ADSS ELECTRICAL STRESS

PROJECT INFORMATION
Customer Name IR Comunicaciones
Project Name ADSS Para Linea de 132 kV - Argentina
Line Number Tipo S - Vertical
Tower Type Suspensión
Level Of Pullution Heavy
2 Medium Low Other [Ω/m]:
INPUT CONDUCTORS INPUT ADSS
Conductor Type or Name 300/50 mm2 ADSS Design No. DNA-XXXX
System Voltage [kV] 132 (Phase to Phase) Cable Diameter [mm] 12.600
System Frequency [Hz] 50
Conductor Diameter [mm] 28.00 ADSS Coordinates
Conductors Coordinates Phase A Phase B Phase C X [meters] -0.3
X1 [meters] 2.60 2.60 2.60 12.00
Y1 [meters] 10.65 14.05 17.45
X2 [meters] Electrical Field [kV/cm] 10.5
Y2 [meters] Rod Diameter [mm] 3.0
Conductors per Phase 1
Bundle Diameter [mm] 0 ADSS Resistance [Ω/m] 1.00E+06
Ground Wire Type or Name 50 mm2 Pollution Level Medium
Ground Wire Diameter [mm] 9.500 RESULTS
Ground Wire Coordinates ADSS Capacitance [F/m] 6.75E-12
X1 [meters] 0.5 ADSS Impedance [MΩ] 21.720
Y1 [meters] 20.9 Space Potential [kV] 6.27
X2 [meters] 0 Electrical Field [kV/cm] 10.5
Y2 [meters] 0 Induced Current [mA] 0.289
22.8 Vertical [meters]
21.8
20.9
19.9
19.0 25
18.0
17.1
16.1 20
30.50-35.50 15.2
14.2
25.50-30.50
Space Potential - kV

13.3
20.50-25.50 12.3 15
11.4
15.50-20.50
10.4 ADSS
10.50-15.50 9.5 10
8.5
5.50-10.50
7.6
0.50-5.50 6.6
5.7 5
4.7
3.8
2.8 0
1.9
-1 0 1 2 3
0.9
0.0 Conductor Distribution
-10.4
-9.5
-8.5
-7.6
-6.6
-5.7
-4.7
-3.8
-2.8
-1.9
-0.9
0.0
0.9
1.9
2.8
3.8
4.7
5.7
6.6
7.6
8.5
9.5
10.4

Horizontal [meters]

Tipo S - Vertical Tower : Suspensión April 14, 2010


ADSS ELECTRICAL STRESS
PROJECT INFORMATION
Customer Name IR Comunicaciones
Project Name ADSS Para Linea de 132 kV - Argentina
Line Number Tipo S - Vertical
Tower Type Suspensión
SPACE POTENTIAL CHART

Vertical [meters]
22.8

21.8

20.9

19.9

19.0

18.0

17.1

16.1

15.2

14.2

13.3

12.3

11.4

10.4

9.5
Vertical [feet]
8.5

7.6

6.6

5.7

4.7

3.8

2.8

1.9

0.9

0.0
-10.4
-9.5
-8.5
-7.6
-6.6
-5.7
-4.7
-3.8
-2.8
-1.9
-0.9
0.0
0.9
1.9
2.8
3.8
4.7
5.7
6.6
7.6
8.5
9.5
10.4

Horizontal [meters]

Space Potential [kV]

0.00-5.00 5.00-10.00 10.00-15.00 15.00-20.00 20.00-25.00 25.00-30.00

Tipo S - Vertical Tower : Suspensión April 14, 2010


ADSS ELECTRICAL STRESS
PROJECT INFORMATION
Customer Name IR Comunicaciones
Project Name ADSS Para Linea de 132 kV - Argentina
Line Number Tipo S - Vertical
Tower Type Suspensión
INDUCED CURRENT CHART

Vertical [meters]

22.8

21.8

20.9

19.9

19.0

18.0

17.1

16.1

15.2

14.2

13.3

12.3

11.4

10.4

9.5

8.5

7.6

6.6

5.7

4.7

3.8

2.8

1.9

0.9

0.0
-10 -9 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 9 10
Horizontal [meters]

Induce Current [mA]

