The miniature circuit breaker S 200 M UC Standards
General Data
Standards IEC/EN 60898-2, IEC/EN 60947-2, UL1077, CSA 22.2 No. 235
Poles 1P, 2P, 3P, 4P
Rated current In 0.2 - 63 A
Rated frequency f 0/50/60 Hz
Rated insulation voltage Ui 253 V AC (phase to ground), 440 V AC (phase to phase)
Overvoltage category III
Pollution degree 2
IEC/EN 60898-2
Tripping characteristics B, C
Rated operational voltage Un 1P: 230 V AC, 220 V DC
2P: 400 V AC, 440 V DC
3...4P: 400 V AC*
Max. power frequency recovery voltage Umax 1P: 253 V AC, 250 V DC
2P: 440 V AC, 500 V DC
3...4P: 440 V AC*
Min. operating voltage 12 V AC – 12 V DC
Rated short-circuit capacity Icn 10 kA
Energy limiting class (B, C up to 40A) 3
Rated impulse withstand voltage Uimp (1.2/50µs) 4 kV (test voltage 6.2 kV at sea level; 5 kV at 2,000 m)
Dielectric test voltage 2.0 kV (50/60 Hz, 1 min)
Reference temperature for tripping characteristics 30 °C
Electrical endurance In ≤ 25 A: 20,000 ops. (AC), In > 25 A: 10,000 ops. (AC); 1,000 ops. (DC)
IEC/EN 60947-2
Tripping characteristics B, C, K, Z
Rated operational voltage Ue 1P: 253 V AC, 220 V DC
2...4P: 440 V AC, 440 V DC
Max. power frequency recovery voltage Umax 1P: 266 V AC, 250 V DC
2...4P: 462 V AC, 500 V DC
Min. operating voltage 12 V AC – 12 V DC
Rated ultimate short-circuit breaking capacity Icu ≤40 A: 10 kA (AC); 10 kA (DC)
>40 A: 6 kA (AC); 10 kA (DC)
Rated service short-circuit breaking capacity Ics ≤40 A: 7.5 kA (AC); 10 kA (DC)
>40 A: 6 kA (AC); 10 kA (DC)
Rated impulse withstand voltage Uimp (1.2/50µs) 4 kV (test voltage 6.2 kV at sea level; 5 kV at 2,000 m)
Dielectric test voltage 2.0 kV (50/60 Hz, 1 min)
Reference temperature for tripping characteristics B, C 55 °C
K, Z 20 °C
Electrical endurance In ≤ 25 A: 20,000 ops. (AC), In > 25 A: 10,000 ops. (AC); 1,500 ops. (DC)
UL 1077/CSA 22.2 No. 235
Tripping characteristics C, K, Z
Rated voltage 1P: 277 V AC, 250 V DC
2...4P: 480Y/277 V AC, 500 V DC
Rated interrupting capacity 6 kA (AC); 10 kA (DC)
Application Supplemental protection, for general use. TC1, OL0, SC:U1
Reference temperature for tripping characteristics 25 °C
Electrical endurance 6,000 ops., 1 cycle (1s.-ON, 9s.-OFF)
Mechanical data
Housing Insulation group I, RAL 7035
Toggle Insulation group II, black, sealable
Contact position indication Real CPI (green OFF/red ON)
Protection degree acc. to DIN EN 60529 IP20, IP40 in enclosure with cover
Mechanical endurance 20,000 ops.
Shock resistance acc. to IEC/EN 60068-2-27 25 g - 2 shocks - 13 ms
Vibration resistance acc. to IEC/EN 60068-2-6 5 g - 20 cycles at 5 ... 150 ... 5 Hz at 0.8 In
Environmental conditions (damp heat cyclic) 28 cycles with 55 °C/90-96 % and 25 °C/95-100 %
acc. to IEC/EN 60068-2-30
Ambient temperature -25 ... +55 °C
Storage temperature -40 ... +70 °C
Installation
Terminal Fail-safe bi-directional cylinder-lift terminal
Cross-section of conductors (top/bottom) Solid, stranded: 35 mm² / 35 mm²
flexible: 25 mm2 / 25 mm2
14 – 4 AWG (Cu only)
Cross-section of busbars (top/bottom) 10 mm² / 10 mm²
14 – 8 AWG
Torque IEC 2.8 Nm
UL 18 in-Ibs.
Screwdriver No. 2 Pozidriv
Mounting On DIN rail 35 mm, acc. to EN 60715 by fast clip
Mounting position Any
Supply Please note polarity of device
Dimensions and weight
Mounting dimensions acc. to DIN 43880 1
Pole dimensions (H x D x W) 85 x 69 x 17.5
Pole weight Approx. 125 g
Combination with auxiliary elements
Auxiliary contact Yes
Signal contact Yes
Shunt trip Yes
Undervoltage release Yes
Motor operating device Yes
B characteristic C characteristic
2CDC022015F0214
2CDC022017F0214
K characteristic Z characteristic
2CDC022060F0211
2CDC022010F0211
Accessory* overview
2CDC092026F0214
H Auxiliary contact S2C-H6R ST-L Shunt trip to be mounted on the left S2C-A...L
H-R Auxiliary contact S2C-H6-...R H-L Auxiliary contact to be mounted on the left S2C-H...L
S/H Signal/Auxiliary contact S2C-S/H6R H-BF Auxiliary contact for bottom fitting
Dimensional drawing
2CDC022007F0010
S 200 M UC MCBs can be used in the one-pole version at 220 For DC incoming supply from above
V DC, and in the 2-pole or 4-pole version with series connection S 200 M UC MCBs have permanent magnets in the area of
of two poles up to 440 V DC. arc chutes. Therefore, it is necessary to take into account
the polarity during the installation process. In the case of a
S 200 M UC differs from the standard S 200 type. It is short circuit, the magnetic field of the permanent magnets
fitted with permanent magnets, which assists in the forced corresponds with the electromagnetic field of the short-circuit
extinguishing of the arc. current. Therefore, safely leading the short circuit into the arc
chute. Incorrect polarities may cause damage to the MCB.
