Index Page
01 Presentation 4
Advantages / Functionnalities / Structure / Feature / Connections / Ratings
02 Product references 14
Air Circuit Breakers / Switch Disconnectors / Accessories / Services
03 Technical guide 24
Protection trip unit (OCR) / Communication function / Remote control units / Voltage
module / Accessories / Circuit diagrams / Dimensions
04 Technical data 78
Internal resistance and power consumption / Insulation distance / Rectification of
rated current / Derating table / Discimination table / Cascading / Operating and
installation conditions
05 Codification 90
High powered
air circuit breakers Hw
4 5 6
Easy maintenance Flexible terminal Wide range of
Event record 200, fault record 250
connection accessories
(reserved for ever), OCR checker tool.
Horizontal/Vertical terminal rotate at Including: arc shield, phase barrier,
90° to make it easier for panel builder temperature sensor, dust cover (IP54),
to mount on busbars. ...
For frame A up to 1600A and frame B
up to 3200A.
Presentation
Introduction to ACB functionnalities
Air Circuit Breaker products get their name from the fact that
their breaking chambers are in the open air to allow better energy
dissipation. Their electrical and mechanical strength, breaking capacity,
maintainability and accessories make them ideal for protection for low
voltage installations.
Rated current This is the maximum current value the circuit breaker can withstand on a
In (A) permanent basis.
This value is always given for an ambient temperature (40/50°C) in
accordance with IEC 60947-2 standard if this temperature is higher, it is
necessary to reduce the operating current.
Rated operating voltage This is the voltage at which the circuit breaker can be used. The value
Ue (V) indicated is usually the maximum value. At lower voltages, certain
characteristics may differ or even be improved, such as the breaking capacity.
Insulation voltage This is the value for the insulation performance of the device. The insulation
Ui (V) test voltages (impulse, industrial frequency) are determined based on this
value.
Impulse voltage This value characterizes the ability of the device to withstand transient
Uimp (kV) overvoltages such as lightning.
Ultimate breaking capacity This is the maximum short-circuit current value that a circuit breaker can
Icu (kA) break at a given voltage and phase angle. The tests are executed according
to the sequence O - t - CO. O represents an automatic break operation, t
a time interval and CO a make operation followed by an automatic break
operation. Following the test, the circuit breaker must continue to provide a
minimum level of safety (isolation, dielectric strength).
Standard breaking capacity This is the value expressed as a percentage of Icu. It will be one of the
Ics (kA) following values: 25% (category A only), 50%, 75% or 100%. The circuit
breaker must be capable of operating normally after breaking the Ics current
several times using the sequence O-CO-CO.
Short-time withstand current This is the value of the short-circuit current that a category B circuit
Icw (kA) breaker is capable of withstanding for a defined period without altering its
characteristics. This value is intended to enable discrimination between
devices. The circuit breaker concerned can remain closed while the fault is
eliminated by the downstream device.
Rated short-circuit making capacity This is the maximum current intensity a device can make at its rated voltage
Icm (kA peak) according to the conditions of the standard. Devices without a protection
function, such as switches, must be able to withstand short-circuit currents
with a value and duration resulting from the action of the associated
protection device.
6
Presentation
Introduction to ACB functionnalities
The ACB Hw offers protection trip unit (OCR) functions and, in the event
of tripping, controls the opening of the circuit-breaker, preventing it from
closing again unless it has been reset by the operator.
Characteristics of OCR
Basic functions Long-time Overload Protection Long-time overload protection function is for the protection of circuit
(LTD) overload.
The protection is based on true rms value of currents.
Short Time Short-time short-circuit protection prevents impedance type short-circuit of
(STD) power distribution system.
Such kind of short-circuit normally is caused by partial short-circuit. Current
normally exceed overload range but not be too large.
Instantaneous Instantaneous short-circuit protection functions prevents solid type short-
(INST) circuit in power distribution system, which is normally
caused by inter-phase fault and will generate large short-circuit current. Then
an instantaneous tripping is required. Such protection is based on true rms
value of currents.
Ground Fault Trip The ground fault protection for equipment is used to detect current flowing
(GFT) through the grounding conductors which may present a hazardous condition.
Neutral protection Available at 100% x In of the phase currents 4P, or disabled, it is applied to
the overcurrent protections L, S and I.
Thermal Memory To prevent unacceptable repeated or periodical overload, control unit will
track and record thermal effect of overload current and trigger tripping
operation when accumulated thermal effect reaches predefined threshold.
Pre Trip Alarm The protection unit includes an alarm indication that will be lit continuously
(PTA) when the current is above 100% of the pickup setting. The settable PTA
indicates the set threshold is reached before the protection is tripped.
Fail-safe ACB must be protected against the short-circuits although Isd and Ii has
set as “NON. When It detects current more than 10 x In , this function is
operating.
Zone selective Interlock (ZSI) This function allows total selective protection between upstream or
downstream ACBs. Once the area has received the signal in the network, it
will coordinate its trip in case of fault.
Making Current Release Closing on short-circuit (MCR): this function trips the ACB when a short-
(MCR) circuit current flows during ACB closing operation, and lock the ACB to keep
it inoperative. MCR is operated by 8 times of CT rating .The function is active
with an auxiliary supply. MCR is operated by 8 times of CT rating.
Field test Field test on circuit breakers have long provided diagnostic for the electrical
components and simulate long time, short time, instantaneous delay.
This function requires a control power supply (available for Amp and Energy
type OCRs).
Override The purpose of this function is to protect ACB and wire from a current over
Icw. Detects a peak value of current. This function breaks the ACB without a
time delay (< 30ms) Pick-up : 15 x Ict.
Fault event Records 256 numbers of the fault info, fault phase, current value and time
stamp.
This function records the last wave of that time when the trip occurs and can
check the wave via the communication.
System event Records 200 numbers of the trip unit information, i.e trip unit power on,
protection setting change and so on.
This event can check via the communication.
Advanced functions Under Voltage Relays and • Minimum voltage protection UVR:
(only energy type) Over Voltage Relay This function calculates the minimum rms value of the three phase to phase
(UVR/OVR) voltages. Protection is activated when at least one of the three phase to
phase voltages is below the threshold set by the user.
• Maximum voltage protection OVR:
This function calculates the maximum rms value of the three phase to phase
voltages. Protection is activated when at least one of the three phase to
phase voltages are simultaneously above the threshold set by the user.
Unbalance voltage and current U unbal calculates the rms value of the unbalance between the three phase
to phase voltages.
I unbal is activated by an unbalance between the rms values of the three
phase currents.
This is set by a communication and monitored.
Reverse power Calculates the value of the total active power on the three phases. Is
rP activated when the total active power of the three phases flows in the
direction opposite.
The direction of flow is set by the user in the “Power Sign”:
• “+” corresponds to the normal direction of flow, i.e from the top on the
acb to the bottom;
• “-” is the opposite.
7
Presentation
Product structure
Front
1
1
2 2
I Z
I
3 E Z
3 E
4 R
5 4 R
6 5
6
7
8 T
T 9
O
A
P
Chassis
Inside Rear
8
Presentation
Accessory feature
Body side
1 2 3
4 5 6
7 8 9
A Z E
R T Y
U I O
9
Presentation
Accessory feature
1 2 3
4 5 6
7 8 9
A Z
1 UVT time delay controller 8 Wrong insertion preventer Accessories included as standard:
2 Remote operation module (RCU) 9 Safety shutter • Auxiliary switch 4NO/5NC
3 Temperature detection module (RCTU) A Arc shield • Door flange for IP30
4 Position switch Z Control terminal protection cover • Safety shutter lock (for draw-out type)
5 Mechanical interlock kit • Rotary handle (for draw-out type)
6 Phase insulation barrier
7 Mechanical operated cell (MOC) switch
10
Presentation
Connections
Standard connection
1)
For frame A up to 1600A and frame B up to 3200A.
