Automation Portal
Main
Name Data type Default value Comment
Input
Initial_Call Bool Initial call of this OB
Remanence Bool =True, if remanent data are available
Temp
TIMER DTL
YEAR UInt
MONTH USInt
DAY USInt
WEEKDAY USInt
HOUR USInt
MINUTE USInt
SECOND USInt
NANOSECOND UDInt
Constant
%M500.0 %FC7
"FirstScan" "FIRST SCAN"
EN ENO
Network 2: CALL
Totally Integrated
Automation Portal
%FC3
"SET SEMI AUTO"
EN ENO
%FC4
"SET MANUAL"
EN ENO
%FC6
"READ TEM-HUMI"
EN ENO
%FC1
"Modbus"
EN ENO
%M507.0
%M500.2 "Emergency_ %FC8
"AlwaysTRUE" Stop" "RUN"
EN ENO
%M507.0
%I0.0 %M507.1 "Emergency_
"I_Sw_EStop" "Error_Freq" Stop"
%M521.5
%I0.2 %M521.5 "BitOutput_Start/ %M521.5
"I_Start/Stop_ "BitOutput_Start/ Stop_Systems" "BitOutput_Start/
Sys_Auto" Stop_Systems" SR Stop_Systems"
P S Q
%M520.5
"Bit_P_Start/
Stop_Systems"
%I0.2 %M521.5
"I_Start/Stop_ "BitOutput_Start/
Sys_Auto" Stop_Systems"
P R1
%M520.5
"Bit_P_Start/
Stop_Systems"
%M512.2
%M507.0 "HMI_ %M507.5
"Emergency_ ConfirmSetting_ "HMI_Change_
Stop" ModeOperation" AutoMode" MOVE
EN ENO
100 IN
%MW509
"HMI_
BitWindows_
OUT1 Operation"
%M507.7
"HMI_Change_
ManMode" MOVE
EN ENO
200 IN
%MW509
"HMI_
BitWindows_
OUT1 Operation"
%M507.6
"HMI_Change_
SemiAutoMode" MOVE
EN ENO
300 IN
%MW509
"HMI_
BitWindows_
OUT1 Operation"
%DB9
"IEC_Timer_0_
DB_3" %M512.3
%M507.5 "Confirm_
"HMI_Change_ TOF Complete_
AutoMode" Time ModeOperation"
IN Q
T#500ms PT ET ...
%M507.7
"HMI_Change_
ManMode"
%M507.6
"HMI_Change_
SemiAutoMode"
%M500.2 %M507.2
100
"AlwaysTRUE" "AutoMode"
==
Int
%MW509 %DB7
"HMI_ "AUTOMATIC_DB"
BitWindows_ %FB3
Operation"
"AUTOMATIC"
EN ENO
%M507.3
200 "ManMode"
==
Int
%MW509 %DB5
"HMI_ "MANUAL_DB"
BitWindows_ %FB1
Operation"
"MANUAL"
EN ENO
2.1 ( Page1 - 5)
Totally Integrated
Automation Portal
%M507.4
300 "SemiAutoMode"
==
Int
%MW509 %DB6
"HMI_ "SEMI AUTO_DB"
BitWindows_ %FB2
Operation"
"SEMI AUTO"
EN ENO
Totally Integrated
Automation Portal
%MW509
"HMI_
BitWindows_ %FC5
Operation"
"RESET SEMI AUTO"
<>
Int EN ENO
300
Network 8: RESET CAC BIT CHON CHE DO VAN HANH O MAN HINH
Totally Integrated
Automation Portal
%M505.1 %M507.5
"HMI_Click_ "HMI_Change_
SettingOperation" AutoMode"
R
"IEC_Timer_0_ %M507.7
DB_2".Q "HMI_Change_
ManMode"
R
%M507.6
"HMI_Change_
SemiAutoMode"
R
%DB8
"IEC_Timer_0_
%M512.3 DB_2"
"Confirm_
Complete_ "IEC_Timer_0_ TON
ModeOperation" DB_2".Q Time
IN Q
T#500ms PT ET ...