If voltages to ground exceeding 220 V DC occur, 2-pole This is why in the case of top-fed devices terminal 1 must be
S 200 M UC should be used for one-pole disconnection and connected to (-) and terminal 3 to (+).
four-pole S 200 M UC for all-pole disconnection.
Example for permissible voltages between the conductors depending on the number of poles and circuit layout:
Voltage between conductors Un 220 V– 440 V– 440 V– 440 V– 440 V– (voltage reversal)
Voltage between conductor and 220 V– 220 V– 440 V– 220 V– 220 V–
earth Un
MCB 1-pole 2-pole 2-pole 2-pole 4-pole
S 201 M UC S 202 M UC S 202 M UC S 202 M UC S 204 M UC
SK 0114 Z 94
Supply from above
SK 0115 Z 94
Example for permissible voltages between the conductors depending on the number of poles and circuit layout:
Voltage between conductors 440 V– 440 V– 440 V–
Un all-pole disconnection 1-pole disconnection all-pole disconnection
Voltage between conductor and 220 V– 220 V– 220 V– circuit unearthed or
earth Un circuit symmetrically earthed unsymmetrically earthed unsymmetrically earthed
MCB 2-pole 2-pole 4-pole
S 202 M UC S 202 M UC S 204 M UC
1 in the circuit diagram, the negative pole is earthed. 2 in the circuit diagram, the positive pole is earthed.
Miniature Circuit Breaker S 200 M UC | 1SXU400144L0201 7
Miniature Circuit Breaker S 200 M UC
Ordering data characteristic B
Number Rated Type Part number Order code bbn/ Packing Weight
of poles current for US and EAN 401361 unit per PCE
In Canada PCE kg
A
1 6 S201M-B6UC S201MUC-B6 2CDS271061R0065 4430596 10 0.125
10 S201M-B10UC S201MUC-B10 2CDS271061R0105 4430602 10 0.125
13 S201M-B13UC S201MUC-B13 2CDS271061R0135 4430619 10 0.125
2CDC021031S0011
Number Rated Type Part number Order code bbn/ Packing Weight
of poles current for US and EAN 401361 unit PCE per PCE
In Canada kg
A
1 0.5 S201M-C0.5UC S201MUC-C0.5 2CDS271061R0984 4430695 10 0.125
1 S201M-C1UC S201MUC-C1 2CDS271061R0014 4430701 10 0.125
1.6 S201M-C1.6UC S201MUC-C1.6 2CDS271061R0974 4430718 10 0.125
2CDC021031S0011
Number Rated Type Part number Order code bbn/ Packing Weight
of poles current for US and EAN 401361 unit per PCE
In Canada PCE kg
A
3 0.5 S203M-C0.5UC S203MUC-C0.5 2CDS273061R0984 4435133 1 0.375
1 S203M-C1UC S203MUC-C1 2CDS273061R0014 4435140 1 0.375
1.6 S203M-C1.6UC S203MUC-C1.6 2CDS273061R0974 4435157 1 0.375
2CDC021034S0011
Number Rated Type Part number Order code bbn/ Packing Weight
of poles current for US and EAN 401361 unit per PCE
In Canada PCE kg
A
1 0.2 S201M-K0.2UC S201MUC-K0.2 2CDS271061R0087 4430862 10 0.125
0.3 S201M-K0.3UC S201MUC-K0.3 2CDS271061R0117 4430879 10 0.125
0.5 S201M-K0.5UC S201MUC-K0.5 2CDS271061R0157 4430886 10 0.125
2CDC021022S0012
Number Rated Type Part number Order code bbn/ Packing Weight
of poles current for US and EAN 401361 unit per PCE
In Canada PCE kg
A
3 0.2 S203M-K0.2UC S203MUC-K0.2 2CDS273061R0087 4435300 1 0.375
0.3 S203M-K0.3UC S203MUC-K0.3 2CDS273061R0117 4435317 1 0.375
0.5 S203M-K0.5UC S203MUC-K0.5 2CDS273061R0157 4435324 1 0.375
0.75 S203M-K0.75UC 2CDS273061R0187 4435331 1 0.375
2CDC021028S0012
Number Rated Type Part number Order code bbn/ Packing Weight
of poles current for US and EAN 401361 unit per PCE
In Canada PCE kg
A
1 0.5 S201M-Z0.5UC S201MUC-Z0.5 2CDS271061R0158 4431111 10 0.125
1 S201M-Z1UC S201MUC-Z1 2CDS271061R0218 4431128 10 0.125
1.6 S201M-Z1.6UC S201MUC-Z1.6 2CDS271061R0258 4431135 10 0.125
2CDC021022S0012
Number Rated Type Part number Order code bbn/ Packing Weight
of poles current for US and EAN 401361 unit per PCE
In Canada PCE kg
A
3 0.5 S203M-Z0.5UC S203MUC-Z0.5 2CDS273061R0158 4435553 1 0.375
1 S203M-Z1UC S203MUC-Z1 2CDS273061R0218 4435560 1 0.375
1.6 S203M-Z1.6UC S203MUC-Z1.6 2CDS273061R0258 4435577 1 0.375
2CDC021028S0012
ABB