11
Presentation
Ratings Hw automatic circuit breakers
Frame A B C
Type H N N S P P
Rated current A 630-2000 630-4000 3200-5000
Rated operating voltage (Ue) V 690
Rated insulation voltage (Ui) V 1000
Rated impulse withstand voltage (Uimp) KV 12
Frequency Hz 50/60
Number of poles poles 3-4
Current setting range (…x In max) Ir 0.4-1.0
Rated current of neutral pole (…% x In) %/In 100%
Rated breaking capacity AC 690/600/550V 36 50 50 65 85 85
KA
(Icu) AC 415/380/220V 50 65 65 85 100 100
Rated service breaking capacity AC 690/600/550V
KA 100% Icu
(Ics) AC 415/380/220V
Rated short-time capacity 1s 50 65 65 85 85 85
KA
(Icw) 3s 36 36 50 55 65 65
Rated making capacity AC 690/600/550V 76 105 105 143 187 187
KA
(Icm) (kA peak) AC 415/380/220V 105 143 143 187 220 220
Utilization category (according to IEC 60947-2) B
Time
Maximum total breaking time ms 40
motor charging time s 5
Closing operating time
max. closing time ms 40
Operating cycle
without maintenance 20000 15000 10000
Mechanical life cycle
with maintenance 30000 20000 20000
up to 2000A: 10000
without maintenance times 5000 2000
from 2500A: 5000
Electrical life cycle
up to 2000A: 15000
with maintenance 10000 5000
from 2500A: 10000
Dimensions
3 pole 337x404x296 408x404x296 633x404x296
fixed type
External dimension 4 pole 422x404x296 523x404x296 803x404x296
mm
(W x H x D, except busbar) draw-out 3 pole 328x460x368 399x460x368 624x460x368
type 4 pole 413x460x368 514x460x368 794x460x368
up to 3200A: 44
3 pole 34 76
4000A: 61
fixed type
up to 3200A: 55
4 pole 44 81
4000A: 81
Weight kg
up to 3200A: 87
3 pole 63 145
draw-out 4000A: 107
type up to 3200A: 130
4 pole 80 173
4000A: 161
440
Fixed type 416 Draw-out type
Ø1
2.1
460
H
H
H
270
164 164
328
W D W W D
12
Presentation
Ratings Hw switch disconnectors
Frame A B C
Type N.....A N.....A P.....A
Rated current A 630-2000 630-4000 3200-5000
Rated operating voltage (Ue) V 690
Rated insulation voltage (Ui) V 1000
Rated impulse withstand voltage (Uimp) KV 12
Frequency Hz 50/60
Number of poles poles 3-4
Rated current of neutral pole (…% x In) %/In 100%
Rated short-time capacity 1s 65 65 85
KA
(Icw) 3s 36 50 65
Rated making capacity AC 690/600/550V 105 105 187
KA
(Icm) (kA peak) AC 415/380/220V 143 143 220
Utilization category (according to IEC 60947-3) AC23
Time
Maximum total breaking time ms 40
motor charging time s 5
Closing operating time
max. closing time ms 40
Operating cycle
without maintenance 20000 15000 10000
Mechanical life cycle
with maintenance 30000 20000 20000
up to 2000A: 10000
without maintenance times 5000 2000
from 2500A: 5000
Electrical life cycle
up to 2000A: 15000
with maintenance 10000 5000
from 2500A: 10000
Dimensions
3 pole 337x404x296 408x404x296 633x404x296
fixed type
External dimension 4 pole 422x404x296 523x404x296 803x404x296
mm
(W x H x D, except busbar) draw-out 3 pole 328x460x368 399x460x368 624x460x368
type 4 pole 413x460x368 514x460x368 794x460x368
up to 3200A: 44
3 pole 34 76
4000A: 61
fixed type
up to 3200A: 55
4 pole 44 81
4000A: 81
Weight kg
up to 3200A: 87
3 pole 63 145
draw-out 4000A: 107
type up to 3200A: 130
4 pole 80 173
4000A: 161
440
Fixed type 416 Draw-out type
Ø1
2.1
460
H
H
H
270
164 164
328
W D W W D
13
Product references
Air Circuit Breakers
Characteristics
Icu=Ics=50KA
Icu=Ics=Icw
Characteristics
Icu=Ics=65KA
Icu=Ics=Icw
Characteristics
Icu=Ics=65KA
Icu=Ics=Icw
14
Product references
Air Circuit Breakers
Characteristics
Icu=Ics=85KA
Icu=Ics=Icw
Characteristics
Icu=Ics=100KA
Icw=85KA
Characteristics
Icu=Ics=100KA
Icw=85KA
15
Product references
Switch Disconnectors
Characteristics
Icw=50KA
Characteristics
Icw=65KA
Characteristics
Icw=65KA
16
Product references
Switch Disconnectors
Characteristics
Icw=85KA
Characteristics
Icw=85KA
Characteristics
Icw=85KA
17
Product references
Accessories
Chassis
LI 1 HWX611
LSI 1 HWX612
LSIG 1 HWX613
Amp LI 1 HWX621
Amp LSI 1 HWX622
Amp LSIG 1 HWX623
Energy LSIG 1 HWX633
HWX633
Voltage module
HWY654
Position switches
18
Product references
Accessories
19
Product references
Accessories
Accessories
Counter 1 HWY638
Lifting lug 1 HWY648
Wrong insertion preventer for draw-out type 1 HWY636
Door flange 1 HWY641
HWY642 Dust cover 1 HWY642
ON/OFF button cover 1 HWY632
Type 1 1 HWY633
Type 2 1 HWY634
HWY6xx Type 3 1 HWY635
Type 4 1 HWY646
Type 5 1 HWY647
Type 6 1 HWY656
Type 7 1 HWY657
Type 8 1 HWY658
Type 9 1 HWY659
Type 1 - AA 1 HWY706
HWY706 Type 2 - AB 1 HWY707
Type 3 - A_ 1 HWY708
Adaptor kit for Castell locks 1 HWY698
Neutral CT
20
Product references
Accessories
Mechanical interlocks
Cable 3m 1 HWY508
Cable 5m 1 HWY509
HWY630
HWY637
21
Product references
Services
HWY649
Safety shutters
Rotary handle
HWY644
22
23
Technical guide
Protection trip unit (OCR)
Characteristics
Power externals • • • • • • •
self • • • • • • •
Protection function LTD • • • • • • •
STD - • • - • • •
INST • • • • • • •
PTA - - - • • • •
GFT - - • - - • •
neutral protection 100% 100% 100% 0-50-100% 0-50-100% 0-50-100% •0-50-100%
fail safe • • • • • • •
MCR • • • • • • •
Indication long time pick up LED • • • • • • •
fault LED L, I L, S/I L, S/I, G L, I L, S/I L, S/I, G L, S/I, G
PTA PTA PTA PTA
Digital output separately continuous contact • (2NO) • (2NO) • (3NO) • (3NO) • (3NO) • (4NO) L, • (4NO) L,
L, I L, S/I L,S/I, G L, I, PTA L, S/I, PTA S/I, G, PTA S/I, G, PTA
ZSI • • • • • • •
Reset button • • • • • • •
Advanced functions COM - - - • • • •
event / fault recording - - - • • • •
under/over voltage protection - - - - - - •
unbalanced current / voltage - - - - - - •
protection
24
Technical guide
Protection trip unit (OCR)
Overview
2 3
1 4
5
Z 8
9
E A
Y
R I
U
T D
Q
O F
G
P
S
w Self power works normally at larger than 10% for 3 phase, 30% for single phase.