0.00-0.50 0.50-1.00

Tipo S - Vertical Tower : Suspensión April 14, 2010


ADSS ELECTRICAL STRESS
PROJECT INFORMATION
Customer Name IR Comunicaciones
Project Name ADSS Para Linea de 132 kV - Argentina
Line Number Tipo R - Vertical
Tower Type Retensión
Level Of Pullution Heavy
2 Medium Low Other [Ω/m]:
INPUT CONDUCTORS INPUT ADSS
Conductor Type or Name 300/50 mm2 ADSS Design No. DNA-XXXX
System Voltage [kV] 132 (Phase to Phase) Cable Diameter [mm] 12.600
System Frequency [Hz] 50
Conductor Diameter [mm] 28.00 ADSS Coordinates
Conductors Coordinates Phase A Phase B Phase C X [meters] -0.3
X1 [meters] 2.60 2.60 2.60 13.00
Y1 [meters] 11.80 14.80 17.80
X2 [meters] Electrical Field [kV/cm] 10.5
Y2 [meters] Rod Diameter [mm] 3.0
Conductors per Phase 1
Bundle Diameter [mm] 0 ADSS Resistance [Ω/m] 1.00E+06
Ground Wire Type or Name 50 mm2 Pollution Level Medium
Ground Wire Diameter [mm] 9.500 RESULTS
Ground Wire Coordinates ADSS Capacitance [F/m] 6.68E-12
X1 [meters] 0.6 ADSS Impedance [MΩ] 21.825
Y1 [meters] 20.8 Space Potential [kV] 5.83
X2 [meters] 0 Electrical Field [kV/cm] 10.5
Y2 [meters] 0 Induced Current [mA] 0.267
22.7 Vertical [meters]
21.7
20.8
19.8
18.9 25
17.9
17.0
16.0 20
30.50-35.50 15.1
14.2
25.50-30.50
Space Potential - kV

13.2
20.50-25.50 12.3 15
11.3 ADSS
15.50-20.50
10.4
10.50-15.50 9.4 10
8.5
5.50-10.50
7.6
0.50-5.50 6.6
5.7 5
4.7
3.8
2.8 0
1.9
-1 0 1 2 3
0.9
0.0 Conductor Distribution
-10.4
-9.4
-8.5
-7.6
-6.6
-5.7
-4.7
-3.8
-2.8
-1.9
-0.9
0.0
0.9
1.9
2.8
3.8
4.7
5.7
6.6
7.6
8.5
9.4
10.4

Horizontal [meters]

Tipo R - Vertical Tower : Retensión April 14, 2010


ADSS ELECTRICAL STRESS
PROJECT INFORMATION
Customer Name IR Comunicaciones
Project Name ADSS Para Linea de 132 kV - Argentina
Line Number Tipo R - Vertical
Tower Type Retensión
SPACE POTENTIAL CHART

Vertical [meters]
22.7

21.7

20.8

19.8

18.9

17.9

17.0

16.0

15.1

14.2

13.2

12.3

11.3

10.4

9.4
Vertical [feet]
8.5

7.6

6.6

5.7

4.7

3.8

2.8

1.9

0.9

0.0
-10.4
-9.4
-8.5
-7.6
-6.6
-5.7
-4.7
-3.8
-2.8
-1.9
-0.9
0.0
0.9
1.9
2.8
3.8
4.7
5.7
6.6
7.6
8.5
9.4
10.4

Horizontal [meters]

Space Potential [kV]

0.00-5.00 5.00-10.00 10.00-15.00 15.00-20.00 20.00-25.00 25.00-30.00

Tipo R - Vertical Tower : Retensión April 14, 2010


ADSS ELECTRICAL STRESS
PROJECT INFORMATION
Customer Name IR Comunicaciones
Project Name ADSS Para Linea de 132 kV - Argentina
Line Number Tipo R - Vertical
Tower Type Retensión
INDUCED CURRENT CHART

Vertical [meters]

22.7

21.7

20.8

19.8

18.9

17.9

17.0

16.0

15.1

14.2

13.2

12.3

11.3

10.4

9.4

8.5

7.6

6.6

5.7

4.7

3.8

2.8

1.9

0.9

0.0
-10 -9 -8 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 8 9 10
Horizontal [meters]

Induce Current [mA]

