Fan Powered Terminal Units

Electric Coils

Product Information

General Information
Electric heat coils are an available accessory
for use with Price variable volume and
constant volume fan powered terminal
units. The electric heating coils have been
specific­ally designed to suit Price fan
powered terminal units. Electric heating
coils are factory-mounted at the discharge
outlet of the terminal unit.
Controls for the electric heat are interlocked
and sequenced with the recirculating fan
in the terminal unit. The electric heat can
be energized only after the recirculating
fan is operating and then only if the warm
plenum air supplied by the recirculating fan
TERMINAL UNITS

has not been suf­ficient to satisfy space heat


requirements.
Benefits of Electric Coils
vs Hot Water Coils
Electric coils offer an alternative to hot water
reheat coils as an optional accessory for fan
powered terminal units. The benefits are:
• No need for water lines which can lead
• Recirculating fan is interlocked with • Up to two additional stages of electric
to potential leaks, damaging property
the heating elements to ensure that the available to allow for staged heating
and reduced installation costs.
fan is operational prior to the heating capacity.
• Advantage can be taken of the electrical elements being energized. • SCR (Silicon Controlled Rectifier)
power supply hookup for the basic fan
• High grade nickel chrome heating option provides infinite heater control
powered terminal unit when making
elements are an available option to using a proportional signal. Element life
the electrical connection for the electric
provide superior element life and is extended and noise from contactors is
coil. (Note: the electrical power supply
corrosion resistance. eliminated. This option may be specified
conductor size increases when electrical
• A single point connection is provided compatible with pneumatic, electronic,
reheat coil load is added, refer to NEC
for both heater and fan motor (except or DDC controls. See description below.
codes for conductor sizing.)
600v/3Ø heater comes with 115V/1Ø (UL and CSA certified)
• No pressure drop across the coils,
motor). Dual point connection is • Primary or Secondary Fusing for added
therefore reduced central fan HP
available as an option on special safety or to meet local electrical codes.
requirements for constant volume fan
request. Conventional Staged Heater
powered terminal unit applications.
• Electric coil units are ETL listed to meet • Pneumatic
Features/Benefits of Price Electric Heat electrical safety standards and comply
Coils: • Electronic
with dual designation CSA 236/UL 1995.
• Digital (DDC)
• Heavy gauge zinc-coated steel electrical Available Options
cabinet and frame. Maximum 3 Stages
• An interlocking main disconnect switch SCR Heater
• Large electrical cabinet door hinged for
is used to de‑energize the electric unit
easy access and designed for secure • Pneumatic
once the electrical en­closure door has
closure. proportional (with the addition of a
been opened.
• Electric coil controls and fan powered pneumatic-electric transducer).
• Positive pressure air flow switch which • Digital (DDC)
terminal unit controls are on the
senses pressure differential between proportional, pulsed AC, or pulsed DC.
same side of the unit reducing design
a factory preset pressure and the
restrictions and providing ease of Note:
combined velocity pressure plus static
servicing. For terminal units with electric reheat a
pressure. If the recirculating fan fails to
• Electric coil configuration and air flow minimum discharge static of 0.2"w.g. is
operate, then the positive pressure air
is matched to eliminate hot spots to recommended for stable operation of heater
flow switch will not allow the electric controls.
provide efficient heat transfer and to
coil to operate.
maintain element life.
• Mercury contactors recommended
• Automatic reset thermal cutout specifically
for use in applications sensitive to
matched to each unit to protect from
noise. Mercury contactors provide
overheating in case the minimum air flow
quiet operating characteristics. Recom­
requirements are not met.
mended for applications which have
• Secondary thermal cutout is in the frequent demand and cycle repeatedly.
power circuit and is used as a backup
• Disconnecting contactors for applica­
in case of failure of the automatic reset
tions where it is necessary to dis­connect
thermal cutout.
all three phase power up.