%M550.0
"Tag_2" %M550.0
"Tag_2"
%DB20
"IEC_Timer_0_
DB_13"
%M515.1
"HMI_ALLOW_ TOF
SettingTimePLC" Time MOVE
IN Q EN ENO
T#60000ms PT ET ... "TIME"."SET
%MW756 Time".YEAR
OUT1
"HMI_
SetTimePLC_
Year" IN
MOVE
EN ENO
"TIME"."SET
%MW758 Time".MONTH
OUT1
"HMI_
SetTimePLC_
Month" IN
MOVE
EN ENO
"TIME"."SET
%MW760 Time".DAY
OUT1
"HMI_
SetTimePLC_
Day" IN
MOVE
EN ENO
"TIME"."SET
%MW762 Time".HOUR
"HMI_ OUT1
SetTimePLC_
Hour" IN
MOVE
EN ENO
"TIME"."SET
%MW764 Time".MINUTE
OUT1
"HMI_
SetTimePLC_
Min" IN
MOVE
EN ENO
"TIME"."SET
%MW766 Time".SECOND
OUT1
"HMI_
SetTimePLC_
Second" IN
MOVE
EN ENO
%MW90 %MW8036
"Year_System" IN "Show Year
OUT1 Systems"
MOVE
EN ENO
%MB92 %MW8038
"Month_System" IN "Show Month
OUT1 Systems"
MOVE
EN ENO
%MB93 %MW8040
"Day_System" IN "Show Day
OUT1 Systems"
2.1 ( Page1 - 9)
Totally Integrated
Automation Portal
MOVE
EN ENO
%MB94 %MW8042
"Hour_System" IN "Show Hour
OUT1 Systems"
MOVE
EN ENO
%MB95 %MW8044
"Min_System" IN "Show Min
OUT1 Systems"
MOVE
EN ENO
%MB96 %MW8046
"Second_System" IN "Show Second
OUT1 Systems"
%M515.1
"IEC_Timer_0_ "HMI_ALLOW_
DB_13".Q SettingTimePLC"
R
%DB2
"IEC_Timer_0_
DB_1" %M515.3
%M515.2 "Confirm_
"HMI_Confirm_ WR_SYS_T TOF Complete_
SettingTimePLC" DTL Time SettingTimePLC"
EN ENO IN Q
"TIME"."SET Time" IN T#1000ms PT ET ...
%MW768
"Result_
RET_VAL SettingTimePLC"
Totally Integrated
Automation Portal
RD_SYS_T
DTL
EN ENO
%MW220
"Check_Get_
RET_VAL RealTime"
OUT #TIMER
%MW220
"Check_Get_
RealTime"
MOVE
==
Int EN ENO
#TIMER.YEAR IN %MW90
0
OUT1 "Year_System"
MOVE
EN ENO
#TIMER.MONTH IN %MB92
OUT1 "Month_System"
MOVE
EN ENO
#TIMER.DAY IN %MB93
OUT1 "Day_System"
MOVE
EN ENO
#TIMER.HOUR IN %MB94
OUT1 "Hour_System"
MOVE
EN ENO
#TIMER.MINUTE IN %MB95
OUT1 "Min_System"
MOVE
EN ENO
#TIMER.SECOND IN %MB96
OUT1 "Second_System"
MOVE
EN ENO
#TIMER.WEEKDAY IN
%MB97
"WeekDay_
OUT1 System"
Network 12: CONFIRM SETTING TIME ON/OFF INVERTER IN SEMI AUTO MODE BTQC1
Totally Integrated
Automation Portal
%M512.6
"HMI_
ConfirmSetting_
FreqQC1_ %FC10
SemiAutoMode" "ConfirmSet On/OffSemiAuto"
EN ENO
%M537.0 %M532.0
"HMI_Bit_On/ Bit On/Off "Bit_On/Off_
Off_BTQC1_ Inverter KTG1 BTQC1_KTG1"
HMI On/Off
KTG1" KTG1
%M532.1
Bit On/Off "Bit_On/Off_
%M537.1 BTQC1_KTG2"
Inverter KTG2
"HMI_Bit_On/
Off_BTQC1_ HMI On/Off %M532.2
KTG2" KTG2 Bit On/Off "Bit_On/Off_
Inverter KTG3 BTQC1_KTG3"
%M537.2
"HMI_Bit_On/ %M532.3
Off_BTQC1_ HMI On/Off Bit On/Off "Bit_On/Off_
