Documente Academic
Documente Profesional
Documente Cultură
Introduction
In most parts of the country, climatic conditions require that outdoor air must
for heating, cooling and ventilating the building is a complex design decision that
must balance a great many factors, including heating and cooling needs, energy
and standards, outdoor air quantity and quality, indoor air quality, and cost.
humidity, flow of air and purity of air. It needs the controlling the properties of
exchanger).
air conditioning engineers to design their system and select the equipment. Design
conditions differ from place to place and depend upon the type of application. The
first important step for designing air conditioning is fixing the design conditions, the
indoor conditions are based on human comfort and outdoor design conditions are
curriculum, it will be helpful for the students; as the proponents will become more
prepared of the basic knowledge about air conditioning and ventilation systems.
Designing a viable and suitable air conditioning system for a proposed or existing
building as a semestral design project lets the students apply all the knowledge
1
acquired from all the lecture materials and various concepts imparted by the
minimum of 5 conditioned spaces per floor. It is also required to state the type of
building design. To check the parameters and solve for the calculation process,
the geographical location as well as the climatic condition of the location of the
The main point of this proposed project is to be able to design an air conditioning
1. Determine all the design requirements of the air conditioning and ventilation
system of the building with respect to the geographical location of the site,
its climatic condition and orientation, and the composition of the building.
materials of construction of the building and all the factors that contribute to
7. Design an air distribution system that best applies to the building structure,
2
Significance of the Study
This study mainly focused with the design to supply a minimum of 4-storey
building with a minimum of 5 conditioned spaces per floor. However, the result of
designing their air conditioning system for the proposed building of their existing
municipal hall. The proposed design would serve as their layout in designing an
in their municipal hall will significantly increase the level of comfort as they avail
To the student proponents, this will serve as basis on how to design and
layout air conditioning system and be able to apply it in their working environment.
It will also be a mechanism for the completion of the department’s goal of providing
To the future researchers, the result of this study will serves as a guide and
reference who wish to conduct the same or any related to this study. This will also
develop the skills and knowledge in working with the actual applications with
3
Block load calculations can be used in municipal buildings since it is multi-
storey structure. The method of calculation allows minimizing the number of list of
condition space per floor of a municipal buidling.
Municipal buildings system loads are primarily imposed by heat loss or gain
through structural components and by air leakage or ventilation. Internal loads,
particularly those from occupants and lights, are larger in comparison to those in
commercial or industrial structures since large number of students are need to be
accommodated in a room. Miscellaneous load depends on the equipment in the
given space.
With these unique features of the municipal building, the engineers and
architects have come up with an idea to design the four-storey municipal building
located in Mauban, Quezon. Through this, the knowledge in designing an air
conditioning system could be applied in this design project.
Definition of Terms
discussed in this paper, the following terms are defined conceptually and
operationally.
4
sense, the term can refer to any form of cooling, heating, ventilation or disinfection
that modifies the condition of air.
Dew Point. It is the temperature at which a moist air sample at the same pressure
would reach water vapor saturation.
Diffuser. It delivers widespread fan shaped flows of air into the room; it provides
air patterns in which the velocity decays before the air reaches the occupied
regions of the room.
Dry Air. It is a non-condensing component of the mixture, mainly the nitrogen and
the oxygen.
Effective Temperature. The combined effect of dry bulb temperature, wet bulb
temperature and air movement, which provides an equal sensation of warmth and
coldness.
Humidity. It is the amount of water vapor in the air. In daily language the term
"humidity" is normally taken to mean relative humidity.
Humidity Control. Used to keep the relative humidity of air conditioned room at a
satisfactory level.
Humidity Ratio. It is the proportion of mass of water vapor per unit mass of dry air
at the given conditions. It is typically the y-axis, the vertical axis, of the graph.
Humidity Ratio is dimensionless, but is sometimes expressed as grams of water
per kilogram of dry air or grains of water per pound of air.
5
Latent Heat. It is the amount of energy in the form of heat released or absorbed
by a substance during a change of phase.
Relative Humidity. It is the ratio of the mole fraction of water vapor to the mole
fraction of saturated moist air at the same temperature and pressure. It is the term
used to express the amount of moisture in a given sample of air in comparison with
the amount of moisture the air would hold if totally saturated at the temperature of
the sample; stated in terms of percentage.
Sensible Heat. The heat added to or removed from a substance that can be
measured by a change in temperature.
Sensible Heat Ratio. A scale given on the right side of the psychrometric chart;
the ratio of sensible heat to the total heat added when moving from one point to
another on the psychrometric chart.
Specific Enthalpy. It is called heat content per unit mass, is the sum of the internal
(heat) energy of the moist air in question, including the heat of the air and water
vapor within.
Specific Heat of Air. The amount of heat required to raise the temperature of one
pound of air per one degree Fahrenheit or one kilogram of air per one degree
Celsius.
Specific Volume. It is the volume per unit mass of the air sample.
Ventilation. It is the term applied to change the air in a workplace or living place
Weather. The conditions in the atmosphere such as temperature, wind velocity
and direction, clouds, moisture and atmospheric pressure.
6
I. Project Location and Design Building Orientation
be Constructed
Fundamentals (SI) and other reliable sources. The data about the
site from sea level, the maximum dry bulb and the corresponding wet
follows:
4. Outdoor Conditions
Indoor Conditions
building orientation including its vicinity map. This plan usually indicates
7
the due north, to be oriented with boundaries and sides of the building.
With this proper orientation of the architectural plan, the students will
Figure 1 shows the of the MAuban Municipal Hall where the renovation will
8
CHAPTER II
COOLING AND HEATING LOAD CALCULATION
This chapter presents the essential data required in establishing the
appropriate air conditioning system to be used in the design proper. This includes
the building components, material construction and the heat load calculation.
The ground floor, second floor, third floor and fourth floor consist of
Office, Office of the Municipal Treasurer, Office of the Municipal Engineers, Office
of the Assessor, Office of the Municipal Civil Registrar, Land Management Office,
the Municipal Mayor, Office of the Staff and Office of the Municipal Vice Mayor.
roof section, glass portion and internal partitions exposed to external condition.
Table 1.0
Components and Properties of the Ground Floor External Wall
Table 1 presents the properties of external wall including outside and inside
air film, 25 mm cement plaster and 100 mm CHB with their respective thermal
summation of resistances of the components. The height of the wall is 3.2 m and
2.5 m for the extension of the municipal building. The color of the wall is permanent
light color.
200 mm concrete
block, sand and gravel
Table 2.0
Components and Properties of Ground Floor Partition Ceiling
The roof top is made of concrete with sand and gravel aggregate that can
be used as a terrace of the building. Therefore, use Type 6 – Roof Terrace System
10
III. Window Schedules
Glass window 1 and glass window 2 are both double glass, double panel, 6mm air
11
Figure 7. Glass Window 4
Glass window 3 and 4 are both single glass, single panel, 6mm air space, venetian
Table 3.0
air film, 25 mm cement plaster and 100 mm CHB with their respective thermal
12
resistivity. Surface density of each component is also listed above. Furthermore,
The partition doors shall be made using double glass with 6 mm air space.
Use 3.5 W/m2K as its heat capacity since it shall be designed for summer
condition.
B. Conditioned Space
These include Land Management Office, DILG Office, Office of the Municipal
Sangguniang Bayan Session Hall, Office of the Municipal Mayor, Office of the
13
Municipal Staff and Office of the Municipal Vice Mayor and six (6) conditioned
spaces.
On the other hand, the third and fourth floor of the proposed Municipal
For internal lighting, use 24 W/m2 floor areas as lamp rating with lighting
m/s.
C. Calculation Information
calculation of external and internal heat loads for each floor and results of those
project.
Assume all walls and roofs are light colored. Use positive ventilation for roof
construction.
14
Service Schedule: 8:00 AM - 5:00 PM
Wall Construction: Type F
Permanent Light Color (Rural Area)
tav=to-1/2(daily range)
Glass Construction: Double glass, Double Panel (1.2m x 0.8m)
6mm Air Space, Venetian Blinds, Light Color,
Regular Sheet
1. External Wall
Solving for Resistance (U)
Table 4.0
Parameters Needed for Solving Resistance (U) of Ground Floor External Wall
Table 4.0 presents the parameters needed for solving resistance (U) of the
external wall of the ground floor. The values of the resistance, thermal resistance
and thickness have been considered. The heat transfer coefficient, U, can be
computed by getting the inverse of the summation of resistances of the
components. The calculated heat transfer coefficient is U=3.241491086 W/m2 K.
Table 5.0
Parameters Needed for Solving Resistance (U) of Ground Floor External Wall
Material
Composition of Thickness Density (ρ) Mass/Unit Area
Wall
Cement Plaster 0.025 m 1598 kg/m³ 39.95 kg/m²
Concrete Block 0.100 m 980 kg/m³ 98kg/m²
Cement Plaster 0.025 m 1598 kg/m³ 39.95 kg/m²
15
𝐌𝐚𝐬𝐬 𝐤𝐠
𝐓𝐨𝐭𝐚𝐥 𝐀𝐫𝐞𝐚 = 𝟏𝟕𝟕. 𝟗 𝐦𝟐 , Type F
Table 5.0 presents the parameters needed for solving resistance (U) of the
external wall of the ground floor. The values of the thickness, density and mass/unit
area have been considered. The total mass/unit area for the external wall of the
ground floor is 177.9 kg/m2 and the wall type is Type F.
Table 6.0
Parameters Needed for Ventilation Load Calculation of the Ground Floor
Presented in Table 6.0 are the parameters needed for the ventilation load
calculation of the ground floor. The total sensible heat calculated is QS =
879.815552W and the total latent heat calculated is QL = 3017W.