25
Technical guide
Protection trip unit (OCR)
Ir
tr
I2t on
Isd
Ig I t on
2
tsd
tg
I2t off Ii
I2t off
Protection
time delay(sec) tr at(1.5×lr) 10.4 26.1 41.7 52 104 208 312 417 521 626
accuracy: ±15%
or below 100ms tr at(6.0×lr) 0.5 1.25 2 2.5 5 10 15 20 25 30
tr at(7.2×lr) 0.35 0.86 1.38 1.73 3.45 6.9 10.4 13.8 17.3 20.7
time delay (sec) tsd l2t off 0.05 0.1 0.2 0.3 0.4 0.5
at 10×ln
l2t on 0.05 0.1 0.2 0.3 0.4 0.5
2
(l t off) min. trip time (ms) 20 80 160 260 360 460
Ground fault current setting (A) lg=lct×... 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1 Non
GFT accuracy: ±20%(lg>0.4ln)
±20%(lg≤0.4ln)
time delay (sec) tg l2t off 0.05 0.1 0.2 0.3 0.4 0.5
at 1×ln
2
accuracy: ±20% l t on 0.05 0.1 0.2 0.3 0.4 0.5
(l2t off) min. trip time (ms) 20 80 160 260 360 460
26
Technical guide
Protection trip unit (OCR) circuit diagram
Basic OCR
AC,DC100-250V S 0-S 2
Source
NCT + -
k
N R S T 21 29 30 19
N R S T L NCT NCT
1 2 S2
Basic OCR
1a for
MCR
Nn Rn Sn Tn 22 24 26 31 32 33 34 5 6 20
+ - + - + -
COMMON IN OUT Remote
ZSI* reset
* ZSI: contacts 31-32 are pre-wired by factory. If you use ZSI function, please remove this wire.
AC,DC100-250V S 0-S 2
Source
NCT + -
k
N R S T 21 23 29 30 19
N R S T L P/T NCTNCT S2
1 2
1a for
MCR
Nn Rn Sn Tn 22 24 26 31 32 33 34 35 36 5 6 20
COMMON + - + - + - + -
IN OUT Com- Remote
ZSI* munica- reset
tion
27
Technical guide
Protection trip unit (OCR)
Protection
time delay (sec) tr at(1.5×lr) 10.4 26.1 41.7 52 104 208 312 417 521 626
accuracy: ±15%
or below 100ms tr at(6.0×lr) 0.5 1.25 2 2.5 5 10 15 20 25 30
tr at(7.2×lr) 0.35 0.86 1.38 1.73 3.45 6.9 10.4 13.8 17.3 20.7
time delay (sec) tsd l2t off 0.05 0.1 0.2 0.3 0.4 0.5
at 10×ln
2
l t on 0.05 0.1 0.2 0.3 0.4 0.5
(l2t off) min. trip time (ms) 20 80 160 260 360 460
Ground fault pick-up (A) lg=lct×... 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1 Non
GFT accuracy: ±15%(lg>0.4ln)
±20%(lg≤0.4ln)
time delay (sec) tg l2t off 0.05 0.1 0.2 0.3 0.4 0.5
at 1×ln
accuracy: ±20% l2t on 0.05 0.1 0.2 0.3 0.4 0.5
2
(l t off) min. trip time (ms) 20 80 160 260 360 460
Pre trip alarm current setting (A) Ip=In×... 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 Non
PTA accuracy: ±15%
28
1a for
MCR
Technical guide
Nn Rn Sn Tn 22 24 26 31 32 33 34 5 6 20
COMMON +
IN
- + Protection
- + - trip unit (OCR) circuit diagram
OUT Remote
ZSI* reset
AC,DC100-250V S 0-S 2
Source
NCT + -
k
N R S T 21 23 29 30 19
N R S T L P/T NCTNCT S2
1 2
1a for
MCR
Nn Rn Sn Tn 22 24 26 31 32 33 34 35 36 5 6 20
COMMON + - + - + - + -
IN OUT Com- Remote
ZSI* munica- reset
tion
* ZSI: contacts 31-32 are pre-wired by factory. If you use ZSI function, please remove this wire.
29
Technical guide
Protection trip unit (OCR)
Protection
time delay (sec) tr at(1.5×lr) 10.4 26.1 41.7 52 104 208 312 417 521 626
accuracy: ±15%
or below 100ms tr at(6.0×lr) 0.5 1.25 2 2.5 5 10 15 20 25 30
tr at(7.2×lr) 0.35 0.86 1.38 1.73 3.45 6.9 10.4 13.8 17.3 20.7
time delay (sec) tsd l2t off 0.05 0.1 0.2 0.3 0.4 0.5
at 10×ln
l2t on 0.05 0.1 0.2 0.3 0.4 0.5
2
(l t off) min. trip time (ms) 20 80 160 260 360 460
Ground fault pick-up (A) lg=lct×... 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1 Non
GFT accuracy: ±15%(lg>0.4ln)
±20%(lg≤0.4ln)
time delay (sec) tg l2t off 0.05 0.1 0.2 0.3 0.4 0.5
at 1×ln
2
accuracy: ±20% l t on 0.05 0.1 0.2 0.3 0.4 0.5
2
(l t off) min. trip time (ms) 20 80 160 260 360 460
Pre trip alarm current setting (A) Ip=In×... 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 Non
PTA accuracy: ±15%
30
Technical guide
Protection trip unit (OCR) circuit diagram
AC,DC100-250V S 0-S 2
3Ø3W/3Ø4W
Source
VM
NCT + -
k
N R S T 21 23 29 30 VR VS VT VN 19
1a for
MCR
Nn Rn Sn Tn 22 24 26 31 32 33 34 35 36 5 6 20
+ - + - + - + -
COMMON IN OUT Com- Remote
ZSI* munica- reset
tion
* ZSI: contacts 31-32 are pre-wired by factory. If you use ZSI function, please remove this wire.
31
Technical guide
Protection trip unit (OCR)
Rated Current (In) - Rated current [In] can be adjusted to 50%, 63%, 70%, 80%, 90% and 100% of
the rated primary CT current [Ict].
- On the ACB nameplate, rated current [In] is marked.
- Rated current [In] can be selected by sliding the base current setting select
switch, which can be set to the predetermined scale.