KTG3" KTG3 Inverter KTG4 BTQC1_KTG4"
%M537.3 %M532.4
"HMI_Bit_On/ Bit On/Off "Bit_On/Off_
Off_BTQC1_ Inverter KTG5 BTQC1_KTG5"
HMI On/Off
KTG4" KTG4
%M532.5
Bit On/Off "Bit_On/Off_
%M537.4 BTQC1_KTG6"
Inverter KTG6
"HMI_Bit_On/
Off_BTQC1_ HMI On/Off %M532.6
KTG5" KTG5 Bit On/Off "Bit_On/Off_
Inverter KTG7 BTQC1_KTG7"
%M537.5
"HMI_Bit_On/ %M532.7
Off_BTQC1_ HMI On/Off Bit On/Off "Bit_On/Off_
KTG6" KTG6 Inverter KTG8 BTQC1_KTG8"
%M537.6
"HMI_Bit_On/
Off_BTQC1_ HMI On/Off
KTG7" KTG7
%M537.7
"HMI_Bit_On/
Off_BTQC1_ HMI On/Off
KTG8" KTG8
Network 13: CONFIRM SETTING TIME ON/OFF INVERTER IN SEMI AUTO MODE BTQC2
%M513.0
"HMI_
ConfirmSetting_
FreqQC2_ %FC10
SemiAutoMode" "ConfirmSet On/OffSemiAuto"
EN ENO
%M538.0 %M533.0
"HMI_Bit_On/ Bit On/Off "Bit_On/Off_
Off_BTQC2_ Inverter KTG1 BTQC2_KTG1"
HMI On/Off
KTG1" KTG1
%M533.1
Bit On/Off "Bit_On/Off_
%M538.1 BTQC2_KTG2"
Inverter KTG2
"HMI_Bit_On/
Off_BTQC2_ HMI On/Off %M533.2
KTG2" KTG2 Bit On/Off "Bit_On/Off_
Inverter KTG3 BTQC2_KTG3"
%M538.2
"HMI_Bit_On/ %M533.3
Off_BTQC2_ HMI On/Off Bit On/Off "Bit_On/Off_
KTG3" KTG3 Inverter KTG4 BTQC2_KTG4"
%M538.3 %M533.4
"HMI_Bit_On/ Bit On/Off "Bit_On/Off_
Off_BTQC2_ Inverter KTG5 BTQC2_KTG5"
HMI On/Off
KTG4" KTG4
%M533.5
Bit On/Off "Bit_On/Off_
%M538.4 BTQC2_KTG6"
Inverter KTG6
"HMI_Bit_On/
Off_BTQC2_ HMI On/Off %M533.6
KTG5" KTG5 Bit On/Off "Bit_On/Off_
Inverter KTG7 BTQC2_KTG7"
%M538.5
"HMI_Bit_On/ %M533.7
Off_BTQC2_ HMI On/Off Bit On/Off "Bit_On/Off_
KTG6" KTG6 Inverter KTG8 BTQC2_KTG8"
%M538.6
"HMI_Bit_On/
Off_BTQC2_ HMI On/Off
KTG7" KTG7
%M538.7
"HMI_Bit_On/
Off_BTQC2_ HMI On/Off
KTG8" KTG8
Network 14: CONFIRM SETTING TIME ON/OFF INVERTER IN SEMI AUTO MODE BTQC3
Totally Integrated
Automation Portal
%M513.2
"HMI_
ConfirmSetting_
FreqQC3_ %FC10
SemiAutoMode" "ConfirmSet On/OffSemiAuto"
EN ENO
%M539.0 %M534.0
"HMI_Bit_On/ Bit On/Off "Bit_On/Off_
Off_BTQC3_ Inverter KTG1 BTQC3_KTG1"
HMI On/Off
KTG1" KTG1
%M534.1
Bit On/Off "Bit_On/Off_
%M539.1 BTQC3_KTG2"
Inverter KTG2
"HMI_Bit_On/
Off_BTQC3_ HMI On/Off %M534.2
KTG2" KTG2 Bit On/Off "Bit_On/Off_
Inverter KTG3 BTQC3_KTG3"
%M539.2
"HMI_Bit_On/ %M534.3
Off_BTQC3_ HMI On/Off Bit On/Off "Bit_On/Off_
KTG3" KTG3 Inverter KTG4 BTQC3_KTG4"
%M539.3 %M534.4
"HMI_Bit_On/ Bit On/Off "Bit_On/Off_
Off_BTQC3_ Inverter KTG5 BTQC3_KTG5"
HMI On/Off
KTG4" KTG4
%M534.5
Bit On/Off "Bit_On/Off_
%M539.4 BTQC3_KTG6"
Inverter KTG6
"HMI_Bit_On/
Off_BTQC3_ HMI On/Off %M534.6