16
Table 7.0
Parameters Needed for Occupant Load Calculation of the Ground Floor
Office of the Mun. Budget Officer 150 0.55 2 0.84 0.45 1 138.6 135
Office of the Mun. Treasurer 150 0.55 3 0.84 0.45 1 207.9 202.5
Office of the Mun. Engineer 150 0.55 7 0.84 0.45 1 485.1 472.5
Office of the Mun. Civil Registrar 150 0.55 3 0.84 0.45 1 207.9 202.5
17
Presented in Table 7.0 are the parameters needed for the occupant load
calculation of the ground floor. The gain per person, sensible heat gain, number of
people, and latent and sensible heat gain has been considered. The ground floor
has the following spaces, Telecommunication Room, Land Management Office,
Office of the Municipal Budget Officer, Treasurer’s Office, Office of the Municipal
Treasurer, Office of the Municipal Engineer, Office of the Assessor, Office of the
Municipal Civil Registrar and three Unassigned Rooms. The total sensible heat
calculated is QS = 2217.6 W and the total latent heat calculated is QL = 2160W.
Assume all walls and roofs are light colored. Use positive ventilation for roof
construction.
50 % Relative Humidity
tav=to-1/2(daily range)
19
1. External Wall
Solving for Resistance (U)
Table 8.0
Parameters Needed for Solving Resistance (U) of Second Floor External Wall
𝟏 𝑾
𝐔= ; 𝑼 = 3.241491086
𝑹𝑻 𝒎𝟐 𝑲
Table 8 presents that in solving for the resistance, the parameters needed for the
second floor external wall is first determine the material composition of the wall, its
Resistance, thermal resistance of the wall and the thickness of the wall. Computing
for the total resistance to get the overall heat transfer using the formula one divided
by the total resistance. The value of the total resistance is 0.3085 and the total
Table 9.0
Parameters Needed for Determining Wall Type of Second Floor External Wall
Material
Composition of Thickness Density (ρ) Mass/Unit Area
Wall
𝐌𝐚𝐬𝐬 𝐤𝐠
𝐓𝐨𝐭𝐚𝐥 𝐀𝐫𝐞𝐚 = 𝟏𝟕𝟕. 𝟗 𝐦𝟐 , Type F
20
In determining the wall type, the parameters needed for the second
floor external wall are the materials composition of the wall, the thickness of the
wall, its density, and the mass per unit area. Having the materials composition of
the cement plaster, concrete block, and another cement plaster comes with the
total mass per unit area of 177.9 and that indicates that the type of wall used is
Type F.
Table 10.0
Components and Properties of External Roof
materials used are the outside air film, 25 mm granite, 200 mm concrete block,
sand & gravel, 25 mm cement plaster and the inside air film using the values of
each component resistance and density to get the total heat transfer of
2.395209581 W/m2K and the type used is Type 6 roof with suspended ceiling.
Table 11.0
Land
51.75385 177.519351
Managemen 38.6 6 2 2.36 5
6 7
t Office
21
DILG Office 27.24 6 2 2.36 5 51.753856 177.5193517
Office of the
Municipal 37.2811 6 2 2.36 5 51.753856 177.5193517
Administrator
Office of the
Municipal 13.2516 6 2 2.36 5 51.753856 177.5193517
Agriculturist
SSB 13.088 6 2 2.36 5 51.753856 177.5193517
Agriculture
32.84 6 2 2.36 5 51.753856 177.5193517
Office
Municipal
29.7024 6 2 2.36 5 51.753856 177.5193517
Mayor’s Office
Office of the
45.9816 6 3 2.36 7.5 77.630784 266.2790275
Staff
Office of the
Municipal Vice 29.6244 6 2 2.36 5 51.753856 177.5193517
Mayor
Office 8.988 6 1 2.36 2.5 25.876928 88.75967584
Unassigned
44.495 6 3 2.36 7.5 77.630784 266.2790275
Room 1
Unassigned
11.676 6 1 2.36 2.5 25.876928 88.75967584
Room 2
Unassigned
16.47 6 1 2.36 2.5 25.876928 88.75967584
Room 3
Unassigned
14.2191 6 1 2.36 2.5 25.876928 88.75967584
Room 4
Unassigned
21.96 6 1 2.36 2.5 25.876928 88.75967584
Room 5
Unassigned
17.238 6 1 2.36 2.5 25.876928 88.75967584
Room 6
Sangguniang
Bayan Session 85.8546 150 128 2.36 300.8 3312.246784 11361.23851
Hall
TOTAL: QS = 4036.800768 W QL = 𝟏𝟑𝟖𝟒𝟔. 𝟓𝟎𝟗𝟒𝟑 W
For the calculation of the ventilation load of the second floor, the parameters
needed are the spaces to be considered, the area of each spaces the estimated
outdoor air, the heat transfer, the values of sensible heat and latent heat of each
22
Table 12.0
Parameters Needed for Occupant Load Calculation of Second Floor
23
The computation of the occupant load is listed according to their parameters
needed. Including the spaces used, the gain per person, sensible heat gain of each
space, the number of people using each spaces, the CLF (SHG), the latent heat
gain CLF (LHG) , the sensible heat, the latent heat of each spaces . considering
all of this parameters we come up to the answer of total sensible heat Qs = 8931.6
Assume all walls and roofs are light colored. Use positive ventilation for roof
construction.
1. External Wall
Solving for Resistance (U)
24
Table 13.0
Parameters Needed for Solving Resistance (U) of Third Floor External Wall
Table 13.0 shows the parameters needed for solving the resistance of the
third floor external wall. It shows the list of the material composition of the wall with
their resistance, thermal resistance and thickness. After having all this parameters
and solving, the obtained resistance for the third floor is 3.241491086 W/m 2.K.
Table 14.0
Parameters Needed for Determining Wall Type of Third Floor External Wall
Material
Thickness Density (ρ) Mass/Unit Area
Composition of
Wall
Cement Plaster 0.025 m 1598 kg/m³ 39.95 kg/m²
Concrete Block 0.100 m 980 kg/m³ 98 kg/m²
Cement Plaster 0.025 m 1598 kg/m³ 39.95 kg/m²
𝐌𝐚𝐬𝐬 𝐤𝐠
𝐓𝐨𝐭𝐚𝐥 𝐀𝐫𝐞𝐚 = 𝟏𝟕𝟕. 𝟗 𝐦𝟐 , Type F
Table 14.0 shows the parameters needed for determining the wall type of
the external wall of the third floor. The material composition of the wall are cement
plaster and concrete block. Thickness, density and mass per unit area were listed
for each material composition. After solving for the total mass per area which is
equal to 177.9 kg/m2 it is then concluded that the wall type for the third floor
25
Table 15.0
Parameters Needed for Ventilation Load Calculation of Third Floor
Table 15.0 shows the parameters needed for ventilation load calculation of
the third floor. The spaces listed are 4 unassigned rooms and the office. Also, given
on the table are the area, estimated occupancy per 100m 2 floor area, number of
occupants, outdoor air requirements per person, the heat flow rate, the sensible
heat and the latent heat. After solving, the acquired total latent heat is
Table 16.0
Parameters Needed for Occupant Load Calculation of Third Floor
Gain
No. Of Qs, W QL, W
Space Per
People (L/s) (L/s)
Person
Unassigned Room (1) 150 3 207.9 202.5
Unassigned Room (2) 150 1 69.3 67.5
Unassigned Room (3) 150 1 69.3 67.5
Unassigned Room (4) 150 2 138.6 135
Office 150 1 69.3 67.5
Table 16.0 shows the parameters needed for occupant load calculation of
the third floor. The spaces listed are 4 unassigned rooms and the office. Also given
in the table are the gain per person, sensible heat gain, no. of people, CLF for
26
latent and sensible heat gain, latent heat gain, and the sensible and latent heat.
Having all the given parameters, the acquired sensible heat is 554.4W while the
Assume all walls and roofs are light colored. Use positive ventilation for roof
construction.
1. External Wall
Solving for Resistance (U)
Table 17.0
Parameters Needed for Solving Resistance (U) of Fourth Floor External Wall
27
Table 17.0 shows the parameters needed for solving the resistance of the
fourth floor external wall. It shows the list of the material composition of the wall
with their resistance, thermal resistance and thickness. After having all this
parameters and solving, the obtained resistance for the fourth floor is 3.241491086
W/m2.K.
Table 18.0
Parameters Needed for Determining Wall Type of Fourth Floor External Wall
Material
Thickness Density (ρ) Mass/Unit Area
Composition of
Wall
Cement Plaster 0.025 m 1598 kg/m³ 39.95 kg/m²
Concrete Block 0.100 m 980 kg/m³ 98kg/m²
Cement Plaster 0.025 m 1598 kg/m³ 39.95 kg/m²
𝐌𝐚𝐬𝐬 𝐤𝐠
𝐓𝐨𝐭𝐚𝐥 𝐀𝐫𝐞𝐚 = 𝟏𝟕𝟕. 𝟗 𝐦𝟐 , Type F
Table 18.0 shows the parameters needed for determining the wall type of
the external wall of the fourth floor. The material composition of the wall are cement
plaster and concrete block. Thickness, density and mass per unit area were listed
for each material composition. After solving for the total mass per area which is
equal to 177.9 kg/m2 it is then concluded that the wall type for the fourth floor
Table 19.0
Components and Properties of External Roof
28
Table 19.0 shows the components and properties of the external roof. Given
in the table is the composition for the external roof with their respective resistances
and densities. The compositions listed are the outside air film, 25 mm granite, 200
mm concrete block, sand and gravel, the 25 mm cement plaster and the inside air
film. After solving, the acquired resistance is equal to 2.395209581 W/m 2.K and
Table 20.0
Parameters Needed for Ventilation Load Calculation of Fourth Floor
Table 20.0 shows the parameters needed for ventilation load calculation of
the fourth floor. The spaces listed are 4 unassigned rooms and the office. Also,
given on the table are the area, estimated occupancy per 100m 2 floor area, number
of occupants, outdoor air requirements per person, the heat flow rate, the sensible
heat and the latent heat. After solving, the acquired total latent heat is
29
Table 21.0
Parameters Needed for Occupant Load Calculation for Fourth Floor
Gain
No. Of Qs, W QL, W
Space Per
People (L/s) (L/s)
Person
Unassigned Room (1) 150 3 207.9 202.5
Table 21.0 shows the parameters needed for occupant load calculation of
the fourth floor. The spaces listed are 4 unassigned rooms and the office. Also
given in the table are the gain per person, sensible heat gain, no. of people, CLF
for latent and sensible heat gain, latent heat gain, and the sensible and latent heat.
