Installation
IM 33M01A20-40E
IM 33M01A20-40E
1st Edition
Introduction
The procedure for installing the CENTUM VP function on a recommended personal computer
and the setup are described in this document. Be sure to read it when installing the CENTUM VP
system.
If a recommended personal computer is used and Windows must be installed or set up, refer to
the Windows manual for the procedure. (Note that the loading of the CENTUM VP software is
referred to as “installation” and the setting of Windows to run the CENTUM VP system on the
personal computer as “setup” throughout this document.)
Chapter 1: Overview
This chapter provides the overview of the installation tasks.
Chapter 2: Hardware Setup
This chapter describes the hardware settings that should be carried out before installing the
software.
Chapter 3: Setting of Windows
This chapter describes the Windows settings need to be performed before installing CENTUM
VP software to the PC.
Chapter 4: Setting of Network
This chapter describes the Windows network setups after installing the communication drivers.
Chapter 5: Installing USB driver for Operator Keyboard (OPKB)
This chapter describes the procedure for installing the USB driver for Operator Keyboard
(OPKB).
Chapter 6: Installing CENTUM VP Software
This chapter describes the procedure for installing CENTUM VP Software.
Chapter 7: IT Security Settings
This chapter describes the settings regarding the IT security strengthening after installing the
software.
Chapter 8: Setups Required after Installation
This chapter describes the settings need to be performed after installing CENTUM VP.
Chapter 9: Console Type HIS Installation
This chapter describes the procedure for installing Console Type HIS.
Chapter 10: Uninstallation of CENTUM VP
This chapter describes the procedures for uninstalling the CENTUM VP software and device
drivers.
Chapter 11: Setting of Windows Domain Environment
The required settings when CENTUM VP acts with Windows domain environment will be
explained in this chapter.
Chapter 12: Troubleshooting
This chapter describes the troubleshooting methods for various troubles.
Chapter 13: Backup
This chapter describes how to backup the system regularly as a precaution against unexpected
troubles.
Media No. IM 33M01A20-40E (DVD) 1st Edition : Mar. 2008 (YK) IM 33M01A20-40E 1st Edition : Mar.23,2008-00
All Rights Reserved Copyright © 2008, Yokogawa Electric Corporation
ii
CENTUM Data
Fieldbus APCS
Access Library
Documentation Documentation
IM 33M05F10-40E
Hardware
Peripherals Input & Output
Migrated-FCS (FIO)
Modules
IM 33M50C10-40E IM 33M50W10-40E
IM 33M50G10-40E
Turbomachinery
I/O Modules
IM 33M10U10-40E
User's manual
Installation CENTUM VP Installation Only available in electronic document
IM 33M01A20-40E Relationship between manuals
that must be read in order
Relationship to a referred manual
Reference manual
Safety Precautions
n Safety, Protection, and Modification of the Product
• In order to protect the system controlled by the product and the product itself and ensure
safe operation, observe the safety precautions described in this user’s manual. We assume
no liability for safety if users fail to observe these instructions when operating the product.
• If this instrument is used in a manner not specified in this user’s manual, the protection
provided by this instrument may be impaired.
• If any protection or safety circuit is required for the system controlled by the product or for
the product itself, prepare it separately.
• Be sure to use the spare parts approved by Yokogawa Electric Corporation (hereafter
simply referred to as YOKOGAWA) when replacing parts or consumables.
• Modification of the product is strictly prohibited.
• The following symbols are used in the product and user’s manual to indicate that there are
precautions for safety:
Indicates that caution is required for operation. This symbol is placed on the product to refer
the user to the user’s manual in order to protect the operator and the equipment. In the
user’s manuals you will find precautions to avoid physical injury or death of the operator,
including electrical shocks.
Identifies a protective grounding terminal. Before using the product, ground the terminal.
Identifies a functional grounding terminal. Before using the product, ground the terminal.
Indicates an AC supply.
Indicates a DC supply.
n Notes on Software
• YOKOGAWA makes no warranties, either expressed or implied, with respect to the
software’s merchantability or suitability for any particular purpose, except as specified in the
terms of warranty.
• This product may be used on a machine only. If you need to use the product on another
machine, you must purchase another product.
• It is strictly prohibited to reproduce the product except for the purpose of backup.
• Store the DVD-ROM (the original medium) in a safe place.
• It is strictly prohibited to perform any reverse-engineering operation, such as reverse
compilation or reverse assembling on the product.
• No part of the product may be transferred, converted or sublet for use by any third party,
without prior written consent from YOKOGAWA.
Documentation Conventions
n Typographical Conventions
The following typographical conventions are used throughout the user’s manuals:
“▼” Mark
This symbol indicates the description for an item for which you should make a setting in the
product’s engineering window.
While operating an engineering window, the help information for the selected item can be
accessed from “Builder Definition Items” in the Help menu.
Listing more than one definition item after this symbol implies that the paragraph on the page
describes more than one definition item.
Example:
▼ Tag Name, Station Name
“Δ” Mark
Indicates a space between character strings that must be entered.
