Sunteți pe pagina 1din 8

1366 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO.

3, JULY 2008

A Universal Fault Location Technique for N-Terminal


(N 3) Transmission Lines
Chih-Wen Liu, Senior Member, IEEE, Kai-Ping Lien, Ching-Shan Chen, and Joe-Air Jiang, Member, IEEE

Abstract—This paper presents a universal fault location tech- few of the many references are included in the references. Abe
nique for N-terminal ( 3) transmission lines based on et al. [6] used synchronized three-phase voltages and currents at
synchronized phasor measurement units. The development of the all terminals. They proposed an algorithm using voltage differ-
technique is based on two-terminal fault location technique. The
proposed algorithm is different from traditional multiterminal entials at terminals to gradually reduce a multiterminal line to a
fault location techniques. We apply two-terminal fault location two-terminal line containing the faulted section. Then, a reactive
technique to N-terminal transmission lines and propose a novel power-based method was used to locate the fault. Nagasawa et
fault section selector/fault locator. The proposed method has a al. [7] used current differentials at terminals to perform a similar
very good tolerance. The proposed approach provides an analyt- reduction. Their reduction procedure was very complicated and
ical solution and its computational burden is very low since it does
not require iterative operations. An extensive series of simulations also normalized section impedances when impedances were dif-
were conducted to verify the accuracy of the proposed algorithm. ferent. However, this is a source of error. Funabashi et al. [8] uti-
The average fault location error under various fault conditions is lized synchronized current inputs from all terminals and devel-
well below 1%. oped two different methods to locate the fault. The paper, how-
Index Terms—Fault location, multiterminal transmission lines, ever, failed to report results for three-phase and two-phase to
phasor measurement units (PMUs). ground faults. Sanderson et al. [9] used both current and voltage
data to identify the terminal electrically nearest to the fault. Al-
though the paper reported successful results in identifying the
I. INTRODUCTION
faulted section, the exact fault location on the section was not
attempted. Brahma [10] adopted synchronized voltage measure-

I N POWER systems, transmission lines are vital links that


achieve the essential continuity of service from the gener-
ating plants to the end users. From views of economics and
ments to locate the exact fault location. Although the paper re-
ported successful results for locating the fault, the exact source
impedance must be considered. The authors proposed fault lo-
quality of power feeding, the importance of fault location to the cation/detection techniques for transmission lines based on syn-
transmission lines is increasing. As a result, the development of chronized phasor measurement units [11], [12]. The developed
a robust and accurate fault location technique is a highly impor- fault location/detection indices also can be used for transmis-
tant research area [1]–[5]. sion line protection [13]–[15].
The fault location techniques of transmission lines can be This paper proposes a new fault section selector/fault locator
mainly classified into one-terminal and multiterminals based for N-terminal transmission lines. All two-terminal fault loca-
techniques. Since the new rights of way for transmission lines tion techniques that use synchronized voltage and current mea-
are difficult to obtain, a lot of double-circuit and three-terminal surement data can apply the proposed method to develop their
transmission lines exist in power systems. With the current fault location techniques for N-terminal lines. Also, the fault
trend toward multiterminal power transmission lines, one-ter- section selector/fault locator is a universal algorithm so that it
minal fault location systems are of limited use because they are is suitable for any type of multiterminal transmission lines such
unable to determine whether or not a fault that lies beyond a as double-circuit lines, nonhomogeneous lines, short lines, long
tap point is a branch line fault. lines, and any multiterminal lines with arbitrary configuration.
Present communication technology allows for use of data
from multi ends of transmission lines. A variety of such mul- II. FAULT LOCATION TECHNIQUE
tiended data based algorithms have been presented, but only a
A. Two-Terminal Fault Location Technique
Consider a single-circuit transmission line shown in Fig. 1.
Manuscript received April 11, 2007; revised July 31, 2007. This work was The voltages and currents at a distance of kilometers away
supported in part by the National Science Council of Taiwan, R.O.C., under
Contract NSC-93-2213-E-002-054. Paper no. TPWRD-00181-2007 from the receiving end can be obtained as [11]
C.-W. Liu is with the Department of Electrical Engineering, National Taiwan
University, Taipei 106, Taiwan, R.O.C. (e-mail: cwliu@cc.ee.ntu.edu.tw). (1)
K.-P. Lien is with Bei-Tou Incinerator, Department of Environmental Protec-
tion, Taipei City Government, Taipei 106, Taiwan, R.O.C. (2)
C.-S. Chen is with the Industrial Technology Research Institute, Hsinchu 310,
Taiwan, R.O.C. (e-mail: JohnsonChen@itri.org.tw). where denotes the characteristic impedance, and
J.-A. Jiang is with the Department of Bio-Industrial Mechatronics Engi- is the propagation constant. and are the se-
neering, National Taiwan University, Taipei 106, Taiwan, R.O.C. (e-mail:
jajiang@ntu.edu.tw). quence impedance and admittance of transmission line, respec-
Digital Object Identifier 10.1109/TPWRD.2008.919244 tively.
0885-8977/$25.00 © 2008 IEEE
LIU et al.: UNIVERSAL FAULT LOCATION TECHNIQUE 1367

