2006 IEEE PES Transmission and Distribution Conference and Exposition Latin America, Venezuela
Fig. 4. Double circuit transmission line single diagram for numeric protection
simulation
The simulations results for the resistive reach faults were ● Sequential Internal Metallic Faults (after a time delay a
satisfactory. All aspects of the simulation were certificated. new fault appears on the same fault point: 50% of TL
BOA protective relay’s fault elimination times practically did extension, with Fault Resistance = 0.04 Ω and Fault
not suffer influence of fault resistance variation and Incidence Angle = 0˚) with 950 A load to the Sobradinho
transmission line position. Also SJP protective relay’s fault SS;
elimination times were excellent for faults in its 1st protection
zone = 80% of TL extension (25% and 75% of TL extension). TABLE V
SIMULATIONS RESULTS: SEQUENTIAL INTERNAL (50% OF TL EXTENSION)
The worst fault elimination times were BOA = 61.6 ms (75% / METALLIC FAULTS (AFTER A TIME DELAY) WITH 950 A LOAD
75 Ω) and SJP = 57.4 ms (25% / 100 Ω ), both faults in 1st TO THE SOBRADINHO SS
protection zone = 80% and with high fault resistance.
All the simulations results for Boa Esperança SS – São João Simulated Fault Fault Elimination
do Piauí SS power transmission line were satisfactory, with [Type/Phases and Time
total fault elimination times below the 100 milliseconds Time Delay (ms)]
SJP SOB
established in the National Operator of the Electrical System - SPF(AG)/DPF(AB) 5 ms 49.2 ms 39.8 ms
ONS [4]. The same simulations were accomplished for the São
SPF(AG)/DPF(AB) 15 ms 48.0 ms 37.4 ms
João from Piauí SS – Sobradinho SS Transmission Line (211.0
km) and significant differences were not found on the SPF(AG)/DPF(AB) 50 ms 45.1 ms 32.2 ms
protective relay selected for the project, demonstrating the SPF(AG)/DPF(AB) 250 ms 40.4 ms 30.1 ms
equipment’s versatility.
6