Sunteți pe pagina 1din 101

1.

Main program’s menu:


- Introduction/Program overview
After the software installation, the main program file (LSPS.exe) is created, and its icon is as shown
in Fig. 1-1.

[Fig. 1-1] Icon of LSPS


By running the LSPS.exe, a window comprising of three different modules, i.e. Susol Design, Susol
T-C Curve and Susol Coordination, is appeared as shown in Fig. 1-2. User can choose any module
for execution.

[Fig. 1-2] Main window of the LSPS program

① Susol Design module: Susol Design module is the most important among the three. Users can
design LV/HV system diagram and analyze short circuit currents related to balance/imbalance/one-
phase circuit. From the analysis, LV/HV circuit breaker (CB) will be selected. By using this module
users can design a real system. The main functions of Susol Design module includes:
- Short circuit analysis (according to IEC 60909)
- Automatic selection of CBs
- LV coordination including discrimination and cascading
② Susol T-C Curve module: Users can confirm the T-C curve of equipments including CBs, fuses,
motors, transformers and relays. Users can also check protection coordination among equipments.
Users can directly insert the rated current and the short circuit current to new devices. Based on this
function, users can analyze protection coordination and compare with the existing devices. Thanks to
adjustable parameters of devices, users can observe the current deviations in time domain.

③ Susol Coordination module: Users can directly use this module to select the upstream (LV/HV)
CB without using the other two modules. Users can choose the CB from a given list of CB, thereafter
a list of proper CBs for downstream side will be appeared. Users can choose one of those CBs for
coordination between upstream and downstream. Users can confirm the T-C curve of the selected CB
in Susol Coordination domain.

- Susol Design Module:


The main window of Susol Design module is as shown in Fig. 1-3.
[Fig. 1-3] Main window of the Susol Design module

1) Susol Design’s main menu:


The main menu consists of File, Edit, View, Analysis, Properties, and Help as shown in Fig. 1-4.

[Fig. 1-4] Susol Design’s main menu


Ø File

Ø Edit
Comprising of Undo, Redo, Cut, Copy, Paste, Delete, Find, Vertical Rotation, Horizontal
Rotation and Grid State.

Ø View

]
Comprising of Tool Bar, Status Bar, Project Manager, Control Manager, Zoom In/Out, and
Move.
Ø Analysis

Drawing is a step of system diagram/data input. SC calculation, CB auto selection, and CB


coordination are most important technical calculation steps.
Ø Properties

• Master File Editor (Main parameters setting): Users can define fundamental values of system
structure and set rated capacity(KVA), reference frequency(Hz), and short circuit
impedance(Ω), etc. The default values for rated capacity, reference frequency, and short circuit
impedance are 100MVA, 60Hz, and 0Ω, respectively.
• Grid Size Scaling: The default display is grid style. The default grid size is 70(width) X
70(vertical) and users can regulate the grid size if needed.
• DB Manager: An initial Database (DB) is included in the program. Users can add new data
to the DB. Only the new data can be edited.
• Characteristics Value (Info. display): This is to display/hide the detailed information of all
components in displayed diagram.
• Language: This is to choose the displayed language. The new language will be applied after
restating the program.
Ø Help

• Contents: detailed user-manual


• About LS Power Solution: information of the software and copyright.
2) Basic Toolbar

3) Executed Function Toolbar:


This toolbar is as shown in following figure. Detailed explanation of each function will be presented
in following sections.

4) Edit Toolbar
5) Properties Toolbar

6) Icon toolbar of system components

Comprising all kinds of components of the system.


Icons Components
Source Generator, Equivalent Source
Circuit Breaker LV/HV CB, Relay, Fuse
Transformer 3-phase transformer, 1-phase transformer
Cable 3-phase cable, 1-phase cable
Busbar Τ/П type
Load Motor, static load

If users click the symbol “…” in the left-up toolbar, the toolbar will change to horizontal display as
shown in the following figure.

7) Zoom In/Out and Status Display


Users can find the zoom in/out ratio in the right-lower corner of the Susol Design window. Users can
also see the current status (Drawing, Short circuit analysis, CB selection, Coordination) at the left
lower.
8) Project Display

LSPS can make multiple projects. The project display function shows all of the being opened
projects. For example, the above figure shows that three projects, i.e. Project 1, Project 2 and Project
3, are being opened. Users can choose any project in the list of projects for activating.
9) Navigator Display

This function shows the whole system diagram. Users can quickly move to specific point of the
system using this function. The left figure shows the initial status without any system, and the right
shows the being run system.

10) Tree-Bar component


This component lists all devices in the designed system. Users can open the component’s properties
window by double click to the device caption.
11) Drawing Display Window
The system can be designed on the Drawing display window. The current position of
cursor is shown as in the figure with symbols “┏ ┑┗ ┛”. New component is created
at the current cursor.
2. Create a system diagram
Users can draw a system diagram using the component toolbar (icon toolbar). When users click the
system component, the corresponding component will be made on the cursor point “┏ ┑┗ ┛” in the
drawing window as depicted in Fig. 2-1 and Fig. 2-2. As the component is created it is expressed in
the tree-bar on the left side of window. LSPS can make multiple projects. The project display
function shows all of the being opened projects. Users can choose any project in the list of projects
for activating.

[Fig. 2-1] Before System Diagram Drawing

[Fig. 2-2] After System Diagram Drawing

1) Change the Size of Components


It is necessary to change the size of some components. Components include busbar and three- and
one-phase cables.
Ø Change the size of the horizontal-busbar
In order to change the size of horizontal busbar, users select the busbar, it’s color will change
to the red as in Fig. 2-5. The squares of the both end sides are symbolized as the size
changeable points and the arrow (“┏ ┑┗ ┛”) appears when users click the point. Users can
change the size of busbar by keeping the left mouse and moving the point.

[Fig. 2-5] Size Change


Another component such as “П” form of busbar, “T” form of busbar, one-phase cable, and three-
phase cable can be changed using the same method.
2) Move a Single Component
Users select a target component as the red color component in Fig. 2-6.

[Fig. 2-6] Component Selection


The selected component can be moved by keeping the left mouse and moving. Users can also move
the component using the movement keys on the key board.

[Fig. 2-7] Component Moving and Finishing


3) Delete a Component
Ø There are two methods to delete a component. First method, users select a component,
indicated as red color, right mouse click and choose “Delete” option. Second method, users
select a component and press “Del” button on the keyboard.

[Fig. 2-8] Delete Method

4) Copy and Paste a Component


Ø Users can use two methods to copy a component, either using “Ctrl+C” keys on the keyboard or
right mouse click at the component and choose “Copy” option.
Ø Similar to copy function, in order to paste a component, users either press “Ctrl+V” buttons on
the keyboard or choose “Paste” option.
5) Group/Move/Copy/Paste Multiple Components
Ø Group multiple components: Users can choose multiple components using the mouse drag. The
selected components’ color become red as shown in Fig. 2-9.

[Fig. 2-9] Component Grouping


Ø Group Moving: In order to move a group, users can either move the mouse cursor to the target
position and click the left mouse or use the direction keys on the keyboard. Figure 2-10 shows
the group that is being moved to the target position.
[Fig 2-10] Component Shifting
Ø Group Copy/Paste: same as Copy/Paste of the single component.
6) Connect Components
Generator, equivalent source and Motor can be directly connected to the busbar without cables. There
are three methods to connect components with each other.
- Method 1: Move the mouse cursor to the connecting point of the existing component on drawing
window, and then select the component icon.

Move the mouse to the connected point before the connection.

In the above figure, the component is created at cursor when users click the cable icon on the icon-
toolbar.
- Method 2: Once the components are created in the drawing window, users can move one component
to the other for connecting.

The above figure show how the components can be connected with each other.
- Method 3: Change the length of busbar and cable.
The following figure show how the component size can be changed.