Having all the given parameters, the acquired sensible heat is 485.1W while the
30
A COMPLETE SUMMARY OF HEAT LOAD CALCULATION IN TABULAR FORM
FOR GROUND FLOOR
Table 22.0
Summary of Heat Load Calculation for External Wall of the Ground Floor
to 1174.359287 watts . For the East orientation, the sensible heat is 2257.118703. In south orientation there is a value of 318.887269 watts sensible
heat and for the calculation in west, the value of sensible heat is 0 value. Having a summation of 3750.365259 sensible heat of all building orientation.
Table 23.0
Summary of Glass Load Calculation of the Ground Floor
31
South 9.18 355 0.51 0.83 1379.49237 3.5 8.9 285.957 1665.44937
West 0 0 0 0 0 0 0 0 0
TOTAL Qs = 11923.81833 W
In table 23, summary of glass load calculation of the ground floor. The North orientation has a value of 1135.96896 watts of sensible heat. For
the calculation of sensible heat in East orientation the computed value is 9122.4 watts. For the analysis of sensible heat in South orientation, the
computed value is 1665.44937 watts. And zero value for the west orientation. Having a total of 11923.81833 watts of sensible heat.
Table 24.0
Summary of Infiltration Load Calculation of the Ground Floor
Volume
No. of Air
of Condition Q, L/s ΔT, K Qs , W H@27.8 Wo Wi Q L, W
Changes
Space
0.2263 1425.39028 89.60161677 8.9 982.4638076 89.0142 0.02182611785 9.289440471 x 10-3 3369.919686
TOTAL: Qs = 982.4638076 W, QL = 3369.919686 W
For the summary of infiltration load calculation. Having a 0.2263 number of changes. The computed value of sensible heat is 982.4638076 watts
32
Table 25.0
Summary of Ventilation Load Calculation of the Ground Floor
33
Internal Heat Load
Table 26.0
Summary of Lighting Load Calculation of the Ground Floor
TOTAL: Qs = 11029.13015 W
Table 27.0
Summary of Miscellaneous Load Calculation of the Ground Floor
Utilization/24
Equipment
Appliances No. of units hrs of Fu CLF Qs , W
Rating, W
operation
Telephone 6 12 8 1 1 24
Water Dispenser 90 3 8 1 1 90
Photocopier 615 3 8 1 1 615
Computer 100 21 8 1 1 700
TOTAL: Qs = 1429 W
Table 27.0 for the summary of miscellaneous load calculation of the ground floor. The listed appliances are telephone, water dispenser,
photocopier and computer. The utilization of appliances is assumed to be 24 hours of operation. The summation of sensible heat is 1429 watts.
34
Table 28.0
Summary of Occupant Load Calculation of the Ground Floor
35
Table 28.0. for the summary of occupant load calculation of the ground floor having the spaces of: telecommunication room, Land management
office, Office of the Municipal budget officer, Treasurer’s office, Office of the Municipal treasurer, Office of the Municipal engineer, Office of the Assessor
. Office of the Municipal Civil Registrar and Unassigned Room 1 2 and 3. The estimated gain person is 150. The calculated sensible heat is 2217.6
Table 29.0
Summary of Partition Load Calculation of the Ground Floor
Outdoor
Partitions
For the summary of the Partition Load Calculation of the ground floor. The calculated value of sensible heat of each component are as follow:
5752. 058072, 1193.379725, 1108.8, 1196.16, 1021.02 and 387.304427 watts having a summation of 10658.72222 watts of sensible heat.
36
Table 30.0
Summary of Heat Load Calculation for Ground Floor
The summary of heat load calculation for ground floor. For the external heat
sources, the total value of latent heat is 5943.950285 watts and for the calculated
total value of sensible heat the computed value is 17407.07831 watts. For the
internal heat sources the total value of sensible heat is 25334.45237 watts and the
latent heat is said to be 2160 watts. The overall computed sensible heat value is
42741.53068 watts and the overall latent heat is 8103.950285 watts and the
37
COMPLETE SUMMARY OF HEAT LOAD CALCULATION IN TABULAR FORM FOR SECOND FLOOR
External Heat Load
Table 31.0
Summary of Heat Load Calculation for External Wall of the Second Floor
Orientation Area, m2 CLTD sel LM K Ti Tav CLTD adj U, W/m2 K Qs, W
North 34.528 13 -0.55 0.65 24 29.35 9.4425 3.241491086 1056.825413
East 48.349 25 -0.55 0.65 24 29.35 17.2425 3.241491086 2702.293785
South 20.045 22 -3.33 0.65 24 29.35 13.4855 3.241491086 876.2296516
West 0 0 0 0 0 0 0 0 0
TOTAL 4635.348849 W
Table 31.0 for the summary of heat load calculation for external wall of the second floor. For the following orientation of the building, north east
south and west orientation the computed sensible heat are the following : 1056.825413 watts, 2702.293785 watts, 876.2296516 watts and zero value
for the west orientation. The summation of sensible heat 4635.348849 watts
Table 32.0
Summary of Glass Load Calculation of the Second Floor
Orientation Area, m2 SHGF SC CLF Qsg, W U, W/m2 K ΔT Qth, W Qs, W
North 17.28 115 0.51 0.91 922.25952 3.5 15.2 538.272 1460.53152
East 34.56 700 0.51 0.80 9870.336 3.5 15.2 1076.544 10946.88
South 9.18 355 0.51 0.83 1379.49237 3.5 15.2 285.957 1665.44937
TOTAL 14072.86089 W
38
In table 32, summary of glass load calculation of the second floor. The North orientation has a value of 1460.53152 watts of sensible heat. For
the calculation of sensible heat in East orientation the computed value is 10946.88 watts. For the analysis of sensible heat in South orientation, the
computed value is 1665.44937 watts. And zero value for the west orientation. Having a total of 14072 watts of sensible heat.
Table 33.0
Summary of Infiltration Load Calculation of the Second Floor
0.2541 1480.76569 93.08257657 15.2 1020.631836 81.672 0.02182611785 9.289440471 x 10-3 3500.838696
1020.631836 W
TOTAL
3500.838696W
For the summary of infiltration load calculation. Having a 0.2541 number of changes. The computed value of sensible heat is 1020 watts and
39
Table 34.0
Summary of Roof Load Calculation of the Second Floor
TOTAL 10741.75728W
For the summary of roof load calculation of the second floor , having an area of approximately 402 square meter, the sensible heat is 10741.75
watts.
For the summary of ventilation load calculation of the second floor. The spaces are telecommunication room, Land management office, Office
of the Municipal budget officer, Treasurer’s office, Office of the Municipal treasurer, Office of the Municipal engineer, Office of the Assessor . Office of
the Municipal Civil Registrar and Unassigned Room 1 2 3 4 5 and 6. Having a 6 estimated occupancy per 100 meter floor area. Having a same value
of humidity ratio of and the summation of sensible heat of 4036 watts. And latent heat is 13846 watts.
40
Table 35.0
Parameters Needed for Ventilation Load Calculation of Second Floor
Outdoor Air
Estimated Occupancy
Requirements Per Qs, W QL, W
Space Area (m2) Per 100 m2 Occupants Q(L/s)
Person (L/s) (L/s)
Floor Area
(L/s)
Land Management Office 38.6 6 2 2.36 5 51.753856 177.5193517
DILG Office 27.24 6 2 2.36 5 51.753856 177.5193517
Office of the Municipal Administrator 37.2811 6 2 2.36 5 51.753856 177.5193517
Office of the Municipal Agriculturist 13.2516 6 2 2.36 5 51.753856 177.5193517
SSB 13.088 6 2 2.36 5 51.753856 177.5193517
Agriculture Office 32.84 6 2 2.36 5 51.753856 177.5193517
Municipal Mayor’s Office 29.7024 6 2 2.36 5 51.753856 177.5193517
Office of the Staff 45.9816 6 3 2.36 7.5 77.630784 266.2790275
Office of the Municipal Vice Mayor 29.6244 6 2 2.36 5 51.753856 177.5193517
Office 8.988 6 1 2.36 2.5 25.876928 88.75967584
Unassigned Room 1 44.495 6 3 2.36 7.5 77.630784 266.2790275
Unassigned Room 2 11.676 6 1 2.36 2.5 25.876928 88.75967584
Unassigned Room 3 16.47 6 1 2.36 2.5 25.876928 88.75967584
Unassigned Room 4 14.2191 6 1 2.36 2.5 25.876928 88.75967584
Unassigned Room 5 21.96 6 1 2.36 2.5 25.876928 88.75967584
Unassigned Room 6 17.238 6 1 2.36 2.5 25.876928 88.75967584
Sangguniang Bayan Session Hall 85.8546 150 128 2.36 300.8 3312.246784 11361.23851
TOTAL: QS = 4036.800768 W QL = 𝟏𝟑𝟖𝟒𝟔. 𝟓𝟎𝟗𝟒𝟑 W
41
Internal Heat Load
Table 36.0
Summary of Lighting Load Calculation of the Second Floor
For the summary of lighting load calculation of the second floor having a lamp rating of 24. The parameter given is listed on table. The total
Table 37.0
Summary of Miscellaneous Load Calculation of the Second Floor
Equipment Utilization/24 hrs of
Appliances No. of units Fu CLF QS , W
Rating, W Operation
Telephone 6 17 8 1 1 34
Water Dispenser 90 3 8 1 1 90
Photocopier 615 3 8 1 1 615
Computer 100 22 8 1 1 733.333
Coffee Maker 600 2 8 1 1 400
TV Set 80 2 8 1 1 53.333
Sound System 244 1 4 1 1 40.667
TOTAL 2016.3333334
42
Table 37.0 for the summary of miscellaneous load calculation of the second floor. The listed appliances are telephone, water dispenser,
photocopier computer, coff ee maker , tv set, projector and sound system. The utilization of appliances is assumed to be 24 hours of operation. The
Table 38.0
Summary of Occupant Load Calculation of the Second Floor
Latent
Gain per Sensible No. of CLF CLF
Space Heat QS , W Q L, W
person Heat Gain People (SHG) (LHG)
Gain
Land Management Office (LMO) 150 0.55 2 0.84 0.45 1 138.6 135
DILG Office 150 0.55 2 0.84 0.45 1 138.6 135
Office of the Municipal 138.6 135
150 0.55 2 0.84 0.45 1
Administrator
Office of the Municipal 138.6 135
150 0.55 2 0.84 0.45 1
Agriculturist
SSB 150 0.55 2 0.84 0.45 1 138.6 135
Agriculture Office 150 0.55 2 0.84 0.45 1 138.6 135
Municipal Mayor’s Office 150 0.55 2 0.84 0.45 1 138.6 135
Office of the Municipal Staff 150 0.55 3 0.84 0.45 1 207.9 202.5
Sangguniang Bayan Session Hall 100 0.60 128 0.84 0.40 1 6451.2 5120
Office of the Municipal Vice Mayor 150 0.55 2 0.84 0.45 1 138.6 135
Office 150 0.55 1 0.84 0.45 1 69.3 67.5
Unassigned Room 1 150 0.55 3 0.84 0.45 1 207.9 202.5
43
Unassigned Room 2 150 0.55 1 0.84 0.45 1 69.3 67.5
Unassigned Room 3 150 0.55 1 0.84 0.45 1 69.3 67.5
Unassigned Room 4 150 0.55 1 0.84 0.45 1 69.3 67.5
Unassigned Room 5 150 0.55 1 0.84 0.45 1 69.3 67.5
Unassigned Room 6 150 0.55 1 0.84 0.45 1 69.3 67.5
TOTAL 8391.6 W 7010 W
Table 38.0. for the summary of occupant load calculation of the ground floor having the spaces of: land management office, DILG office, office
of the municipal administrator, office of the municipal agricultural, SSB, agricultural office, municipal mayor’s office, office of the municipal staff,
sangguniang bayan session hall, office the municipal vice mayor, office and Unassigned Room 1 2 3 4 5 and 6.