Fig. 1. One-line diagram of a single-circuit transmission line under a fault oc-


curs at a distance x= DL away from the receiving end R.

Constants A and B in (1) can be determined by the boundary


condition of voltages and currents measured at receiving end R Fig. 2. One-line diagram of a three-terminal line under a fault occurs.
and sending end S, respectively. Therefore, the voltage equation
of (1) can be further rewritten as We can derive the voltage and current phasors at point and
express them in terms of the data sets ( , ) at sending end
(3)
(8)
(4)
(9)
where the subscripts and in the voltages measured at “x”
point denote that the voltages are expressed in terms of the two
data sets ( , ) and ( , ) measured at the sending and According to Kirchhoff’s law, we have
receiving ends of the line, respectively.
(10)
Suppose that a midway fault occurred at the point F which
is km away from receiving end on a transmission where is the injective current of the tap branch, which is given
line shown in Fig. 1. Equating and solving the two (3) and (4), a by
per-unit fault location index can be obtained via the following
equation [11]:
(11)
(5)
Similarly, we can derive the new fault location index , and
where and are given by then obtain the fault location away from receiving
end
(6)
(12)
(7) where
When no fault or an external fault occurs, the fault location (13)
index is an indefinite value [11], [12]. If the fault location
technique uses symmetrical components of voltages and cur- and
rents rather than phase values, the three-phase system can be
treated like three single circuits. By virtue of these decoupled (14)
single-phase circuits, the fault location of the original three-
phase transmission line system can be obtained and thus the Similarly, we can derive the voltage and current phasors at
computation burden is reduced significantly. Moreover, use of point and express them in terms of the data sets ( , ) at
positive sequence quantities (applicable for all fault types) is the sending end . We also acquire the new fault location index
preferred choice to avoid fault type identification. , and then obtain the fault location away from
receiving end
B. Fault Location Technique for Multi-Terminal Lines
(15)
1) Three-Terminal Lines: As shown in Fig. 2, it is a one-line
diagram of a three-terminal transmission line. The PMUs are in- where
stalled at buses and . Therefore, we can obtain three-ter-
minal synchronized voltage and current phasors. We will con- (16)
sider the injective currents that come from the tap branch of mul-
titerminal lines. Tap point of the transmission line system is and
selected as virtual sending end . We define the line section
length as reference per-unit length of fault location indices. (17)
1368 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 3, JULY 2008

TABLE I
FAULTED SECTION/FAULT LOCATION IDENTIFICATION
FOR THREE-TERMINAL LINES

Fig. 3. One-line diagram of an N + 1 terminal transmission lines.