7) Rotate a Component
All components in LSPS can be rotated. Users can rotate the direction of components using the
rotation buttons as shown in Fig. 2-11. Components can be rotated 90 degrees.

[Fig. 2-11] Component Rotation Icon


In Fig. 2-11, the right icon is for horizontal rotation and the left one is for vertical rotation of the
component. Using these functions, users can make the system like Fig. 2-12.

[Fig. 2-12] System design with the rotation function

8) Design a Single-phase System


There are two cases of a single-phase system.
Ø Case 1: In order to connect a three-phase component to a single-phase component, users use the
single-phase busbar. Before connecting a single-phase component with a three-phase component,
users need to create a single-phase busbar at the connection point.
[Fig. 2-13] Connection of a single-phase cable with a three-phase cable

Ø Case 2: In order to connect single-phase components with each other, users can either connect
directly or use a single-phase busbar. If users want to use the single-phase busbar, first create a
three-phase busbar, and then, change the busbar’s properties to single-phase.

[Fig. 2-14] Single-phase Components Connection


After changing the busbar’s property to single-phase, a “1f” symbol will appear beside the busbar, as
depicted in following figures.

[Fig. 2-15] Change busbar’s property from three-phase to single-phase)


[Fig. 2-16] Connection of single-phase busbar with single-phase cable.

[Fig. 2-17] Direct Connection of the Single-phase Component


The single-phase components can connect with each other directly as shown in Fig. 2-17.
3. Input / Setting for Component Data
Refer to the following system (Fig. 3-1) for inputting / setting the component data for LS Power
Solution:

[Fig. 3-1] System Example for Data Input / Set


Input the following parameters on the drawing window after comprising the system (example). Such
data may be imported from DB or subject to the manual input. Make sure, however, to manually input
data for this case of example. Power Solution automatically updates the name and main parameters of
your component on the left and right side of the window, respectively, as you finish inputting data.
1) Activating Component Data Input
Double-click the desired object or run ‘Property’ on a right-click pop-up to activate a data input
window for your component of each system.
[Fig. 3-2] Double-click-and-activate

[Fig. 3-3] Right-click’n-choose-property


2) Setting ‘Master File’
Make sure to properly set the base capacity, base frequency, and fault resistance value of Master File
to run a scenario. User may also determine circuit breaker’s adjustability on a matter of temperature
or the applicability of MetaMEC to block one(s) used least. Default values of the base capacity and
base frequency have been set to be 100,000kVA (100MVA) and 60Hz, respectively, that may be
varied by User (Two options of 50Hz, 60Hz offered for base frequency). Fault resistance value is
subject to the User input as not defaulted, in the unit of ‘ohm’.
[Fig. 3-4] Master File Manager.

[Fig. 3-5] Temp. Adjustment for Circuit Breaker


Reflecting T-C curve effect by different temperature levels, the circuit breaker in a scenario may be
adjusted as User desires. If necessary, choose a proper ‘Under Spec’ option to best fit the condition of
circuit breaker as temperature varies.

3) Input / Setting for Utility Bus(P1)


[Fig. 3-6] Data Input / Setting for Utility Bus
Object name (Updated on the window as input), system voltage (Make sure not to omit as P1 is where
the system starts), 3-phase short circuit capacity, and X/R(+) (Ratio of R to Positive-phase-sequence
X Reactance) are all necessary for making P1 work. With this scheme, a positive-phase-sequence-
impedance will be regarded for fault calculating of P1 among short circuit capacity and the so called
X/R ratio.
Whenever available, User may input further information (as highlighted Orange below) including
short circuit capacities, ground current, as stated hereafter. Check the item to activate input.
Activate ‘Radio Button’ and check ‘% Impedance’, when known over short circuit capacity or X/R
ratio, to activate input (refer to Fig. 3-7). Check, as well, negative phase or 0-phase impedance when
known. Make sure to designate base capacity (kVA) and voltage (kV) for manual input of %
impedance.
[Fig. 3-7] % Impedance Setting for Utility Bus
System automatically sends an error message when the necessary field is empty or over-represented.
Such wrong input will not be saved as long as properly adjusted.

[Fig. 3-8] Error Pop-up over Improper Input

Determination of the Utility Bus impedance has been done in accordance with IEC Standard. Contact
the relevant institute, stated herein, for any question arising.

4) Input / Setting for Generator (G1)


Object name (Updated on the window as input), system voltage (Make sure not to omit as G1
generates for the system), generator capacity (in kVA), and impedance data (positive-subtransient
reactance X(+), positive reactance X(+), X/R ratio) are all in the list of the necessary input for G1.
User may further adjust grounding method (Non-grounding, direct-grounding, resistance-grounding,
defaulted to be direct-grounding pending user adjustment) and more as follows: .
[Fig. 3-9] Data Input / Setting for Generator
Beware the rated voltage and actual system voltage may not be square, deriving different impedance
value.

[Fig. 3-10] Different Voltage Indicating


Subtransient reactance of negative phase or neutral-phase, when known, may be subject to User’s
input. Empty value will be deemed square with that of positive phase.
[Fig. 3-10] Subtransient Reactance of Negative Phase / 0-phase
User may choose, without any given data, among numerous different generator data offered by Power
Solution. As contained generator data represent “most general value applicable”, beware it may not
be exact as User want to put in a scenario.

[Fig. 3-11] Generator DB List


Determination of the generator impedance has been done in accordance with IEC Standard. Contact
the relevant institute, stated herein, for any question arising.
5) Generator (G1) Simulation
Power Solution offers generator and circuit breaker simulation. Run / Stop your virtual generator
triggering ‘Radio Button’ (Defaulted as ‘Run’) on top of the input pop-up. For example, deletion of
CB6 from the system may deactivate any of system branched out of the generator, as the virtual
generator is set to be ‘Stop’. This offers a chance for User to run varied scenarios with a single file.

[Fig. 3-12] Virtual Generator Operation

[Fig. 3-13] Inactive System as Generator Stops


6) Input / Setting for Transformer (T1)
Data may be imported from the transformer DB or manually input.

[Fig. 3-14] Input / Setting for Transformer


From the Fig. above, object name, system voltage (kVA) connection type, secondary voltage, and %
impedance are all comprising the necessary input for T1. Make sure to manually input secondary
voltage as primary voltage is auto-defined as the software detects. Grounding reactance and
resistance may also be set by User, by different connection types. A manual input to one of four entire
text box is to re-adjust the rest of three % impedance values so that User does not need to (This may
also be adjusted by User). Note that the rated voltage and actual system voltage do not necessarily
need to be square with each other. Above these, User may further adjust as follows:

[Fig. 3-15] Voltage Differences


Make sure to apply the same for single-phase transformer as it offers almost the same with 3-phase
besides that there is no connection type variation.
Determination of the transformer impedance has been done in accordance with IEC Standard. Contact
the relevant institute, stated herein, for any question arising.
7) Input / Setting for Low Voltage Circuit Breaker (CB1)
Object name, rated voltage (in the unit of ‘A’), and rate of margin are all necessary input for CB1 as
stated in Fig. 3-16. User may further adjust on matters of the following: Protecting object, # of phase,
Circuit breaker type, Icu / Ics, etc.
[Fig. 3-16] Input / Setting for Low Voltage Circuit Breaker