Operation characteristics
32
Technical guide
Protection trip unit (OCR)
Ii
I
Ip
Tp
I
33
Technical guide
Protection trip unit (OCR)
ACB 1
Out
Zone 1
In
Out
Zone 2 Fault A
In
In In In
ZSI connecting
34
Technical guide
Protection trip unit (OCR) curves
General feeder
4
hour
3
4 1
2
1
5
50
40
30 2
minute
20
10
8
6 3
5
4
3
2
Operating time
1
50
40
30
20
10
8
6
5
second
4
3
2
1
0.8
0.6
0.5 500ms 500ms
0.4
0.3
0.2
0.1
0.08
0.06 50ms 50ms
0.0
0.05
0.04
0.03
0.02
0.01
0.008
0.006
0.005
1000
1500
2000
2500
3000
100
100
125
150
200
250
300
400
500
600
700
800
900
10
15
20
30
40
50
60
70
80
90
60
70
80
90
7
8
9
Percent for rated primary current Percent for rated current of OCR (Ict)
of OCR (Ict)
35
Technical guide
Protection trip unit (OCR) system diagram
ACB trip
ACB
Display (LCD,
LED)
MHT
Trip operation
Rogowski Relay
Measure-
CT selection
ment part
PTA contact
MCU
processing
LTD contact
External
contact
STD/INST contact
GFT contact
Power
CT
Self power COMMON contact
ZSI output +
ZSI output -
ZSI
ZSI input +
ZSI input -
RS-485 +
Comm. RS-485 -
Test
110V - 220V SMPS power terminal
36
Technical guide
Communication function
The ACB Hw series OCR Amp and Energy types are equipped with
communication module.
It allows to get all breakers information from network at any location
connected to the bus, such as:
• measurements: current, voltage, power, power factor, energy,
frequency
• breaker status: closing, opening and other state
• fault recording: time-stamped trip information
• event logging
• protect the controller setting
• protect pre-alarm controller
Scada system
Modbus RTU
(Remote Terminal Unit)
HWY639
HWY639 HWY650
Characteristics
37
Technical guide
Remote control units
TEMP. °C
Remote Control Remote Control Unit
Temperature
Unit
HWY654 HWY639
Shape
38
Technical guide
Voltage module
56.4 46.6
42 29.1
27.6
1 2 3 4
75
91.4
5 7 8 9
Voltage connection
Trip unit offers VM (Voltage module) as an essential option, to measure voltage.
Voltage input range:AC 69 ~ 690V
connect busbar
connect with
ACB terminal ACB HW
HW
3 pole 3 wire
(L1)(L2)(L3)
R S T VN VR VS VT
VN ACB
VT
VS
VR
ACB terminal
(L1)(L2)(L3)
R S T N
VN VR VS VT
VN ACB
VT
VS
VR
ACB terminal
39
Technical guide
Accessories
Motor (MO)
Connection diagram
Source
1 15
Spring Ready
charge to close
off sw. switch
2 16
Ratings
starting pick up(A) 5-6 times of rated current HWX543 AC/DC 110V
1)
charging time (s) within 5 sec HWX544 AC/DC 220V
Wire ratings
Rated voltage
20 300 20 600
40
Technical guide
Accessories
Connection diagram
Source
PB
(close)
CC
4
• A control device which closes a circuit breaker remotely, when
applying 85-110% of rated control voltage over 150ms to coil
terminals (3,4).
Ratings
Power supply (Vn) operating Power consumption (VA) Opening Reference Rating
limits time
DC (V) AC (V) inrush steady-state (ms) HWX551 DC 24V
HWX556 AC 440V
Wire ratings
Rated voltage
20 300 20 600
41
Technical guide
Accessories
Connection diagram
Source
PB(Open)
7
SH
8
• A control device which trips a circuit breaker remotely, when
applying 70-110% of rated control voltage over 150ms to coil
terminals (7,8).
Ratings
Power supply (Vn) Operating Power consumption (VA) Opening Reference Rating
limits time
DC (V) AC (V) inrush steady-state (ms) HWX501 DC 24V
HWX505 AC 380/415V
HWX506 AC 440V
Wire ratings
Rated voltage
20 300 20 600
42
Technical guide
Accessories
Connection diagram
Source Source
PB(Open)
PB(Open)
7 9
SH sSH
8 10
• A control device which trips a circuit breaker doubly from the
outside.
• When second shunt trip coil is installed, there is no possibility to
fit the UVT coil
• Rated control voltage range 70-110%, applying voltage over
150ms to coil terminals (9,10).
Ratings
Power supply (Vn) Operating Power consumption (VA) Opening Reference Rating
limits time
DC (V) AC (V) inrush steady-state (ms) HWX521 DC 24V
HWX525 AC 380/415V
HWX526 AC 440V
Wire ratings
Rated voltage
20 300 20 600
43
Technical guide
Accessories
Connection diagram
Source
PB(Open)
9
UVT
10
• If the voltage of the main or the control power is under
70% of the standard, UVT breaks the circuit automatically.
• Connect instantaneous type with both terminals (9,10) and
connect with time delay type in order to present time delay
controller.
- The circuit breaker is opened with trip unit power supply
voltages below 70%.
- The circuit breaker is closed with unit power supply
voltage above 85%.
• Instantaneous type can not be used with double trip coil.
Ratings
- 380
- 440
Wire ratings
Rated voltage
20 300 20 600
44
Technical guide
Accessories
Connection diagram
COM
U1
a Source
U2
b
C1
T2
PB(Open)
controller
U1
COM 电
a U2 源
C2
UVT
b
T1
Controller
C1
PB(Open)
T2
UVT
9 T1
C2
UVT
UVT
10
UVT trip
91.4
91.4
75
75
Ratings
Reference Rating
HWX535 AC 380/415V
HWX536 AC 440V
45
Technical guide
Accessories
Position switch
Connection diagram
61 64 71 74 81 84
62 63 65 66 72 73 75 76 82 83 85 86
• This switch is for indicating the position of ACB in the chassis. It is "a" contact = NO contact
mounted on the side of chassis. "b" contact = NC contact
• Indicating position Connected/Test/Isol/Insert.
• Only one switch is applicable.
Ratings References
Load Resistance Lamp Inductor Motor References Inserted Isolated Test Connected
DC30V 6A 3A 6A 3A HWX571 1C 1C 1C 1C
63.5 mm
86
Connected
Test
Isolated
Inserted
46
Technical guide
Accessories
• A device to make an ACB easy to shift. • It is used to interlock closing and trip between two or three
• Hang it to both handles of the arc shield, chassis, and ACB. breakers mechanically so as to prevent unintended operation at
• When handling products, please be sure to use crane. In case of the same time.
products under 3,200A and handling chassis only, please comply • The MI is a safety gear installed in ACB for distribution line and
with safety regulation. it creates a mechanical interlock between two or three circuit-
• Offered 2ea of 1set as a standard in 5,000A "C" frame. breakers through each ACB’s open/close work.
• To operate the MI every component linked to the MI unit and the
MI must be combined before use.
• MI unit is separate product. After installing ACB it is additionally
attached.
• When ordering MI wire of parts all components linked to the MI
unit are provided.
• MI is provided with cable length: 1.5 m.(additional cables can be
ordered for 3 and 5 m)
• Phase insulation barrier prevents the arc which may arise • Prevents manual operation of ACB's closing/tripping button due to
and result in short-circuit between phase in advance. user's wrong handling.
• It is not possible to handle on/off operation under the "Button
lock" status.
• Padlock is not included, key locksize: Ø5-Ø8
47
Technical guide
Accessories
Key lock device Key Ronis lock and key Castell lock
• The key lock prevents the circuit breaker closing, it maintains Kirk and Profalux type of locks may also be applied.
interlock condition (Mechanical prevention).