Table 39.0
Summary of Partition Load Calculation of the Second Floor
Outdoor
Partitions
Area U ΔT Qs
Partition Wall 1 379.976 2.503128911 6 4646.963384
Partition Wall 2 43.007 2.503128911 11.3 990.5568962
Partition Glass 1 43.92 3.5 6 922.32
Partition Glass 2 20.16 3.5 11.3 797.328
Partition Door 36.96 3.5 6 776.16
TOTAL 8517.338793 W
44
For the summary of the Partition Load Calculation of the second floor. The
calculated value of sensible heat of each component is as follow:, 4646, 990, 922,
797, 776, and 384 watts approximately. having a summation of 8517 watts of
sensible heat.
Table 40.0
Summary of Heat Load Calculation for Second Floor
The summary of heat load calculation for second floor. For the external heat
sources, the total value of latent heat is 17347 watts and for the calculated total
value of sensible heat the computed value is 34507 watts. For the internal heat
sources the total value of sensible heat is 30462 watts and the latent heat is said
to be 7010 watts. The overall computed sensible heat value is 64969 watts and
the overall latent heat is 24357 watts and the summation is 89326.9038 watts.
45
A COMPLETE SUMMARY OF HEAT LOAD CALCULATION IN TABULAR FORM FOR THIRD FLOOR
External Heat Load
Table 41.0
Summary of Heat Load Calculation for External Wall of the Third Floor
Table 41.0 shows the summary of heat load calculation for external wall of the third floor. Given all the orientations North, South, West
and East only the North and South part has an external wall for the third floor. Different parameters were listed together with their quantity. After
solving the acquired total sensible heat for the external wall of the third floor is equal to 1954.222947 W.
Table 42.0
Summary of Glass Load Calculation of the Third Floor
U, W/m2
Orientation Area, m2 SHGF SC CLF Qsg, W ΔT Qth, W Qs, W
K
North 8.64 115 0.51 0.91 461.12976 3.5 8.9 269.136 730.26576
East 0 0 0 0 0 0 0 0 0
South 4.59 355 0.51 0.83 689.746185 3.5 8.9 142.9785 832.724685
TOTAL 1562.990445 W
46
Table 42.0 shows the summary of glass load calculation of the third floor. Given all the orientations North, South, West and East only the
North and South part has an external wall for the third floor. Different parameters were listed together with their quantity. After solving the
acquired total sensible heat for the glass of the third floor is equal to 1562.990445 W.
Table 43.0
Summary of Infiltration Load Calculation of the Third Floor
Table 43.0 shows the summary of the Infiltration Load Calculation of the third floor. The table includes the parameters number of air
changes, heat and change in temperature to solve for the sensible heat which is equal to 223.6597487W. While for the latent heat, the
parameters listed are the enthalpy and humidity ratios. And the acquired latent heat is 767.1686064 W.
Table 44.0
Summary of Ventilation Load Calculation of the Third Floor
47
Unassigned 2.36 2.36 8.9 0.02182611785
11.676 6 1 25.876928 9.289440471 x 10-3 88.75967584
Room (2)
Unassigned 2.36 2.36 8.9 25.876928 0.02182611785 88.75967584
14.245 6 1 9.289440471 x 10-3
Room (3)
Unassigned 2.36 4.72 8.9 51.753856 0.02182611785 177.5193517
22 6 2 9.289440471 x 10-3
Room (4)
2.36 2.36 8.9 25.876928 0.02182611785 88.75967584
Office 8.988 6 1 9.289440471 x 10-3
TOTAL 8 207.015424 W 710.0774067W
Table 44.0 shows the summary of ventilation load calculation of the third floor. The spaces given are 4 unassigned rooms and the office.
While the parameters listed are the area, estimated occupancy per 100m 2 floor area, number of occupants, outdoor air requirements per person,
the heat flow rate and the humidity ratios. Having all these parameters the computed sensible heat is 207.015424W and the latent heat is
710.0774067W.
Table 45.0
Summary of Roof Load Calculation of the Third Floor
0 0 0 0 0 0 0 0 0
TOTAL 0 W
48
Table 45.0 shows the Summary of the Roof Load Calculation of the Third Floor. It shows that all the parameters are 0 since there is no
Table 46.0 shows the summary of the lighting load calculation of the third floor. Having all the parameters needed in solving for the
sensible heat for the lighting load, the computed sensible heat is equal to 2394.756864W.
Table 47.0
Summary of Occupant Load Calculation of the Third Floor
49
Table 47.0 shows the summary of occupant load calculation for the third floor. The spaces listed are 4 unassigned rooms and the office.
Also given in the table are the gain per person, sensible heat gain, no. of people, CLF for latent and sensible heat, latent heat gain, to solve for
the sensible and latent heat. Having all the given parameters, the acquired sensible heat is 554.4W while the latent heat is equal to 540W.
Table 48.0
Summary of Miscellaneous Load Calculation of the Third Floor
Table 48.0 shows the summary of miscellaneous load calculation of the third floor.. After solving, the total computed sensible heat load
Table 49.0
Summary of Partition Load Calculation of the Third Floor
Partitions Outdoor
Area U ΔT Qs
Partition Wall 147.424 2.502427355 6 2213.507102
Partition Door 8.836.96 3.5 6 184.8
TOTAL 2398.307102 W
50
Table 49.0 shows the summary of the partition load calculation of the third
floor. Listed are the partition door and the partition wall. The parameters needed
to solve for the sensible heat are the area, resistance, and the change in
temperature. After having all of these, the computed overall sensible heat for the
Table 50.0
Summary of Heat Load Calculation for Third Floor
Table 50.0 shows the summary of the heat load calculation for third floor.
Listed are the sensible and latent heat for the internal and external heat load. For
the external heat load the total sensible heat is equal to 3947.888565W while the
total latent heat is 1477.246013W. On the other hand, for the internal heat load the
total sensible heat is equal to 5759.130633W while the total latent heat is 540W.
Adding the sensible and latent heat of the external and internal heat load, the
2017.246013W respectively.
51
A COMPLETE SUMMARY OF HEAT LOAD CALCULATION IN TABULAR FORM FOR FOURTH
FLOOR
External Heat Load
Table 51.0
Summary of Heat Load Calculation for External Wall of the Fourth Floor
Table 51.0 shows the summary of heat load calculation for external wall of the fourth floor.. After solving, the acquired total sensible heat
Table 52.0
Summary of Glass Load Calculation of the Fourth Floor
U, W/m2
Orientation Area, m2 SHGF SC CLF Qsg, W ΔT Qth, W Qg, W
K
North 8.64 115 0.51 0.91 461.12976 3.5 8.9 269.136 730.26576
East 0 0 0 0 0 0 0 0 0
South 6.12 355 0.51 0.83 919.66158 3.5 8.9 190.638 1110.29958
TOTAL 1840.56534 W
52
Table 52.0 shows the summary of glass load calculation of the fourth floor. Given all the orientations North, South, West and East only
the North and South part has an external wall for the third floor. Different parameters were listed together with their quantity. After solving, the
acquired total sensible heat for the glass of the fourth floor is equal to 1840.56534 W.
Table 53.0
Summary of Infiltration Load Calculation of the Fourth Floor
Volume
No. of Air
of Condition Q, L/s ΔT 𝐐𝑺 , W H@27.8 𝛚𝟎 𝛚𝒊 𝐐𝑳 , W
Changes
Space
9.289440471 x
0.2541 324.4928 20.39797796 8.9 223.6597487 89.0142 0.02182611785 767.1686063
10-3
Table 53.0 shows the summary of the Infiltration Load Calculation of the fourth floor. The table includes the parameters number of air
changes, volume of condition space, heat and change in temperature to solve for the sensible heat which is equal to 223.6597487W. While for
the latent heat, the parameters listed are the enthalpy and humidity ratios. And the acquired latent heat is 767.1686064 W.