User may choose among Cable / Motor / Trip Current (Defaulted as Cable) for protecting object as
desired. Power Solution may detect an optimal circuit breaker option for User’s selection of Motor /
Trip Current.
Rate of margin defines how much ‘margin’ User allows in auto-determination of a circuit breaker.
Combination of 100% margin rate and 10kA fault current will get Power Solution to auto-detect a
circuit breaker properly getting rid of 10kA fault current, whereas 150% margin rate for the same
option shall detect the one good enough for 15kA fault current, 150% of 10kA. The following figures
each suppose margin rate of 100% and 150%, as fault current nears 12kA and 18kA, respectively.
Fault current. Note that the divergent result came from the application of the sheer different margin
rates.
[Fig. 3-17] Margin Rate Variation for CB1
8) Low Voltage Circuit Breaker (CB1) Simulation
Power Solution offers generator and circuit breaker simulation. User may choose among Close / Open
triggering ‘Radio Button’ (Defaulted as Close) on mid-left side of the window.
For example, any system with opened CB will be inactive, once CB1 set to be Open, and will not be
concerned for fault current calculation. This offers a chance for User to run varied scenarios with a
single file.
9) Input / Setting for High Voltage Circuit Breaker (CB1)
High voltage circuit breaker features almost the same with LV one at large, with the exceptions that
offering HV options for circuit breaker variation (Susol VCB(Hi-capacity), Susol VCB(Mid-
capacity), Susol VCB(Low-capacity), pro-MEC) and designation of an object name for each.
[Fig. 3-18] Input / Setting for High Voltage Circuit Breaker
10) Input / Setting for 3-phase Cable (W1)
Data may be imported from DB or manually set as you can see in Fig. 3-19. User may manually set
object name, cable length, ohm, % impedance, and thermal constraint, with system voltage auto-
detected and set by Power Solution. User may also adjust as follows:
[Fig. 3-19] Input / Setting 3-phase Cable

Data are automatically imported from DB if chosen. Note that the imported data represent ‘most
general value applicable’ and may thus not be square with the actual cable data of the system. ‘%
impedance’ value, if known, may also be set by User as the figure above. The same is applied to
single-phase cable and bent-type 3-phase cable (upward / downward).

Determination of the transformer impedance has been done in accordance with IEC Standard. Contact
the relevant institute, stated herein, for any question arising.

11) Input / Setting for Fuse (F1)


High voltage system may embrace a fuse. Note that a fuse may not be manually adjusted as the circuit
breaker relay does so the fuse choice for the appropriate purpose / circuit adaptation is deemed most
important.
Fuses vary by the dimension of them. Default setting is DIN, with the allowed rated voltage scope of
5~200A. Note that User may set the desired name of the fuse, as seen in Fig. 3-20, which may also be
applied to the drawing window.
[Fig. 3-20] Input / Setting for Fuse
12) Input / Setting for Relay
High voltage system may also embrace a relay, classified into ‘Feeder / Incoming’, ‘Transformer’,
‘Motor’, and ‘Motor Incoming’ according to what it protects. System incorporates a relay of LS
brand. Note that use of a relay shall accompany a circuit breaker so that the rated voltage can
properly be induced. A concerned relay is able to detect and break overcurrent and classified once
again into, ‘Standard Inverse’, ‘Very Inverse, ‘Extremely Inverse’, ‘KEPCO-SI’, ‘KEPCO-VI’, ‘IEEE
MI’, ‘IEEE EI’, and ‘IEEE VI’, according to its performance characteristics. User may manually input
‘CT ratio’, ‘operating value’, ‘operating time’, and ‘delay’ or allow the system to auto-set by
importing the data of the standard relay. For instantaneous value input, check the box, as stated in Fig.
3-21’ to activate ‘operating value’ and ‘operating time’.
[Fig. 3-21] Input / Setting for Relay
Contact the relevant institute, stated herein, for any question arising associated with a relay.
13) Input / Setting for Low Voltage Motor(M1)
As seen in Fig. 3-22, data may be imported from DB or subject to the manual input. User may
manually set object name, motor capacity (in the unit or kW or kVA), % impedance (positive-
subtransient reactance X(+), positive reactance X/R), power factor, efficiency, etc. System voltage is
auto-set. Click on ‘Combo’ button to adjust differences between the rated voltage and system voltage.
Note that # of phase and grounding method are also subject to User selection.
[Fig. 3-22] Input / Setting for Low Voltage Motor
User may specify negative-phase / subtransient reactance when known. Empty value will be deemed
the same as positive-phase does.
Add cable(s) for a low voltage motor by clicking on “Add Cable between Motor and Switch” and
“Yes” to activate a window to input wire information as desired. This offers User an option to add
cable(s) often required during the operation.
14) Input / Setting for TOR, EMPR, & Type2 Coordination
Make sure to set a motor protection relay such as M/C, M/S, TOR, and EMPR at the bottom of a
motor input window. Choose a desired operating method and select TOR for a motor protection relay
to determine the applied voltage. TOR is a proper choice to protect a motor from overload, open-
phase, and stall or for an extensive start-up time. Note that Class 10A and Class 20A are both
classified into Trip Class, in compliance with IEC 60747, the International Standard for relay.
Standard and open-phase relay are Class 10A type, while time-lagged relay is Class 20A type.
Meanwhile, EMPR (Electronic Motor Protection Relay), also called as ‘Electronic Overcurrent
Relay’ or ‘Electronic Overload Relay) may replace TOR to protect a low voltage motor. This
comprises GMP, DMP, IMP series.
Check the type of relays at the bottom of the relay setting window. EMPR and TOR may be chosen to
be one of general-type or digital-type as seen in Fig. 3-23 and 3-24. Note, at the bottom right of the
window, that Type2 Coordination is classified into MCCB+MC, MMS+MC. Though combined use of
a circuit breaker and switch allows CB to break the cable in case of an accident, it is inevitable to
totally break short circuit current toward a contactor or EMPR which demands such downstream
devices to bear certain level of resistance against the unintended short circuit current inflow. Type2
Coordination thus defines, by IEC terms, the qualified level that the devices shall be able to bear.
Power Solution offers a broad database, qualified by LS Industrial System Power Testing Center, for
a proper application of Type2 Coordination.

[Fig. 3-23] Pop-up as TOR Chosen


[Fig. 3-24] Pop-up as EMPR Chosen
User may choose among Cold Start Curve / Hot Start Curve, according to the starting current of the
motor operation, to define an operating method. As EMPR basically operated on the basis of ‘Inverse
Time’ property, however, there would be a transition to Hot Start curve. For direct operation of a
motor, Cold Start method will rather be chosen for Hot Start operation. Such Cold / Hot Start curve
are classified by the rated voltage scope of each.
Note that chosen CB and Switch are indicated on top of the drawing window and component window.

[Fig. 3-25] Low Voltage Motor Composition

15) Input / Setting for High Voltage Motor


With the exception of a switch connected, HV and LV motor are basically the same in terms of their
properties.
Make sure to properly choose ‘Port Type’ in the middle of Fig. 3-26 among Fixed / Single Draw-out /
Combination (PF combination) / Single External Draw-out / Combined (PF combination) External
Draw-out. Note that Combination (PF combination) option incorporates ‘LS PF Fuse (3.6/7.2kV)’.
Select a desired fuse and fuse current to check your choice on a high voltage motor input window or
drawing window.
Combination shall incorporate one of ‘Firm Excitation’ or ‘Instantaneous Excitation’. ‘Firm
Excitation’ induces the operating core into the fixed one to turn the contactor ON, only during coil
excitation, otherwise the operating core, by the effect of a spring, rotates around the cross bar to turn
the contactor OFF. ‘Instantaneous Excitation’ incorporates a ‘latch’ that mechanically holds the
current after the operating core is induced in. To turn OFF the contactor, it excites the trip coil and
deactivate a latch to finish turning OFF. Such process may manually be done by turning the trip button
on to ‘OFF’ a latch to finally trip the contactor.