Example:
. ALΔPIC010Δ-SC
“...” Mark
Indicates that the previous command or argument may be repeated.
Example:
Imax (arg1, arg2, ...)
n Symbol Marks
Throughout this user’s manual, you will find several different types of symbols are used to identify
different sections of text. This section describes these icons.
CAUTION
Identifies instructions that must be observed in order to avoid physical injury and electric
shock or death of the operator.
WARNING
Identifies instructions that must be observed in order to prevent the software or hardware
from being damaged or the system from becoming faulty.
IMPORTANT
Identifies important information required to understand operations or functions.
TIP
Identifies additional information.
SEE
ALSO
n Drawing Conventions
Some drawings may be partially emphasized, simplified, or omitted, for the convenience of
description.
Some screen images depicted in the user’s manual may have different display positions or
character types (e.g., the upper / lower case). Also note that some of the images contained in this
user’s manual are display examples.
n Trademark Acknowledgments
• CENTUM and Vnet/IP are registered trademarks of YOKOGAWA.
• Microsoft, Windows, Windows Vista, Visual Basic, Visual C++ and Visual Studio are either
registered trademarks or trademarks of Microsoft Corporation in the United States and/or
other countries.
• Adobe, Acrobat and Acrobat Reader are either registered trademarks or trademarks of
Adobe Systems Incorporated in the United States and/or other countries.
• Ethernet is a registered trademark of XEROX Corporation.
• Java is a registered trademark of Sun Microsystems,Inc.
• MELSEC is a registered trademark of Mitsubishi Electric Corporation.
• Modicon and Modbus are registered trademarks of Schneider Electric SA.
• Memocon-SC is a registered trademark of Yaskawa Electric Corporation.
• PLC is a registered trademark of Rockwell Automation, Inc.
• SYSMAC is a registered trademark of OMRON Corporation.
• SIEMENS and SIMATIC are registered trademarks of Siemens Industrial Automation Ltd.
• “FOUNDATION” in “FOUNDATION fieldbus” is a registered trademark of Fieldbus
Foundation.
• SmartPlant is a registered trademark of Intergraph Corporation.
• “HART” is a registered trademark of the HART Communication Foundation.
• All other company and product names mentioned in this user’s manual are trademarks or
registered trademarks of their respective companies.
• We do not use TM or ® mark to indicate those trademarks or registered trademarks in this
user’s manual.
CENTUM VP
Installation
IM 33M01A20-40E 1st Edition
CONTENTS
1. Overview..................................................................................................... 1-1
1.1 Flow Chart of Installation Procedures............................................................. 1-3
1.2 Hardware Environment..................................................................................... 1-7
1.3 Software Environment....................................................................................... 1-8
2. Hardware Setup......................................................................................... 2-1
2.1 Control Bus Station Address............................................................................ 2-2
2.2 Processor Unit.................................................................................................... 2-5
2.3 Bus Converter.................................................................................................... 2-8
2.4 HF Bus/RL Bus Interface Card......................................................................... 2-9
2.5 V net Interface Card......................................................................................... 2-11
2.6 Communication Gateway Unit........................................................................ 2-13
2.7 Installing Ethernet Card.................................................................................. 2-16
2.8 Setup Vnet/IP Station Address On Control Bus........................................... 2-17
2.9 Setup Vnet/IP Station Address On Processor Module................................ 2-20
2.10 Setup V net Router Addresses....................................................................... 2-23
3. Setting of Windows................................................................................... 3-1
3.1 File System......................................................................................................... 3-2
3.2 Setting of Virtual Memory................................................................................. 3-3
3.3 Set Display Properties....................................................................................... 3-5
3.4 Setting of System Properties.......................................................................... 3-11
3.5 Setting a Power Options................................................................................. 3-13
3.6 Disable Windows Sidebar............................................................................... 3-19
3.7 Disable Windows Security Alerts................................................................... 3-20
3.8 Disabling Windows Defender......................................................................... 3-23
3.9 Notices on Installing CENTUM VP in Windows XP Environment............... 3-26
3.10 Disable Scheduled Disk Defragmenter Tool....................................................3-27
3.11 Cautions on Using CAMS for HIS................................................................... 3-28
4. Setting of Network..................................................................................... 4-1
4.1 Installation of Control Bus Driver.................................................................... 4-2
4.1.1 Adding Control Bus Driver.................................................................. 4-3
4.1.2 Updating Control Bus Driver............................................................. 4-11
4.1.3 Removing Control Bus Driver........................................................... 4-15
4.1.4 Troubleshooting................................................................................ 4-17
1. Overview
In this document, the procedure for installing the CENTUM VP software (including
the electronic documents) will be explained. The installation procedures of Windows
operating systems, related service packs and Microsoft security patches are beyond the
scope of this document.
Must Read
Chapter 1
n Administrative User
For the initial logon of Windows Vista, no account of administrative user can be used to logon.
In this case, the administrative user account created during the installation of Windows Vista
should be used.
The account for the administrative user of Windows XP and Windows Server 2003 are the
Administrator account.
In this document, the users that have the administrator privileges in various Windows operating
systems are all referred to as the administrative users. The user who is installing the CENTUM
VP will be one of the administrative users.
