Sunteți pe pagina 1din 12

O/G FEEDER (03-06-2019) Page 1

Properties
Customer : TSTRANSCO
Project : TESTING
Switchboard : 33KV
Cubicle :
Print date : 07-06-19
O/G FEEDER (03-06-2019) Page 2

Sepam hardware configuration


Type of application : Substation (S24)
Sepam Type : O/G FEEDER
Sepam model : UD model (with fixed advanced UMI)
MES (Input / output module) : MES114 (10I + 4O module)
MSA141 (1 analog output module) : Absent
DSM303 (Remote advanced UMI module) : Absent
Interface de communication : ACE 969-TP
Synchronization mode : Network

Communication configuration S-LAN port


Communication protocol : MODBUS
Sepam address : 1
Speed : 19200 Bauds
Parity : Even

MODBUS Protocol parameters


Remote Control Mode : Direct

Communication configuration E-LAN port


Sepam address : 1
Speed : 38400 Bauds
Parity : Odd
O/G FEEDER (03-06-2019) Page 3

Program logic
Circuit breaker control : Yes
Logic discrimination : No
Protections excluded from CB control :
50/51 - 1A : No
50/51 - 1B : Yes
50/51 - 2A : No
50/51 - 2B : Yes
50N/51N - 1A : No
50N/51N - 1B : Yes
50N/51N - 2A : No
50N/51N - 2B : Yes
46 : No

Use of logic inputs


I11 : Open position
I12 : Closed position
I13 : Customized use
I14 : Customized use
I21 : Customized use
I22 : Customized use
I23 : Customized use
I24 : Customized use
I25 : Customized use
I26 : Customized use

Set up outputs
Used Shunt coil Undervoltage coil Impulsed mode
O1 Yes X
O2 Yes X
O3 Yes X
O4 Yes X
O11 Yes X
O12 Yes X
O13 Yes X
O14 Yes X
O/G FEEDER (03-06-2019) Page 4

Cold Load Pick-Up


Activation threshold : 10 % In
Delay before activation (Tcold) : 15 s

Cold Load Pick-Up 50/51


Factor type : Blocking

On Delay Current threshold 50/51


Group A
Unit 1 3 s 200 A
Unit 2 3 s 600 A
Group B
Unit 1 3 s 1260 A
Unit 2 3 s 1260 A

Cold Load Pick-Up 50N/51N


Factor type : Blocking

On Delay Current threshold 50N/51N


Group A
Unit 1 3 s 40 A
Unit 2 3 s 200 A
Group B
Unit 1 3 s 630 A
Unit 2 3 s 630 A
O/G FEEDER (03-06-2019) Page 5

General characteristics
Network frequency : 50 Hz
Setting group : A
Remote setting enabled : Yes
Sepam working language : English
Sepam date and time : 03-06-19 - 14:36:55
CT rating : TC 1A
Number of CTs : I1, I2, I3
Rated current (In) : 200 A
Base current (Ib) : 120 A
Integration period : 5 mn
Residual current : 3I sum
Rated residual current (In0) : 200 A
Number of periods which are memorised before the fault recording trigger : 36 Periods
O/G FEEDER (03-06-2019) Page 6

Protection: Phase overcurrent (50/51)


Element number : 1
Element activity : On

Setting group A
Tripping curve : IEC SIT /A
Threshold current : 200 A
Delay : 120 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : No
Icc current : 6300 A

Setting group B
Tripping curve : Definite time
Threshold current : 1260 A
Delay : 300 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : No
Icc current : 6300 A

Tripping behavior
Output O1 - Type : Shunt coil
Output O1 - Mode: Continuous
Latching : Yes
Activate output O1 : Yes
Trigger fault recording : With
Activate indicators : L1, L9
O/G FEEDER (03-06-2019) Page 7

Protection: Phase overcurrent (50/51)


Element number : 2
Element activity : On

Setting group A
Tripping curve : Definite time
Threshold current : 600 A
Delay : 0 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : No
Icc current : 6300 A

Setting group B
Tripping curve : Definite time
Threshold current : 1260 A
Delay : 300 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : No
Icc current : 6300 A

Tripping behavior
Output O1 - Type : Shunt coil
Output O1 - Mode: Continuous
Latching : Yes
Activate output O1 : Yes
Trigger fault recording : With
Activate indicators : L2, L9
O/G FEEDER (03-06-2019) Page 8

Protection: Earth fault (50N/51N)


Element number : 1
Element activity : On

Setting group A
Tripping curve : IEC SIT /A
Threshold current : 40 A
Delay : 120 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : No

Setting group B
Tripping curve : Definite time
Threshold current : 630 A
Delay : 300 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : No

Tripping behavior
Output O1 - Type : Shunt coil
Output O1 - Mode: Continuous
Latching : Yes
Activate output O1 : Yes
Trigger fault recording : With
Activate indicators : L3, L9
O/G FEEDER (03-06-2019) Page 9

Protection: Earth fault (50N/51N)


Element number : 2
Element activity : On

Setting group A
Tripping curve : Definite time
Threshold current : 200 A
Delay : 0 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : No

Setting group B
Tripping curve : Definite time
Threshold current : 630 A
Delay : 300 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : No

Tripping behavior
Output O1 - Type : Shunt coil
Output O1 - Mode: Continuous
Latching : Yes
Activate output O1 : Yes
Trigger fault recording : With
Activate indicators : L4, L9
O/G FEEDER (03-06-2019) Page 10

Protection: Breaker failure (50BF)


Element activity : Off
Threshold current : 40 A
Delay : 200 ms
Use closed breaker position : No
Activated by :
50/51 - 1A : Yes
50/51 - 1B : No
50/51 - 2A : Yes
50/51 - 2B : No
50N/51N - 1A : Yes
50N/51N - 1B : No
50N/51N - 2A : Yes
50N/51N - 2B : No
46 : Yes
External tripping 5 : No

Tripping behavior
Output O1 - Type : Shunt coil
Output O1 - Mode: Continuous
Latching : Yes
Activate output O1 : Yes
Trigger fault recording : Without
Activate indicators : L9
O/G FEEDER (03-06-2019) Page 11

Protection: Negative sequence current / unbalance (46)


Element activity : Off

Setting group
Tripping curve : Definite time
Threshold current : 10 % of Ib
Delay : 300 ms

Tripping behavior
Output O1 - Type : Shunt coil
Output O1 - Mode: Continuous
Latching : Yes
Activate output O1 : Yes
Trigger fault recording : With
Activate indicators : L9
O/G FEEDER (03-06-2019) Page 12

Protection: Recloser (79)


Element activity : Off
Number of reclosing cycles : 4
Inhibition by input I26 : No

Activation of reclosing cycles


Protection Cycle 1 Cycle 2, 3 and 4
50/51 - 1 Inactive Inactive
50/51 - 2 Inactive Inactive
50N/51N - 1 Inactive Inactive
50N/51N - 2 Inactive Inactive

Disengaging time delay : 5000 ms


Inhibition time delay : 1000 ms
Isolation time delay for cycle 1 : 1000 ms
Isolation time delay for cycle 2 : 1000 ms
Isolation time delay for cycle 3 : 1000 ms
Isolation time delay for cycle 4 : 1000 ms