[Fig. 3-26] High Voltage Motor Composition and Setting-up


4. Skeleton Checking
Click on the second ‘Dice’ on a tool-bar to activate skeleton checking procedure. This turns out Error
(unable to proceed) or Warning (Warns improper setting while proceeding) where:

[Fig. 4-1] Tool-bar Executions


Errors:
1) The rated voltage of branching circuit breaker exceeds the thermal constraint of cable.
à Solution: Lower the rated voltage of circuit breaker / Change cable bearing greater thermal
constraint level.
2) The rated voltage of branching circuit is insufficient to match that of motor.
à Solution: Enhance the rated voltage of circuit breaker / Change motor bearing lower rated voltage.
3) Required data are not provided
à Solution: Properly input every datum demanded.
4) Device is improper for the certain voltage level.
à Solution: Use device appropriate for the voltage level.
For the system example herein, skeleton checking may show up the following result:

[Fig. 4-2] Error Report


Fix the detected errors / warnings by manually opening the listed result or work on the input window
directly from the above error report window. Refer to following to activate the component input
window:
[Fig. 4-2] Activation of Component Input / Setting via Error Report Window
Double-click on the given error list to activate the corresponding component input window to fix.
Make sure to click on the first ‘Dice’ button to resume skeleton checking to ensure no error.
5. Fault Calculation
The following Fig. is a fault calculation procedure after finishing skeleton checking:

[Fig. 5-1] Fault Calculation Run


Make sure to check the fault calculation result on the window and the status bar notifying the finished
status of the calculation. Further make sure that the drawing window un-gridded so the system is set
ready to be finalized.

[Fig. 5-2] Post-calculation Component Input Window


Open the component input window to ensure ‘Set Ready’ status as on Fig. 5-2 as ‘Saving’ function is
deactivated. Click once again on the first ‘Dice’ button to adjust the system. Note that the third ‘Dice’
button is activated, on post-calculation status, to auto-set circuit breaker in accordance with the
calculated result.
Part of the system, such as circuit breaker (LV/ HV), fuse, or relay may be adjusted on post-
calculation status. User may previously narrow down the scope of circuit breaker auto-setting by
manual setting as Fig. 5-3:

[Fig. 5-3] Changeable Item on Post-calculation Status


6. Relay Auto-set
Click on the third ‘Dice’ Button to auto-set relay. Note that relay auto-set deactivates the second
‘Dice’ button, while activating the first (System adjustment) and fourth (Protection Coordination)
ones.

[Fig. 6-1] Tool-bar Presentation as Third Dice Button Clicked On


Ensure the proper auto-selection of circuit breakers as Fig. 6-2 and refer to Fig. 6-3 to adjust each
CB:

[Fig. 6-2] Circuit Breaker Auto-selection


System example previously sets CB1 to be Susol MCCB Electronic-type, with the rated voltage of
400A. On such basis, the fault calculation result comes up with 7.57. Note that, under 100% margin
rate, the calculated result 7.57 will be considered as it is for the auto-set procedure of circuit
breaker(s). List of CBs, highlighted red in Fig. 6-3, are all Susol MCCB Electronic-type satisfying
the foresaid conditions, in order of ‘suitability’. Double-click on a desired option to select. User may
set the temperature level, that CB shall be able to bear, on Master File Manager and Icu / Ics option
as well.
Selection of Icu / Ics on the component input window may also be applied to the CB list to
immediately sort out.
[Fig. 6-3] List of CBs Falling Within
Choose a different CB, if desired, and click on ‘Save’ to activate the selection and check the CB title
on the drawing window.
User may also deviate from Susol MCCB Electronic-type by forcing manual selection of the desired
CB.
Note that, upon such forced selection of ACB, Susol ACB, or Metasol ACB, the different icon is
presented on the drawing window. Despite the difference in icon presentation for an high voltage CB,
the icon will be presented in VCB-type as a low voltage CB is set to be ‘High Voltage’ system-wise.
Same is applied for the high voltage CB setting.
[Fig. 6-4] Selection of ACB-type CB

[Fig. 6-5] Drawing Window for High Voltage CB


7. Protection Coordination
The purpose of protection coordination is mainly to protect the subject device(s) and minimize black-
out extent and period when happened and classified into ‘Cascading Method’ and ‘Discrimination
Method’ as follows:
Cascading Method: Appropriate when ‘downstream CB is incapable of 100% fault current break
within the entire range of protection. Application of the method forces a ‘branching’ relay to work
simultaneously or prior to ‘branched’ ones do to alleviate burden. While efficiently protecting the
entire system, this may harm the ‘sustainable’ operation of the system.
Discrimination Method: Appropriate when downstream CB is capable of 100% fault current break
within the entire range of protection’. Application of the method remains Upstream CB resting. While
securing the operational ‘sustainability’, establishment of the system costs more, compared to
Cascading Method.
Click on the fourth ‘Dice’ button to review and secure the properly coordinated state.

[Fig. 7-1] Post-‘Protection Coordination’ Tool-bar Presentation


Refer to Fig. 7-1 to note C/D option, each indicating Cascading / Discrimination (Defaulted as ‘D’).
Next, select, in order, each CB that you want to refer to. Use Shift key combination to click on a
couple. Right-click the selected CB to activate a pop-up on Fig. 7-2. Select Protection Coordination
option to check ‘properly coordinated’ status of CBs (on the basis of LS Standard) on the top /
bottom. Note that inappropriate coordination result pops up a menu saying ‘Would you choose another
protectable CB?’. Click on ‘No’ or ‘Yes’ to reject or manually select another CB, respectively.
Selection of ‘Yes’ activates the component input window for the downstream CB where User may
check the list of CBs in order of suitability to the current system environment. Manually choose a CB
from the list as desired.
[Fig. 7-2] Protection Coordination Status Review

[Fig. 7-3] Result Pop-up


The foresaid Fig. says CB1 and CB2 are properly coordinated with each other, under the limited
voltage of 50kV. Note that, on the contrary to the above, inappropriate coordination state may pop-up
a reject message stating the given CB combination is not existing within LS Standard. Upon
appearance of such message, LS Industrial System does not guarantee the successful coordination and
operation of such combination.
Furthermore, Power Solution also offers User to simply check the coordination state by limitedly
referring to CB parameters, without reference to the drawing window via the coordination window.
See ‘Susol Coordination’ part for more information.
8. T-C Curve Reference
User may refer to T-C curves for up to five different components after CB auto-set, inclusive of:
Low Voltage Circuit Breaker / Transformer / Low Voltage, High Voltage Motor / Fuse / Relay.
Note that CB and transformer each feature two different T-C curves, representing maximum and
minimum values and ‘damage curve’ and ‘inrush curve’, respectively. Motors also represent two
different curves of ‘operation characteristic curve’ and ‘relay characteristic curve’. Alike CB, fuse
curves also represent max / min values, while relay curves each represent ‘Inverse Time’, ‘Definite
Time‘, ‘Time Delay’, or ‘Instantaneous’ section. Note, however, the different presentation of sections
where solid line section is guaranteed by LS and dotted line section is not (but detectable).
For T-C curve reference, select the desired object first and click on ‘T-C curve representation’ on
Tool-bar or right-click the object to activate one of T-C Curve / T-C Curve Scheme options.
Note that T-C Curve represents a curve of a single object selected, while T-C Curve Scheme
overviews that of the entire system over the course of all hierarchy and represents the single-line
diagram of the selected portion, as seen in the bottom left of Fig. 8-1 for User’s convenience without
necessity to go back to the drawing window for T-C curve reference.

[Fig. 8-1] T-C Curve Scheme Overview

As this part limitedly explains on a matter of T-C curve reference, see ‘Susol T-C Curve’ part for
more information on T-C Curve presentation.
Select, at least one, the object(s) as stated in Fig. 8-2. Next, right-click on the selected object to pop-
up and select T-C Curve to present the corresponding curve as Fig. 8-1. Note that this does not
presents the single-line diagram, which may only be available in ‘T-C Curve Scheme’ option.
[Fig. 8-2] Selection of T-C Curve from Drawing Window

Make sure to limit your selection within a couple of CBs on the top and bottom for ‘T-C Curve
Scheme’ option. Note, as well, that right-clicking when T-C Curve window is on does not activate ‘T-
C Curve Scheme’ as it is only able to add a new T-C curve as stated below. This, however, just adds
another curve on the ‘existing’ T-C Curve window on, without drawing the whole new curve or
making it possible to overview the single-line diagram.
Select, alternatively, the desired object on the drawing window and click on the shortcut below to
activate T-C Curve window, likewise.