• When the key has been unlocked you can operate spring
changing/manual on or off, when the key is removed from circuit
breaker it becomes interlock. The key doesn’t turn to lock position Ref. Key type Suitable with Adaptor kit
until user push the off button, when the key is locked. Lock type ref.
HWY703 3 3, 5
HWY704 4 4
HWY705 5 5
HWY708 3 -
Key interlock
Configure the system with three breaker mounted key lock device.
Only two breakers are possible to input with 2ea key, and the other
breaker can supply stable load with interlocking.
Bus-tie
ACB 3 ACB 3 ACB 3
48
Technical guide
Accessories
• When the main body of ACB is inserted to the chassis if the ratings
of ACB do not match with chassis it mechanically prevents ACB
from being inserted into chassis of ACB.
• Each part will have been installed on body or chassis.
• This device is set by CT rated current.
CT Mounting position
chassis ACB
C
D
E
F
G
49
Technical guide
Accessories
• Arc which may arise while breaking fault current is extinguished • Protects control terminals which are exposed to the outside, and
first by arc chute in main body of circuit breaker and then prevent damage from foreign substances.
completely extinguished by arc cover.
Counter
50
Technical guide
Accessories
• RCTU is installed on the chassis or inside of panel, and • The RCTU is used with temperature sensor installed inside of the
communicates with Modbus/RS-485 basically. ACB.
• It can be purchased separately and can be operated with • The temperature sensor is installed in designated position.
temperature alarm unit at the same time: RCTU However user can change the position to applicable extra site.
• It is used with temperature sensor.
• Temperature alarm unit is a device to show the busbar's
temperature through a sensor inside of ACB.
• Temperature sensor can be installed up to 3 and alarm can occur
when it reaches the specified temperature.
• Display the maximum temperature on the segment LED and
transmits through a network.
• Installed on the chassis or inside of panel, and can be operated
with remote closing & trip unit at the same time.
51
Technical guide
Accessories
Neutral CT
Dimensions (mm)
2-Sec. M5
76
92
4-
Ø1
4
50 0
20
300
240
300
68 Ø
3 - Ø6.4
43 40 3
90
28
129
111
30
30 240
300 40
105 55
155 71
130
231
252
52
Technical guide
Accessories
Door flange
door flange
panel door
• Protects the protruding front of ACB and the cutting side of panel
door by attaching it to the panel door.
• Both fixed/draw-out type are the same size of the panel cutting,
even if the dust cover is installed.
• Refer to dimension for panel cutting size.
• Protection rating of IP30.
292
5
103.5 100 103.5 R
4-
122.5
345
115
4
-Ø
122.5
12
7.5
Bottom
7.5
25.6
Dust cover
53
Technical guide
Accessories
Auxiliary switch
Connection diagram
41 43 45 47 49 51 53 55 57 59
45 47 49 51 53 55 57 59 61 64 67 101 71 74 77 81 84 91 94 121 123 125 127 129 131 133 135 137 139
46 48 50 52 54 56 58 60 62 63 65 66 68 69 102 103 72 73 75 76 78 79 82 83 85 86 92 93 95 96 122 124 126 128 130 132 134 136 138 140
54
Technical guide
Accessories
Connection diagram
Item Specifications
Keypad Externals
3 110.6 mm
4
OCR CHECKER HW
2 HWY649 3
1 4
1
6
5 2
193.4 mm
Nr Button Function
screen
55
Technical guide
Accessories
56
Technical guide
Accessories
Draw-in/out handle
57
Technical guide
Circuit diagrams
3Ø3W/3Ø4W
Source Source Source Source Source
VM
+ -
NCT PB
PB(Open)
PB(Open)
K L (close)
R S T N 21 23 29 30 VN VR VS VT 19 37 39 1 15 3 7 9
spring
charge
off sw.
NCTNCT S2
N R S T L P 1 2 VN VR VS VT
over-current
protective device
MO CC SH sSH
Nn Rn Tn Tn Ac S/I G ZI ZI ZO ZO
1 2 1 2 COMCOM RR+ RR-
MCR MCR T T S
+ - N P 0
CT 4
TP
CT 3
CT 2
MHT
CT 1
TN
1a for MCR
Rn Sn Tn Nn 22 24 26 31 32 33 34 35 36 5 6 20 38 40 2 16 4 8 10
+ - + - + - + -
IN OUT com- remote
ZSI muni- reset
cation
S/I STD/INST terminal 9-10 UVT coil / secondary shunt trip coil
58
Technical guide
Circuit diagrams
U1
COM
Source
a U2
Source b
Time Dela y
UVT C1
T2
PB(Open)
PB(Open)
C2
T1
9 9 41 43 45 47 49 51 53 55 57 59 61 64 67 101 71 74 77 81 84 91 94 121 123 125 127 129 131 133 135 137 139
used for MCR
UVT UVT
10 10 42 44 46 48 50 52 54 56 58 60 62 63 65 66 68 69 102 103 72 73 75 76 78 79 82 83 85 86 92 93 95 96 122 124 126 128 130 132 134 136 138 140
19 20 23 21 24 26 22 Tp Tn
Control circuit Auxiliary switch
UVT MCR 2a 3a 4a 5a 1b 2b 3b 4b 5b
MO CC SH /sSH RTC
Z0- ZI- G MCR
1 3 7 9 15 41 43 45 47 49 51 53 55 57 59 Z0+ ZI+ Pc- Pc+ N+ MCR
2 4 8 10 16 42 44 46 48 50 52 54 56 58 60
59
Technical guide
A frame fixed type dimensions
296 381
404.4
404.4
270 270
168.7 253.7
337.4 422.4
313.4 398.4
85 85 85 85 85
15 15
5
5
186.8
152.5
186.8
152.5
ø14 ø14
20
20
109
109
156.7
[ 630-1,600A ] [ 2000A ]
35 13
35 13 3-ø
2-ø
50
75
50
50
25
15 15
144
330
144
330
75
50
132
132
33
33
60 49 186.8 60 49 186.8
295.8 43.6 295.8 43.6
60
Technical guide
A frame fixed type dimensions
313.4 398.4
85 85 85 85 85
50 50
5
5
152.5
186.8
186.8
152.5
ø14 ø14
20
20
109
109
156.7
35 13
2-ø
15
50
25
15
129
144
330
15
132
33
60 49 186.8
295.8 43.6
85 85 85 85 85
50 50
5
5
152.5
152.5
186.8
186.8
4 4
Ø1 Ø1
20
20
112
112
313.4 398.4
11
2-Ø
25
50
15
461
144
330
132
33
60 49 186.8
53
295.8
15
208.4
61
Technical guide
A frame draw-out type dimensions
466
440
270 270
164 164 164 249
328.1 413
85 85 85 85 85
15 15
28.8
28.8
250
250
368.4
368.4
Ø1 Ø1
4 4
210 59 210 85
[ 630-1,600A ] [ 2,000A ]
11.5 11.5
(isol) (isol)
119.3 6 119.3 6
50
75
465.8
465.8
144
330
144
330
50
75
132
15
132
Ø13 Ø13 15
50 250 50 250
33.1
15
33.1
15
328.8 35 Ø1
3 328.8 35 13
2- 3-Ø
352.8 352.8
39.6 381.6
50
39.6 381.6
50
75
421.2 421.2
25
15
15
A frame 2,000A of ACB HW is applicable vertical terminal only.