SEE
ALSO For more information about setups of IT security, see the following:
7, “IT Setting Security”
n Installation Procedures
The procedure for installing Windows and setup device drivers vary with the Windows operating
systems. For the procedure that common for all the operating systems, the explanation will
mainly use the user interfaces of Windows Vista. However, for the procedures typical for each
operating system, the explanation will use the user interfaces of each system and describe the
procedure separately.
SEE
ALSO • For more information about installation of Windows, Windows service packs and security patches, see the
related documents provided by Microsoft Corporation.
• For more information about Installation of Console type HIS, see the following:
9, “Console type HIS Installation”
START
Installation of Windows
Security patch
Setting after the installation Refer to “8. Activities after the installation”
(Create user account, Setup
Windows environment for
that user and setup UPS)
END
010101E.ai
010103E.ai
RS driver for Console HIS Install RS-232C driver for console type HIS 9.2 Installation of RS-232C Driver
CS 1000 Project DB Upgrade CS 1000 project database to CENTUM 6.4 Installation for Upgrading CS
conversion VP. 1000 to CENTUM VP
010102E.ai
IMPORTANT
Make sure to match the names of a computer and a station. If they do not match, we cannot
guarantee the proper performance of the CENTUM VP system.
A computer name is a name used to identify each computer on the Windows network. An
arbitrary computer name can be specified using the Windows Control Panel.
A station name is a name uniquely specified according to the Control bus address in the
CENTUM VP system.
EXAMPLE: HIS0164
(HISddss: “dd” is the domain number and “ss” is the station number.)
l IP Address
This is the address of the computer which can uniquely be identified by the Control bus or
Ethernet.
Make sure to specify network addresses for the Control bus and Ethernet on separate subnets.
EXAMPLES: 172.16.1.64 (Control Bus), 172.17.1.64 (Ethernet)
SEE
ALSO If an error occurs when IP address of an HIS is changed and downloaded, see the following:
“n If an error occurs when IP address of an HIS is changed and downloaded” in 12, “Troubleshooting”
IMPORTANT
• Even if no control bus interface card is installed, installed the control bus driver before using
the Test Function.
• If using the Expanded Test Functions, be sure not to duplicate the control bus address that
needs to be set for each connected PC.
The IP addresses set for control bus adapters should be the same control bus addresses set on
System View for the PCs.
Example: 172.16.dd.ss
The IP addresses for different PCs should not be identical.
Note that the address can be the same as “domain number.station number” used for the HIS, but
that the address should not be the same as “domain number.station number” used for the FCS.
Set from 1 to 16 for the domain number.
Set from 1 to 64 for station number.
IMPORTANT
Note the following items regarding to the subnet mask:
• Use the exist setting of the current network environment when installing the CENTUM VP
system in an existing network environment.
• Use the default value determined by the IP address when installing the CENTUM VP
system in a newly provided local network environment.(IP address: 172.17.dd.ss, subnet
mask: 255.255.0.0).
Use the default IP address for the Control Bus (IP address: 172.16.dd.ss, subnet mask:
255.255.0.0).
l Preparations when User Account and User Group are Managed in Windows
Domain Controller.
SEE
ALSO For more information about the preparations when user account and user group are managed in Windows
domain controller., see the following:
11, “Setting of Windows domain environment”
SEE
ALSO • For information about Hardware Environment of HIS and Builder, see the following:
Model LHS1100, LHM1101 Standard Operation and Monitoring Function (GS 33M05D10-40E)
Model LHS5100, LHM5100 Standard Builder Function (GS 33M10D10-40E)
• For information about Hardware Environment of GSGW, see the following:
Model LFS1250 GSGW Generic Subsystem Gateway Package (GS 33M20F10-40E)
• For information about Hardware Environment of SIOS, see the following:
LBC2100 System Integration OPC Client Package (GS 33M20D10-40E)
IMPORTANT
In the PC that Windows is preinstalled; some third party utilities other than the operating systems
might have been installed too. These utilities may not only unnecessarily occupy the HIS
resource, but also jeopardize the HIS performance. Thus, it is recommended to reinstall the OS
only to the PC.
In the PC recommended by Yokogawa, the required software applications are all properly setup.
l Software Compatibility
The CENTUM VP software is compatible with the commercial software listed below:
Table Compatible Commercial Software
Software type Software name Version Remarks
Used with the report package, and
Spreadsheet Microsoft Excel (*1) 2003, 2007 Settings for FCS Data Setting/Acquisition
Package (PICOT).
Word processing Microsoft Word 2003, 2007
Microsoft Visual C++ 6.0+SP5
Software development
Visual Studio 2005
Microsoft Internet Explorer 6.0, 7.0 Used with the electronic document
Document reader
3.0 package.
.NET Framework
Uninterruptible
power supply (UPS) APC PowerChute Business Edition 7.0.5
SEE
ALSO For more information about the report package revisions, see the following and check the release numbers of the
Microsoft products:
Table “Compatible Commercial Software”
When generating the report applications in different PCs, the versions of Microsoft Excel should
be the same.