[Fig. 8-3] Susol T-C Curve Shortcut


[Fig. 8-4] Pop-up Presentation when Susol T-C Curve Window Already On
See ‘Susol T-C Curve’ part for more information on post-operation of curve adjustment or triggering
within the curve adjustment window.
9. DB Management
Power Solution also offers User manual management (addition / adjustment / deletion of Generator /
Motor / Cable / Transformer DBs. Click on ‘DB management’ button to activate the function.

[Fig. 9-1] DB Management


Clicking on the highlighted box activates the following, the DB of the selected component:

[Fig. 9-2] DB Management Window


Click on ‘Input’ at the bottom of the window to manually add DB for each object.
[Fig. 9-3] DB Input Window for each Object
Input the desired data and click on ‘Apply’ to finalize DB addition.
Refer to the following example of a transformer DB addition:

[Fig. 9-4] Transformer DB Addition


Fig. 9-4 represents a DB addition window for transformer. Input any given information and click on
‘Apply’ to finalize DB addition and check the added data as the list now comprising 111 different
DBs, adding User’s one to the existing DB.
[Fig. 9-5] Addition of an User’s Transformer DB
Adjust data priority, as desired according to the reference frequency, by triggering arrows on the right
side of the window.
Refer to Fig. 9-6 to see how it works. IEC 4000_Test of 111th priority has moved up to 107th as
triggered.

[Fig. 9-6] Priority Adjustment after DB Addition


‘Modify’ or ‘Delete’ data by clicking on the corresponding icon at the bottom of the window.
[Fig. 9-6] Transformer DB Deletion
Click on ‘Yes’ on the pop-up to confirm the deletion of the selected DB

[Fig. 9-6] Post-deletion Priority of Transformers


10. Editing Tool-bar

[Fig. 10-1] Editing Tool-bar Presentation


1) Gridding
- Grids the drawing window field as desired by User.

[Fig. 10-2] Gridding Variations


From the Grid Status, user can select one of four grid options: Blank, Point, Dotted Line and
Solid Line as shown up in Fig. 10-2 and Fig. 10-3

[Fig. 10-3] Grid Options Available


2) Vertical / Horizontal Rotation
- An object can be stretched vertically or horizontally for User’s convenience to see the
detail or entire drawing.
After completing the system representation, click on Verticality / Horizontality icon to rotate
the object in a desired direction as shown in the Fig. 10-4. Application of Horizontal
rotation alters the following (left) object to be stretched out to horizontal direction (right):

[Fig. 10-4] Object Rotation


Note that the object information is transversally represented as the object is rotated

3) Undo / Redo
- Power Solution allows up to 10 repetitions of Undo / Redo without saving property.

4) Activating Component Input on ‘Tree bar’ Representation


- Addition of any component will immediately added to ‘Tree Bar’ on the left panel. Click
or double-click on the desired component in the ‘Tree Bar’ to directly activate the
component by an input pop-up menu.
[Fig. 10-5] Activating Component Input out of Tree Bar
Components may also be removed directly from ‘Tree-bar’.
11. Cad Conversion / Multiple Window Activation
1) Cad Export
Power Solution allows User to export the entire system out to a Cad file for conveniences in Cad
works.

[Fig. 11-1] System Composition and Cad Export Feature


Click on ‘Cad’ icon from Toll-bar to export the composed system (Refer to Fig. 11-1) out to a Cad
file. Make sure, to check the exported file, your computer is needed to install the Cad program.

[Fig. 11-2] Completion of Cad Export-out


Check the message as shown on Fig. 11-2 for a successful exporting-out. Move on to the designated
directory to check the created Cad file.
[Fig. 11-2] Exported File in Cad

2) Multiple Window Activation


As Susol Design basically features multiple window activation, User may work on a multiple-
window basis for system composition works as shown in Fig. 11-3.

[Fig. 11-3] Multiple Presentation / Activation of Different Windows


A project can be activated from the Project Manager panel on the top-left or manually click on the
window to make it on top. Note that a project also can be removed from the Project Manager.
12. Report
Report is logged in Excel type file for best represent the properties of each object.

Compose a system, perform calculations, and click on ‘Report’ Icon to activate the setting
window, there are two tabs: Project Information / Fault Information.

[Fig. 12-1] Project Information Tab


Input the information on blank: Project Name, Author, Date, Organization, Version Information as
shown in Fig. 12-1. Activate ‘Outline’ to evoke down Miscellaneous information. Activate the
desired impedance data option(s) to view the entire impedance data and object overview.
Presentation of impedance may be in % impedance or P.U. type depending on User’s selection.
Refer to Fig. 12-2 to check Fault Information tab. Click on the desired Fault Information or ‘Add All’
to look into. Click on the information and ‘Remove’ to remove any fault information that is not
needed.
[Fig. 12-2] Fault Information Tab
Fault Calculation output offers varied options of Bus Model, Branch, Phase-analysis, Single-phase
Branch Circuit-analysis or plural. Basic information such as 3-phase short-circuit / 2-phase short-
circuit / Line-to-ground / Phase-to-ground is all offered, classified into 1/2 period, 3-period, 5-
period, steady. Note that the less the selection is, the faster the process will be.
Following Fig. 12-3 is the presentation the case when all options are selected:

[Fig. 12-3] Report Setting


Refer to Progress Bar (Fig. 12-4) to check the procedure. Power Solution’s detailed reporting system
may exceed more than 100 pages in case of the full option status so beware it takes time. Following
Fig. 12-5 states the final report is totaling up to 148 pages:

[Fig. 12-4] Report Progress Bar


User may print out the entire Excel-type report file, stating report name, author, date, organization,
version information all input by User.

[Fig. 12-5] Printed-out Report

Refer to the following Fig. 12-6 to see the table of contents of the report:
[Fig. 12-6] Report TOC
Make sure that every information is presented by each object. Reports also includes the design
composed within the software for User’s convenience to see & check the composition of the system.
[Fig. 12-7] System Composition on Report
Report is composed on a ‘Sheet’ basis as follows:

Cover

0. TOC
1. Outline
2. System
3. Outline
Inf. Bus HV Circuit LV Circuit
Generator Transformer HV Motor LV Motor
Model Breaker Breaker

4. Impedance Outline
Inf. Bus HV Circuit LV Circuit
Generator Transformer HV Motor LV Motor
Model Breaker Breaker

5. CB Selection
Protective
HV LV Motor-protective
Coordination

6. Motor Selection
HV LV

7. MC Selection
TOR EMPR

8. Relay/ Fuse
Relay Fuse

9. Fault Current by Bus Model


3-phase short-circuit 2-phase short-circuit Line-to-ground Phase-to-ground

10. Fault Current by Cable

3-phase short-circuit 2-phase short-circuit Line-to-ground Phase-to-ground

11. Single-phase Fault Current


13. Susol T-C Curve Startup Menu
Run Susol T-C Curve, the second menu from Chapter 1 start-up, to check the following:

[Fig.13-1] T-C Curve


Menu works as follows:
1) Pull-down Menu

[Fig.13-2] Pull-down Menu

Ø File

: Comprises New File / Open / Save / Save As / Print / Print Preview / Print Setting / Exit
Ø Edit
: Comprises Undo / Redo / Trim / Copy / Paste / Delete

Ø View

: Comprises Result / Zoom In / Zoom Out / Move / CB in 2D / CB in 3D

Ø Properties

Features ‘Find Object’(Self T-C Curve presentation’ without Susol Design), ‘Master File Editor’
(Showing default settings), ‘Single Line Diagram’ (Upon T-C Curve Scheme), Coloring Curve, Output
(General / Engineering Mode), Graph Axis Setting / Fault Indication

Ø Move

Move to another window, i.e. ‘Susol Design’ (Auto-detects CB), Susol Coordination Search Window
(Refer to the corresponding Chapter), Report Window, LS Website
Ø Help

Comprises TOC / LS Power Solution Information. Refer to User Manual on TOC.