53
Table 54.0
Summary of Ventilation Load Calculation of the Fourth Floor
Area, Q,
Space Occupants L/s ΔT 𝐐𝑺 , W 𝛚𝟎 𝛚𝒊 𝐐𝑳 , W
m2 L/s
Unassigned
44.495 3 2.36 7.08 8.9 77.630784 0.01798769262 9.289440471 x 10-3 266.2790275
Room (1)
Unassigned 25.876928 88.75967582
11.676 1 2.36 2.36 8.9 0.01798769262 9.289440471 x 10-3
Room (2)
Unassigned 25.876928 88.75967582
14.245 1 2.36 2.36 8.9 0.01798769262 9.289440471 x 10-3
Room (3)
Unassigned 25.876928 88.75967582
22 1 2.36 2.36 8.9 0.01798769262 9.289440471 x 10-3
Room (4)
Office 8.988 1 2.36 2.36 8.9 25.876928 0.01798769262 9.289440471 x 10-3 88.75967582
TOTAL 7 181.138496 W 621.3177308 W
Table 54.0 shows the summary of ventilation load calculation of the fourth floorHaving all these parameters the computed sensible heat
Table 55.0
Summary of External Roof Load Calculation of the Fourth Floor
54
Table 55.0 shows the Summary of the External Roof Load Calculation of the Fourth Floor. Having an area of 185.9 m2, CLTDmax of 18
and CLTDadj of 14.7625, the computed resistance is equal to 2.3952 W/m 2.K and the sensible heat is equal to 6573.290419W.
Table 56.0 shows the summary of the lighting load calculation of the fourth floor. Having all the parameters needed in solving for the
sensible heat for the lighting load, the computed sensible heat is equal to 2394.756864W.
Table 57.0
Summary of Occupant Load Calculation of the Fourth Floor
55
Table 57.0 shows the summary of occupant load calculation for the fourth floor. The spaces listed are 4 unassigned rooms and the office.
Also given in the table are the gain per person, sensible heat gain, no. of people, CLF for latent and sensible heat, latent heat gain, to solve for
the sensible and latent heat. Having all the given parameters, the acquired sensible heat is 485.1W while the latent heat is equal to 472.5W.
Table 58.0
Summary of Miscellaneous Load Calculation of the Fourth Floor
Utilization/24 hrs of
Appliance Equipment Rating, W No. of units Fu CLF QS , W
Operation
Telephone 6 5 8 1 1 10
Water Dispenser 90 1 8 1 1 30
Photocopier 615 1 8 1 1 205
Computer 100 5 8 1 1 166.6666667
TOTAL 411.6666667 W
Table 58.0 shows the summary of miscellaneous load calculation of the fourth floor. After solving, the total computed sensible heat load
Table 59.0
Summary of Partition Load Calculation of the Fourth Floor
Partitions Outdoor
Area U ΔT Qs
Partition Wall 147.424 2.503128911 6 2214.127659
Partition Door 8.8 3.5 6 184.8
TOTAL 2398.927659 W
56
Table 59.0 shows the summary of the partition load calculation of the fourth
floor. After having all of these, the computed overall sensible heat for the partition
Table 60.0
Summary of Heat Load Calculation for Fourth Floor
Table 60.0 shows the summary of the heat load calculation for fourth floor.
Listed are the sensible and latent heat for the internal and external heat load. For
the external heat load the total sensible heat is equal to 10705.99586W while the
total latent heat is 1388.486337W. On the other hand, for the internal heat load the
total sensible heat is equal to 5690.45119W while the total latent heat is 472.5W.
Adding the sensible and latent heat of the external and internal heat load, the
1860.986337W respectively.
57
Table 61.0
Summary of Heat Load Calculation for Ground Floor –Fourth Floor
Table 61.0 shows the summary of heat load calculation for ground floor to
fourth floor. For the total sensible heat of all floors, it is equal to 133814.5523W
while the total latent heat for all floors is equal to 36339.53074W and the overall
58
CHAPTER III
This chapter presents the calculation for entering and leaving coil condition
GROUND FLOOR
Table 62.0
Summary of Heat Load Calculation for Ground Floor
Selection.
59
Figure 10.0 A/C Diagram for Ground Floor
Outside Condition:
TDB= 32.9C
TWB= 27.8C
te=24.89
SHF= 0.840616115
TL=14.2C
Psychrometric Calculation:
GROUND FLOOR:
Qs = 42741.53068 W
QL = 8103.950285 W
QS 42741.53068 W
SHF = = = 𝟎. 𝟖𝟒𝟎𝟔𝟏𝟔𝟏𝟏𝟓
QT 50845.48097 W
60
@ Outdoor Condition: 32.9 CDB and 27.8 CWB
Ps = 3.434982412 KPa
Then,
0.287 (32.9 + 273)
Vo =
101.325 − 2.847871882 KPa
𝐦𝟑
𝐕𝐨 = 𝟎. 𝟖𝟗𝟔𝟖𝟓𝟔𝟓𝟏𝟒𝟕
𝐤𝐠
Ventilation Load:
L 1m3 m3
Q = 68.44 × = 0.06844
s 1000 L s
m3
0.06844 s 𝐤𝐠
mo = = 𝟎. 𝟎𝟕𝟔𝟑𝟏𝟎𝟗𝟖𝟎𝟒𝟗
m3 𝐬
0.8968565147
kg
Then,
Qs = me Cp∆T
𝑚𝑒 = 𝑚𝑎
42.74153068 KW = ma (1.0062)(32.9 − 24)
𝐤𝐠
𝐦𝐚 = 𝟒. 𝟕𝟕𝟐𝟖𝟐𝟕𝟔𝟒𝟔
𝐬
𝒎𝒐 0.07631098049 𝑘𝑔/𝑠
= 𝑥 100%
𝒎𝒂 4.772827646 𝑘𝑔/𝑠
61
𝒎𝒐
= 𝟏. 𝟓𝟗𝟖𝟖𝟔𝟑𝟏𝟎𝟗 %
𝒎𝒂
𝒎𝒐 𝒎
Since, is less than 10%, use 10% for the value of 𝒎𝒐 .
𝒎𝒂 𝒂
mo wo + mR wR = me we
(0.1𝑚𝑎 )(0.0218261178 kg wv ⁄kg da ) + (0.9𝑚𝑎 )( 9.289440471 × 10−3 kg wv ⁄kg da )
= (𝑚𝑎 ) (we )
𝐰𝐞 = 𝟎. 𝟎𝟏𝟎𝟓𝟒𝟑𝟏𝟎𝟖𝟐 𝐤𝐠⁄𝐤𝐠
mo ho + mR hR = me he
(0.1𝑚𝑎 )(89.0142 kJ⁄kg) + (0.9𝑚𝑎 )( 47.79507072 kJ⁄kg) = (𝑚𝑎 ) (he )
𝐡𝐞 = 𝟓𝟏. 𝟗𝟏𝟔𝟗𝟖𝟑𝟔𝟓 𝐤𝐉⁄𝐤𝐠
mo t o + mR t R = me t e
(0.1𝑚𝑎 )(32.9℃) + (0.9𝑚𝑎 )( 24℃) = (𝑚𝑎 ) (Te )
𝐭 𝐞 = 𝟐𝟒. 𝟖𝟗𝐂
𝐓𝐋 = 𝟏𝟒. 𝟐𝐂
Capacity = me (he − hL )
𝑪𝒑 (𝒕𝑹 − 𝒕𝑳 )
𝑺𝑯𝑭 =
𝒉𝑹 − 𝒉𝑳
𝟏. 𝟎𝟎𝟔𝟐(𝟐𝟒 − 𝟏𝟒. 𝟐)
𝟎. 𝟖𝟒𝟎𝟔𝟏𝟔𝟏𝟏𝟓 =
𝟒𝟕. 𝟕𝟗𝟓𝟎𝟕𝟎𝟕𝟐 − 𝒉𝑳
Then, substituting,
𝟏 𝑻𝑶𝑹
A/C Capacity = 𝟕𝟓. 𝟔𝟔𝟎𝟑𝟓𝟏𝟕𝟓 𝐤𝐖 ∗ = 𝟐𝟏. 𝟓𝟏𝟒𝟓𝟖𝟖𝟎𝟒 𝑻𝑶𝑹
𝟑.𝟓𝟏𝟔𝟕 𝒌𝑾
75.66035175 kW 2
1 𝑇𝑂𝑅
𝑥 35.4102 𝑚 = 5.736695708 𝑘𝑊 ( )
467.0194 𝑚2 3.5167 𝑘𝑊
62
= 𝟏. 𝟔𝟑𝟏𝟐𝟕𝟐𝟒𝟏𝟕 𝑻𝑶𝑹
75.66035175 kW 1 𝑇𝑂𝑅
2
𝑥 49.5828 𝑚2 = 8.03275429 𝑘𝑊 ( )
467.0194 𝑚 3.5167 𝑘𝑊
= 𝟐. 𝟐𝟖𝟒𝟏𝟕𝟑𝟖𝟖𝟐 𝑻𝑶𝑹
75.66035175 kW 1 𝑇𝑂𝑅
2
𝑥 104.4966 𝑚2 = 16.92916721 𝑘𝑊 ( )
467.0194 𝑚 3.5167 𝑘𝑊
= 𝟒. 𝟖𝟏𝟑𝟗𝟑𝟓𝟓𝟔𝟕 𝑻𝑶𝑹
75.66035175 kW 1 𝑇𝑂𝑅
2
𝑥 73.5264 𝑚2 = 11.91178201 𝑘𝑊 ( )
467.0194 𝑚 3.5167 𝑘𝑊
= 𝟑. 𝟑𝟖𝟕𝟐𝟎𝟒𝟒𝟖𝟒 𝑻𝑶𝑹
75.66035175 kW 1 𝑇𝑂𝑅
2
𝑥 39.5694 𝑚2 = 6.410514686 𝑘𝑊 ( )
467.0194 𝑚 3.5167 𝑘𝑊
= 𝟏. 𝟖𝟐𝟐𝟖𝟕𝟕𝟖𝟗𝟑 𝑻𝑶𝑹
75.66035175 kW 1 𝑇𝑂𝑅
2
𝑥 25.88 𝑚2 = 4.192737825 𝑘𝑊 ( )
467.0194 𝑚 3.5167 𝑘𝑊
= 𝟏. 𝟏𝟗𝟐𝟐𝟑𝟔𝟒𝟐𝟐 𝑻𝑶𝑹
75.66035175 kW 1 𝑇𝑂𝑅
2
𝑥 12.64 𝑚2 = 2.047766851 𝑘𝑊 ( )
467.0194 𝑚 3.5167 𝑘𝑊
= 𝟎. 𝟓𝟖𝟐𝟐𝟗𝟕𝟖𝟓𝟎𝟔 𝑻𝑶𝑹
75.66035175 kW 1 𝑇𝑂𝑅
2
𝑥 27.24 𝑚2 = 4.41306717 𝑘𝑊 ( )
467.0194 𝑚 3.5167 𝑘𝑊
= 𝟏. 𝟐𝟓𝟒𝟖𝟖𝟖𝟕𝟐𝟐 𝑻𝑶𝑹
75.66035175 kW 2
1 𝑇𝑂𝑅
𝑥 44.495 𝑚 = 7.208495731 𝑘𝑊 ( )
467.0194 𝑚2 3.5167 𝑘𝑊
63
= 𝟐. 𝟎𝟒𝟗𝟕𝟖𝟗𝟕𝟖𝟑 𝑻𝑶𝑹
75.66035175 kW 1 𝑇𝑂𝑅
2
𝑥 17.934 𝑚2 = 2.905431227 𝑘𝑊 ( )
467.0194 𝑚 3.5167 𝑘𝑊
= 𝟎. 𝟖𝟐𝟔𝟏𝟖𝟏𝟏𝟒𝟑𝟑 𝑻𝑶𝑹
75.66035175 kW 1 𝑇𝑂𝑅
2
𝑥 36.245 𝑚2 = 5.871939044 𝑘𝑊 ( )
467.0194 𝑚 3.5167 𝑘𝑊
= 𝟏. 𝟔𝟔𝟗𝟕𝟐𝟗𝟖𝟕𝟑 𝑻𝑶𝑹
SECOND FLOOR:
Table 63.0
Summary of Heat Load Calculation for Second Floor
Equipment Selection.