SEE
ALSO For the procedure of using the report files generated in the old version of Microsoft Excel in the new version of
Microsoft Excel, see the following:
“n Defining a Report” in M3.1, “Flow of Report Creation” in Reference Options (IM 33M01A30-40E)
2. Hardware Setup
This Chapter describes how to setup the hardware before the CENTUM VP software
installation.
It is necessary to set domain and station numbers for the following switches before
installing the software:
• Control Bus interface card (VF701)
• HF bus/RL bus interface card (FC311)
• Field control station processor unit
• Bus Converter (ABC11D, ABC11S)
• Communication Gateway Unit (ACG10S)
If you do not use the Bus Converter and Communication Gateway Unit, you do not need
to set these items.
TIP
When the domain number and station number are correctly defined and a Control Bus is properly connected, the
SND and RCV lamps turn on at power-on.
If the RCV lamp turns on while the SND lamp does not, check the dip switch setting of the corresponding card.
Specifically, before installation, be sure that the control bus interface card for the PC is correctly set.
CAUTION
When removing the cards for setting dipswitches, the damages caused by static electricity should
be prevented.
SEE
ALSO For more information about prevention of static electricity, see the following:
A5.1 “Precautionary Notes with Respect to Static Electricity” in Peripherals (IM33M50C10-40E)
DIP switches
SW1 DOMAIN
DOM Domain number
STATION
SW2
STN Station number
020101E.ai
Bit setting:
0: Turn the switch to the lower in the above figure.
1: Turn the switch to the upper in the above figure.
Bit setting:
0: Turn the switch to the lower in the above figure.
1: Turn the switch to the upper in the above figure.
Their DIP switches must properly be set as described below. There is no difference
between the two types of processor unit for the setting.
HRDY
RDY
CTRL
COPY
START
/STOP
CN1
CN1 connector
STATION
ADDRESS
Dip switches used for setting the station address
0 1
PARTY
0 1
PARTY
020201E.ai
(LSB)
Bit setting:
0: Turn the switch to the left in the above figure.
1: Turn the switch to the right in the above figure.
STA
Station number (7-bit)
No.
(LSB)
Station number 17 18 30 31 32 33 60 61 62 63 64
Bit 1 1 1 1 0 0 1 1 0 0 1 0
Bit 2 0 0 0 0 0 0 0 0 0 0 1
Bit 3 0 0 0 0 1 1 1 1 1 1 0
Bit 4 1 1 1 1 0 0 1 1 1 1 0
-- --
Bit 5 0 0 1 1 0 0 1 1 1 1 0
Bit 6 0 0 1 1 0 0 1 1 1 1 0
Bit 7 0 1 1 1 0 0 0 0 1 1 0
Bit 8 1 0 0 1 0 1 0 1 0 1 0
020205E.ai
Bit setting:
0: Turn the switch to the left in the above figure.
1: Turn the switch to the right in the above figure.
HRDY
RDY
CTRL
COPY
START
/STOP
CN1
LSB
020301E.ai
SEE
ALSO Form and setting of the bus converter DIP switches are same as the processor unit.
For above, see the following:
2.2, “Processor Unit”
RDY
CTRL
020401E.ai
STA
Station number
NO.
(LSB)
Staition number 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Bit 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 1
Bit 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Bit 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
Bit 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0
Bit 5 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0
Bit 6 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0
Bit 7 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0
Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0
020403E.ai
020501E.ai
SEE
ALSO For the domain number setting, see the following:
“n Setting the Domain Number” in 2.2, “Processor Unit”
SEE
ALSO For the station number setting, see the following:
“n Setting the Station Number” in 2.2, “Processor Unit”
020601E.ai
Bit setting:
0: Turn the switch to the down side in the above figure.
1: Turn the switch to the up side in the above figure.
Bit setting:
0: Turn the switch to the down side in the above figure.
1: Turn the switch to the up side in the above figure.
n Ethernet Card
The Ethernet is required when a network other than the Control Bus is connected.
Confirm that the Ethernet card is properly inserted and connected to the network via the proper
cable.
SEE
ALSO Refer to the network adapter manual for details.
DOMAIN
SW1
STATION
SW2
Action mode
SW4
020801E.ai
Domain number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Bit 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 0
Bit 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Bit 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Bit 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
Bit 5 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0
Bit 6 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0
Bit 7 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0
Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0
020803E.ai
Station number 17 18 30 31 32 33 60 61 62 63 64
Bit 1 1 1 1 0 0 1 1 0 0 1 0
Bit 2 0 0 0 0 0 0 0 0 0 0 1
Bit 3 0 0 0 0 1 1 1 1 1 1 0
Bit 4 1 1 1 1 0 0 1 1 1 1 0
Bit 5 0 0 1 1 0 0 1 1 1 1 0
Bit 6 0 0 1 1 0 0 1 1 1 1 0
Bit 7 0 1 1 1 0 0 0 0 1 1 0
Bit 8 1 0 0 1 0 1 0 1 0 1 0
020805E.ai
DOMAIN NO.
STATION NO.