Therefore, the two-terminal data fault location technique de-
scribed previously can be used to derive the fault location in-
dices. Both of the indices and can be applied to locate
faults occurring in , , and . There are special relation-
ships between the two indices and . They can be used to
identify the faulted line segment and locate faults. The relation-
ships are summarized and listed in Table I. In next section, we
will develop a general form of the faulted section/fault location
identification for any multiterminal lines.
2) -Terminal Transmission Lines: Consider an -ter-
minal transmission lines depicted in Fig. 3. The PMUs
are installed at receiving bus R and sending buses . There-
fore, we can obtain the synchronized voltage and current phasors
at terminals of the considered system. First, we select tap
point P1 as virtual sending end P1. The line section length is
definedasreferenceper-unitlengthoffaultlocationindices.Fig.4
illustrates the procedure of our fault location technique for multi-
terminal transmission lines. The procedures of the proposed fault
location algorithm for multiterminal lines are divided into three
steps.
Step 1) Select any one bus as receiving end and the others
are sending ends. The nearest tap point P1 to receiving
end is selected as virtual sending end. The line sec- Fig. 4. Fault location scheme for multiterminal lines.
tion length from P1 to receiving end is defined as
reference per unit length of fault location index. So,
Step 3) Fault Section Selector/Fault Locator
in this case.
The indices can be applied to
Step 2) Fault Index Generator
locate faults occurring in all branches of the trans-
1) The voltages and currents at the virtual sending
mission line system. There are some special relation-
end P1 are expressed in terms of the boundary
ships among these indices to identify the faulted line
conditions at sending ends , where
branch and locate faults. The details will be presented
.
in the next subsection. According to the special rela-
2) Apply the adopted two-terminal fault location
tionships among these indices, the proposed fault sec-
technique to acquire fault location indices of all
tion selector/locator can correctly identify a faulted
sending ends and storage all fault location in-
section and fault location for multiterminal lines.
dices.
We derive the fault location indices , where C. Proposed Fault Location Indices
In order to introduce the proposed fault location indices con-
(18) veniently, we define the path that is from receiving end to
sending end as the fault location path of (refering to
Also, and are, respectively, expressed as Fig. 5, the dotted line sections represent that they do not be-
long to the fault location path of ). The fault location indices
(19) ’s are used to locate faults at the fault location path of .
For internal faults, there are two types of fault events that should
and be considered. Type A (as shown in Fig. 5) is that a fault occurs
at the fault location path of . Type B (as shown in Fig. 6) is
(20) that a fault does not occur at the fault location path of .
LIU et al.: UNIVERSAL FAULT LOCATION TECHNIQUE 1369

Fig. 5. Type A: Fault occurs at the fault location path of D . Fig. 7. Fault occurs at the tap point P (K 0 1).

Fig. 8. Case 1: Fault occurs at the line section PK 0 P (K +) 1 .

equals that of the tap point, i.e., the joint of the faulted section
and the fault location path of , to the receiving end.
Fig. 6. Type B: Fault does not occur at the fault location path of D . According to the above discussion, we find that any a fault
location index can be used to locate fault at its fault loca-
tion path of . As for fault beyond its fault location path of
Type A: Suppose that a midway fault occurred at the point , the fault location index merely point out the joint of
F which is km away from receiving end R on the the faulted section and the fault location path of , to the re-
fault location path of as shown in Fig. 5. The fault location ceiving end. Based on this fact, a novel algorithm is proposed in
path of is thus divided into two parts. One is line section the following section.
– , the other is line section – .
The voltages at fault point that are expressed in terms of D. Fault Section Selector/Fault Position Locator
these two data sets ( , ) and ( , ) are identical. We can
derive the fault location index . The fault location index For an multiterminal line, there are sending ends and
can correctly locate the fault that is a distance of a receiving end. Therefore, the proposed fault location technique
from away receiving end . can generate fault location indices . We can find
Type B: An internal fault does not occur at the fault location four special relationships among these indices.
path of (refer to Fig. 6). Case 1: A fault occurs at the line section .
As shown in Fig. 6, a fault occurs at the line section As shown in Fig. 8, the fault occurs at the line section
. This line section does not belong to the fault lo- . The computed fault location indices for Case 1 are
cation path of . As mentioned above, we have considered shown in Fig. 9. It is clearly seen that the values of the fault
the injective currents of all tap points during estimating the location indices are equal
voltage and current phasors at virtual sending end P1. Due to and bigger than the remaining indices. We know that the
the fault occurred in tap branch, we know that the injective cur- correct fault location is
rent of tap point estimated by PMU at away from receiving end .
Bus is wrong. Therefore, the fault location path of is Case 2: A fault occurs at the section
thus divided into two parts. One is line section , Fig. 10 depicts the case that the fault occurs at the line section
the other is line section . The voltage at tap point . The computed fault location indices for Case 2 are
that are expressed in terms of these two data sets ( , shown in Fig. 9. It is clearly seen that the value of the fault lo-
) and ( , ) are identical. Thus, we can derive the fault lo- cation index is the maximum. We conclude that the correct
cation index . But, the fault location index points out fault location is away from receiving end .
tap point that is a distance of from away Case 3: A fault occurs at the line section .
receiving end (as shown in Fig. 7). In summary, if a fault does As shown in Fig. 11, the fault occurs at the line section
not occur at the fault location path of , the proposed algo- . The magnitudes of all fault location indices are equal as
rithm still can output a value of fault location index , which shown in Fig. 9.
corresponds to the actual distance . This distance Case 4: An external fault or no fault occurs.
1370 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 3, JULY 2008