64
Figure 12.0 A/C Diagram of Second Floor
Outside Condition:
TDB= 32.9C
TWB= 27.8C
te=24.89
SHF= 0.7273234892
TL=12.3C
Psychrometric Calculation:
SECOND FLOOR:
Qs = 64969.55535 W
QL = 24357.34813 W
65
QS 64969.55535 W
SHF = = = 𝟎. 𝟕𝟐𝟕𝟑𝟐𝟑𝟒𝟖𝟗𝟐
QT 89326.9038 W
SHF = 𝟎. 𝟕𝟐𝟕𝟑𝟐𝟑𝟒𝟖𝟗𝟐
0.622 Ps
𝐖𝐨 = = 𝟎. 𝟎𝟐𝟏𝟖𝟐𝟔𝟏𝟏𝟕𝟖𝟓 𝐤𝐠 𝐰𝐯 ⁄𝐤𝐠 𝐝𝐚
101.325−Ps
Ps = 3.434982412 KPa
Then,
0.287 (32.9 + 273)
Vo =
101.325 − 3.434982412 KPa
𝐦𝟑
𝐕𝐨 = 𝟎. 𝟖𝟗𝟔𝟖𝟓𝟔𝟓𝟏𝟒𝟕
𝐤𝐠
Ventilation Load:
L 1m3 m3
Q = 368.16 × = 0.36816
s 1000L s
m3
0.36816 s 𝐤𝐠
𝐦𝐨 = = 𝟎. 𝟒𝟏𝟎𝟓𝟎𝟎𝟒𝟒𝟔𝟖
m3 𝐬
0.8968565147
kg
66
Then,
Qs = me Cp∆T
𝐤𝐠
𝐦𝐞 = 𝟕. 𝟐𝟓𝟒𝟗𝟔𝟗𝟐𝟑
𝐬
𝒎𝒐 0.4105004468 𝑘𝑔/𝑠
= 𝑥 100%
𝒎𝒆 7.25496923 𝑘𝑔/𝑠
𝒎𝒐
= 𝟓. 𝟔𝟓𝟖𝟏𝟗𝟔𝟗𝟑𝟖 %
𝒎𝒂
𝒎𝒐 𝒎𝒐
Since, is less than 10%, use 10% for the value of .
𝒎𝒂 𝒎𝒂
mo wo + mR wR = me we
= me (we )
𝐰𝐞 = 𝟎. 𝟎𝟏𝟏𝟖𝟑𝟓𝟎𝟏𝟐𝟑𝟖 𝐤𝐠⁄𝐤𝐠
mo ho + mR hR = me he
mo t o + mR t R = me t e
𝐭 𝐞 = 𝟐𝟒. 𝟖𝟗𝐂
𝐓𝐋 = 𝟏𝟐. 𝟑𝐂
Capacity = me (he − hL )
𝑪𝒑 (𝒕𝑹 − 𝒕𝑳 )
𝑺𝑯𝑭 =
𝒉𝑹 − 𝒉𝑳
67
1.0062(24 − 12.3)
0.7273234892 =
51.44900635 − ℎ𝐿
Then, substituting,
114.6836003 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 38.6 𝑚2 = 9.061632654 𝑘𝑊 ( )
488.5198 𝑚 3.5167 𝑘𝑊
= 𝟐. 𝟓𝟕𝟕𝟐𝟓𝟔𝟏𝟓𝟗 𝑻𝑶𝑹
114.6836003 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 27.24 𝑚2 = 6.394789 𝑘𝑊 ( )
488.5198 𝑚 3.5167 𝑘𝑊
= 𝟏. 𝟖𝟏𝟖𝟕𝟔𝟖𝟑𝟑𝟔 𝑻𝑶𝑹
114.6836003 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 37.2811 𝑚2 = 8.752011221 𝑘𝑊 ( )
488.5198 𝑚 3.5167 𝑘𝑊
= 𝟐. 𝟒𝟖𝟖𝟔𝟗𝟗𝟗𝟖 𝑻𝑶𝑹
114.6836003 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 13.2516 𝑚2 = 3.1190110137 𝑘𝑊 ( )
488.5198 𝑚 3.5167 𝑘𝑊
= 𝟎. 𝟖𝟖𝟒𝟔𝟏𝟎𝟔𝟏𝟏𝟐 𝑻𝑶𝑹
For SSB:
114.6836003 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 13.088 𝑚2 = 3.07062578 𝑘𝑊 ( )
488.5198 𝑚 3.5167 𝑘𝑊
= 𝟎. 𝟖𝟕𝟑𝟏𝟓𝟓𝟒𝟓𝟐𝟔 𝑻𝑶𝑹
114.6836003 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 32.84 𝑚2 = 7.709430475 𝑘𝑊 ( )
488.5198 𝑚 3.5167 𝑘𝑊
= 𝟐. 𝟏𝟗𝟐𝟐𝟑𝟒𝟑𝟑𝟐 𝑻𝑶𝑹
68
114.6836003 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 29.7024 𝑚2 = 6.9728559 𝑘𝑊 ( )
488.5198 𝑚 3.5167 𝑘𝑊
= 𝟏. 𝟗𝟖𝟐𝟕𝟖𝟑𝟖𝟑𝟏 𝑻𝑶𝑹
114.6836003 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 45.9816 𝑚2 = 10.79451731 𝑘𝑊 ( )
488.5198 𝑚 3.5167 𝑘𝑊
= 𝟑. 𝟎𝟔𝟗𝟓𝟎𝟏𝟖𝟗𝟑 𝑻𝑶𝑹
114.6836003 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 85.8546 𝑚2 = 20.15499603 𝑘𝑊 ( )
488.5198 𝑚 3.5167 𝑘𝑊
= 𝟓. 𝟕𝟑𝟏𝟐𝟐𝟒𝟏𝟔𝟖 𝑻𝑶𝑹
114.6836003 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 29.6244 𝑚2 = 6.954544829 𝑘𝑊 ( )
488.5198 𝑚 3.5167 𝑘𝑊
= 𝟏. 𝟗𝟕𝟕𝟓𝟕𝟔𝟗𝟒𝟏 𝑻𝑶𝑹
114.6836003 𝑘𝑊 2
1 𝑇𝑂𝑅
𝑥 44.495 𝑚 = 10.44552707 𝑘𝑊 ( )
488.5198 𝑚2 3.5167 𝑘𝑊
= 𝟐. 𝟗𝟕𝟎𝟑𝟐𝟔𝟑𝟗𝟎𝟒 𝑻𝑶𝑹
114.6836003 𝑘𝑊 2
1 𝑇𝑂𝑅
𝑥 11.676 𝑚 = 2.741026499 𝑘𝑊 ( )
488.5198 𝑚2 3.5167 𝑘𝑊
= 𝟎. 𝟕𝟕𝟗𝟒𝟑𝟏𝟒𝟐𝟔𝟗 𝑻𝑶𝑹
114.6836003 𝑘𝑊 2
1 𝑇𝑂𝑅
𝑥 16.47 𝑚 = 3.866253104 𝑘𝑊 ( )
488.5198 𝑚2 3.5167 𝑘𝑊
= 𝟏. 𝟎𝟗𝟗𝟒𝟓𝟒𝟗𝟏𝟔 𝑻𝑶𝑹
114.6836003 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 14.2191 𝑚2 = 3.338037846 𝑘𝑊 ( )
488.5198 𝑚 3.5167 𝑘𝑊
= 𝟎. 𝟗𝟒𝟗𝟏𝟗𝟔𝟎𝟕𝟕𝟔 𝑻𝑶𝑹
69
114.6836003 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 21.96 𝑚2 = 5.155270805 𝑘𝑊 ( )
488.5198 𝑚 3.5167 𝑘𝑊
= 𝟏. 𝟒𝟔𝟓𝟗𝟑𝟗𝟖𝟖𝟖 𝑻𝑶𝑹
114.6836003 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 17.238 𝑚2 = 4.046746728 𝑘𝑊 ( )
488.5198 𝑚 3.5167 𝑘𝑊
= 𝟏. 𝟏𝟓𝟎𝟕𝟐𝟐𝟕𝟓𝟗 𝑻𝑶𝑹
For Office:
114.6836003 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 8.988 𝑚2 = 2.109998816 𝑘𝑊 ( )
488.5198 𝑚 3.5167 𝑘𝑊
= 𝟎. 𝟓𝟗𝟗𝟗𝟗𝟑𝟗𝟕𝟔𝟏 𝑻𝑶𝑹
THIRD FLOOR
Table 64.0
Summary of Heat Load Calculation for Third Floor
70
Figure 14.0 A/C Diagram of the Third Floor
Outside Condition:
TDB= 32.9C
TWB= 27.8C
te=24.89
SHF= 0.8279426491
TL=12.3C
Psychrometric Calculation:
THIRD FLOOR:
Qs = 9707.019197 W
QL = 2017.246013 W
QS 9707.019197 W
SHF = = = 𝟎. 𝟖𝟐𝟕𝟗𝟒𝟐𝟔𝟒𝟗𝟏
QT 11724.26521 W
71
@ Outdoor Condition: 32.9 CDB and 27.8 CWB
0.622 Ps
𝐖𝐨 = = 𝟎. 𝟎𝟐𝟏𝟖𝟐𝟔𝟏𝟏𝟕𝟖𝟓 𝐤𝐠 𝐰𝐯 ⁄𝐤𝐠 𝐝𝐚
101.325−Ps
Ps = 3.434982412 KPa
Then,
0.287 (32.9 + 273)
Vo =
101.325 − 3.434982412 KPa
𝐦𝟑
𝐕𝐨 = 𝟎. 𝟖𝟗𝟔𝟖𝟓𝟔𝟓𝟏𝟒𝟕
𝐤𝐠
For return air condition: @ 24CDB , 50% RH
0.622 PS 0.622 (0.5 × 3.434982412 2KPa)
𝐖𝐑 = =
PT − PS 101.325 − (0.5 × 3.434982412 KPa)
= 𝟎. 𝟎𝟏𝟎𝟕𝟐𝟒𝟖𝟖𝟗𝟓𝟓 𝐤𝐠 𝐰𝐯 ⁄𝐤𝐠 𝐝𝐚
Ventilation Load:
L 1m3 m3
Q = 16.52 × = 0.01652
s 1000 L s
m3
0.01652 s 𝐤𝐠
mo = = 𝟎. 𝟎𝟏𝟖𝟒𝟏𝟗𝟖𝟗𝟏𝟖𝟒
m3 𝐬
0.8968565147
kg
Then,
Qs = me Cp∆T
𝑚𝑒 = 𝑚𝑎
9.707019197 = ma (1.0062)(32.9 − 24)
𝐤𝐠
𝐦𝐚 = 𝟏. 𝟎𝟖𝟑𝟗𝟓𝟓𝟕𝟖𝟖
𝐬
𝒎𝒐 0.01841989184 𝑘𝑔/𝑠
= 𝑥 100%
𝒎𝒂 1.083955788 𝑘𝑔/𝑠
72
𝒎𝒐
= 𝟏. 𝟔𝟗𝟗𝟑𝟐𝟏𝟑𝟐𝟑 %
𝒎𝒂
𝒎𝒐 𝒎
Since, is less than 10%, use 10% for the value of 𝒎𝒐 .
𝒎𝒂 𝒂
mo ωo + mR ωR = me ωe
= (𝑚𝑎 ) (we )
𝐰𝐞 = 𝟎. 𝟎𝟏𝟏𝟖𝟑𝟓𝟎𝟏𝟐𝟑𝟖 𝐤𝐠⁄𝐤𝐠
mo ho + mR hR = me he
(0.1𝑚𝑎 )(89.0142 kJ⁄kg) + (0.9𝑚𝑎 )( 51.44900635 kJ⁄kg) = (𝑚𝑎 ) (he )
𝐡𝐞 = 𝟓𝟓. 𝟐𝟎𝟓𝟓𝟐𝟓𝟕𝟐 𝐤𝐉⁄𝐤𝐠
mo t o + mR t R = me t e
(0.1𝑚𝑎 )(32.9℃) + (0.9𝑚𝑎 )( 24℃) = me t e
𝐭 𝐞 = 𝟐𝟒. 𝟖𝟗𝐂
𝐓𝐋 = 𝟏𝟐. 𝟑𝐂
Capacity = me (he − hL )
𝑪𝒑 (𝒕𝑹 − 𝒕𝑳 )
𝑺𝑯𝑭 =
𝒉𝑹 − 𝒉𝑳
1.0062(24 − 12.3)
0.8279426491 =
51.44900635 − ℎ𝐿
Then, substituting,
73
For Unassigned Room 1:
19.48469899 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 44.495 𝑚2 = 8.549679278 𝑘𝑊 ( )
101.404 𝑚 3.5167 𝑘𝑊
= 𝟐. 𝟒𝟑𝟏𝟏𝟔𝟓𝟑𝟕𝟔 𝑻𝑶𝑹
19.48469899 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 11.676 𝑚2 = 2.243534223 𝑘𝑊 ( )
101.404 𝑚 3.5167 𝑘𝑊
= 𝟎. 𝟔𝟑𝟕𝟗𝟔𝟓𝟕𝟔𝟗𝟗 𝑻𝑶𝑹
19.48469899 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 36.245𝑚2 = 6.964448262 𝑘𝑊 ( )
101.404 𝑚 3.5167 𝑘𝑊
= 𝟏. 𝟗𝟖𝟎𝟑𝟗𝟑𝟎𝟓𝟕 𝑻𝑶𝑹
For Office:
19.48469899 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 8.988 𝑚2 = 1.727037144 𝑘𝑊 ( )
101.404 𝑚 3.5167 𝑘𝑊
= 𝟎. 𝟒𝟗𝟏𝟎𝟗𝟓𝟗𝟓𝟒𝟕 𝑻𝑶𝑹
FOURTH FLOOR
Table 65.0
Summary of Heat Load Calculation for Fourth Floor
74
The following data are used in Psychrometric Calculation leading to Equipment
Selection.
Total Sensible Heat load = 16396.44705 W
Total Latent Heat Load = 1860.986337 W
Total Heat Load = 18257.43339 W
Sensible Heat Ratio, SHR = 0.898069663
Outside Condition:
TDB= 32.9C
TWB= 27.8C
te=24.89
SHF= 0.898069663
TL=14.1C
75
Psychrometric Calculation:
FOURTH FLOOR:
Qs = 16396.44705 W
QL = 1860.986337 W
QS 16396.44705 W
SHF = = = 0.898069663
QT 18257.43339 W
0.622 Ps
𝐖𝐨 = = 𝟎. 𝟎𝟐𝟏𝟖𝟐𝟔𝟏𝟏𝟕𝟖𝟓 𝐤𝐠 𝐰𝐯 ⁄𝐤𝐠 𝐝𝐚
101.325−Ps
Ps = 3.434982412 KPa
Then,
0.287 (32.9 + 273)
Vo =
101.325 − 3.434982412 KPa
𝐦𝟑
𝐕𝐨 = 𝟎. 𝟖𝟗𝟔𝟖𝟓𝟔𝟓𝟏𝟒𝟕
𝐤𝐠
Ventilation Load:
L 1m3 m3
Q = 16.52 × = 0.01652
s 1000 L s
76
m3
0.01652 𝐤𝐠
mo = s = 𝟎. 𝟎𝟏𝟖𝟒𝟏𝟗𝟖𝟗𝟏𝟖𝟒
m3 𝐬
0.8968565147
kg
Then,
Qs = me Cp∆T
𝑚𝑒 = 𝑚𝑎
16.39644705 = ma (1.0062)(32.9 − 24)
𝐤𝐠
𝐦𝐚 = 𝟏. 𝟖𝟑𝟎𝟗𝟒𝟓𝟓𝟓𝟗
𝐬
𝒎𝒐 0.01841989184 𝑘𝑔/𝑠
= 𝑥 100%
𝒎𝒂 1.830945559/𝑠
𝒎𝒐
= 𝟏. 𝟎𝟎𝟔𝟎𝟑𝟏𝟔𝟓𝟏%
𝒎𝒂
𝒎𝒐 𝒎
Since, is less than 10%, use 10% for the value of 𝒎𝒐 .