F-480 All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.
© Copyright Price Industries Limited 2011.
Fan Powered Terminal Units
Electric Coils

Price Silent Guard™ – Silent Operating Electric Heater Control Module

The Price Silent Guard Heater Control


Module provides efficient operation of of PSG (Price Silent Guard)
duct heaters with a wide range of features to
cover all control, safety and troubleshooting
concerns. The on-board PCB relays provide
quiet and reliable operation to give the end
user peace of mind.
Benefits
• Quiet on-board relays
• Auto resetting 24VAC fuse
• On-board air flow switch
• Status LED to aid troubleshooting
General Information
The Price Silent Guard (PSG) is an all-in-one

TERMINAL UNITS
solution to duct heater control.The complex
internal wiring normally associated with
duct heater assemblies is eliminated and
replaced with the sleek and compact all-
inclusive PSG circuit board. Installing the
board is very straight forward: thanks to
the snap-in design and fully labeled on-
board connectors, wiring is made quick
and efficient.
Features Installation and Maintenance Safety
The Price Silent Guard incorporates many The design of the PSG greatly reduces The PSG has undergone rigorous testing
features on to the board to make it the safest installation time and increases convenience: and earned ETL approval giving the user
and most reliable product possible: the unit simply snaps in to the duct heater. comfort in the safe operation of the device.
Wiring connections for every possible Numerous innovative concepts were
• Accepts either switched HOT or switched configuration are labeled on the board in a incorporated into the design of the circuit
COMMON input signals. straight forward and simple to understand board ensuring not only the safety of the
• Software averaging of input signal manner. This reduces wiring clutter and building and its occupants, but also the
prevents relay chatter and extends space required for the assembly. safety and longevity of the fan and heater
device life. Troubleshooting the unit is even easier. An components.
• Fan interlock option prevents coil from on-board status LED sequentially blinks out
overheating. a troubleshooting code which indicates the
• FR-4 rated circuit board complies with current status of the board. (For example:
safety standards. three blinks means 3 stages of heating
• PCB mounted air flow switch with are active, six blinks means auto reset
has tripped, etc.) The indicator lights also
Intelliflow technology.
show the user which individual circuits are
• Easy to use with One-Phase, Three- currently energized.
Phase Y or Three-Phase Delta power
systems.
• Each stage handles up to 277VAC.
• Indicator lights show operation of each
stage of heat and fan output.
• Programmed time delays prevent short
cycling of fan or heater stages.
• PCB Relays are much quieter than
standard magnetic contactors.
• Price Silent Guard is also a great
alternative to expensive mercury
contactors.

F-481
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Fan Powered Terminal Units
Electric Coils

Electronic Heating Controls

Silicon Controlled Rectifier SCR Benefits of SCR


(SCR) The Price SCR Controller is a Silicon • Proportional modulation of the heater
Controlled Rectifier that provides maintains set-point more accurately
proportional modulation to the output over than on/off control, providing maximum
its full operating range. The SCR acts like comfort in the space.
an electronic switch that turns on and off
• Energy efficient by avoiding overshooting
large amounts of power to the load (heater).
and undershooting and reduces
The Price SCR uses a Zero Crossing feature
that allows a soft start of the electronic load, operation costs.
which eliminates power surges. • Quiet operation of solid state relays
compared to mechanical relay or
Features
contactor pulling in and dropping out.
• Power requirements – 24 VAC, polarity • SCR can be tied into existing BAS
sensitive. controller, or can be used in a stand
• Large, finned aluminum Heat Sink to alone application.
provide proper heat dissipation.
TERMINAL UNITS

• Load Power ranging from 120 VAC to


480 VAC, and a current rating up to 25
or 45 amps (depending on model).
Multiple Control Input signals
from stand alone controller or BAS
controller: 2-10 vdc signal, 4-20 mA
signal, 24 VAC Pulsed signal
• LED indication for: Firmware Version,
Type of Input Signal, and Output
Indication.
Factory or Field installable optional
Discharge Air Temperature (DAT)
Probe for maintaining outlet air