0.00-0.50 0.50-1.00

Tipo R - Vertical Tower : Retensión April 14, 2010


ADSS ELECTRICAL STRESS
PROJECT INFORMATION
Customer Name IR Comunicaciones
Project Name ADSS Para Linea de 132 kV - Argentina
Line Number Tipo R - Alternada
Tower Type Retensión
Level Of Pullution Heavy
2 Medium Low Other [Ω/m]:
INPUT CONDUCTORS INPUT ADSS
Conductor Type or Name 300/50 mm2 ADSS Design No. DNA-XXXX
System Voltage [kV] 132 (Phase to Phase) Cable Diameter [mm] 12.600
System Frequency [Hz] 50
Conductor Diameter [mm] 28.00 ADSS Coordinates
Conductors Coordinates Phase A Phase B Phase C X [meters] -0.3
X1 [meters] 2.40 -2.40 2.40 12.50
Y1 [meters] 13.20 14.70 16.20
X2 [meters] Electrical Field [kV/cm] 10.5
Y2 [meters] Rod Diameter [mm] 3.0
Conductors per Phase 1
Bundle Diameter [mm] 0 ADSS Resistance [Ω/m] 1.00E+06
Ground Wire Type or Name 50 mm2 Pollution Level Medium
Ground Wire Diameter [mm] 9.500 RESULTS
Ground Wire Coordinates ADSS Capacitance [F/m] 6.71E-12
X1 [meters] 0.6 ADSS Impedance [MΩ] 21.774
Y1 [meters] 20 Space Potential [kV] 6.52
X2 [meters] 0 Electrical Field [kV/cm] 10.5
Y2 [meters] 0 Induced Current [mA] 0.300
21.8 Vertical [meters]
20.9
20.0
19.1
18.2 25
17.3
16.4
15.5 20
30.50-35.50 14.5
13.6
25.50-30.50
Space Potential - kV

12.7
20.50-25.50 11.8 15
10.9
15.50-20.50 ADSS
10.0
10.50-15.50 9.1 10
8.2
5.50-10.50
7.3
0.50-5.50 6.4
5.5 5
4.5
3.6
2.7 0
1.8
-4 -2 0 2 4
0.9
0.0 Conductor Distribution
-10.0
-9.1
-8.2
-7.3
-6.4
-5.5
-4.5
-3.6
-2.7
-1.8
-0.9
0.0
0.9
1.8
2.7
3.6
4.5
5.5
6.4
7.3
8.2
9.1
10.0

Horizontal [meters]

Tipo R - Alternada Tower : Retensión April 14, 2010


ADSS ELECTRICAL STRESS
PROJECT INFORMATION
Customer Name IR Comunicaciones
Project Name ADSS Para Linea de 132 kV - Argentina
Line Number Tipo R - Alternada
Tower Type Retensión
SPACE POTENTIAL CHART

Vertical [meters]
21.8

20.9

20.0

19.1

18.2

17.3

16.4

15.5

14.5

13.6

12.7

11.8

10.9

10.0

9.1
Vertical [feet]
8.2

7.3

6.4

5.5

4.5

3.6

2.7

1.8

0.9

0.0
-10.0
-9.1
-8.2
-7.3
-6.4
-5.5
-4.5
-3.6
-2.7
-1.8
-0.9
0.0
0.9
1.8
2.7
3.6
4.5
5.5
6.4
7.3
8.2
9.1
10.0

Horizontal [meters]

Space Potential [kV]

0.00-5.00 5.00-10.00 10.00-15.00 15.00-20.00 20.00-25.00 25.00-30.00

Tipo R - Alternada Tower : Retensión April 14, 2010


ADSS ELECTRICAL STRESS
PROJECT INFORMATION
Customer Name IR Comunicaciones
Project Name ADSS Para Linea de 132 kV - Argentina
Line Number Tipo R - Alternada
Tower Type Retensión
INDUCED CURRENT CHART

Vertical [meters]

21.8

20.9

20.0

19.1

18.2

17.3

16.4

15.5

14.5

13.6

12.7

11.8

10.9

10.0

9.1

8.2

7.3

6.4

5.5

4.5

3.6

2.7

1.8

0.9

0.0
-10 -9 -8 -7 -6 -5 -5 -4 -3 -2 -1 0 1 2 3 4 5 5 6 7 8 9 10
Horizontal [meters]

Induce Current [mA]