020901E.ai
1 2 3 4 5 6 7 8
Fixed to 0
MSB
Domain number
LSB
Bit number
MSB : Most Significant Bit (highest-order bit)
LSB : Least Significant Bit (lowest-order bit) 020902E.ai
Domain number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Bit 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 0
Bit 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Bit 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Bit 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
Bit 5 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0
Bit 6 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0
Bit 7 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0
Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0
020903E.ai
0
1
Station number parity (1 bit, odd parity)
P
1 2 3 4 5 6 7 8
MSB
Station number
LSB
Bit number
MSB : Most Significant Bit (highest-order bit)
LSB : Least Significant Bit (lowest-order bit) 020904E.ai
Station number 17 18 30 31 32 33 60 61 62 63 64
Bit 1 1 1 1 0 0 1 1 0 0 1 0
Bit 2 0 0 0 0 0 0 0 0 0 0 1
Bit 3 0 0 0 0 1 1 1 1 1 1 0
Bit 4 1 1 1 1 0 0 1 1 1 1 0
Bit 5 0 0 1 1 0 0 1 1 1 1 0
Bit 6 0 0 1 1 0 0 1 1 1 1 0
Bit 7 0 1 1 1 0 0 0 0 1 1 0
Bit 8 1 0 0 1 0 1 0 1 0 1 0
020905E.ai
V Net VNET/IP
ADDRESS ADDRESS
0 1 0 1 Dipswitches for address in
Vnet/IP domain
PARITY
0 0
0
(MSB)
DOMAIN
(LSB)
PARITY
(MSB)
STATION
Dipswitches for address in
V net domain
(LSB)
VNET/IP
MODE
Mode switch NORM
MNT
RCV
BUS1
RCV
BUS2
SND
Vnet/IP BUS2 connector
021001E.ai
0 0 Fixed to 0
0 MSB
MSB
Domain number
DOMAIN
LSB LSB
Domain number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Bit 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 0
Bit 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Bit 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Bit 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
Bit 5 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0
Bit 6 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0
Bit 7 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0
Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0
021003E.ai
MSB
LSB
Station number 17 18 30 31 32 33 60 61 62 63 64
Bit 1 1 1 1 0 0 1 1 0 0 1 0
Bit 2 0 0 0 0 0 0 0 0 0 0 1
Bit 3 0 0 0 0 1 1 1 1 1 1 0
Bit 4 1 1 1 1 0 0 1 1 1 1 0
Bit 5 0 0 1 1 0 0 1 1 1 1 0
Bit 6 0 0 1 1 0 0 1 1 1 1 0
Bit 7 0 1 1 1 0 0 0 0 1 1 0
Bit 8 1 0 0 1 0 1 0 1 0 1 0
021005E.ai
3. Setting of Windows
The Windows settings need to be defined before installing CENTUM VP Software to the
PC are described as follows.
After installing Windows operating system, service packs and all the required security
patches, do the following.
The procedure explained below is based on the Classic style of Windows Vista Control
Panel.
030201E.ai
Figure System
030202E.ai
030203E.ai
5. The paging file size of the selected drive can be defined as follows:
Choose [Custom size] and then enter the sizes for [Initial size] and [Maximum size].
A size that is three times of main memory size is recommended for the initial size. However,
4096MB is the upper limit. For an example, if the main memory size is 1GB, the initial size
can be defined with 3072MB. However, if the main memory size is 2GB or 4GB, 4096MB
should be used.
6. Click [OK] button.
030301E.ai
030302E.ai
030303E.ai
TIP
In Windows Vista, when the background color is defined as a solid color or another color after the first logon,
the background color may revert to black at the second logon. If this problem occurs, you need to define the
background color again with the same procedure.
030304E.ai
030305E.ai
030306E.ai
030307E.ai
030308E.ai
030401E.ai
030402E.ai
030403E.ai
030501E.ai
030502E.ai
4. Click [Change advanced power settings] so as to display [Advanced settings] tab of “Power
Options”.
The advanced settings of Power Options can define the following items. However, some of
the items may not be displayed in your computer. The absent item indicates that your PC
does not have that function.
030503E.ai
030504E.ai
030505E.ai
030506E.ai
TIP
UPS settings will be explained in “8. Activities after the installation.”
030507E.ai
030508E.ai
030509E.ai
030601E.ai
3. Uncheck the option of [Start Sidebar when Windows starts] and then click [OK] button.
030701E.ai
030702E.ai
Figure Windows Security Center (Change the way Security Center alerts me)
4. Choose [Don’t notify me and don’t display the icon (not recommended)].
030703E.ai
3. On the left hand side of [Windows Security Center], choose [Change the way Security
Center alerts me] so as to display “Alert Settings” dialog box.
030704E.ai
030801E.ai
030802E.ai
030803E.ai
030804E.ai
6. Click [Close].
n Administrator Password
In some Windows XP preinstalled PCs, the Administrator account or other administrative user
accounts are not set with passwords. You need to confirm if your administrative account is
protected with a password. If not, you need to set a password for it.