Selection Parameters

Supply Voltage/Phase Selection


Common Supply Voltages: NEC Code Requirements
Electric coils for Fan power Terminal units In order to comply with NEC Code requirements for fan terminals with electric heat
can be ordered for a variety Voltage supplies. the following factory supplied options are available
When possible, a single point connection a) All heaters are furnished with a fan interlock contact as standard. An optional air
is provided for the heater and fan motor. flow switch (pressure type) is also available.
Table 1, below, indicates compatible b) Optional door interlock disconnect to disconnect power to the heater and fan
heater/fan motor voltages. terminal immediately upon opening of the control panel door.
c) Supplemental heater fusing circuit is required if total of heater and motor amps
Heater Fan Motor exceeds 48 amps.
Volts/Phase Volts/Phase
d) Standard contactors are of the de-energizing type. Optional disconnecting
Single Point Connection 115V/1PH 115V/1PH
contactors provide a full-line break to assure all wires are de-energized when the
208V/1PH 208V/1PH contactor is open.
240V/1PH 240V/1PH
277V/1PH 277V/1PH
* When 480 V/3PH or 480/1PH power is specified a neutral line must be run in order
480V/1PH* 3wire 277V/1PH
to provide a one point connection. The neutral and one of the hot 480 V legs in used to
208V/3PH 208V/1PH supply 277 V to the fan motor. See illustration.
480V/3PH* 4wire 277V/1PH
Two Point Connection 600V/3PH 115V/1PH

F-482 All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.
© Copyright Price Industries Limited 2011.
Fan Powered Terminal Units
Electric Coils

Selection Guidelines

Electric Coil Selection Coil Selection Chart – Maximum kW


In selecting electric coils, consider the FXC, FXCG Max – kW for Conventional *Available with ECM motor option only.
following: 1 Phase Voltage 3 Phase Voltage
1. Once the design air flow has been Size 120 208 240 277 480 208 480 600
determined and the model type selected kW kW kW kW kW kW kW kW
10 5.5 5.7 5.7 5.7 5.7 5.7 5.7 5.7
(either constant or variable volume)
20 5.4 9.8 10.0 10.0 10.0 10.0 10.0 10.0
refer to the appropriate fan performance
30 5.3 9.6 11.0 12.8 17.0 12.9 17.0 15.0
curves and select the model size of unit 40, Q2 5.2 9.5 10.9 12.6 22.2 12.9 27.0 26.0
required to deliver the specified air flow. 50 5.0 9.1 10.5 12.2 21.7 12.9 29.4 31.0
2. With the model size and air flow known, 60 *4.9 8.9 10.3 11.9 20.6 12.9 29.4 37.0
electric coil capacity can be calculated. 70 4.6 8.3 9.7 11.2 19.3 14.5 29.4 41.3
Refer to the electric coil selection FXC, FXCG Max – kW for SCR Control
procedure for details. 1 Phase Voltage 3 Phase Voltage
3. With the heating capacity (kW) of the unit Size 120 208 240 277 480 208 480 600