Fig. 9. Variation curves of fault location indices under Case 1, 2, and 3.

Fig. 12. Proposed fault section selector/locator for N-terminal lines.

Fig. 10. Case 2: Fault occurs at the line section PK-K.

Fig. 13. Simulation system consists of a transposed double-circuit five-ter-


minal transmission line and an external line 4–5.

Fig. 11. Case 3: Fault occurs at the line section P1- R.


B. Untransposed Multiterminal Lines
The previously developed technique is based on the assump-
When no fault or an external fault occurs, the voltages at any tion that the considered transmission line system is transposed.
point on the transmission line that are expressed in terms of For these cases, we can use positive sequence equivalent cir-
the two data sets ( , ) and ( , ) are identical. It can cuits to calculate the fault location. If the transmission line
be found that all the fault location indices ’s are indefinite system is untransposed, the diagonal quantities of the phase
values. impedance and admittance matrices can be averaged to obtain
Based on the observations from the above four cases, we pro- self-impedance and self-admittance. Similarly, the off-diagonal
pose a fault section selector/fault position locator for multiter- quantities can be averaged to obtain the mutual impedance
minal lines, which can be illustrated by Fig. 12. The proposed and admittance. Then, using symmetrical components trans-
fault section selector/locator meets all multiterminal transmis- formation, we can obtain the approximate positive sequence
sion lines. The values of some fault location indices are equal parameters and equivalent positive sequence single-circuit. The
(for example, ) in simulation results indicate that only slight error is introduced to
theory, even if, there are few differences among the values of the estimation of fault location under untranposed line system
these indices in simulations. The difference within 1% among considered.
these indices will be treated equally without discrimination.
IV. SIMULATION RESULTS
III. FAULT LOCATION TECHNIQUE FOR OTHER
TYPES OF MULTITERMINAL LINES A. Five-Terminal Transmission Line System
A 345-kV 60-Hz transposed double-circuit five-terminal
A. Double Circuit/Multiterminal Lines
transmission line with zero sequence mutual coupling was
Since only positive sequence data is used in the proposed modeled as shown in Fig. 13. The simulated sample system
algorithm, the double-circuit transmission line can be treated can be used to demonstrate the correctness of the mentioned
as two independent single-circuit lines. The transmission line fault location technique for transmission lines. Circuit 2 is the
system in Fig. 13 is equivalent to two individual multiterminal protected transmission line system. Line 4–5 is used to evaluate
lines. Therefore, the fault location technique developed previ- the performance of the proposed algorithm for external faults.
ously also can be directly applied to the transmission line system The related parameters of the simulated system are summarized
shown in Fig. 13. in Table II. The transmission line parameters are obtained
LIU et al.: UNIVERSAL FAULT LOCATION TECHNIQUE 1371

TABLE II
PARAMETERS OF A FIVE-TERMINAL TRANSMISSION LINE SYSTEM

Fig. 14. The post-fault response curves of the proposed fault location indices
for (a) an external fault and (b) an internal fault.