2) Basic Tool-bar

Similar with the one in Susol Design, Basic Tool-bar features Windows-style menu as seen
above. Comprises File / Edit / etc.
3) Setting Tool-bar

Shortcuts ‘Setting’ options. Turns Single Line Diagram on / off / Colors curve / Website
linkage / CB in 2D / CB in 3D

4) View Tool-bar

Comprises Zoom-in / Zoom-out / Move. Note that Move works with dragging movement. Click
on once again to return the point to the middle.
5) Output Toolbar
Features General / Engineering mode for T-C Curve readability / information detail,
respectively.
6) Voltage / Current Adjustment Toolbar

Sets standard voltage / current upon T-C curve presentation. Refer to the corresponding
Chapter.
7) Voltage / Current Indication

Corresponding voltage / current of T-C Curve, as drawn, will be indicated according to where
it points.
8) Setting Adjustment Window
Comprises CB, Relay, TR/Motor, Fuse.
Features multiple tabs corresponding to the different objects
Refer to the corresponding Chapter.

9) Output Window
Located top-right. Indicates object names, types, AF, In_max, temperature of objects on T-C
Curve. Hide or activate by clicking on Arrow on top.
10) Log-log / Current Ratio

T-C Curve is represented in the form of ‘log-log graph’. Meanwhile, current ratio is presented
at the bottom of the window for adjustment. Power Solution thus is able to represent the
different curve by current within a single window of graph. Adjust voltage / current at the
bottom to correspondingly alter current ratio / voltage and, immediately afterwards, the graph.
14. T-C Curve Search / Adjustment for Circuit Breaker
Note that Susol T-C Curve Window features are not only for representing T-C Curve of a given
system but also searching the object directly from the window. Once designing a system and checking
the corresponding T-C Curve, User may import T-C Curve of the desired object(s) to make a
comparison with the existing one. Refer to Fig. 14-1 and click on ‘Search’ icon on Toolbar on top to
pop-up ‘Display a Curve’ as follows:

[Fig. 14-1] Searching Object


Circuit breaker, relay, fuse, transformer, and motor are all searchable within the system. To narrow
down, let see an example of a circuit breaker.
Activate pop-up and input object name, object type, AF, and rated current to draw out T-C Curve.
Power Solution offers 11 different CBs available to choose as follows:
Susol MCCB Electronic-type, Susol MCCB(Adjustable), Susol MCCB Thermostatic-type(Fixed),
Metasol MCCB Electronic-type, Metasol MCCB Thermostatic-type(Fixed), MetaMEC MCCB,
MetaMEC MCCB Electronic-type, Susol ACB, Metasol ACB, ACB, MCB
Make sure to input in order of object name, object type, AF, and rated current to back-track a CB that
User desires to choose.
Fig. 14-2 shows CB selection and indication onto T-C Curve.
Chosen options are:
Susol MCCB Electronic-type / Normal Type / 1600A for AF / 1600 for rated current / 400V for
system voltage. Make sure not to miss system voltage as demanded for the proper adjustment of curve
upon voltage rate adjustment. Click on ‘Confirm’ to draw out T-C Curve of the desired CB.
[Fig. 14-2] Object Search

[Fig. 14-3] T-C Curve Presentation


List of objects is to be appeared as T-C Curve is worked on ‘log-log’ window out of an object search
window. Note that multiple choices of objects correspondingly add the result.
Click on the name of CB, right next to T-C Curve, or choose the desired CB out of the result list to
apply adjustment on T-C Curve. As chosen, T-C Curve will turn red, indicating the specific
information on the bottom-right window that also shows rated current, current sending capacity, trip
current and period of ‘Definite Time’, ‘Inverse Time’, and ‘Instantaneous’.

[Fig. 14-4] Highlighting T-C Curve


Use Arrows to adjust values on tap options, where User may check the scope of CB setting and
corresponding results. Note that non-adjustable values (thermostatic CB, etc.) are not appeared on
such options.
Remove unnecessary curve(s) by un-checking the option(s). Re-check the option to appear the
curve(s) again.
15. Relay T-C Curve Search / Adjustment
Relay T-C Curve can be referred directly from the system composition (‘Show T-C Curve’ option) or
by searching the object out of T-C Curve window:

[Fig. 15-1] T-C Curve Selection


Refer to Fig. 15-1 to note the sequence of selections. Choose ‘Relay’ to activate the list of the
available protective element, usage, performance characteristics, in order. Make sure to properly
choose options, particularly ‘Usage’ by which the relay setting shall vary.
As stated above, performance characteristics are also classified into ‘Standard Inverse’, ‘Very
Inverse, ‘Extremely Inverse’, ‘IEEE MI’, ‘IEEE EI’, ‘IEEE VI’, ‘KEPCO-SI’, and ‘KEPCO-VI’.
These are determined on the basis of the constants applied to the following ‘Characteristics Formula’,
where:

Trip Time = , where IS : Current set , IF: Fault current.

Check application of constants <A, B, C> as follows: *TL = 0.05~1.20/0.01, DT = 0~300s/0.001s


Sort Type A B C
SI 0.14 0.02 0
VI 13.5 1 0
IEC
EI 80 2 0
LI 120 1 0
MI 0.0515 0.02 0.114
IEEE[ANSI] VI 19.61 2 0.491
EI 28.2 2 0.1217
SI 0.11 0.02 0.42
KEPCO
VI 39.85 1.95 1.084

As determined by the formula, each relay bears ‘default values’, subject to User adjustment, on its
performance characteristics.
Note that ‘Fault Current’ value is necessary to draw out relay curve without system composition
procedure.
Choose the tab ‘Relay’ or click on the title of the desired relay to adjust relay settings and
correspondingly, the curve as seen in Fig. 15-1:

[Fig. 15-2] Relay T-C Curve


Fig. 15-3: the un-checked status of ‘Instantaneous’ value that is reflected in Fig. 15-2. Note the
adjustment of setting alters the corresponding curve immediately afterwards:

[Fig. 15-2] Relay T-C Curve (Un-checked ‘Instantaneous’ Value)


Note that all the relay information except for object name, usage, relay model, and protective element
is all adjustable from the adjustment tap, reflecting the immediate alteration of the corresponding
curve. Relay is set default to be ‘High-voltage’ one.
16. Transformer / Motor T-C Curve Search / Adjustment
1) Refer to Fig. 16-1 to see how transformer T-C Curve is searched. Choose ‘Transformer’ and the
desired dimension to activate ‘Capacity’ options. Choose, then, the desired capacity and input
primary / secondary voltage to check the corresponding curve shape.

