Documente Academic
Documente Profesional
Documente Cultură
3, JULY 2008
Abstract—This paper presents a universal fault location tech- few of the many references are included in the references. Abe
nique for N-terminal ( 3) transmission lines based on et al. [6] used synchronized three-phase voltages and currents at
synchronized phasor measurement units. The development of the all terminals. They proposed an algorithm using voltage differ-
technique is based on two-terminal fault location technique. The
proposed algorithm is different from traditional multiterminal entials at terminals to gradually reduce a multiterminal line to a
fault location techniques. We apply two-terminal fault location two-terminal line containing the faulted section. Then, a reactive
technique to N-terminal transmission lines and propose a novel power-based method was used to locate the fault. Nagasawa et
fault section selector/fault locator. The proposed method has a al. [7] used current differentials at terminals to perform a similar
very good tolerance. The proposed approach provides an analyt- reduction. Their reduction procedure was very complicated and
ical solution and its computational burden is very low since it does
not require iterative operations. An extensive series of simulations also normalized section impedances when impedances were dif-
were conducted to verify the accuracy of the proposed algorithm. ferent. However, this is a source of error. Funabashi et al. [8] uti-
The average fault location error under various fault conditions is lized synchronized current inputs from all terminals and devel-
well below 1%. oped two different methods to locate the fault. The paper, how-
Index Terms—Fault location, multiterminal transmission lines, ever, failed to report results for three-phase and two-phase to
phasor measurement units (PMUs). ground faults. Sanderson et al. [9] used both current and voltage
data to identify the terminal electrically nearest to the fault. Al-
though the paper reported successful results in identifying the
I. INTRODUCTION
faulted section, the exact fault location on the section was not
attempted. Brahma [10] adopted synchronized voltage measure-
TABLE I
FAULTED SECTION/FAULT LOCATION IDENTIFICATION
FOR THREE-TERMINAL LINES
Fig. 5. Type A: Fault occurs at the fault location path of D . Fig. 7. Fault occurs at the tap point P (K 0 1).
equals that of the tap point, i.e., the joint of the faulted section
and the fault location path of , to the receiving end.
Fig. 6. Type B: Fault does not occur at the fault location path of D . According to the above discussion, we find that any a fault
location index can be used to locate fault at its fault loca-
tion path of . As for fault beyond its fault location path of
Type A: Suppose that a midway fault occurred at the point , the fault location index merely point out the joint of
F which is km away from receiving end R on the the faulted section and the fault location path of , to the re-
fault location path of as shown in Fig. 5. The fault location ceiving end. Based on this fact, a novel algorithm is proposed in
path of is thus divided into two parts. One is line section the following section.
– , the other is line section – .
The voltages at fault point that are expressed in terms of D. Fault Section Selector/Fault Position Locator
these two data sets ( , ) and ( , ) are identical. We can
derive the fault location index . The fault location index For an multiterminal line, there are sending ends and
can correctly locate the fault that is a distance of a receiving end. Therefore, the proposed fault location technique
from away receiving end . can generate fault location indices . We can find
Type B: An internal fault does not occur at the fault location four special relationships among these indices.
path of (refer to Fig. 6). Case 1: A fault occurs at the line section .
As shown in Fig. 6, a fault occurs at the line section As shown in Fig. 8, the fault occurs at the line section
. This line section does not belong to the fault lo- . The computed fault location indices for Case 1 are
cation path of . As mentioned above, we have considered shown in Fig. 9. It is clearly seen that the values of the fault
the injective currents of all tap points during estimating the location indices are equal
voltage and current phasors at virtual sending end P1. Due to and bigger than the remaining indices. We know that the
the fault occurred in tap branch, we know that the injective cur- correct fault location is
rent of tap point estimated by PMU at away from receiving end .
Bus is wrong. Therefore, the fault location path of is Case 2: A fault occurs at the section
thus divided into two parts. One is line section , Fig. 10 depicts the case that the fault occurs at the line section
the other is line section . The voltage at tap point . The computed fault location indices for Case 2 are
that are expressed in terms of these two data sets ( , shown in Fig. 9. It is clearly seen that the value of the fault lo-
) and ( , ) are identical. Thus, we can derive the fault lo- cation index is the maximum. We conclude that the correct
cation index . But, the fault location index points out fault location is away from receiving end .
tap point that is a distance of from away Case 3: A fault occurs at the line section .
receiving end (as shown in Fig. 7). In summary, if a fault does As shown in Fig. 11, the fault occurs at the line section
not occur at the fault location path of , the proposed algo- . The magnitudes of all fault location indices are equal as
rithm still can output a value of fault location index , which shown in Fig. 9.
corresponds to the actual distance . This distance Case 4: An external fault or no fault occurs.
1370 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 3, JULY 2008
TABLE II
PARAMETERS OF A FIVE-TERMINAL TRANSMISSION LINE SYSTEM
Fig. 14. The post-fault response curves of the proposed fault location indices
for (a) an external fault and (b) an internal fault.
TABLE III
PERFORMANCE EVALUATION OF THE PROPOSED FAULT LOCATION
TECHNIQUE FOR FIVE-TERMINAL LINES
TABLE IV
FAULT LOCATION STATISTICAL RESULTS FOR THE TESTED
SAMPLE SYSTEM OF A FIVE-TERMINAL LINE
Fig. 15. One-line diagram of a six-terminal transmission line system (with ar-
bitrary configuration).
TABLE V
PARAMETERS OF A SIX-TERMINAL TRANSMISSION LINE SYSTEM