62
Technical guide
A frame draw-out type dimensions
28.8
250
250
368.4
368.4
Ø1 Ø1
4 4
210 59 210 85
26.5 60 arc shield surface
(test) 20.4
(option)
11.5
(isol)
119.3 6 35 13
2-Ø
15
50
465.8
25
15
129
144
330
15
132
Ø13 15
33.1
50 250
15
328.8
352.8
39.6 381.6
421.2
28.8
250
250
371.4
371.4
Ø14
Ø1
4
210 59 295 59
(test) 26.7 63 arc shield surface
20.4 (option)
(isol)11.5
11
2-Ø
25
50
464.3
469
15
329.79
144
135.3
15
Ø13
49.8
50 250
36.5
18.2
328.8
42.6 352.8 15
359.6
63
Technical guide
B frame fixed type 630 - 3200A dimensions
367 482
404.4
404.4
270 270
408.4 204.2 319.2
523.4
384.4 499.4
115 115 115 115 115
20 20
5
5
186.8
152.5
186.8
152.5
4 4
Ø1 Ø1
20
20
109
109
192.2
[ 630-2,500A ] [ 3,200A ]
35 13 35 13
3-Ø 3-Ø
75
50
90
75
50
90
144
144
15
330
330
15
75
90
132
132
33
33
60 49 186.8 60 49 186.8
295.8 43.6 295.8 43.6
64
Technical guide
B frame fixed type 630 - 3200A dimensions
5
5
186.8
152.5
186.8
152.5
4
4 Ø1
Ø1 Range A (mm)
20
630 - 2500A 75
20
109
109
3200A 90
192.2
[ 3,200A ] [ 630~2,500A ]
35 13 35 13
3-Ø 3-Ø
50
75
90
50
15
330
144
330
144
15
20
20
132
132
33
33
60 49 186.8 60 49 186.8
43.6 295.8 43.6
295.8
5
152.5
152.5
186.8
186.8
4 4
Ø1 Ø1
20
20
112
112
11
3-Ø
50
75
461
15
144
330
132
33
60 49 186.8
53
295.8
20
213.4
65
Technical guide
B frame draw-out type 630 - 3200A dimensions
440
466
270 270
199.5 199.5 199.5 314.5
399 514
250
250
368.4
368.4
Ø1 Ø1
4 4
[ 630-2,500A ] [ 3,200A ]
26.5 60 26.5 60
arc shield surface arc shield surface
(test) (test) (option)
20.4 (option) 20.4
11.5 11.5
(isol) (isol)
13 35 13
119.3 6
35
3-Ø 119.3 6 3-Ø
90
90
50
75
75
50
465.8
465.8
143
330
330
143
15 15
90
75
132.5
132.5
Ø13 15 Ø13 15
50 250 50 250
33.1
33.1
15
15
328.8 328.8
352.8 352.8
39.6 383.6 39.6 383.6
423.2 423.2
66
Technical guide
B frame draw-out type 630 - 3200A dimensions
28.8
250
250
368.4
368.4
Range A (mm)
Ø1 630 - 2500A 75 Ø1
4 4
3200A 90
210 94.5 210 115
[ 630-2,500A ] [ 3,200A ]
26.5 60 arc shield surface 26.5 60 arc shield surface
(test) 20.4 (option) (test) 20.4 (option)
11.5 11.5
(isol) (isol)
35 13 35 13
119.3 6 3-Ø 119.3 6 3-Ø
20
20
50
75
50
90
465.8
465.8
143
124
15
330
330
143
124
15
20
20
132.5
132.5
Ø13 15 Ø13 15
50 250 50 250
33.1
33.1
15
15
328.8 328.8
352.8 352.8
39.6 383.6 39.6 383.6
423.2 423.2
28.8
250
250
371.4
371.4
Ø1
4
281 59 396
26.7 63 arc shield surface
(test) 20.4 (option)
11.5
(isol)
11
3-Ø
50
75
464.8
469
15
329.79
143
135.7
15
Ø13
49.3
50 250
36.5
18.2
328.8
352.8
42.6 20
366.6
67
Technical guide
B frame fixed type 4000A dimensions
367 482
404.4
404.4
270 270
204.2 319.2
408.4 523.4
384.4 499.4
152.5 152.5 140 140 140
15 10 15 15 10 15
5
5
186.8
152.5
186.8
152.5
ø14 ø14
20
20
109
109
192.2
13
35 5-ø
25*4=100
125
125
330
169
44
15
125
119.5
57
33
60 49 186.8
295.8 87
68
Technical guide
B frame fixed type 4000A dimensions
405 520
152.5 152.5 140 140 140
100 100
5
5
186.8
152.5
186.8
152.5
ø14 ø14
20
20
109
109
13
35 3-ø
25*3=75
100
40
330
144
15
15
10
15
132
33
60 49 186.8
295.8 58.6
69
Technical guide
B frame draw-out type 4000A dimensions
466
466
440
270 270
199.5 199.5 199.5 314.5
399 514
28.8
250
250
368.4
368.4
ø1 ø1
4 4
26.5 60
(test) arc shield surface
20.4 (option)
11.5
(isol) 13
35 5-ø
119.3 6
25*4=100
125
125
465.8
15
330
193
68
125
107.5
ø13 15
50 250
33.1
15
328.8
352.8
39.6 425.6
465.2
70
Technical guide
B frame draw-out type 4000A dimensions
405 520
28.8
28.8
250
250
368.4
368.4
ø1 ø1
4 4
119.3 6
25*3=75
10
100
15
465.8
168
15
330
40
132.5
ø13 15
33.1
50 250
15
328.8
352.8
39.6 399.6
439.2
71
Technical guide
C frame fixed type 3200-5000A dimensions
592 762
404.4
404.4
270
464.7 168.7 270
609.4 779.4
190.5 190.5 190.5 190.5 190.5
20 70 20 148 20 70 20 148
5
5
152.5
152.5
186.8
186.8
20
20
109
109
241.7
13
35 5-ø
25*4=100
125
125
15
194
69
330
125
107
33
60 49 186.8
44.5
295.8 63.6
72
Technical guide
C frame fixed type 3200-5000A dimensions
609.4 779.4
190.5 190.5 190.5 190.5 190.5
148 125 148
5
5
152.5
186.8
186.8
152.5
20
20
109
109
241.7
13
35 5-ø
20
25*4=100
110
125
70
20
15
330
196
86
110
106
51
33
60 49 186.8
295.8 63.6
73
Technical guide
C frame draw-out type 3200-5000A dimensions
440
466
440
270 270
460 164 545 249
624 794
368.4
368.4
175
175
4 4
ø1 ø1
50
50
11.5 13
(isol) 35 5-ø
119.3 6
25*4=100
125
125
465.8
15
194
69
330
125
107
ø13 15
44.5
50 175
33.1
15
328.8
352.8
39.6 401.6
441.2
74
Technical guide
C frame draw-out type 3200-5000A dimensions
103.8
103.8
368.4
368.4
175
175
4 4
ø1 ø1
50
50
11.5 13
(isol) 35 5-ø
20
119.3 6
25*4=100
125
110
70
465.8
15
20
330
196
86
51 110
106
ø13 15
33.1
50 175
15
328.8
352.8
39.6 401.6
441.2
75
Technical guide
Draw-out type dimensions
Panel door cut-out for dust cover (mm) Panel door cut-out for door flange (mm)
operating operating
panel center panel center
196 196 R5
292 4- 292
4-
ø5 5.2 R5
.2 42.5 103.5 100 103.5 42.5 -ø 103.5 100 103.5 4-
4
20
122.5
122.5
15
290
229
115
345
115
345
4
-ø
4
122.5
122.5
-ø
12
12
68.6 15
7.5
7.5
20
bottom bottom
7.5 7.5
E
D
Side view (mm) Rear panel cutting size (mm)
26.5 60
(test) 20.4
B
rear panel
C
(IP30)
bottom
32
31
bottom
33.1
4
panel door
(25) (323)
Model A B C D E
76
Technical guide
Fixed type dimensions
Panel door cut-out for dust cover (mm) Panel door cut-out for door flange (mm)
operating operating
panel center panel center
196 196 R5
292 4- 292
4- 2
ø5
.2 42.5 103.5 100 103.5 42.5 5. R5
4-
ø 103.5 100 103.5 4-
20
122.5
122.5
15
290
229
115
345
115
345
4
4
122.5
-ø
122.5
-ø
12
12
68.6 15
7.5
7.5
20
bottom bottom
33.1
25.6
25.6
7.5 7.5
ACB center
A
144
330
B
75
132
33
bottom
bottom
(95) (188)
rear panel
C
panel door
Model A B C
77
Technical data
Internal resistance, power consumption and insulation distance
frame A 630 15 18 30 36
800 15 29 30 58
1000 15 45 30 90
1250 15 70 30 141
1) Power consumption listed is maximum power consumption for each rated current, 50/60Hz, 3/4 pole.