[Fig. 16-1] Transformer Curve Selection


Note Fig. 16-2 to see the representation of transformer curve (built on the basis of IEEE Std
C57.109) is classified into Damage Curve / Inrush Curve:

[Fig. 16-2] Damage / Inrush Curves for Transformer


Click on the name of a transformer, right next to T-C Curve, or choose the desired transformer out of
the result list to apply adjustment on T-C Curve. User may set ‘Inrush Current’ value as desired.
2) Refer to Fig. 16-3 to check T-C Curve search window for a motor. Choose ‘Motor’ and one of the
motor types available to activate ‘Capacity’. Choose, then, a capacity to activate ‘Power Factor’.
Finalize the procedure by inputting ‘System Voltage’ to check the curve.
[Fig. 16-3] Motor Curve Selection

[Fig. 16-4] Damage / Inrush Curve for Motor


Motor represents two different currents of ‘Starting Current’ and ‘Inrush Current’. Note, from Fig.
16-4, that the starting current and inrush current each work 8 and 12 times greater than the rated one,
respectively, and represented within 2 sec / 0.04 sec. Motor settings are pending User adjustment
current.
Check TR/Motor Adjustment Window and use TOR / EMPR options to double-check the curve drawn
out and adjust the corresponding tap settings.
17. Fuse T-C Curve Search / Adjustment
Refer to Fig. 17-1 for Fuse T-C Curve Search. Choose ‘Fuse’ and dimension to activate ‘Rated
Voltage’ option. Choose, then, a rated voltage to activate ‘Rated Current’. Finalize the procedure by
inputting ‘System Voltage’ to check the curve.

[Fig. 17-1] Fuse Curve Selection

[Fig. 17-2] Fuse Curve


Fig. 17-2 shows that the fuse’s curves are represented both in solid and dotted lines, according to the
‘Security’ of values by LS. Value. The solid line means that it is guaranteed by LS, whereas dotted
line is unguaranteed.
Choose ‘Fuse’ from the result window to activate ‘Fuse’ tap where User may check the object name
or adjust dimension, rated voltage, and rated current. Any change will be reflected to the
corresponding curve immediately afterwards.
18. T-C Curve Movement by Voltage / Current Ratio
Susol T-C Curve Module features current movement and voltage ratio adjustment functions to
simultaneously represent LV and HV values. Refer to Fig. 18-1 to compose a Susol MCCB
Electronic-type curve bearing 400V of system voltage and a fuse bearing 22900V of system voltage:

[Fig. 18-1] Curves with Different System Voltages

[Fig. 18-2] Curve Stretching Out of Screen


Note the fuse curve is stretched out (Indicated in Arrow Mark) of screen due to the voltage spread.
Rightward and leftward arrow mark indicate greater and smaller current, respectively so that User
can be aware of further stretch of curve to check. Adjust ‘Current Ratio’ on top (Select or Input) to
stretch-view the curve as depicted in Fig. 18-3, multiplying 100 times ‘Ratio 1’:
[Fig. 18-3] Stretch-viewing Curve by Adjusting ‘Current’ Ratio
Note that Arrow Mark is disappeared and indication of the unit at the bottom stating the presentation
status (CURRENT IN AMPERES 100 @ 400 VOLTS).
Make sure to apply the ratio multiplication, if any, to properly read ‘Current’ value.
Apply the same for ‘Voltage’ ratio. Suppose an example of a curve 400V status and User wanting to
stretch the curve to 22900V one. To do so, input the desired value (22900V) at ‘Voltage Ratio’ option
on top of the screen. Note that the input value will be working as a default when the curve is drawn
directly from a T-C Curve window and corresponding system. The following figure is the same what
Fig. 18-2 does, with the exception of Voltage Ratio change to 22900V:

[Fig. 18-4] Stretch-viewing Curve by Adjusting ‘Voltage’ Ratio

Note the changed Voltage Ratio value to 22900V and the corresponding status presentation
(CURRENT IN AMPERES 1 @ 22900 VOLTS). Note further that the formula of Existing current X
Current Voltage / Projected Voltage comes up with Voltage Ratio.
19. General / Engineering Mode of Susol T-C Curve
T-C Curve is presented in dual forms of General / Engineering Mode as shown in Fig. 19-1:

[Fig. 19-1] Mode Changing Short-cut


General mode limitedly represents the object of curve, within the screen, so that User can further
check the information on the right side or from the result adjustment pop-up by clicking on each curve.

[Fig. 19-2] General Mode Presentation

[Fig. 19-3] Engineering Mode Presentation


Activate Engineering Mode for further information within the screen as depicted in Fig. 19-3.
Following table shows detail information of Engineering Mode:
Output on Engineering
Object Description
Mode
CB 100 Name of CB
Susol MCCN Elec. Type
TS1000NNX Name of Type
Circuit Breaker In_max Current, Icu
I(max)=1000A, I(cu)=50kA Current
Fault Current@System
I(fault)=5.0kA@400V
Voltage
MOTOR 106 Motor Name
100kW, 17% Capacity, X”(+)
Motor
Fault Current@System
I(fault)=5.0kA@400V
Voltage
Relay103 Name of Relay
X-GIPAM, ‘Inverse Time’-
Relay Model
VI
CT=400:5, I(n)=0.95 CT Ratio, Fig. k-up Current
Relay TL = 0.19, DT(Td)=0sec Operating Time, Delay
Instantaneous Fig. k-up
Inst.I(n)=5.5, TL =0.05sec
Current, Operating Time
Fault Current@System
I(fault)=15.0kA@22900V
Voltage
TR107 Name of Transformer
1000kVA, 6% Capacity, Z
Wiring Method, Primary /
Transformer Y-Δ, 22900/6600V
Secondary Voltage
Fault Current@System
I(fault)=15.0kA@6600V
Voltage
FUSE102 Fuse Name
DIN, In=200A Type, Rated Current
Fuse
Fault Current@System
I(fault)=15.0kA@22900V
Voltage
20. Zoom-in / Zoom-out / Move
Zoom-in / Zoom-out / Move or drag the T-C Curve screen, as desired, by using the following short-
cut:

[Fig. 20-1] Short-cuts for Zoom-in / Zoom-out / Move


Zoom-in or zoom-out within the scale of 100~150% or 50~100%, respectively. Fig. 20-2 indicates
the maximum state of zoom-in (the scale info. is at the bottom-right).

[Fig. 20-2] T-C Curve in 150%


And Fig. 20-3 indicates the minimum state of zoom-out:

[Fig. 20-3] T-C Curve in 50%


Drag & stretch-view the screen, when zoomed-in using ‘Move’ function (Hand-shaped icon). Click,
once again, on ‘Move’ icon to restore.
[Fig. 20-4] Dragging ’n Stretching T-C Curve
21. Axis Set / Fault Indication
Current and time scales of ‘log-log’ axis of T-C Curve window are defaulted as 1~100,000 and
0.01~100,000, respectively.
Choose ‘Axis Setting’ from the tab ‘Setting’ as in Fig. 21-1:

[Fig. 21-1] Activating Axis Setting


Click on to proceed to the following pop-up:

[Fig. 21-2] Axis Setting Pop-up


Adjust time and current scales of T-C Curve within the scope of 0.001~100000sec and
0.001~1000000A, respectively.
22. Misc. (2D View/3D View/Website Short-cut/Coloring Curve/Show Single-line Diagram)
Refer to the following 2D View/3D View/Website Short-cut/Coloring Curve/Show Single-line
Diagram functions:

[Fig. 22-1] Misc Short-cuts


1) 2D View/3D View
Click on 2D View/3D View to look into the selected circuit breaker from the system
composition procedure / T-C Curve window. Use 2D view to reflect the dimension values onto
the image, as shown in Fig. 22-2 referring to ACB’s circuit breaker:

[Fig. 22-2] ACB 2D View


2) Website Short-cut
Click on Website Short-cut to proceed to LS Website where User may inquire or refer to
catalogues.
3) Coloring Curve
Color the desired curve to clearly indicate, in a readable way, multiple min~max curve
crossing over each other as in Fig. 22-3. Note that this does not work for ‘non-guaranteed’
dotted lines.
[Fig. 22-3] T-C Curve Coloring

4) Show Single-line Diagram


Though also referred from the system composition by ‘T-C Curve Scheme’, Single-line
Diagram of the desired section may also be activated / deactivated by short-cut. The following
Fig. 22-4 shows the activated status of a diagram bottom-left:

