Test Report Transformer Two-

Winding
Client Name / WO 6/13/2019 Job 1
Execution Date 6/13/2019 10:38:20 AM Reason of the Job Routine
Tested By roni, yovi, ade Location PLTU Ombilin
Approved By Halwan MN Asset Transformer
Report ID 1 Asset Type Two-Winding
Report Issue Date 6/13/2019 11:38:26 AM Asset Serialnumber 80 MVA
Manufacturer

Summary

Test Overview
Performed Tests Assessment

Winding DF & CAP None

Tested By: Approved By:

1
Location & Company Information
Location Company
Name PLTU Ombilin Company PT. PLN (Persero)
Region Talawi Department Sektor Ombilin
Division Pemeliharaan Address Jalan Prof. M. Yamin SH.talawi
Area Sawahlunto City Sawah Lunto
Plant PLTU Ombilin State/Province Sumbar
Address Jl. Prof. Dr. M. Yamin SH Postal Code 27446
City Talawi-Sawahlunto Country Indonesia
State/Province Sumatera Barat Phone No. 0754410351
Postal Code 27446 E-Mail
Country Indonesia

Geo Coordinates

Contact Person
Name
Phone No. 1
Phone No. 2
E-Mail

Transformer nameplate data


Serial Number 80 MVA ApparatusId
Manufacturer No. Phases 3
Manufacturing Year Vector group YNd1
Manufacturer Type

Voltage ratings
Winding Voltage L-L (kV) Voltage L-N (kV) Insul. Level L-L (kV)
Prim 158.650 kV 91.597 kV kV
Sec 110.000 kV kV kV

Power ratings
Rated Power Cooling Class Temp. Rise. Wind
80 MVA OFAF K

Current ratings
Winding
Primary 291.000 A A A A A A
Secondary 4200.000 A A A A A A

Max. short-circuit current kA

Impedances
Ref. Temp. 75 °C

2
Impedances
Description Zk[%] Base Power Base Voltage Load Losses Pk OLTC Position DETC Positio
Primary - Secondary % VA V W
Primary - Secondary % VA V W
Primary - Secondary % VA V W
Primary - Secondary % VA V W
Primary - Secondary % VA V W

Zero sequence impedance


Base Power 80.00 MVA
Base Voltage 158.650 kV
Description Z0[%]
Primary %

Others
Tank Type n/a
Insulation Medium
Fluid insulation volume l
Fluid insulation weight kg
Total weight kg

Bushings nameplate data

Pos. Serial No. Manufact. Manufacturer Type Man. Year Voltage L-Ground Max. System Voltage Rated Current
A kV kV A
B kV kV A
C kV kV A
N kV kV A
a1 kV kV A
b1 kV kV A
c1 kV kV A

Pos. Insul. Level LL Cap. (C1) DF(C1) Cap. (C2) DF(C2) Insulation type Tap Type
A V pF % pF %
B V pF % pF %
C V pF % pF %
N V pF % pF %
a1 V pF % pF %
b1 V pF % pF %
c1 V pF % pF %

Test Set Information


Test Set Model CPC100
Test Set Serial Number NC421T
Calibration Date 07/18/2012 13:34:03

3
Global Test Conditions
Weather Clear Humidity %
Unit Location Outside Ambient temperature °C
Counter Reading Found
Counter Reading Left

Winding DF & CAP


Top Oil Temperature °C Weather Clear
Ambient temperature °C Correction Temp. °C
Humidity %

Comments

Condensed Table

Corr. Factor (K) 1


Block 1: Injection at Prim
No. Measurement Test mod Freq. V Out I Out Watt Losses Cap. meas. DF meas. DF corr. Assessment
1 ICH+ICHL GST 50.00 Hz 10.00 kV 25.39 mA 1538.51 mW 8076.1 pF 0.6060 % 0.6060 % None
2a ICH GSTg-A 50.00 Hz 10.04 kV 12.74 mA 1339.06 mW 2559.2 pF 1.0469 % 1.0469 % None
3a ICHL UST-A 50.00 Hz 10.00 kV 18.11 mA 784.45 mW 5762.0 pF 0.4332 % 0.4332 % None
Block 2: Injection at Sec
No. Measurement Test mod Freq. V Out I Out Watt Losses Cap. meas. DF meas. DF corr. Assessment
4 ICL+ICLH GST 50.00 Hz 10.00 kV 60.75 mA 3163.46 mW 19328.1 pF 0.5207 % 0.5207 % None
5a ICL GSTg-A 50.00 Hz 10.00 kV 42.64 mA 2379.02 mW 13566.0 pF 0.5579 % 0.5579 % None
6a ICLH UST-A 50.00 Hz 10.00 kV 18.10 mA 783.23 mW 5761.7 pF 0.4327 % 0.4327 % None

4