2) This is inner resistance value per pole.
3) Power factor = 1.0
Insulation distance
ACB A B A
Fixed type 150 (415V) 60
300 (690V)
Insulating voltage D
D
(V) ≤ 600 V 8
78
Technical data
Rectification of rated current
40°C 45°C 50°C 55°C 60°C 40°C 45°C 50°C 55°C 60°C
frame 630A 15t x 50mm x 1EA 5t × 50mm × 2EA 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A
A
10t × 60mm × 1EA
800A 6t × 50mm×2EA 800A 800A 800A 800A 800A 800A 800A 800A 800A 800A
10t × 60mm × 1EA
1000A 8t × 50mm × 2EA 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A
6t × 75mm × 2EA - - - - -
1250A 8t × 60mm × 2EA 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A
10t × 50mm × 2EA
6t × 75mm × 3EA - - - - -
1600A 10t × 60mm × 3EA 1600A 1600A 1520A 1480A 1420A 1600A 1600A 1600A 1550A 1550A
8t × 60mm × 3EA
frame 2000A 20t × 75mm × 1EA 8t × 75mm × 3EA - - - - - 2000A 2000A 2000A 1860A 1860A
A
10t × 100mm × 2EA
frame 630A 20t × 75mm × 1EA 5t × 50mm × 2EA 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A
B
10t × 60mm × 1EA
800A 6t × 50mm × 2EA 800A 800A 800A 800A 800A 800A 800A 800A 800A 800A
10t × 60mm × 1EA
1000A 8t × 50mm × 2EA 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A
6t × 75mm × 2EA - - - - -
1250A 8t × 60mm × 2EA 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A
10t × 50mm × 2EA
6t × 75mm × 3EA - - - - -
1600A 10t × 60mm × 3EA 1600A 1600A 1600A 1600A 1600A 1600A 1600A 1600A 1600A 1600A
8t × 60mm × 3EA
2000A 8t × 75mm × 3EA 2000A 2000A 2000A 2000A 2000A 2000A 2000A 2000A 2000A 2000A
10t × 100mm × 2EA - - - - -
2500A 10t × 75mm × 3EA 2500A 2500A 2500A 2400A 2300A 2500A 2500A 2500A 2500A 2500A
8t × 75mm × 4EA
frame 3200A 20t × 90mm × 1EA 10t × 100mm × 3EA - - - - - 3200A 3200A 3200A 3050A 3050A
B
10t × 75mm × 4EA 3200A 3200A 3100A 3000A 2900A
frame 4000A 15t × 100mm × 2EA 10t × 100mm × 4EA 4000A 4000A 3900A 3800A 3640A - - - - -
B horizontal
10t × 125mm × 3EA
4000A 15t × 125mm × 2EA 10t × 100mm × 4EA - - - - - 4000A 4000A 4000A 3800A 3800A
vertical
10t × 125mm × 3EA
frame 3200A 20t × 125mm × 2EA 10t × 100mm × 3EA 3200A 3200A 3100A 3000A 2900A 3200A 3200A 3200A 3000A 3000A
C
4000A 10t × 100mm × 4EA 4000A 4000A 3920A 3860A 3800A 4000A 4000A 4000A 3900A 3900A
5000A 10t × 125mm × 4EA 5000A 5000A 4900A 4800A 4700A 5000A 5000A 5000A 4900A 4900A
t= thickness (mm) EA=number of parts
Altitude
Altitude 2000m 3000m 4000m 5000m
ACB HW is designed for operation at altitudes under 2000m. At withstand voltage (V) 3500 3150 2500 2100
altitudes higher than 2000m, change the ratings upon service
condition. average insulating voltage (V) 1000 900 700 600
79
Technical data
Derating table
Derating table
Switchboard composition 4
connection type 4 3
3 2
2 1
1
H Ta = 45°C 4 800
H
3 800 800 1000
: vertical
80
Technical data
Derating table
Derating table
Switchboard composition 4
connection type 4 3
3 2
2 1
1
3 1250 2000
H Ta = 45°C 4
H
3 1250 1900
3 1250 1800
3 1250 1750
H Ta = 45°C 4
H
3 1250 1750 1650
81
Technical data
Derating table
Derating table
Switchboard composition 4 4 4 4
connection type 4 3 4 3 4 3 4 3
3 2 3 2 3 2 3 2
2 1 2 1 2 1 2 1
1 1 1 1
3 2000
H Ta = 45°C 4
H
3 2000
1
D W
D W Ta = 55°C 4
3 2000
1
5)
non-ventilated switchboard (IP52) Ta = 35°C 4
3 2000
H Ta = 45°C 4
H
3 1900
1
D W
D Ta = 55°C 4
W
3 1780
: vertical
82
Technical data
Derating table
Derating table
Switchboard composition 4 4
connection type 4 3 4 3
3 2 3 2
2 1 2 1
1 1
H Ta = 45°C 4
H
3
1
D W
D W Ta = 55°C 4
1
5)
non-ventilated switchboard (IP52) Ta = 35°C 4
H Ta = 45°C 4
H
3
1
D W
D Ta = 55°C 4
W
3
83
Technical data
Discrimination table
OCR: LI, LSI, LSIG,LI Amp, LSI Amp, LSIG Amp, LSIG Energy
IR, tR of the ACB > IR, tR of the MCCB / Isd, tsd of the ACB > Isd, tsd of the MCCB / li = 16xIn, NON,MCR ON
Icc (kA) Upstream Frame A, type HWAH Frame A, type HWAN Frame B, type HWBN
max. rated current 2000A max. rated current 2000A max. rated current 4000A
Icu = Ics = 50kA at 415V Icu = Ics = 65kA at 415V Icu = Ics = 65kA at 415V
Downstream (A) 630 800 1000 1250 1600 2000 630 800 1000 1250 1600 2000 630 800 1000 1250 1600 2000
HDA x160 TM 16 T T T T T T T T T T T T T T T T T T
HHA 18/25/40kA 20 T T T T T T T T T T T T T T T T T T
HNA 25 T T T T T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T T T T T
50 T T T T T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T T T T T
80 T T T T T T T T T T T T T T T T T T
100 T T T T T T T T T T T T T T T T T T
125 T T T T T T T T T T T T T T T T T T
160 T T T T T T T T T T T T T T T T T T
HHB x250 TM 100 T T T T T T T T T T T T T T T T T T
HNB 25/40kA 125 T T T T T T T T T T T T T T T T T T
160 T T T T T T T T T T T T T T T T T T
200 T T T T T T T T T T T T T T T T T T
225 T T T T T T T T T T T T T T T T T T
250 T T T T T T T T T T T T T T T T T T
HHG h250 TM 20 T T T T T T T T T T T T T T T T T T
HNG 25/50/65kA 32 T T T T T T T T T T T T T T T T T T
