a single stud construction made of galvanised
UW-profiles _________ mm and CW-profiles _________ mm;
brand __________________.
Centre distance of the stud profiles < 625 mm, Fix the edge profiles at a distance of < 1000 mm from each other on the ceiling and floor.
m² If necessary, fit water-tight and slip-proof insulating boards, brand ______________, as a cavity insulation. Install the single layer
panelling on both sides. AQUAPANEL ® Cement Board Indoor 12.5 mm, (cement-bonded mineral structural panel, non-combustible (A1),
free of cellulose fibres), glued with AQUAPANEL® Joint Adhesive in the joint areas and screwed together with AQUAPANEL® Maxi Screws.
After the curing period (usually on the next day), the protruding AQUAPANEL® Joint Adhesive is chipped away. In the case of pre-cut parts:
keep a distance of ≥ 15 mm to the panel edge and < 215 cm between screws.
m² If necessary, apply an alternative seal to the entire surface, e.g. Knauf Flächendicht or _________________*.
m² Application of ceramics (tile size < 300 x 300 mm) with a flexible adhesive (at least C2/S1 according to DIN EN 12004 / 12002 and
the directive for flexible grout) or apply a surface ready to be painted made entirely of AQUAPANEL® Joint Filler & Skim Coating – white,
primed to a thickness of at least 4 mm, with a fabric inlay embedded close to the surface made of AQUAPANEL® Reinforcing Mesh.
m² Additional item: Apply AQUAPANEL® Q4 Finish to the entire finished plaster surface. Maximum layer thickness for each application:
2 mm. Polish the surface (grade 120 or smaller) after the drying period (approx. 1 day/mm layer thickness).
Note:
The vertical joints of the opposing panelling must be arranged offset by at least one stud profile distance.
Horizontal joints must be arranged offset by at least 400 mm. Vertical joints must be butted to the metal studs.
All work must be carried out according to the manufacturer’s instructions.
46
Sample specification
m² Corrosion-resistant substructure
Build a single stud construction made of galvanised
UW-profiles _________ mm and CW-profiles _________ mm;
brand __________________.
Centre distance of the stud profiles < 625 mm, Fix the edge profiles at a distance of < 1000 mm from each other on the ceiling and floor.
m² If necessary, fit water-tight and slip-proof insulating boards, brand ______________, as a cavity insulation
m² If necessary, apply an alternative seal to the entire surface, e.g. Knauf Flächendicht or _________________*.
m² Application of ceramics (tile size < 300 x 300 mm) with a flexible adhesive (at least C2/S1 according to DIN EN 12004 / 12002 and
the directive for flexible grout) or apply a surface ready to be painted made entirely of AQUAPANEL® Joint Filler & Skim Coating – white,
primed to a thickness of at least 4 mm, with a fabric inlay embedded close to the surface made of AQUAPANEL® Reinforcing Mesh.
m² Additional item: Apply AQUAPANEL® Q4 Finish to the entire finished plaster surface. Maximum layer thickness for each application:
2 mm. Polish the surface (grade 120 or smaller) after the drying period (approx. 1 day/mm layer thickness).
Note:
The vertical joints of the opposing panelling must be arranged offset by at least one stud profile distance.
Horizontal joints must be arranged offset by at least 300 mm. Vertical joints must be butted to the metal studs.
All work must be carried out according to the manufacturer’s instructions.
47
Sample specification
Wall lining / shaft wall with cement-bonded structural panels Construction type: wall lining / shaft wall with single layer panelling and
without fire safety requirements
m² Fitting of water-tight and slip-proof insulation layer according to the requirements made from mineral wool DIN EN 13162,
Insulation thickness: _________ mm
Density: _________ kg/m³
Thermal conductivity group _____
Brand ___________________.
m² Additional item:
Depending on the requirements, a vapour barrier / vapour seal *, brand ____________________, must be fixed to the
substructure according to the manufacturer’s instructions prior to the panelling.
m² Installation of panelling on one side made of 1 layer of AQUAPANEL® Cement Board Indoor 12.5 mm, joint areas butted tightly together,
glued with AQUAPANEL® Joint Adhesive and screwed together with AQUAPANEL® Maxi Screws SN 39. After the curing period (usually on
the next day), the protruding AQUAPANEL® Joint Adhesive is chipped away. For pre-cut parts: keep a screw distance of ≥ 20 mm to the
panel edge and < 215 cm between screws.
m² Surface coating
Apply the ceramics (tile size < 300 x 300 mm) with a flexible adhesive, at least C2 according to DIN EN 12004.
m² Alternative item:
Apply a surface ready to be painted made entirely of AQUAPANEL® Joint Filler & Skim Coating – white, primed to a thickness of at least
4 mm, with a fabric inlay embedded close to the surface made of AQUAPANEL® Interior Reinforcing Mesh.
m² Alternative item:
Apply AQUAPANEL® Q4 Finish to the entire finished surface according to the processing instructions.
m² Alternative item:
Apply the ceramics (tile size < 300 x 300 mm), glued with a flexible adhesive, at least C2 according to DIN EN 12004, backsplash height
_____m, apply AQUAPANEL® Q4 Finish to the entire finished surface above the backsplash according to the processing instructions.