TABLE III
PERFORMANCE EVALUATION OF THE PROPOSED FAULT LOCATION
TECHNIQUE FOR FIVE-TERMINAL LINES

using EMTP LINE CONSTANTS program [16], [17] based


on related tower data encountered in Taiwan. The sampling
frequency is 3840 Hz (64 sampling points per cycle). This
work uses a digital mimic filter [18] to eliminate dc-offset
and full-cycle discrete Fourier transform (DFT) is applied to
estimate the phasors with fundamental frequency.
The simulation studies have been conducted with respect to
various system operation and fault conditions. The error of fault
location algorithm is evaluated as

estimated location-actual location


Error (21)
the line section length of

1) Test for Fault Section Selector/Fault Locator: Fig. 14(a)


shows the post-fault response curves of the proposed fault lo-
cation indices for a phase-“abc” to ground fault (abc-g fault) in Symbol represents that the output of fault selection selector is correct.
Symbol “--” represents an infinite value. R represents the fault resistance.
line section between Bus 4 and Bus 5 (external fault). The fault
position is set at 40 (km) away from bus 4, the fault resistance
is 100 and fault inception angle is zero degree with respect 2) Statistical Evaluation: The same sample system shown
to phase-“a” voltage waveform at bus 4. From Fig. 14(a), we in Fig. 13 is utilized to perform statistical evaluation. There are
observe that all of the four indices , , , do not con- in total of eight fault sections in the sample system are con-
verge. Fig. 14(b) shows the post-fault response curves of the pro- sidered and up to 736 different tested cases including internal
posed fault location indices for a phase-“a” to ground fault (a–g and external faults are conducted. The performance of the pro-
fault) in section of the five-terminal line (internal fault). The posed technique under various fault conditions for transposed
fault position is set at 90 (km) away from P3, the fault resistance lines is presented in Table IV. It is clearly seen that the pro-
is 100 and fault inception angle is zero degree with respect to posed fault location technique provides excellent performance
phase-“a” voltage waveform at bus 4. From Fig. 14(b), we ob- under different fault conditions such as different fault types,
serve that all of the four indices , , , converge to fault positions, fault resistance, and fault inception angles. The
1, 2, 3, and 3.9039, respectively. Since this simulation belongs average fault location error under various fault conditions is
to Case 2, the index is the correct fault location. about 0.31%.
Therefore, from (13) the fault location error is 0.39%. The line parameters for untransposed lines are also obtained
To demonstrate the correctness of the developed faulted line using EMTP LINE CONSTANTS program and the related
branch identification logic, 8 fault events are conducted. The data for tower configuration is the same as that of transposed
fault conditions and results are summarized in Table III. Note lines mentioned previously. The performance of applying the
that in some tested cases the fault resistance is intentionally set proposed algorithm to untransposed multiterminal lines is also
as 10 k (only one case is included in Table III). An inspec- evaluated. There are up to 736 different tested cases including
tion of Table III clearly observes that the four indices still can internal and external faults are conducted. The average fault
accurately locate the fault even a high impedance fault occurs. location error under various fault conditions is about 0.59%.
Therefore, the proposed technique is virtually unaffected by the The simulation results indicate that the proposed technique also
fault path resistance. works well for five-terminal untransposed lines.
1372 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 3, JULY 2008

TABLE IV
FAULT LOCATION STATISTICAL RESULTS FOR THE TESTED
SAMPLE SYSTEM OF A FIVE-TERMINAL LINE

Fig. 15. One-line diagram of a six-terminal transmission line system (with ar-
bitrary configuration).

TABLE V
PARAMETERS OF A SIX-TERMINAL TRANSMISSION LINE SYSTEM

Symbol “--” represents an infinite value (external fault).


Total rested cases include different fault types, fault inception angles, and
fault resistance.

B. Six-Terminal Transmission Line System With Arbitrary


Configuration

We test the proposed fault location technique with respect to TABLE VI


a multiterminal transmission line with arbitrary configuration. PERFORMANCE EVALUATION OF THE PROPOSED FAULT LOCATION TECHNIQUE
Fig. 15 shows the sample transmission line system, which is a FOR A SIX-TERMINAL TRANSMISSION LINE SYSTEM

