Providing compete FM Global Wind Uplift Ratings


construction specifications By David Stutzman, AIA, CSI, CCS, SCIP, LEED AP
documentation, systems
and performance Factory Mutual Wind Uplift
descriptions, and risk and The first thing that should be Wind uplift is defined as a force that
quality advisory services. explained about Factory Mutual (FM occurs when air pressure below the
Global) is that they are not a roof assembly is greater than the air
ABSTRACT: governing code body, they are an pressure above the roof system. As
FM Global Data Sheet 1-28 helps
calculate the wind uplift load. insurance company. All testing is air flows over the roof the pressure
FM Global Property Loss Prevention conducted by, and their standards directly above roof decreases and at
Data Sheet 1-29 provides a simple, written by, their own in-house the same time the air pressure inside
prescriptive method for the installation engineers. Factory Mutual does not the building increases in an attempt to
of base sheets, insulation, and have any control over buildings they equalize the pressure differential.
system membranes. do not insure, even though many Many design professionals assume
design professionals use the FM on- wind classification ratings such as 1-
FILING:
UniFormat™ line calculator (www.roofnav.com) to 60, 1-75, or 1-90 represents wind
B3010 Roofing determine wind uplift calculations. FM speed. This is not true. For instance,
Global Loss Prevention Data Sheets the 1-90 rating represents a Class 1
MasterFormat™
1-28, 1-29 and 1-49 are the most interior fire classification and the 90
07 50 00 Membrane Roofing
commonly referenced data sheets represents 45 pounds per square foot
KEYWORDS: when designing a roof system. of actual field of roof wind uplift
Wind uplift, wind loads, FM Ratings, Before calculating a wind uplift pressure. Wind uplift pressures often
Factory Mutual, FM Global. pressure and specifying a roof vary at different locations of the roof.
system, certain types of data about The most vulnerable roof areas are
STANDARDS:
the building must be known. Overall the corners and the perimeter. The
FM 1-28 - Design wind Loads
FM 1-29 - Roof Deck Securement and height of the building, terrain field area of the roof is less
Above-Deck Roof Components surrounding the building, type of roof susceptible to uplift damage.
FM 1-49 - Perimeter Flashing deck that will be installed, whether or "Importance Factor" and "Safety
not the building is considered a Factor" also play a role in roof design.
"special use facility" (hospitals, The Importance Factor was originated
assisted living buildings, etc.) and the to increase the designed seismic
height of parallel walls are all taken forces to provide additional seismic
into consideration. resistance where required. In time, the
As stated above the type of roof deck Importance Factor eventually made
to be installed is critical to the type of it's way into snow and wind load
roof system to be specified. The designs as well. FM Global
following is a list of FM approved roof recommends a minimum Importance
decks: Factor of 1.15 for all roof designs.
1.) Steel, 22 gauge and heavier. The Safety Factor is defined as "The
2.) Structural concrete, minimum ratio of the maximum stress or load
2,500 psi. which something can withstand to the
3.) Wood, minimum 3/4 inch thick fire stress or load that it was designed to
rated plywood or minimum 2 inch withstand under normal operation."
thick dimensional lumber. FM Global recommends a minimum
4.) Cementitious wood fiberboard. Safety Factor of 2.0 for all roof
5.) Lightweight insulating concrete. designs unless the roof is to be
6.) Fiberglass reinforced plastic. installed on a "special use facility",
TECH TIPS
www.conspectusinc.com
Vol12.10.01 ©2012 Conspectus Inc.
Page 2 of 2

where a Safety Factor of 3.0 should consideration when specifying a roof is essential to the building owner's
be specified. system. best interest, enabling the owner to
Prior to 2006, after the appropriate properly insure his property.
Testing Roofing manufacturers have systems
rating had been determined for the
For mechanically attached single-ply
field of the roof, FM called for an that meet various FM ratings. It is very
roof systems a test assembly is
increase of 50% more fasteners at the important for the designer to review
constructed consisting of a 5 x 9 foot
perimeter, and 75% more in the the manufacturer's recommended
frame with 22 gauge steel roof deck
corners. The latest FM Revision system against the design, to make
attached to purlins. Insulation is then
requires that the perimeter and certain that the manufacturer
mechanically attached to the steel
corners have separate ratings based specifically includes every design
deck followed by single-ply membrane
on the field rating. In the case of feature. For example, the
mechanically attached over the
FM 1-90, the system must meet manufacturer's description of the
insulation into the steel deck. The test
FM 1-150 at the perimeter and recommended roofing system may
frame is clamped to a pressure vessel
FM 1-225 in the corners. This type of describe a maximum thickness of rigid
that is then pressurized to 15 lbs. psf
rating is not generally achievable with insulation. The designer must check
and held at that level for one minute. If
mechanically attached insulation, such provisions against his or her
the roofing system remains
especially on steel decks. In some design to ensure that all aspects of
undamaged for the one minute then
instances, enhancements to the the design are within the limits of the
the pressure is raised to 30 psf for
structural deck are required to meet system. Any outstanding items can
one minute. The process in repeated
these ratings. In the case of the higher usually be addressed in a technical
in 15 lb. increments until any
ratings for the field of the roof, such as letter from the manufacturer. Careful
component in the system fails. When
FM1-150, compliance may not be design and careful review of
the failure occurs the test is stopped
possible regardless of the system type recommended systems will result in a
and the approval rating is established
or number of fasteners used. sound roof system.
at the level PRECEEDING the failure,
Examples of differing rating
for example, if the failure occurs at
requirements per the FM revision are:
105 psf then the approval level will be
Field of Roof- FM 1-90
set at 90 psf. Fully adhered single ply
Perimeter Requirement FM 1-150
systems and built-up systems are
Corner Requirement FM 1-225
tested in the same manner but only on
Field of Roof- FM1-120
a 5 x 9 foot test frame, and only to
Perimeter Requirement FM 1-195
approvals of up to I-90. For ratings
Corner Requirement FM 1-295
greater than 1-90 the system must be
Field of Roof- FM1-135
tested on a 12 x 24 foot test frame,
Perimeter Requirement FM 1-225
probably at considerable additional Add Your Comments
Corner Requirement FM 1-330
cost to the roofing system We invite your comments. Visit our blog
Field of Roof- FM1-150
manufacturer. and add your comments.
Perimeter Requirement FM 1-255
Miscellaneous Corner Requirement FM 1-360
1-90 is considered the default Like it? Share it!
standard for roofing systems that are
Conclusion Tweet or Email your friends
FM Ratings for roof construction are
not located on a coastal or high wind
an example of "outside forces" other
area, but project location must also be The information contained in this document
than Mother Nature exerting strong
considered before specifying a roof is offered for educational purposes, only,
influence on building design. In this
system. A roof in the State of and not as technical advice suitable for any
case the findings and requirements of
Wisconsin may be designed to the 1- particular project or specific condition.
insurers actually drive the design
60 or 1-75 uplift requirements to cut Technical consulting is unique to the facts
requirements of roof systems.
down on the cost of the materials of a particular condition, and Conspectus
Regardless of whether or not this can
required for the installation of the roof recommends that a specialist be consulted
be considered a desirable condition, it
but since Wisconsin will have more to determine solutions for each specific
is a fact of life. Achieving the required
hail storms than other areas of the condition.
FM ratings for the area and exposure
country hail must be taken into