48
Sample specification
Wall covering with cement-bonded structural panels Construction type: double stud wall with single layer panelling and without fire
safety requirements
m² Building of substructure
from galvanised sheet steel profiles, corrosion-resistant, as a double stud construction, connected to AQUAPANEL® Panel Strips,
UW-profile 2 x _________ mm and
CW-profile 2 x _________ mm;
brand __________________.
Centre distance of the stud profiles < 625 mm / _______ mm*.
m² Fitting of water-tight and slip-proof insulation layer according to the requirements made from mineral wool DIN EN 13162,
Insulation thickness: _________ mm
Density: _________ kg/m³
Thermal conductivity group _____
Brand ___________________.
m² Alternative item:
Depending on the requirements, a vapour barrier / vapour seal *, brand ____________________, has to be fixed to the
substructure according to the manufacturer’s instructions prior to the panelling.
m² Installing of panelling on both sides made of 1 layer of AQUAPANEL® Cement Board Indoor 12.5 mm, joint areas butted tightly together,
glued with AQUAPANEL® Joint Adhesive and screwed together with AQUAPANEL® Maxi Screws SN 39. After the curing period (usually on
the next day), the protruding AQUAPANEL® Joint Adhesive is chipped away. In the case of pre-cut parts: keep a screw distance of ≥ 20
mm to the panel edge and < 215 cm between screws.
m² Surface coating
Apply the ceramics (tile size < 300 x 300 mm) with a flexible adhesive, at least C2 according to DIN EN 12004.
m² Alternative item:
Apply a surface ready to be painted made entirely of AQUAPANEL® Joint Filler & Skim Coating – white, primed to a thickness of at least
4 mm, with a fabric inlay embedded close to the surface made of AQUAPANEL® Reinforcing Mesh.
m² Alternative item:
Apply AQUAPANEL® Q4 Finish to the entire finished surface according to the processing instructions.
m² Alternative item:
Apply the ceramics (tile size < 300 x 300 mm), glued with a flexible adhesive, at least C2 according to DIN EN 12004, backsplash height
_____m, apply AQUAPANEL® Q4 Finish to the entire finished surface above the backsplash according to the processing instructions.
49
Sample specification
Install the AQUAPANEL Cement Board Indoor according to the manufacturer’s instructions and glue them together with Aquapanel Joint
®
Adhesive in the joint area. Chip off any excess adhesive on the next day.
Cover all visible joints with AQUAPANEL® Q4 Finish, press fibre glass joint cover strips (e.g. Knauf) into the filler so that they overlap at
the joints, apply AQUAPANEL® Q4 Finish again in a thin layer to the cover strips and remove any excess.
Remove any irregularities on the surface and on the screw holes with a grinding pencil after the drying period.
Apply AQUAPANEL® Q4 Finish again to the existing filler layer with a width of at least 20 cm.
Apply another layer of AQUAPANEL® Q4 Finish after the drying period and, if necessary, after having polished the surface in-between.
After approx. 24 hours of drying time, it is possible to polish the surface with sand paper (grade 120 or smaller). Very polished surfaces
are finished with e.g. an electric orbital grinder.
Corrosion protection* according to DIN ________, table _________, minimum corrosion protection class _______. Fix the
substructure on the existing raw ceiling with appropriate fixing devices. In damp rooms e.g. Kunkel ceiling anchors, type KDM, material
1.4529, MKT ceiling bolts B 6-da, material 1.4529 or fischer nail anchors FNA II, material 1.4529 for indoor areas, damp rooms and
indoor swimming pools.
Fixing of AQUAPANEL® Cement Board Indoor onto the substructure with AQUAPANEL® Maxi Screws SN 39, SN 25 (25 screws/panel
necessary). In the case of pre-cut parts: keep a distance of ≥ 15 mm to the panel edge and < 215 cm between screws.
Fill the panel joints and screw heads with AQUAPANEL® Joint Filler – grey. Insert an AQUAPANEL® Tape (10 cm) in the joint area.
Prime the panels with AQUAPANEL® Board Primer (usage approx. 40-60 g/m²)
In the case of surfaces which are ready to be painted or which are plastered, it is necessary to embed the fibre glass fabric AQUAPANEL®
Reinforcing Mesh on the entire surface into the AQUAPANEL® Joint Filler & Skim Coating – white (at least 4 mm). At the joints, the
fabric must overlap by 10 cm.
Additional item: Apply AQUAPANEL® Q4 Finish to the entire finished plaster surface. Maximum layer thickness for each application:
2 mm. Polish the surface (grade 120 or smaller) after the drying period (approx. 1 day/mm layer thickness).
50
Reference of additional documentation
51
All technical changes reserved. Only the current printed instructions are valid.
Our warranty is expressly limited to our products in flawless condition.
The constructional and structural properties and characteristic building
physics of Knauf systems can solely be ensured with the exclusive use of
Knauf system components, or other products expressly recommended by
Knauf. All application quantities and delivery amounts are based on empirical