S. No.

Characteristics PLANTE TUBULAR VRLA NI-CD

1 Chemistry Cd
Cathode Pb Pb Pb
[Positive Plate]
Anode PbO2 PbO2 PbO2 NiOOH
[Negative Plate]
Electrolyte H2SO4 H2SO4 H2SO4 KOH
[Aqueous Solution] [Aqueous Solution] [Aqueous Solution] [Aqueous Solution]

2 Cell Voltage
Nominal End Cell 2.0 Volts 2.0 Volts 2.0 Volts 1.2 Volts
Voltage 1.85 Volts at 10Hr rate 1.85 Volts at 10 Hr rate 1.80 Volts at 10 Hr rate 1.00 Volts at 5 Hr rate
[Requires more
consequence number of
cells than lead-acid battery
for a given DC voltage]

3 Application Ideal for Float application Ideal for frequent charge/ For short time back up Ideal for very high rate of
in Power Plants/ SubStations discharge cycling duties. with low depth of discharge under very abusive
discharge very condition. These are also
occasional use good in cycling applications

4 Reliability Most reliable in float Reliable but not as Generally reliable, Most popular alkaline
operations reliable as Plante' however pronr to secondary cell.
unexpected malfunctioning Reliable during duty cycles,
however, prone to
malfunctioning during
emergency operation
S. No. Characteristics PLANTE TUBULAR VRLA NI-CD

5 Monitoring State of Other than measuring Can be done by No easy method to ascertain Electrolyte sp. Gravity does
Charge electrolyte specific gravity measuring electrolyte the state of charge [health] not indicate the cell condition.
battery condition can be specific gravity since the cells are completely Monitoring the state of
monitored visually through sealed. The cells thereby charge of the battery is very
the transparent containers act as black boxes. difficult and therefore
performance failure is
unpredictable.
6 Susceptibility to High Satisfactory operations upto Satisfactory operations upto Prolonged operation at high Satisfactory operations
temperature 48/50 Deg. C. electrolyte 48/50 Deg. C. electrolyte ambient temperature curtails upto 48/50 deg. C
temperature. temperature. battery life by approx. electrolyte temperature.
50% for every
8 deg. C above 25 deg. C
[Ref. c1.6.1 of IEEE Spec
1189-1996]
7 Discharge Much superior to HDP Standard Best Discharge performance
Tubular but slightly inferior very good
to SMF

8 Maintenance a) Topping up with distilled/ a) Topping up with distilled/ a) No toppig up required a) Topping up with DM water
Requirement DM once in 12 - 18 months DM water once in a month Not possible 4/5 times a year

b) Battery to be kept clean & b) Battery to be kept clean & b) Battery to be kept clean & b) Battery to be kept clean &
dry and terminal & dry and terminal & dry and terminal & dry and terminal &
connectionsto be checked connectionsto be checked connectionsto be checked connectionsto be checked
periodically. periodically. periodically. periodically.

c) State of charge to be c) State of charge to be c) Voltage and physical c) Requires replacement of


regularly monitored by using regularly monitored by using conditionof the battery to be entire electrolyte once in
hydrometer [Sp.Gr] & cell hydrometer [Sp.Gr] & cell monitoredregularly 6/7 years due to carbonation
testing voltmeter testing voltmeter

S. No. Characteristics PLANTE TUBULAR VRLA NI-CD

9 Recharge Capable of quick recharge by Very fast recharge by boost These batteries require special Requires frequent equalising
boost charging upto 2.7 V/Cell charging upto 2.7 V/Cell and CCCV charger. Regular boost charge to maintain full
normal float-cum-boost charger 0.25 C10 Amps recharge charging not recommended. To capacity in float condition
can be used current charging can be done be maintained only to Float since charge rentention of
using a normal float cum charge at 2.23 V per cell. Quick this system is rathat poor
boost charger recharge limited to fast
chargingupto 2.4V Cell and
0.15 C10 AMPS limit current.
Recharging timeafter full
discharge is double thanthat of
Tubular of Plante' cells
10 Ageing Plante' capacity does not drop. Tubular cell capacity degrades Degrades gradually during Degrades gradually during
Rather increases in service continuously during service service life and capacity falls service life and therefore
life. As such no ageing margin life and falls to about 80% of to about 80% in about 8-10 capacity has to be increased
needs to be provided. initial rates capacity in about years 25% capacity has to be by 10% to compensate for
{Ref: IEEE Spec. No. 485 - 1997 8 - 10 year. 25% capacity has increased to compensate for ageing while battery sizing
Cl. No. 6.2,3} to be increased to ageing while sizing battery
compensatefor ageing while
sizing thebattery

11 Life Expectancy 15 - 20 Years 10 - 12 Years 8 - 10 Years 15 - 20 Years

12 Internal Resistance 30 - 40 % lower than equivalent Highest Lowest Low


HDP tubular cells

13 Sensitivity to over Moderately sensitive Moderately sensitive Extremely sensitive Moderately sensitive
charge & undercharge
14 Space Requirement High Moderate Low Moderate

S. No. Characteristics PLANTE TUBULAR VRLA NI-CD

15 Thermal Runaway Not Susceptible Not Susceptible Very Susceptible Generally not susceptible but
prolonged boot charge may
lead to thermal runaway

16 Dry Out Not Susceptible Not Susceptible Very Susceptible Generally not suspectible but
prolonged boost charge may
lead to thermal runaway

17 Memory Effect Not Susceptible Not Susceptible Not Susceptible Susceptible and hence prone
to sudden failure during
emergency.

18 Cost of Electricity Minimum Moderate Moderate High


consumption during
Float Charge