Question
How does the manual recommend setting the 1789-SIM module?
How to configure the Emulate 5000 I/O in the RSLogix 5000/Studio 5000 software?
How do I configure 1789-SIM module in RSLogix 5000/Studio 5000 software?

Environment
RSLogix Emulate 5000
RSLogix 5000
Studio 5000 Logix Designer

Answer
You will need to add SIM module to RSLogix Emulate 5000 Chassis Monitor and configure generic 1756-Module
in I/O configuration of RSLogix 5000/Studio 5000 software.

Note: Starting with version 13 of RSLogix 5000 software the 1789 Sim module is no longer available. Use 1756-
Module instead.

1. Right click on any empty slot in the RSLogix Emulate 5000 Chassis Monitor and select Create
2. Select 1789-SIM 32 Point Input/Output Simulator. Accept defaults
3. 1789-SIM module should appear in the RSLogix Emulate 5000 Chassis Monitor
4. Open RSLogix 5000/Studio 5000 project file (create new if necessary), Right click on I/O Configuration,
and select New Module
5. Select 1756-MODULE
6. Select the Slot number where the module was inserted into the chassis and configure it
Input: Assembly Instance: 1, Size: 2
Output: Assembly Instance: 2, Size: 1
Configuration: Assembly Instance 16, Size 0
Comm Format Data - DINT

https://rockwellautomation.custhelp.com/app/answers/detail/a_id/732965/page/1 1/3
9/2/2019 732965 - RSLogix 5000 Emulate software - SIM module configuration

7. After that go to Connection tab and change RPI to 50.0 ms or more

8. Download project file to RSLogix Emulate 5000 and go online


9. Go back to RSLogix Emulate 5000 Chassis Monitor, right click on 1789-SIM and select Properties
10. Click on I/O Data tab
11. Simulate Inputs by clicking on the appropriate bit Address.

Note: The input data will appear in the second DINT tag, for example: Local:1:I.Data[1].0 (module in slot 1, first bit
of data).

See video below for reference:

Using the Rockwell Automation Support Center


Download video: MP4 format (https://images.rakb.link/732965/sim2.mp4)

https://rockwellautomation.custhelp.com/app/answers/detail/a_id/732965/page/1 2/3
9/2/2019 732965 - RSLogix 5000 Emulate software - SIM module configuration

Attachments

DISCLAIMER
This knowledge base web site is intended to provide general technical information on a particular subject or
subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this web site is not
intended to constitute application, design, software or other professional engineering advice or services. Before
making any decision or taking any action, which might affect your equipment, you should consult a qualified
professional advisor.

ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF


ANY OF THE DATA CONTAINED IN THIS WEB SITE AND MAY MAKE CHANGES THERETO AT ANY TIME IN ITS
SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO
USERS "AS IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING
DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL
AUTOMATION HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN RESPECT


OF THE INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES
OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON-INFRINGEMENT. Note that certain
jurisdictions do not countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you.

This page is best viewed in Internet Explorer 11, Edge, Firefox 41, Chrome 46, Safari 9 or newer.

https://rockwellautomation.custhelp.com/app/answers/detail/a_id/732965/page/1 3/3

S-ar putea să vă placă și