031001E.ai
3. Uncheck the option of [Run on a schedule (recommended)] and then click [OK] button.
4. Setting of Network
For the Software of CENTUM VP to operate, both Control bus driver and Ethernet driver
are necessary.
In this chapter, the installation of Control bus and Vnet/IP open communication driver are
described.
Install the appropriate Ethernet driver referring to the attached manual when using the
Ethernet that comes with PC or the commercially available Ethernet communication card
that is added in a PCI slot.
In the following descriptions, VF701 is the control bus card for Vnet and VI701 is the
control bus card for Vnet/IP.
Start
Execute installation of the Choose [Control Bus Driver] on CENTUM VP Installation menu.
control bus driver
End
040101E.ai
IMPORTANT
• When installing the control bus driver, the installer will look for the installed control bus card
(VF701/VI701). Therefore, the control bus card needs to be installed before installing the
control bus driver.
• When moving the installed control bus card to a different slot, the existing control bus driver
needs to be deleted before moving the card. The control bus driver needs to be installed
again after moving the card to the new slot.
• If the control bus driver is installed, by mistake, before the control bus card is installed, the
installed driver should be deleted. After installing the control bus card, the control bus driver
needs to be installed again.
• When removing a normally running control bus card from a PC (normally running means the
driver is properly installed), the control bus driver should be deleted first.
• After installing the driver, the network setup needs to be performed.
• The control bus driver can be installed either before or after installing the CENTUM VP
packages. However, it is better to install the control bus driver before installing the CENTUM
VP packages.
040102E.ai
040103E.ai
040104E.ai
3. Set the CENTUM VP software media into the DVD drive, the CENTUM VP installation
menu will be automatically started. (If the installation menu is not automatically started, use
Windows Explorer to find CENTUMSetup.exe program under the top folder of the CENTUM
VP software media and then double click the program to run it.)
4. On CENTUM VP installation menu, click [Control Bus Driver] button.
5. When the Setup confirmation dialog box is displayed, click [OK].
040105E.ai
040106E.ai
040107E.ai
TIP
• Do not click the [Don’t Install] button on the Windows Security confirmation dialog boxes for installing device
software and adapter’s driver.
• Do not select the checkbox of [Always trust software from “Yokogawa Electric Corporation”].
040108E.ai
7. When the message telling successful installation is displayed, click [OK] to finish.
040109E.ai
TIP
If you install for the first time or uninstall another device before initially installing the control bus driver, the
following message (prompting a restart) may appear instead of the message box in step 7. If so, after you do step
8, make sure to restart your PC.
040110E.ai
IMPORTANT
• It takes about 1 minute to display the “Set Network Location” dialog box. If nothing abnormal
happens, the dialog box appears. Wait for the dialog box to appear, and follow step 8.
• Depending on the network status, the “Set Network Location” dialog box may not appear. If
it does not appear after a few minutes, skip step 8.
• Even if you skip step 8 or if you click the wrong item other than [Work], they are offset in the
later network setup.
040111E.ai
040112E.ai
Whether the Yokogawa Vnet protocol is properly installed can be confirmed on Device Manager
as shown in the figure below after enabling [Show hidden devices] on [View] menu of Device
Manager. “Yokogawa Vnet Protocol” will be displayed under Non-Plug and Play Drivers. If the
protocol is not working properly, an exclamation mark (!) will be displayed next to the icon of the
protocol driver.
TIP
Yokogawa Vnet Protocol may not be displayed right after installing the driver. In this case, choose [Scan for
hardware changes] on [Action] menu of the Device Manager, and then it will be displayed.
040113E.ai
Start
Execute installation of the Choose [Control Bus Driver] on CENTUM VP Installation menu.
control bus driver (Same as the procedure for adding the driver)
Restart PC
End
040114E.ai
IMPORTANT
When updating the control bus driver, the updated driver will take effect after the PC is restarted.
040115E.ai
TIP
If other device is already updated, after clicking [OK] button, a message box saying “Vnet driver has been already
upgraded” will be displayed.
040116E.ai
040117E.ai
TIP
• Do not click the [Don’t Install] button on the Windows Security confirmation dialog box for installing the
network adapter.
• Do not select the checkbox of [Always trust software from “Yokogawa Electric Corporation”].
040118E.ai
6. When the message telling successful installation (prompting to restart PC) is displayed, click
[OK].
040119E.ai
Start
Restart PC
End
040120E.ai
IMPORTANT
After removing the control bus driver, the PC needs to be restarted.
040121E.ai
TIP
The User Account Control dialog box will not be displayed in Windows XP and Windows Server 2003
040122E.ai
6. When the message telling successful removal (prompting to restart PC) is displayed, click
[OK].
040123E.ai
4.1.4 Troubleshooting
Troubleshooting the problems of control bus driver installation will be explained below.
IMPORTANT
In Windows Vista, the installation needs to be performed by the administrative user. When the
User Account Control dialog box is displayed, you need to click [Continue] to continue operation.
However, only the administrative user is permitted to continue.
040124E.ai
040125E.ai
040126E.ai
(Note) The affixed ** is a two-digit number that indicates VF701 or VI701. 00 stands for VF701; the other stands for VI701.
