Product Information
General Information
Electric heat coils are an available accessory
for use with Price variable volume and
constant volume fan powered terminal
units. The electric heating coils have been
specifically designed to suit Price fan
powered terminal units. Electric heating
coils are factory-mounted at the discharge
outlet of the terminal unit.
Controls for the electric heat are interlocked
and sequenced with the recirculating fan
in the terminal unit. The electric heat can
be energized only after the recirculating
fan is operating and then only if the warm
plenum air supplied by the recirculating fan
TERMINAL UNITS
TERMINAL UNITS
solution to duct heater control.The complex
internal wiring normally associated with
duct heater assemblies is eliminated and
replaced with the sleek and compact all-
inclusive PSG circuit board. Installing the
board is very straight forward: thanks to
the snap-in design and fully labeled on-
board connectors, wiring is made quick
and efficient.
Features Installation and Maintenance Safety
The Price Silent Guard incorporates many The design of the PSG greatly reduces The PSG has undergone rigorous testing
features on to the board to make it the safest installation time and increases convenience: and earned ETL approval giving the user
and most reliable product possible: the unit simply snaps in to the duct heater. comfort in the safe operation of the device.
Wiring connections for every possible Numerous innovative concepts were
• Accepts either switched HOT or switched configuration are labeled on the board in a incorporated into the design of the circuit
COMMON input signals. straight forward and simple to understand board ensuring not only the safety of the
• Software averaging of input signal manner. This reduces wiring clutter and building and its occupants, but also the
prevents relay chatter and extends space required for the assembly. safety and longevity of the fan and heater
device life. Troubleshooting the unit is even easier. An components.
• Fan interlock option prevents coil from on-board status LED sequentially blinks out
overheating. a troubleshooting code which indicates the
• FR-4 rated circuit board complies with current status of the board. (For example:
safety standards. three blinks means 3 stages of heating
• PCB mounted air flow switch with are active, six blinks means auto reset
has tripped, etc.) The indicator lights also
Intelliflow technology.
show the user which individual circuits are
• Easy to use with One-Phase, Three- currently energized.
Phase Y or Three-Phase Delta power
systems.
• Each stage handles up to 277VAC.
• Indicator lights show operation of each
stage of heat and fan output.
• Programmed time delays prevent short
cycling of fan or heater stages.
• PCB Relays are much quieter than
standard magnetic contactors.
• Price Silent Guard is also a great
alternative to expensive mercury
contactors.
F-481
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Fan Powered Terminal Units
Electric Coils
Selection Parameters
Selection Guidelines
TERMINAL UNITS
known, Select the Power supply voltage kW kW kW kW kW kW kW kW
based on maximum recommended kW, 10 5.1 5.7 5.7 5.7 5.7 5.7 5.7 5.7
referring to the coil selection chart. 20 5.1 9.3 10.0 10.0 10.0 10.0 10.0 10.0
4. Verify that minimum air flow 30 5.1 9.3 10.8 12.4 17.0 12.9 17.0 15.0
requirements of 70 cfm/kW [33L/s per 40 5.1 9.3 10.8 12.4 21.6 12.9 27.0 26.0
50 5.0 9.1 10.5 12.2 21.6 12.9 29.4 31.0
kw] are met, and that the discharge air
60 4.9 8.9 10.3 11.9 20.6 12.9 29.4 37.0
temperature does not exceed 120 °F.
70 4.6 8.3 9.7 11.2 19.3 14.5 29.4 41.3
Refer to example.