HEG 50 T T T T T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T T T T T
100 T T T T T T T T T T T T T T T T T T
125 T T T T T T T T T T T T T T T T T T
160 T T T T T T T T T T T T T T T T T T
200 T T T T T T T T T T T T T T T T T T
250 T T T T T T T T T T T T T T T T T T
HNH h250 TM+ 20 T T T T T T T T T T T T T T T T T T
HEH 50/70kA 32 T T T T T T T T T T T T T T T T T T
50 T T T T T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T T T T T
100 T T T T T T T T T T T T T T T T T T
125 T T T T T T T T T T T T T T T T T T
160 T T T T T T T T T T T T T T T T T T
250 T T T T T T T T T T T T T T T T T T
HNC h250 LSI 40 T T T T T T T T T T T T T T T T T T
HEC 50/70kA 125 T T T T T T T T T T T T T T T T T T
250 T T T T T T T T T T T T T T T T T T
HHD h400 TM 250 T T T T T T T T T T T T T T T T T T
HND 25/50/70kA 300 T T T T T T T T T T T T T T T T T T
HKD 350 T T T T T T T T T T T T T T T T T T
400 T T T T T T T T T T T T T T T T T T
HND h630 LSI 250 T T T T T T T T T T T T T T T T T T
HED 50/70kA 400 T T T T T T T T T T T T T T T T T T
500 T T T T T T T T T T T T T T T T T T
600 T T T T T T T T T T T T T T T T
630 T T T T T T T T T T T T T T T
HNK h800 TM 630 T T T T T T T T T T T T T T T
HEK 50/70kA 800 T T T T T T T T T T T T T
HNE h1000 LSI 630 T T T T T T T T T T T T T T T
HEE 50/70kA 700 T T T T T T T T T T T T T T T
800 T T T T T T T T T T T T
1000 T T T T T T T T T
HNF h1600 LSI 800 T T T T T T T T T T T T
HEF 50/70kA 1250 T T T T T T
1600 T T T T
84
Technical data
Discrimination table
85
Technical data
Cascading
Upstream
HHA 25kA 25 25 25 25 25 25
HNA 40kA 40 40 40 40 40 40
HNB 40kA 40 40 40 40 40 40
HNG 50kA 50 50 50 50 50 50
HEG 65kA 50 50 65 65 65 65
HEH 70kA 50 50 50 65 65 65
HEC 70kA 50 50 50 65 65 65
HND 50kA 50 50 50 50 50 50
HKD 70kA 50 50 50 65 65 65
HED 70kA 50 50 50 65 65 65
HEK 70kA 50 50 50 65 65 65
HEE 70kA 50 50 65 65
HEF 70kA 50 65
86
Technical data
Cascading
Frame B, type HWBN Frame B, type HWBS Frame B, type HWBP Frame C, type HWCP
630-800A 1000- 1600- 630-800A 1000- 1600- 630-800A 1000- 1600- 3200-5000A
1250A 4000A 1250A 4000A 1250A 4000A
18 18 18 18 18 18 18 18 18 18
25 25 25 25 25 25 25 25 25 25
40 40 40 40 40 40 40 40 40 40
25 25 25 25 25 25 25 25 25 25
40 40 40 40 40 40 40 40 40 40
25 25 25 25 25 25 25 25 25 25
50 50 50 50 50 50 50 50 50 50
65 65 65 65 65 65 65 65 65 65
50 50 50 50 50 50 50 50 50 50
65 65 65 70 70 70 70 70 70 70
50 50 50 50 50 50 50 50 50 50
65 65 65 70 70 70 70 70 70 70
25 25 25 25 25 25 25 25 25 25
50 50 50 50 50 50 50 50 50 50
65 65 65 70 70 70 70 70 70 70
50 50 50 50 50 50 50 50 50 50
65 65 65 70 70 70 70 70 70 70
50 50 50 50 50 50 50 50 50 50
65 65 65 70 70 70 70 70 70 70
50 50 50 50 50 50 50
65 65 70 70 70 70 70
50 50 50 50
65 70 70 70
87
Technical data
Operating conditions
• Operating condition: -5˚C to 50˚C is recommended. • Relative humidity should be under 85%.
• Chassis is fixed to a switchboard.
• The average temperature for 24 hours should be within 35˚C.
• Reduce the continuous conducting current when the
temperature is over 50˚C (45°C for horizontal type connection).
Atmospheric conditions
Altitude
Item Altitude
88
Technical data
Installation conditions
150 150
119.3 6 119.3 6
278.3
278.3
250
119.3 6 119.3 6
278.3
278.3
250
70
89
Codification
H W A H 3 16 E F A 0 A A 0 A 0 A 0
Frame size
A = Frame size A
B = Frame size B
C = Frame size C
Number of poles
3 = 3 poles
4 = 4 poles
Market
E = Market letter
Version
F = fixed
D = draw-out
Trip unit
A = no OCR switch disc. E = OCR LCD display Amp LI
B = OCR STD LI F = OCR LCD display Amp LSI
C = OCR STD LSI G = OCR LCD display Amp LSIG
D = OCR STD LSIG H = OCR LCD display Energy LSIG
Terminal connection
0 = without 5 = front terminal (FC/FC)
1 = horizontal terminal (HC/HC) 6 = front terminal and horizontal terminal (FC/HC)
2 = vertical terminal (VC/VC) 7 = front terminal and vertical terminal (FC/VC)
3 = horizontal and vertical (HC/VC) 8 = horizontal terminal and front terminal (HC/FC)
4 = vertical and horizontal (VC/HC) 9 = vertical terminal and front terminal (VC/FC)
90
Codification
MOC 2nd Auxiliary Switch & Counter & Arc Shield (only DO ACB)
0 = without Counter & without MOC & without Arc Shield
1 = with Counter & without MOC & without Arc Shield
2 = without Counter & with MOC & without Arc Shield
3 = with Counter & with MOC & without Arc Shield
4 = without Counter & without MOC & with Arc Shield
5 = with Counter without MOC & with Arc Shield
6 = without Counter & with MOC & with Arc Shield
7 = with Counter & with MOC & with Arc Shield
Closing release
0 = without 4 = AC 440V
1 = AC/DC 110V 5 = DC 24V
2 = AC/DC 220V 6 = DC 48V
3 = AC 380V
Shunt release
A = without E = AC 440V
B = AC/DC 110V F = DC 24V
C = AC/DC 220V G = DC 48V
D = AC380V
91
Hager
Zum Gunterstal
66440 Blieskastel
Germany