SEMINAR ON POWER DISTRIBUTION OF A COMMERCIAL BUILDING

COMMERCIAL COM-11, GURGAON, HARYANA

ELECTRICAL & COMMUNICATION SYSTEMS

Al-Falah School of Engineering & Technology,


Dhauj, Faridabad, Haryana, (India)
COMMERCIAL COM-11 SHIVAM

• Commercial (Office 1)

• Commercial (Office 2)

• Residential 1

• Residential 2

• Residential 3
Electrical System

• Commercial (Office 3) - Phase II

• Basements
BASIS OF DESIGN

Electrical Supply Authority Dakshin Haryana Bijlee Vitaran Nigam Ltd


(DHBVNL)

Chief Electrical Inspector to the Govt. of


Approving Authority
Haryana.

• Bulk supply from DHBVNL Direct billing


Electrical System

by Vatika to each Consumer


Billing
• Vatika Shall be responsible for payment
of Energy charges to DHBVNL
DHBVNL NORMS FOR POWER SUPPLY

• Supply at Voltage level of 33 kV for Loads less than 25 MVA

• Load calculation as per DHBVNL Norms


Electrical System

• Separate 33kV connections for Each of the Two Land


Parcels.
ELECTRICAL LOAD
Electrical Load Total Load
Area
Description (Commercial)
Diversity
Sq. mt @ 21 kW/100 Sq. mt In kW

Commercial (Office 1) Block D 39,282.7 8,249.37 60% 4,949.62

Commercial (Office 2) Block E 10,203 2,142.63 60% 1,285.58

Residential 1 (Block A) 6,211.22 1,304.36 60% 782.61

Residential 2 (Block B) with Club 2,521.56 529.53 60% 317.72


Electrical System

Residential 3 (Block C) with Retail 12,142.21 2,549.86 60% 1,529.92

Commercial (Office 3) Phase II 54,781.32 11,504.08 60% 6,902.45

TOTAL I5,767.89
POWER DISTRIBUTION

• RECEIPT OF POWER AT 33 KV

• MAIN SUBSTATION 33/11 KV

• AVR AT 33 KV LEVEL

• 11 KV FEED TO LOCAL SUBSTATION IN THE COMPLEX & CHILLERS AT


ENERGY CENTER
Electrical System

• ESS 1 – IN BASEMENT
• ESS 2 – IN BASEMENT
• CSS – FOR RESIDENTIAL 1 – ON GROUND
BACK UP POWER GENERATION

 100% Power Backup shall be provided

 Load shall be as per Design Calculations (9W per sq. ft)

 11 KV DG Sets Proposed at Service Yard

 DG Sets shall be Radiator Cooled

 DG Exhaust pipes to be routed 6 m above the tallest building as per


Electrical System

CPCB Norms.
Electrical System

BLOCK DIAGRAM
MAIN SUBSTATION 33/11 KV
Electrical System
SUBSTATION PARAMETERS (ESS -1)
Parameter Requirement
A Incoming Voltage 11 KV
A Step Down Voltage 433 KV
A Approving Authority Chief Electrical Inspectorate, Govt. of Haryana

► 1ST Basement away from the building foot print on Solid Ground
► Close to Ramp
► At periphery of the Basement
A Location of sub station ► Clear Height 3.6 meters soffit of beam
► Fire Rating shall be 4 Hrs
► Fire Rating for Doors shall be 4 Hrs
► Locating of LT switchboard proposed at 1st Basement near substation
TRANSFORMER RATING
A 11KV/433 V Substation 1 This Substation comprises Office 1, Office 2, Residential 2 and Residential 3

A Total Load in KVA 8980 KVA


A Less of Chiller @ 0.75 KVA per 250 Sq. ft of office
Electrical System

1600 KVA
spaces (assumed)
A Total KVA (Less Load for Central Chillers) 7380 KVA

A Recommended Installed Capacity at 80% loading 9225 KVA


A Rating KVA 2250 KVA
A Number of transformers with standby 5 x 2250 KVA
A Percentage load met in case of failure of one
100%
transformer
SOLAR LIGHTING

Solar Lighting shall be provided as per Haryana Government


Renewable Energy Department Order dated 3rd September 2014.

► 3% of the Load shall be provided with Solar Lighting as per the Order.
► 450 kW Solar Lighting provisions shall be made accordingly.
► Area of approx. 6000 sq.mt shall be required.
Electrical System
FIRE DETECTION SYSTEM (RESIDENTIAL BUILDING)

The National Building Code stipulates 2005 the following code for provision of Fire
Detection system for residential Building

• Less than 15 m in height No requirement


• 15 m to 60 m height Manually operated fire alarm
• 60 m and above Automatic Fire detection & Alarm system.

 Automatic Fire Detection should be provided in Block C

 Block A&B are less than 60 m however One Some/Heat detector in each
Electrical System

apartment shall be provided

 Fire Alarm System shall be augmented by Public Address System with Talk Back
Unit
SECURITY SYSTEM

Closed Circuit TV surveillance shall be provided with cameras to cover the


following areas

► Lift Lobby /Escalator Lobby at each floor

► Service Lift Lobbies at all floors

► Ground Floor entrance

► Basement Parking & Entry Ramp


Electrical System

► External car Parking areas

This may be considered by the Owner and specific requirements intimated.