TERMINAL UNITS
known, Select the Power supply voltage kW kW kW kW kW kW kW kW
based on maximum recommended kW, 10 5.1 5.7 5.7 5.7 5.7 5.7 5.7 5.7
referring to the coil selection chart. 20 5.1 9.3 10.0 10.0 10.0 10.0 10.0 10.0
4. Verify that minimum air flow 30 5.1 9.3 10.8 12.4 17.0 12.9 17.0 15.0
requirements of 70 cfm/kW [33L/s per 40 5.1 9.3 10.8 12.4 21.6 12.9 27.0 26.0
50 5.0 9.1 10.5 12.2 21.6 12.9 29.4 31.0
kw] are met, and that the discharge air
60 4.9 8.9 10.3 11.9 20.6 12.9 29.4 37.0
temperature does not exceed 120 °F.
70 4.6 8.3 9.7 11.2 19.3 14.5 29.4 41.3
Refer to example.
FXV Max – kW for Conventional Control
5. Select options.
1 Phase Voltage 3 Phase Voltage
6. For terminal units with electric reheat
Size 120 208 240 277 480 208 480 600
a minimum discharge static of 0.2"w.g. kW kW kW kW kW kW kW kW
is recommended for stable operation of 20 5.4 9.8 10.7 10.0 10.7 10.7 10.0 10.7
heater controls. 30 5.4 9.8 11.4 13.1 17.5 12.9 19.2 19.2
40 5.2 9.4 10.8 12.5 21.6 12.9 25.0 28.5
50 5.0 9.1 10.5 12.1 20.9 12.9 29.7 34.2
60 4.9 8.9 10.2 11.8 20.4 12.9 29.7 37.0
FXV Max – kW for SCR Control
1 Phase Voltage 3 Phase Voltage
Size 120 208 240 277 480 208 480 600
kW kW kW kW kW kW kW kW
20 5.1 9.3 10.7 10.0 10.7 10.7 10.7 10.7
30 5.1 9.3 10.8 12.4 17.5 12.9 19.2 19.2
40 5.1 9.3 10.8 12.4 21.6 12.9 25.0 28.5
50 5.0 9.1 10.5 12.1 20.9 12.9 29.7 34.2
60 4.9 8.9 10.2 11.8 20.4 12.9 29.7 37.0
FPCLP, FXVLP Max – kW for Conventional Control
1 Phase Voltage 3 Phase Voltage
Size 120 208 240 277 480 208 480 600
kW kW kW kW kW kW kW kW
10, 20 5.0 8.5 8.5 8.5 8.5 8.5 8.5 8.5
30 5.0 9.5 11.0 11.0 13.5 14.0 14.0 14.0
40 5.0 9.0 11.0 10.5 21.0 15.0 22.5 22.5
50 4.5 9.0 9.0 10.0 21.0 14.0 23.5 23.5
FXCLP, FXVLP Max – kW for SCR Control
Notes
1 Phase Voltage 3 Phase Voltage
1. ETL certified assemblies. Size 120 208 240 277 480 208 480 600
2. Minimum kW: kW kW kW kW kW kW kW kW
Single Phase = 0.5 kW per stage. 10, 20 5.0 8.5 8.5 8.5 8.5 8.5 8.5 8.5
Three Phase = 1.5 kW. 30 5.0 9.0 10.5 12.0 14.0 9.0 14.0 14.0
3. The recommend limit of 48 Amps may by exceeded. 40 5.0 8.5 10.0 12.0 20.0 9.0 20.5 22.0
This requires supplemental fusing to meet NEC code 50 4.5 8.0 9.5 12.0 20.0 9.0 20.5 23.5
requirements. Contact your local Price representative for FXCQ2 Max – kW for Conventional or SCR Control
further details. 1 Phase Voltage 3 Phase Voltage
4. Maximum kW limitations is the lesser of Size 120 208 240 277 480 208 480 600
a) coil selection chart kW kW kW kW kW kW kW kW
or 10 4.0 7.5 8.5 12.0 21 13.0 15.5 15.5
b) minimum air flow requirements of 70 cfm/kW [33 L/s 12 4.0 7.5 8.5 12.0 21 13.0 25.5 25.5
perkW]. 14 4.0 7.5 8.5 12.0 21 13.0 28.5 28.5

F-483
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Fan Powered Terminal Units
Electric Coils

Selection Guidelines

Price Silent Guard Coil Selection Chart – Maximum kW


In selecting electric coils, consider the FXC, FXCG, FXCGQ
following: Max – kW for Price Silent Guard Controller *Available with ECM motor option only.
1. Once the design air flow has been 1 Phase Voltage 3 Phase Voltage
determined and the model type selected
Size 120 208 240 277 480 208 480 600
(either constant or variable volume) kW kW kW kW kW kW kW kW
refer to the appropriate fan performance
10 3.4 5.5 5.5 5.5 -- 5.5 8.3 --
curves and select the model size of unit
required to deliver the specified air flow. 20 3.4 6.2 7.2 8.3 -- 10.0 8.3 --
2. With the model size and air flow known, 30 3.4 6.2 7.2 8.3 -- 10.0 8.3 --
electric coil capacity can be calculated. 40 3.4 6.2 7.2 8.3 -- 10.0 8.3 --
Refer to the electric coil selection 50 3.4 6.2 7.2 8.3 -- 10.0 8.3 --
procedure for details.
60 3.4 6.2 7.2 8.3 -- 10.0 8.3 --
3. With the heating capacity (kW) of the unit
70 3.4 6.2 7.2 8.3 -- 10.0 8.3 --
TERMINAL UNITS