When driver does not start up, it may be caused by VF701/VI701 card failure or effect of other
devices. In this case, you can try to replace the VF701/VI701 card or temporarily uninstall other
devices from the PC.
040128E.ai
040129E.ai
Click [Browse] so as to browse for the path to bktdi.sys file in the installation media (\CENTUM\
COMDRV\TDI\bktdi.sys). And then click [OK].
040130E.ai
In this case, you need to uninstall the installed control bus driver and restart the PC. And then you
can install the control bus driver again.
Start
End
040201E.ai
IMPORTANT
• When installing the Vnet/IP open communication driver, the installer will look for the
installed Vnet/IP open communication card (VI701). Therefore, theVI701card needs to be
installed before installing the Vnet/IP open communication driver.
• When moving the installed VI701card to a different slot, the existing Vnet/IP open
communication driver needs to be deleted before moving the card. The Vnet/IP open
communication driver needs to be installed again after moving the card to the new slot.
• When removing a normally running VI701 card from a PC (normally running means the
driver is properly installed), the Vnet/IP open communication driver should be deleted first.
• After installing the driver, the network setup needs to be performed.
• The control bus driver can be installed either before or after installing the Windows
programs, CENTUM VP packages, and other communication driver such as control bus
driver. There is no specified sequence for installation of the driver and packages.
• In general, there is no need to restart the PC. However, if the message displayed at
successful installation prompts to restart your PC, you need to restart the PC.
040202E.ai
040203E.ai
3. Set the CENTUM VP software media into the DVD drive, the CENTUM VP installation
menu will be automatically started. (If the installation menu is not automatically started, use
Windows Explorer to find CENTUMSetup.exe program under the top folder of the CENTUM
VP software media and then double click the program to run it.)
4. On CENTUM VP installation menu, click [Vnet/IP Open com driver] button.
5. When the setup confirmation dialog box is displayed, click [OK].
040204E.ai
040205E.ai
TIP
Do not select the checkbox of [Always trust software from “Yokogawa Electric Corporation”].
7. When the message telling successful installation is displayed, click [OK] to finish.
040206E.ai
040207E.ai
TIP
• When Program Compatibility Assistant dialog box is displayed, it does not indicate any error. It is for
deciding whether the installer/uninstaller has worked properly.
• When the dialog box telling successful installation is displayed, the installation is completed.
040208E.ai
n Flow of Updating
Start
End
040209E.ai
IMPORTANT
In general, there is no need to restart the PC after updating the driver. However, if the message
displayed at successful installation prompts to restart your PC, you need to restart the PC.
040210E.ai
Figure Message of Successful Installation (Prompt to Restart PC)
040211E.ai
040212E.ai
TIP
Do not select the checkbox of [Always trust software from “Yokogawa Electric Corporation”].
6. When the message telling successful installation (prompting to restart PC) is displayed, click
[OK].
040213E.ai
040214E.ai
TIP
• When Program Compatibility Assistant dialog box is displayed, it does not indicate any error. It is for
deciding whether the installer/uninstaller has worked properly.
• When the dialog box telling successful installation is displayed, the installation is completed.
n Flow of Removal
Start
End
040215E.ai
IMPORTANT
• After removing the Vnet/IP Open Communication Driver, the PC does not need to be
restarted.
• When removing the driver from a PC while the VI701card is not installed in the PC, a
message box of [VI701 not found] will be displayed, removing the driver will be denied.
Thus, when removing the Vnet/IP open communication driver, the VI701 card must be
installed in the PC.
040216E.ai
040217E.ai
TIP
The “User Account Control” dialog box will not be displayed in Windows XP and Windows Server 2003
040218E.ai
040219E.ai
040220E.ai
040221E.ai
040222E.ai
Figure User Account Control – when the User is Not an Administrative User
040223E.ai
TIP
If the error message like “Figure Adding Driver Error Message 2” is displayed before the error message of “Figure
Driver Installation Error Message 1,” click [OK] on the error message box.
040224E.ai
040225E.ai
SEE
ALSO For information about troubleshooting in updating the Vnet/IP Open Communication Driver, see the following. You
may read adding the driver and updating the driver in the same meaning.
“n Adding Vnet/IP Open Communication Driver”
l PC was Restarted after Removing the Driver without Unplugging VI701 Card
After removing the Vnet/IP open communication driver, if the PC is restarted without unplugging
the VI701 card from the PC, Windows will see the VI701 card as a new hardware and
automatically shows the Found New Hardware dialog box. In this case, you need to click [Ask me
again later] and then shutdown the PC. And then restart the PC after unplugging the VI701 card.
040226E.ai
See
Also • For more information about network setup in Windows Vista environment, see the following:
4.3.1 “Setting Network Connection - Windows Vista”
• For more information about network setup in Windows XP/Windows Server 2003 environment, see the
following:
4.3.2 “Setting Network Connection - Windows XP/Windows Server 2003”
• For more information about the restrictions on network setting, see the following:
4.3.3 “Restrictions on Network Setting”
• For more information about the advanced setups of Windows network, see the following:
4.3.4 “Windows Advanced Setup of Windows Network”
040350E.ai
n Vnet/IP Setup
In Windows Vista environment, the setup procedure for Vnet/IP network connection is the same
as that for Vnet.