𝒎𝒂 𝒂
mo ωo + mR ωR = me ωe
(0.1𝑚𝑎 )( 0.02182611785 kg wv ⁄kg da )
+ (0.9𝑚𝑎 )( 9.289440471 × 10−3 kg wv ⁄kg da ) = (𝑚𝑎 ) (we )
𝐰𝐞 = 𝟎. 𝟎𝟏𝟎𝟓𝟒𝟑𝟏𝟎𝟖𝟐𝟏 𝐤𝐠⁄𝐤𝐠
mo ho + mR hR = me he
(0.1𝑚𝑎 )(89.0142 kJ⁄kg) + (0.9𝑚𝑎 )( 51.44900635 kJ⁄kg) = (𝑚𝑎 ) (he )
𝐡𝐞 = 𝟓𝟓. 𝟐𝟎𝟓𝟓𝟐𝟓𝟕𝟐 𝐤𝐉⁄𝐤𝐠
mo t o + mR t R = me t e
(0.1𝑚𝑎 )(32.9℃) + (0.9𝑚𝑎 )( 24℃) = me t e
𝐭 𝐞 = 𝟐𝟒. 𝟖𝟗𝐂
𝐓𝐋 = 𝟏𝟒. 𝟏𝐂
Capacity = me (he − hL )
77
Solving for hL:
𝑪𝒑 (𝒕𝑹 − 𝒕𝑳 )
𝑺𝑯𝑭 =
𝒉𝑹 − 𝒉𝑳
1.0062(24 − 14.1)
0.898069663 =
51.44900635 − ℎ𝐿
Then, substituting,
27.18681286 𝑘𝑊 2
1 𝑇𝑂𝑅
𝑥 44.495 𝑚 = 11.92928522 𝑘𝑊 ( )
101.404 𝑚2 3.5167 𝑘𝑊
= 𝟑. 𝟑𝟗𝟐𝟏𝟖𝟏𝟔𝟓𝟑 𝑻𝑶𝑹
27.18681286 𝑘𝑊 2
1 𝑇𝑂𝑅
𝑥 11.676 𝑚 = 3.130302922 𝑘𝑊 ( )
101.404 𝑚2 3.5167 𝑘𝑊
= 𝟎. 𝟖𝟗𝟎𝟏𝟐𝟓𝟎𝟗𝟓𝟐 𝑻𝑶𝑹
27.18681286 𝑘𝑊 2
1 𝑇𝑂𝑅
𝑥 36.245𝑚 = 9.717183061 𝑘𝑊 ( )
101.404 𝑚2 3.5167 𝑘𝑊
= 𝟐. 𝟕𝟔𝟑𝟏𝟓𝟑𝟖𝟐𝟔 𝑻𝑶𝑹
For Office:
27.18681286 𝑘𝑊 1 𝑇𝑂𝑅
2
𝑥 8.988 𝑚2 = 2.409718295 𝑘𝑊 ( )
101.404 𝑚 3.5167 𝑘𝑊
= 𝟎. 𝟔𝟖𝟓𝟐𝟐𝟏𝟒𝟓𝟔𝟐 𝑻𝑶𝑹
78
Table 66.0
Summary of Required A/C Capacity per Floor
79
CHAPTER IV
CATALOGUE
After computing the A/C capacity of the air conditioning unit for each floor
level, the selection of the appropriate unit follows. This is based from the catalogue
given by A/C unit providers presented at the appendix. The chilled water air
For Second,
80
EQUIPMENT SCHEDULE
Table 67.0
Schedule of Air-Cooled Package Water Chiller
Electrical
Tag No. Quantity Description Make/Model Capacity Area Served Service Room Electrical
V Φ Hz
see attached
Series Water Ground Floor,
Carrier/ catalogue for
Cooled Screw Second Floor
Chiller - 1 1 100ZX100- 306 KW Roof Top 220 1 60 equipment
Compressor , Third Floor,
200 detailed
Chiller Fourth Floor
specification
Table 68.0
Schedule of CHW Pump
Service Electrical
Tag No. Quantity Description Make/Model Capacity Area Served Remarks
Room V Φ Hz
see attached
Self-Priming First Floor,
catalogue for
Open Impeller 100ZX100- Second Floor,
CHWP 2 27.8 L/s Roof Top 220 1 60 equipment
Pump, 200 Third Floor &
detailed
Fourth Floor
specification
81
Table 69.0
Schedule of CHW Fan Coil Unit (Ground Floor)
Service Electrical
Tag No. Quantity Description Make/Model Capacity Area Served Remarks
Room V Φ Hz
see attached
Suspended Land Management Office, catalogue for
Daikin /
FCU - 1 2 Ceiling Type 1.0 TOR Unassigned Room 2 First 220 1 60 equipment
FXHQ12MVJU
Fan Coil Unit detailed
specification
see attached
Office of the Municipal Treasurer(2x),
Suspended First catalogue for
Koppel / KCM- Unassigned Room 1 (2x),
FCU - 2 6 Ceiling Type 1.5 TOR 220 1 60 equipment
18CHW Telecommunication Room,
Fan Coil Unit detailed
Office of the Municipal Budget Officer
specification
see attached
Office of the Civil Registrar,
Suspended catalogue for
Daikin / Treasurer’s Office,
FCU - 3 5 Ceiling Type 2 TOR First 220 1 60 equipment
FXHQ24MVJU Unassigned Room 3,
Fan Coil Unit detailed
Office of the Assessor (2x)
specification
see attached
Suspended catalogue for
Koppel /
FCU-4 2 Ceiling Type 3 TOR First 220 1 60 equipment
KCM-36CH Office of the Municipal Engineer (2x)
Fan Coil Unit detailed
specification
82
Table 70.0
Schedule of Exhaust Fan (Ground Floor)
83
Table 71.0
Schedule of CHW Fan Coil Unit (Second Floor)
Electrical
Tag No. Quantity Description Make/Model Capacity Area Served Remarks
W RPM Hz
84
Table 72.0
Schedule of Exhaust Fan (Second Floor)
85
Table 73.0
Schedule of CHW Fan Coil Unit (Third Floor)
Electrical
Tag No. Quantity Description Make/Model Capacity Area Served Service Floor Remarks
W RPM Hz
see attached
Suspended catalogue for
Daikin / 1.0 TOR Unassigned Room 2,
FCU - 1 2 Ceiling Type Third 220 1 60 equipment
FXHQ12MVJU Office
Fan Coil Unit detailed
specification
see attached
Suspended catalogue for
Koppel / KCM- Unassigned Room 1
FCU - 2 2 Ceiling Type 1.5 TOR Third 220 1 60 equipment
18CHW (2x)
Fan Coil Unit detailed
specification
see attached
Suspended catalogue for
Daikin /
FCU - 3 1 Ceiling Type 2 TOR Third 220 1 60 equipment
FXHQ24MVJU Unassigned Room 3
Fan Coil Unit detailed
specification
86
Table 74.0
Schedule of Exhaust Fan (Third Floor)
Table 75.0
Schedule of CHW Fan Coil Unit (Fourth Floor)
Electrical
Tag No. Quantity Description Make/Model Capacity Area Served Service Floor Remarks
W RPM Hz
87
see attached
Suspended catalogue for
Daikin /
FCU - 3 2 Ceiling Type 2 TOR Unassigned Room 1 Third 220 1 60 equipment
FXHQ24MVJU
Fan Coil Unit (2x) detailed
specification
see attached
Suspended catalogue for
Koppel / KCM-
FCU - 4 1 Ceiling Type 3 TOR Unassigned Room 3 Third 220 1 60 equipment
36CHW
Fan Coil Unit detailed
specification
Table 76.0
Schedule of Exhaust Fan (Fourth Floor)
88
Table 77.0
Schedule of Exhaust Fan (Roof Deck)
Table 78.0
Schedule of Orbital Fan (Ground Floor)
89
Table 79.0
Schedule of Orbital Fan (Second Floor)
Table 80.0
Schedule of Orbital Fan (Third Floor and Fourth Floor)
90
CHAPTER V
This chapter presents the design of air distribution of chilled-water air conditioning system for a four-storey proposed renovation of the Municipal
Building of the Municipality of Mauban, Quezon.
Pipe Water Pressure
Flow Rate Pipe Equivalent Length Pressure Drop
Pipe Run Diameter Velocity Gradient
(L/s) (m) (Pa)
(mm) (m/s) (Pa/m)
Pump- Chiller 12.1854311 75/77.92 2.555366101 800 4m + 24m + (3)2.7m + 12m + (4)3m = 60.1m 48080
Chiller - A 12.1854311 75/77.92 2.555366101 800 2m+24m+2.7m+3m+0.9m+(3)3m = 41.6m 33280
A-B 11.20534015 75/77.92 2.349834498 650 3.2m + 0.9m = 4.1m 2665
B-C 10.2252492 75/77.92 2.144302895 510 2.5m + 0.9 + 17.34265072 = 20.74265072m 10578.75187
C-D 4.971761981 50/52.51 2.295812473 1000 3.2m + 0.6m = 3.8m 3800
D-E 4.691735996 50/52.51 2.166504764 880 3.546m + 0.6m + 2.1m = 6.246m 5496.48
E-F 4.481716507 50/52.51 2.069523983 820 4.045m + 0.6m = 4.645m 3808.9
F-G 4.271697018 50/52.51 1.972543201 800 4.1m + 0.6m = 4.7m 3760
G-H 4.131684026 50/52.51 1.907889347 790 1.5m + 0.6m + 2.1m = 4.2m 3318
H-I 3.29160607 50/52.51 1.519966221 490 13.92m + 0.6m = 14.52m 7114.8
I-J 3.081586581 50/52.51 1.42298544 470 2.4m + 0.6m = 3m 1410
J-K 2.661547603 50/52.51 1.229023877 300 0.8m + 0.6m = 1.4m 420
K-L 2.451528114 50/52.51 1.132043095 270 3.3m + 0.6m = 3.9m 1053
L-M 2.031489137 50/52.51 0.9380815327 200 3.715m + 0.6m = 4.315m 863
M-N 1.751463151 50/52.51 0.8087738237 150 7.585m+0.6m+3.74202009m=11.92702009m 1789.053014
N-O 1.541443662 40/40.90 1.17325161 400 1.58m + 1.5m + 0.5m = 3.58m 1432
O-FCU-1 1.40143067 40/40.90 1.066682378 340 4.815m + (2)1.7m + 1.5m = 9.715m 3303.1
Total Pressure Drop: 132172.0849 Pa
91
CHAPTER VI
DESIGN RECOMMENDATION AND CONCLUSION
CONCLUSIONS
orientation.
heating load calculations in this study are the temperature and air
92
needed by the air conditioning system as required by the heat
system that best suit the building structure, design condition, and
heat capacities.
RECOMMENDATIONS
Chilled Water Type Air Conditioning System for the Proposed Four-Storey
Province.
provide information about the new plan. Revisions in the plan may
affect the air conditioning and ventilation system design. The reason
for this is because the entire cooling load calculations are completely
noted as they are significant factors that will greatly affect the cooling
the calculations.
93
94