Electrical System
• Basements
BASIS OF DESIGN
TOTAL I5,767.89
POWER DISTRIBUTION
• RECEIPT OF POWER AT 33 KV
• AVR AT 33 KV LEVEL
• ESS 1 – IN BASEMENT
• ESS 2 – IN BASEMENT
• CSS – FOR RESIDENTIAL 1 – ON GROUND
BACK UP POWER GENERATION
CPCB Norms.
Electrical System
BLOCK DIAGRAM
MAIN SUBSTATION 33/11 KV
Electrical System
SUBSTATION PARAMETERS (ESS -1)
Parameter Requirement
A Incoming Voltage 11 KV
A Step Down Voltage 433 KV
A Approving Authority Chief Electrical Inspectorate, Govt. of Haryana
► 1ST Basement away from the building foot print on Solid Ground
► Close to Ramp
► At periphery of the Basement
A Location of sub station ► Clear Height 3.6 meters soffit of beam
► Fire Rating shall be 4 Hrs
► Fire Rating for Doors shall be 4 Hrs
► Locating of LT switchboard proposed at 1st Basement near substation
TRANSFORMER RATING
A 11KV/433 V Substation 1 This Substation comprises Office 1, Office 2, Residential 2 and Residential 3
1600 KVA
spaces (assumed)
A Total KVA (Less Load for Central Chillers) 7380 KVA
► 3% of the Load shall be provided with Solar Lighting as per the Order.
► 450 kW Solar Lighting provisions shall be made accordingly.
► Area of approx. 6000 sq.mt shall be required.
Electrical System
FIRE DETECTION SYSTEM (RESIDENTIAL BUILDING)
The National Building Code stipulates 2005 the following code for provision of Fire
Detection system for residential Building
Block A&B are less than 60 m however One Some/Heat detector in each
Electrical System
Fire Alarm System shall be augmented by Public Address System with Talk Back
Unit
SECURITY SYSTEM