345-kV 60-Hz transposed six-terminal transmission line with


zero sequence mutual coupling. The simulated system can be
used to demonstrate the correctness of the mentioned fault loca-
tion technique. Notably, the line section between tap point
and in Fig. 15 is an unusual arrangement. The configura-
tion of the simulation system is more complicated than that of
the aforementioned system. Moreover, this multiterminal line
system is a nonhomogeneous one. Two groups of line segments
with different line parameters are adopted in this simulation
sample system, which are the groups of line segments ( , ,
, , , ) and ( , , , Bus 5-Bus
6), respectively. The related parameters of the simulated system
are shown in Table V.
Table VI shows the performance evaluation results of the
proposed fault location technique with respect to the six-ter-
minal transmission line with arbitrary configuration. The pro-
posed fault section selector/locator can correctly identify the
faulted section. The average fault location error under various
fault conditions is about 0.27%. The results indicate that the
proposed algorithm works well for a six-terminal transmission Symbol represents that the output of fault selection selector is correct.
nonhomogeneous line system with arbitrary configuration. Symbol “--” represents an infinite value. R represents the fault resistance.
LIU et al.: UNIVERSAL FAULT LOCATION TECHNIQUE 1373

V. CONCLUSION [12] J. A. Jiang, Y. H. Lin, J. Z. Yang, T. M. Too, and C. W. Liu, “An


adaptive PMU based fault detection/location technique for transmis-
A new fault location technique for N-terminal trans- sion lines, part II: PMU implementation and performance evaluation,”
mission lines is presented in this paper. Basic principles and IEEE Trans. Power Del., vol. 15, no. 4, pp. 1136–1146, Oct. 2000.
detail formulation are given. There is no particular restriction [13] C. S. Chen, C. W. Liu, and J. A. Jiang, “A new adaptive PMU based
protection scheme for transposed/untransposed parallel transmission
on the power source behind each terminal or the grounding lines,” IEEE Trans. Power Del., vol. 17, no. 4, pp. 395–404, Oct. 2002.
system when adopts the proposed algorithm. We develop the [14] J. A. Jiang, C. S. Chen, and C. W. Liu, “A new protection scheme for
faulted line branch identification selector and fault locator. The fault detection, direction discrimination, classification, and location in
transmission lines,” IEEE Trans. Power Del., vol. 18, no. 1, pp. 34–42,
proposed approach is analytic compared to traditional heuristic Jan. 2003.
approaches. Extensive simulation studies show that the perfor- [15] C. S. Chen, C. W. Liu, and J. A. Jiang, “Application of combined adap-
mance of the proposed algorithm is very excellent and the av- tive fourier filtering technique and fault detector to fast distance protec-
tion,” IEEE Trans. Power Del., vol. 21, no. 2, pp. 619–626, Apr. 2006.
erage error of fault location is well less than 1% under various [16] H. W. Dommel, EMTP Theory Book, 2nd ed. Vancouver, British Co-
system operation and fault conditions considered. The simula- lumbia: Microtran Power System Analysis Corporation, May 1992.
tion results also demonstrate the feasibility and effectiveness of [17] Alternative Transient Program Rule Book. Leuven, Belgium: Euro-
pean EMTP Center, 1987.
the proposed fault location technique for multiterminal trans- [18] G. Benmouyal, “Removal of DC-Offset in current waveforms using
mission lines with arbitrary configurations. The proposed fault digital mimic filtering,” IEEE Trans. Power Del., vol. 10, no. 2, pp.
location technique is an accurate method and its performance 624–630, Apr. 1995.
is almost unaffected by system operation conditions and fault
events.
Chih-Wen Liu (S’93–M’96–SM’02) was born in Taiwan, R.O.C., in 1964. He
REFERENCES received the B.S. degree in electrical engineering from National Taiwan Univer-
[1] T. T. Takagi, Y. Yamakoshi, J. Baba, K. Uemura, and T. Sakaguchi, sity (NTU), Taipei, Taiwan, in 1987, and the M.S. and Ph.D. degrees in electrical