0.00-0.50 0.50-1.00

Tipo R - Alternada Tower : Retensión April 14, 2010


ADSS ELECTRICAL STRESS
PROJECT INFORMATION
Customer Name IR Comunicaciones
Project Name ADSS Para Linea de 132 kV - Argentina
Line Number Tipo S - Alternada
Tower Type Suspensión
Level Of Pullution Heavy
2 Medium Low Other [Ω/m]:
INPUT CONDUCTORS INPUT ADSS
Conductor Type or Name 300/50 mm2 ADSS Design No. DNA-XXXX
System Voltage [kV] 132 (Phase to Phase) Cable Diameter [mm] 12.600
System Frequency [Hz] 50
Conductor Diameter [mm] 28.00 ADSS Coordinates
Conductors Coordinates Phase A Phase B Phase C X [meters] -0.3
X1 [meters] 2.60 -2.60 2.60 14.95
Y1 [meters] 13.60 15.40 17.20
X2 [meters] Electrical Field [kV/cm] 10.5
Y2 [meters] Rod Diameter [mm] 3.0
Conductors per Phase 1
Bundle Diameter [mm] 0 ADSS Resistance [Ω/m] 1.00E+06
Ground Wire Type or Name 50 mm2 Pollution Level Medium
Ground Wire Diameter [mm] 9.500 RESULTS
Ground Wire Coordinates ADSS Capacitance [F/m] 6.57E-12
X1 [meters] 0.6 ADSS Impedance [MΩ] 22.008
Y1 [meters] 20.7 Space Potential [kV] 6.00
X2 [meters] 0 Electrical Field [kV/cm] 10.5
Y2 [meters] 0 Induced Current [mA] 0.273
22.6 Vertical [meters]
21.6
20.7
19.7
18.8 25
17.9
16.9
16.0 20
30.50-35.50 15.0
14.1
25.50-30.50
Space Potential - kV

13.2
20.50-25.50 12.2 15 ADSS
11.3
15.50-20.50
10.3
10.50-15.50 9.4 10
8.5
5.50-10.50
7.5
0.50-5.50 6.6
5.6 5
4.7
3.8
2.8 0
1.9
-4 -2 0 2 4
0.9
0.0 Conductor Distribution
-10.3
-9.4
-8.5
-7.5
-6.6
-5.6
-4.7
-3.8
-2.8
-1.9
-0.9
0.0
0.9
1.9
2.8
3.8
4.7
5.6
6.6
7.5
8.5
9.4
10.3

Horizontal [meters]

Tipo S - Alternada Tower : Suspensión April 14, 2010


ADSS ELECTRICAL STRESS
PROJECT INFORMATION
Customer Name IR Comunicaciones
Project Name ADSS Para Linea de 132 kV - Argentina
Line Number Tipo S - Alternada
Tower Type Suspensión
SPACE POTENTIAL CHART

Vertical [meters]
22.6

21.6

20.7

19.7

18.8

17.9

16.9

16.0

15.0

14.1

13.2

12.2

11.3

10.3

9.4
Vertical [feet]
8.5

7.5

6.6

5.6

4.7

3.8

2.8

1.9

0.9

0.0
-10.3
-9.4
-8.5
-7.5
-6.6
-5.6
-4.7
-3.8
-2.8
-1.9
-0.9
0.0
0.9
1.9
2.8
3.8
4.7
5.6
6.6
7.5
8.5
9.4
10.3

Horizontal [meters]

Space Potential [kV]

0.00-5.00 5.00-10.00 10.00-15.00 15.00-20.00 20.00-25.00 25.00-30.00

Tipo S - Alternada Tower : Suspensión April 14, 2010


ADSS ELECTRICAL STRESS
PROJECT INFORMATION
Customer Name IR Comunicaciones
Project Name ADSS Para Linea de 132 kV - Argentina
Line Number Tipo S - Alternada
Tower Type Suspensión
INDUCED CURRENT CHART

Vertical [meters]

22.6

21.6

20.7

19.7

18.8

17.9

16.9

16.0

15.0

14.1

13.2

12.2

11.3

10.3

9.4

8.5

7.5

6.6

5.6

4.7

3.8

2.8

1.9

0.9

0.0
-10 -9 -8 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 8 9 10
Horizontal [meters]

Induce Current [mA]

0.00-0.50 0.50-1.00