FXV Max – kW for Conventional Control
5. Select options.
1 Phase Voltage 3 Phase Voltage
6. For terminal units with electric reheat
Size 120 208 240 277 480 208 480 600
a minimum discharge static of 0.2"w.g. kW kW kW kW kW kW kW kW
is recommended for stable operation of 20 5.4 9.8 10.7 10.0 10.7 10.7 10.0 10.7
heater controls. 30 5.4 9.8 11.4 13.1 17.5 12.9 19.2 19.2
40 5.2 9.4 10.8 12.5 21.6 12.9 25.0 28.5
50 5.0 9.1 10.5 12.1 20.9 12.9 29.7 34.2
60 4.9 8.9 10.2 11.8 20.4 12.9 29.7 37.0
FXV Max – kW for SCR Control
1 Phase Voltage 3 Phase Voltage
Size 120 208 240 277 480 208 480 600
kW kW kW kW kW kW kW kW
20 5.1 9.3 10.7 10.0 10.7 10.7 10.7 10.7
30 5.1 9.3 10.8 12.4 17.5 12.9 19.2 19.2
40 5.1 9.3 10.8 12.4 21.6 12.9 25.0 28.5
50 5.0 9.1 10.5 12.1 20.9 12.9 29.7 34.2
60 4.9 8.9 10.2 11.8 20.4 12.9 29.7 37.0
FPCLP, FXVLP Max – kW for Conventional Control
1 Phase Voltage 3 Phase Voltage
Size 120 208 240 277 480 208 480 600
kW kW kW kW kW kW kW kW
10, 20 5.0 8.5 8.5 8.5 8.5 8.5 8.5 8.5
30 5.0 9.5 11.0 11.0 13.5 14.0 14.0 14.0
40 5.0 9.0 11.0 10.5 21.0 15.0 22.5 22.5
50 4.5 9.0 9.0 10.0 21.0 14.0 23.5 23.5
FXCLP, FXVLP Max – kW for SCR Control
Notes
1 Phase Voltage 3 Phase Voltage
1. ETL certified assemblies. Size 120 208 240 277 480 208 480 600
2. Minimum kW: kW kW kW kW kW kW kW kW
Single Phase = 0.5 kW per stage. 10, 20 5.0 8.5 8.5 8.5 8.5 8.5 8.5 8.5
Three Phase = 1.5 kW. 30 5.0 9.0 10.5 12.0 14.0 9.0 14.0 14.0
3. The recommend limit of 48 Amps may by exceeded. 40 5.0 8.5 10.0 12.0 20.0 9.0 20.5 22.0
This requires supplemental fusing to meet NEC code 50 4.5 8.0 9.5 12.0 20.0 9.0 20.5 23.5
requirements. Contact your local Price representative for FXCQ2 Max – kW for Conventional or SCR Control
further details. 1 Phase Voltage 3 Phase Voltage
4. Maximum kW limitations is the lesser of Size 120 208 240 277 480 208 480 600
a) coil selection chart kW kW kW kW kW kW kW kW
or 10 4.0 7.5 8.5 12.0 21 13.0 15.5 15.5
b) minimum air flow requirements of 70 cfm/kW [33 L/s 12 4.0 7.5 8.5 12.0 21 13.0 25.5 25.5
perkW]. 14 4.0 7.5 8.5 12.0 21 13.0 28.5 28.5
F-483
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Fan Powered Terminal Units
Electric Coils
Selection Guidelines
FXCQ2
Max – kW for Price Silent Guard Controller
1 Phase Voltage 3 Phase Voltage
Size 120 208 240 277 480 208 480 600
kW kW kW kW kW kW kW kW
10 3.5 6.0 7.0 8.0 -- 10.5 -- --
12 3.5 6.0 7.0 8.0 -- 10.5 -- --
14 3.5 6.0 7.0 8.0 -- 10.5 -- --
TERMINAL UNITS
How To Use the Chart
Electric Coil Selection Procedure 4. With the point of intersection from 3, 5. Leaving air temperature ‑ 68° + 38.5° =
The selection of an electric coil for a the air temperature rise (ATR), can be 106.5 °F. Since the leaving air temperature
fan powered terminal unit requires the obtained by interpolating between the is less than the recommended maximum
determination of the two components of air temperature n/se lines on the graph. limit of 120 °F, the selection is satisfactory.
the heat loss. One component is the heat 5. To verify the selection, sum the air 6. Select a suitable power supply from
required to satisfy the space load.The second temperature rise and the temperature Table 3.
component is the heat required to raise the of the recirculated plenum air. The sum
temperature of the recirculated plenum air • For Model FPV, 18.3 kW, use
total should be less than 120 °F.
to that of the space. This can be determined 480v/3Ø/4 wire or 600v/3Ø/3 wire.
as follows, using the Electric Coil Selection Example
7. Verify power supply connection from
Chart and the equation as given below. Select an electric coil for a Size 60 Model Table 2.
1. Locate the room heat loss on the MBH FPV, with a recirculating fan capacity of
1500 cfm. Space heat loss is estimated at • For Model FPV Size 480v/3Ø/4,
scale on the far left side of the chart. single point connection.
Convert to kW by moving horizontally to 56 MBH and space design temperature is 72
the right to the kW scale (1 kW = 3.413 °F. The temperature of recirculated plenum • For Model FPV, Size 600v/3Ø/3 dual
MBH). air is 68 °F. point connection 600 volts and 115
2. Calculate the kW required to heat 1. Space heat loss (56 MBH) = 16.4 kW volts.
the recirculated plenum air to room 2. Heat required to raise the temperature 8. Verify minimum air flow requirements
temperature using the following equation: of the recirculated plenum air. are met.
1500 cfm
kW = cfm x 1.08 x ∆T kW = 1500 x 1.08 x 4 = 1.9 kW = 82 cfm/kw
18.3 kW
3413 3413
3. Add the kW value obtained in step 2 3. Total heat required = 16.4 + 1.9 = 18.3 kW. • 82 cfm per kW is greater than 70 cfm
to the kW scale at the left side. Move 4. Air temperature rise (ATR) = 38.5 °F. per kW from Table 1 — a satisfactory
horizontally to the right to the point where selection.
the kW value and the air flow volume
intersect.
F-485