known, Select the Power supply voltage


based on maximum recommended kW,
FXV
referring to the coil selection chart.
Max – kW for Price Silent Guard Controller
4. Verify that minimum air flow
requirements of 70 cfm/kW [33L/s per 1 Phase Voltage 3 Phase Voltage
kw] are met, and that the discharge air
Size 120 208 240 277 480 208 480 600
temperature does not exceed 120 °F. kW kW kW kW kW kW kW kW
Refer to example.
20 3.4 6.2 7.2 8.3 -- 10.0 8.3 --
5. Select options.
30 3.4 6.2 7.2 8.3 -- 10.5 8.3 --
40 3.4 6.2 7.2 8.3 -- 10.5 8.3 --
50 3.4 6.2 7.2 8.3 -- 10.5 8.3 --
60 3.4 6.2 7.2 8.3 -- 10.5 8.3 --

FXCQ2
Max – kW for Price Silent Guard Controller
1 Phase Voltage 3 Phase Voltage

Size 120 208 240 277 480 208 480 600
kW kW kW kW kW kW kW kW
10 3.5 6.0 7.0 8.0 -- 10.5 -- --
12 3.5 6.0 7.0 8.0 -- 10.5 -- --
14 3.5 6.0 7.0 8.0 -- 10.5 -- --

F-484 All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.
© Copyright Price Industries Limited 2011.
Fan Powered Terminal Units
Electric Coils

Electric Coil Selection Chart

TERMINAL UNITS
How To Use the Chart
Electric Coil Selection Procedure 4. With the point of intersection from 3, 5. Leaving air temperature ‑ 68° + 38.5° =
The selection of an electric coil for a the air temperature rise (ATR), can be 106.5 °F. Since the leaving air temperature
fan powered terminal unit requires the obtained by interpolating between the is less than the recommended maximum
determination of the two components of air temperature n/se lines on the graph. limit of 120 °F, the selection is satisfactory.
the heat loss. One component is the heat 5. To verify the selection, sum the air 6. Select a suitable power supply from
required to satisfy the space load.The second temperature rise and the temperature Table 3.
component is the heat required to raise the of the recirculated plenum air. The sum
temperature of the recirculated plenum air • For Model FPV, 18.3 kW, use
total should be less than 120 °F.
to that of the space. This can be determined 480v/3Ø/4 wire or 600v/3Ø/3 wire.
as follows, using the Electric Coil Selection Example
7. Verify power supply connection from
Chart and the equation as given below. Select an electric coil for a Size 60 Model Table 2.
1. Locate the room heat loss on the MBH FPV, with a recirculating fan capacity of
1500 cfm. Space heat loss is estimated at • For Model FPV Size 480v/3Ø/4,
scale on the far left side of the chart. single point connection.
Convert to kW by moving horizontally to 56 MBH and space design temperature is 72
the right to the kW scale (1 kW = 3.413 °F. The temperature of recirculated plenum • For Model FPV, Size 600v/3Ø/3 dual
MBH). air is 68 °F. point connection 600 volts and 115
2. Calculate the kW required to heat 1. Space heat loss (56 MBH) = 16.4 kW volts.
the recirculated plenum air to room 2. Heat required to raise the temperature 8. Verify minimum air flow requirements
temperature using the following equation: of the recirculated plenum air. are met.
1500 cfm
kW = cfm x 1.08 x ∆T kW = 1500 x 1.08 x 4 = 1.9 kW = 82 cfm/kw
18.3 kW
3413 3413
3. Add the kW value obtained in step 2 3. Total heat required = 16.4 + 1.9 = 18.3 kW. • 82 cfm per kW is greater than 70 cfm
to the kW scale at the left side. Move 4. Air temperature rise (ATR) = 38.5 °F. per kW from Table 1 — a satisfactory
horizontally to the right to the point where selection.
the kW value and the air flow volume
intersect.

F-485
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.