[Fig. 22-4] Showing Single-line Diagram


5) Minimizing Result Screen
Minimize the result or adjustment window, or both, to better view T-C Curve window allowing
more spaces. Fig. 22-5 refers to checking the minimized status of windows:
[Fig. 22-5] Minimizing Result Screen
23. Susol Coordination Startup Menu
Run Susol Coordination, the third menu from Chapter 1, to check the following. This features CB
database searching without the system composition and determination of protective coordination
feasibility, according to the given parameters:

[Fig. 23-1] Susol Coordination Startup


Refer to the following functions
1) Pull-down Menu

[Fig. 23-2] Pull-down Menu


Ø File

: Comprises New File / Open / Save / Save As / Print / Print Preview / Print Setting / Exit

Ø Edit
: Comprises Catalog View / CB 2D View / CB 3D View

Ø Setting

: Comprises Low Voltage CB Search / High Voltage CB Search / Protective Coordination


Search / Master File Editor / T-C Curve Coloring

Ø Move

Move to another window, i.e. ‘Susol Design’ (Auto-detects CB), T-C Curve Search Window,
Report Window, and LS Website

Ø Help

Comprises TOC / LS Power Solution Information. Refer to User Manual on TOC.

2) Basic Toolbar

Similar with the one in Susol Design, Basic Tool-bar features Windows-style menu as seen
above. Comprises New File / Open / Save / Print.

3) Setting Toolbar

Shortcuts ‘Setting’ options. Searches HV CB / LV CB / Protective Coordination / Curve


Coloring.
4) Move Toolbar

Shortcuts ‘Move’ options. Moves to Susol Design Main / Susol T-C Curve / Website
5) Voltage / Current Indication

Susol Coordination indicates T-C Curve for protective coordination status of CB. As the curve
is drawn and tracked by the pointer, it indicates voltage / current bottom-left.
6) Circuit Breaker List

[Fig. 23-3] Circuit Breaker List


List indicates the result out of LV CB / HV CB / Protective Coordination search when queried.
7) Circuit Breaker Search Pop-up
The above Fig. shows Low Voltage which may vary for HV / Coordination Search. This allows
efficient searching procedure with the least parameters given.

8) T-C Curve Summary

This figure shows the summary of T-C Curve and does not feature specific functions as Susol
T-C Curve offers.
24. High Voltage Circuit Breaker Search

As classified into HV CB / LV CB / Protective Cooperation search, click on the short-cut on


toolbar on top to activate the following window:

[Fig. 24-1] High Voltage Circuit Breaker Search Pop-up


Pop-up requires the necessary parameters to search proper HV CBs as shown above. Refer to Fig.
24-2 to narrow down the scope within: Entire CBs / Susol VCB Hi-cap, Mid-cap, Low-cap, Pro-
MEC

[Fig. 24-2] High Voltage Circuit Breaker Types


Input the rated voltage and current Icu, type, and type name as in Fig. 24-3.
Further input, when known, AF, sort, and output #, where AF refers to that of a circuit breaker. AF
option will be activated only in case ‘type’ is chosen to be one of the following:
General / High-break type.
Limit output # for better readability of the result window.

[Fig. 24-3] Type / Name of Type


Though more parameters are preferable for the optimal result, the system proceeds to search settling
for the given information.
Fig. 24-4 shows parameter input and HV CB searching.

[Fig. 24-4] Parameter Input for High Voltage Circuit Breaker Search
Note that parameter inputs querying 5 circuit breakers satisfying:
Susol VCB Hi-cap / rated voltage of 22.9kV / rated current of 100A / Icu of 10kA / Fixed type /
Name of type to be 210mm.
As queried, the system proceeds to search DB to match the optimal five. The greater the output #, the
more the number of object searched.
Fig. 24-5 shows search result upon the said condition and determine the full satisfaction of condition:

[Fig. 24-5] High Voltage Circuit Breakers Searched


All searched CBs in the list, Fig. 24-5, satisfy the parameters input.
25. Low Voltage Circuit Breaker Search
Low voltage circuit breaker search is almost alike HV, with the exception of the slight parameter
differences.

Click on the short-cut on toolbar on top to activate the following pop-up for LV:

[Fig. 25-1] Low Voltage Circuit Breaker Search Pop-up


Fig. 25-2 shows low voltage circuit breakers from the drop-down menu:

[Fig. 25-2] Low Voltage Circuit Breaker Sorts


Note, further, the new parameters of pole # and protecting object. Input cable protection type / motor
protection / instantaneous break, as done on the Susol Design component window. Choose one of the
pole # options among:
1, 1+N, 2, 3, 3+N, 4.
Though more parameters are preferable for the optimal result, the system proceeds to search settling
for the given information.
Refer to Fig. 25-3 to note parameter input and LV CB searching.

[Fig. 25-3] Low Voltage Circuit Breaker Search Pop-up


Note parameter inputs querying 5 circuit breakers satisfying:
Rated voltage of 0.4kV / current of 100A / Icu of 10kA / 3 poles / cable-protecting purpose
As queried, the system proceeds to search DB to match the optimal five. The greater the output #, the
more the number of object searched.
Refer to Fig. 25-4 to note search result upon the said condition and determine the full satisfaction of
condition:

[Fig. 25-4] Low Voltage Circuit Breakers Searched


The searched are all satisfied the parameters input.
Double-check the appropriateness of the searched CB with reference to the T-C curve. Check the
corresponding menu on the result window to activate the following graph:
[Fig. 25-5] T-C Curve of Selected Low Voltage Circuit Breaker
Uncheck the same to remove the curve.
26. Coordination Search

Click on the short-cut to assess protective coordination status. Select one of Discriminating
break / Cascading break, as desired, to select CBs on top / bottom.
Note the extended menu from Fig. 26-1:

[Fig. 26-1] Coordination Search Pop-up


Separate the search conditions for upstream and downstream. Make sure to further select one of
Cascading / Discrimination at the bottom to define the protective coordination condition. Execute the
same with LV CB for parameter input.
Fig. 26-2 shows searching ‘coordinated’ circuit breakers in accordance with the given parameters:
[Fig. 26-2] Coordination Search Parameter Input
For example, chose Cascading option, click on ‘Search’ to proceed, and following Progress Bar, Fig.
26-3, will be activated to show the status of searching procedure:

[Fig. 26-3] Progress Bar


As finished, the system pops up the following result:
Note that CB type / Name / AF / Max Rated Current / Icu / Ics are all indicated for both streams,
classified within the separate column.
Refer to the following Fig. 26-3 to note that ‘1’ and ‘1_1’ (saying the 1st downstream CB branched
out of upstream 1) indicates upstream and downstream CBs, respectively.
[Fig. 26-3] Searched CBs according to Protective Coordination Condition
Scroll down to check further. Check the desired object, as done for LV CB, to activate the
corresponding T-C curve.
Refer to the following Fig. 26-4 to note the activation of T-C Curve by checking as follows:

[Fig. 26-4] T-C Curve Presentation for Coordinating CB


Graph indicates CB 5 and CB 5_4. Make sure to double-check the protective coordination feasibility.
27. Language Pack
Use language packs, with the use of XML function enabling language selection both before and after
installation, to operate Power Solution in different languages without re-installation procedure. Set a
different language and restart the program to apply the change.
Power Solution now offers Korean, English, Russian, Chinese, and Vietnamese. Further languages
can be added upon request.
Refer to Fig. 27-1 to change the system language as follows:
Menu baràSettingàLanguage Selection.

[Fig. 27-1] Language Selection

After choosing a new language, a new pop-up window appears to notice user.

[Fig. 27-2] Language Selection Check

After restarting the program, the language will be applied as, for example, shown in Fig. 27-3.
[Fig. 27-3] Apply Language Change

S-ar putea să vă placă și