“Development of a new fault locator using the one-terminal voltage engineering from Cornell University, Ithaca, NY, in 1992, and 1994, respec-
and current data,” IEEE Trans. Power App. Syst., vol. PAS-101, pp. tively.
2892–2898, Aug. 1982. Since 1994, he has been with NTU, where he is a Professor of electrical engi-
[2] L. Eriksson, M. M. Saha, and G. D. Rockefeller, “An accurate fault neering. His main research interests include application of computer technology
locator with compensation for apparent reactance in the fault resistance to power system monitoring, protection, and control. His other research inter-
resulting from remote-end infeed,” IEEE Trans. Power App. Syst., vol. ests include motor control and power electronics.
PAS-104, no. 2, pp. 424–436, Feb. 1985.
[3] A. G. Phadke and J. S. Thorp, Computer Relaying for Power Systems.
New York: Wiley, 1988.
[4] Power Engineering Education Committee and the Power System Re- Kai-Ping Lien was born in Tainan, Taiwan, R.O.C., in 1970. He received the
laying Committee of the IEEE Power Engineering Society, Advance- B.S. degrees in electrical engineering from National Sun Yat-Sen University,
ments in Microprocessor Based Protection and Communication, IEEE Taiwan, and the Ph.D degree in electrical engineering from National Taiwan
Tutorial Course 1997. University (NTU), Taipei, Taiwan, in 1992 and 2006, respectively.
[5] D. Novosel, D. G. Hart, E. Udren, and M. M. Saha, “Fault location At present, he works at Bei-Tou Incinerator, Department of Environmental
using digital relay data,” IEEE Comp. Appl. Power, vol. 8, no. 3, pp. Protection, Taipei City Government.
45–50, Jul. 1995.
[6] M. Abe, N. Otsuzuki, T. Emura, and M. Takeuchi, “Development of a
new fault location system for multiterminal single transmission lines,”
IEEE Trans. Power Del., vol. 10, no. 1, pp. 159–168, Jan. 1995.
[7] T. Nagasawa, M. Abe, N. Otsuzuki, T. Emura, Y. Jikihara, and M. Ching-Shan Chen was born in Taichung, Taiwan, R.O.C., in 1976. He received
Takeuchi, “Development of a new fault location algorithm for multi- the B.S. degree in electrical engineering from the National Taiwan University
terminal two parallel transmission lines,” IEEE Trans. Power Del., vol. of Science and Technology, Taipei, in 1998, and the M.S. and Ph.D. degrees
7, no. 3, pp. 1516–1532, Jul. 1992. in electrical engineering from National Taiwan University, Taipei, in 2000, and
[8] T. Funabashi, H. Otoguro, Y. Mizuma, L. Dube, and A. Ametani, 2003, respectively.
“Digital fault location algorithm for parallel double-circuit multiter- At present, he works at Industrial Technology Research Institute, Hsinchu,
minal transmission lines,” IEEE Trans. Power Del., vol. 15, no. 2, pp. Taiwan, and his research interests include distributed generation systems and
531–537, Apr. 2000. computer relaying.
[9] J. V. H. Sanderson, R. G. R. Santana, and B. Al-Fakri, “Improved di-
rectional comparison based algorithm for protection of multiterminal
transmission lines,” in Proc. 5th Int. Conf. Developments Power Syst.
Protection, 1993, vol. 368, pp. 153–156. Joe-Air Jiang (M’01) was born in Tainei, Taiwan, R.O.C., in 1963. He received
[10] S. M. Brahma, “Fault location scheme for a multiterminal transmission the M.S. and Ph.D. degrees in electrical engineering from National Taiwan Uni-
line using synchronized voltage measurements,” IEEE Trans. Power versity, Taipei, Taiwan, in 1990 and 1999, respectively.
Del., vol. 20, no. 2, pp. 1325–1331, Apr. 2005. From 1990 to 2001, he was with Kuang-Wu Institute of Technology, Taipei,
[11] J. A. Jiang, J. Z. Yang, Y. H. Lin, C. W. Liu, and J. C. Ma, “An adaptive Taiwan. Currently, he is an Associate Professor of bio-industrial mechatronics
PMU based fault detection/location technique for transmission lines, engineering at National Taiwan University, Taipei. His areas of interest are in
part I: Theory and algorithms,” IEEE Trans. Power Del., vol. 15, no. 2, computer relaying, mechatronics, neuro-engineering, wireless sensor network,
pp. 486–493, Apr. 2000. and bio-effects of electromagnetic wave.

S-ar putea să vă placă și