KTG5" KTG5 Bit On/Off "Bit_On/Off_
Inverter KTG7 BTQC3_KTG7"
%M539.5
"HMI_Bit_On/ %M534.7
Off_BTQC3_ HMI On/Off Bit On/Off "Bit_On/Off_
KTG6" KTG6 Inverter KTG8 BTQC3_KTG8"
%M539.6
"HMI_Bit_On/
Off_BTQC3_ HMI On/Off
KTG7" KTG7
%M539.7
"HMI_Bit_On/
Off_BTQC3_ HMI On/Off
KTG8" KTG8
Network 15: CONFIRM SETTING TIME ON/OFF INVERTER IN SEMI AUTO MODE BTQH1
%M513.4
"HMI_
ConfirmSetting_
FreqQH1_ %FC10
SemiAutoMode" "ConfirmSet On/OffSemiAuto"
EN ENO
%M540.0 %M535.0
"HMI_Bit_On/ Bit On/Off "Bit_On/Off_
Off_BTQH1_ Inverter KTG1 BTQH1_KTG1"
HMI On/Off
KTG1" KTG1
%M535.1
Bit On/Off "Bit_On/Off_
%M540.1 BTQH1_KTG2"
Inverter KTG2
"HMI_Bit_On/
Off_BTQH1_ HMI On/Off %M535.2
KTG2" KTG2 Bit On/Off "Bit_On/Off_
Inverter KTG3 BTQH1_KTG3"
%M540.2
"HMI_Bit_On/ %M535.3
Off_BTQH1_ HMI On/Off Bit On/Off "Bit_On/Off_
KTG3" KTG3 Inverter KTG4 BTQH1_KTG4"
%M540.3 %M535.4
"HMI_Bit_On/ Bit On/Off "Bit_On/Off_
Off_BTQH1_ Inverter KTG5 BTQH1_KTG5"
HMI On/Off
KTG4" KTG4
%M535.5
Bit On/Off "Bit_On/Off_
%M540.4 BTQH1_KTG6"
Inverter KTG6
"HMI_Bit_On/
Off_BTQH1_ HMI On/Off %M535.6
KTG5" KTG5 Bit On/Off "Bit_On/Off_
Inverter KTG7 BTQH1_KTG7"
%M540.5
"HMI_Bit_On/ %M535.7
Off_BTQH1_ HMI On/Off Bit On/Off "Bit_On/Off_
KTG6" KTG6 Inverter KTG8 BTQH1_KTG8"
%M540.6
"HMI_Bit_On/
Off_BTQH1_ HMI On/Off
KTG7" KTG7
%M540.7
"HMI_Bit_On/
Off_BTQH1_ HMI On/Off
KTG8" KTG8
Network 16: CONFIRM SETTING TIME ON/OFF INVERTER IN SEMI AUTO MODE BTB1
%M513.6
"HMI_
ConfirmSetting_
FreqB1_ %FC10
SemiAutoMode" "ConfirmSet On/OffSemiAuto"
EN ENO
%M541.0 %M536.0
"HMI_Bit_On/ HMI On/Off Bit On/Off "Bit_On/Off_
Off_BTB1_KTG1" KTG1 Inverter KTG1 BTB1_KTG1"
%M541.1 %M536.1
"HMI_Bit_On/ HMI On/Off Bit On/Off "Bit_On/Off_
Off_BTB1_KTG2" KTG2 Inverter KTG2 BTB1_KTG2"
%M541.2 %M536.2
"HMI_Bit_On/ HMI On/Off Bit On/Off "Bit_On/Off_
Off_BTB1_KTG3" KTG3 Inverter KTG3 BTB1_KTG3"
%M541.3 %M536.3
"HMI_Bit_On/ HMI On/Off Bit On/Off "Bit_On/Off_
Off_BTB1_KTG4" KTG4 Inverter KTG4 BTB1_KTG4"
%M541.4 %M536.4
"HMI_Bit_On/ HMI On/Off Bit On/Off "Bit_On/Off_
Off_BTB1_KTG5" KTG5 Inverter KTG5 BTB1_KTG5"
%M541.5 %M536.5
"HMI_Bit_On/ HMI On/Off Bit On/Off "Bit_On/Off_
Off_BTB1_KTG6" KTG6 Inverter KTG6 BTB1_KTG6"
%M541.6 %M536.6
"HMI_Bit_On/ HMI On/Off Bit On/Off "Bit_On/Off_
Off_BTB1_KTG7" KTG7 Inverter KTG7 BTB1_KTG7"
%M541.7 %M536.7
"HMI_Bit_On/ HMI On/Off Bit On/Off "Bit_On/Off_
Off_BTB1_KTG8" KTG8 Inverter KTG8 BTB1_KTG8"
Totally Integrated
Automation Portal