The explanations in this section assume that Ethernet and Vnet/IP open communication are
not used together. For example, if Vnet/IP open communication is used while Ethernet is not
used, Vnet/IP network connection is named as “Ethernet.” However, if both Vnet/IP open
communication and Ethernet are used together, the Ethernet connection shall be named as
“Ethernet” and the Vnet/IP communication would be given a name, for example, “VnetIPOpen”
so as to distinguish the two.
l Indication of Connection
For Vnet/IP, [Vnet/IP Open Communication Driver (BUS2)] is indicated.
040301E.ai
In the above window, choose [Manage network connection], and then Network Connections
window will be displayed.
040302E.ai
040303E.ai
l Setting Properties
Before setting the IP addresses, you need to select the items for use in the properties dialog box
for each network connection.
Table Items for Use by Each Network Connection
Item Ethernet / Vnet/IP Vnet
Client for Microsoft Networks OK NG
QoS Packet Scheduler OK –
File and Printer Sharing for Microsoft Networks OK NG
Yokogawa V net Protocol NG OK
Internet Protocol version 6 (TCP/IPv6) NG NG
Internet Protocol version 4 (TCP/IPv4) OK OK
Link-Layer Topology Discovery Mapper I/O Driver OK NG
Link-Layer Topology Discovery Responder OK NG
040304E.ai
TIP
Except Yokogawa V net Protocol, the items in the above table are installed during installation of Windows Vista.
040305E.ai
040306E.ai
040307E.ai
040308E.ai
The above figure shows an example of the case where the domain number is 1 and the station
number is 24.
After setting, click [OK]. There is no need to restart the PC after setting the IP address.
IMPORTANT
• Do not set the DNS server address.
• Do not change any settings accessed by clicking the [Advanced] button.
040309E.ai
040310E.ai
TIP
If you do not change the bindings, the later installed network card has higher priority in establishing network
connection than the earlier installed network card.
The Ethernet should be placed at a higher priority than the Control Bus (Vnet).
1. From [Advanced] menu on Network Connections window, choose [Advanced Settings] to
open Advanced Settings dialog box.
TIP
If you cannot find the [Advanced] menu, press the Alt key to display the menu bar.
040311E.ai
In the above figure, the control bus has higher priority than the Ethernet because the control bus
(Vnet) driver was installed later than the Ethernet driver.
040312E.ai
3. After setting the priority of Ethernet higher than the control bus, click [OK] to finish setting of
bindings.
After changing the bindings, there is no need to restart the PC.
IMPORTANT
• Do not change the priority of [Remote Access connections] so as to keep it at the lowest
position.
• There is no need to set the Provider Order tab.
• Do not change the bindings for Ethernet and Vnet, which are shown in the Bindings box
below the Connections box.
040313E.ai
040314E.ai
Click [OK]. A message box appears to prompt for restarting the PC. The new computer
name will become valid after the PC is restarted.
3. Restart the PC.
040351E.ai
2. Choose [Network List Manager Policies] in the left pane, and then double click [Unidentified
Networks] in the right pane so as to display “Unidentified Networks Properties” dialog box.
040352E.ai
040315E.ai
040316E.ai
2-2. Click [Private] and click [Next]. [Successfully set network settings] dialog box appears. Click
[Close].
040317E.ai
n Vnet/IP Setup
In Windows XP or Windows Server 2003 environment, the setup procedure for Vnet/IP network
connection is the same as that for Vnet.
The explanations in this section assume that Ethernet and Vnet/IP open communication are
not used together. For example, if Vnet/IP open communication is used while Ethernet is not
used, Vnet/IP network connection is named as “Ethernet.” However, if both Vnet/IP open
communication and Ethernet are used together, the Ethernet connection shall be named as
“Ethernet” and the Vnet/IP communication would be given a name, for example, “VnetIPOpen”
so as to distinguish the two.
l Indication of Connection
For Vnet/IP, [Vnet/IP Open Communication Driver (BUS2)] is indicated.
Network Connections
File Edit View Favorites Tools Advanced Help
Create a new
connection Local Area Local Area
Set up a home or small Connection Connection 2
office network
See Also
Network Troubleshooter
040320E.ai
As many Local Area Connection icons are displayed as there are drivers installed in the
order of installation. If the connection you expect is not displayed here, the device or the
device driver may not be properly installed or the driver is not running normally.
In the above figure, since the Ethernet driver and control bus drivers have been installed in
the PC, their connections are shown as Local Area Connection and Local Area Connection
2, which are difficult to identify. Therefore, rename them to Ethernet and Vnet, respectively.
Network Connections
File Edit View Favorites Tools Advanced Help
Create a new
connection Ethernet Vnet
Set up a home or small
office network
040321E.ai
Connect using:
Configure...
This connection uses the following items:
QoS Packet Scheduler
Yokogawa Vnet/VLnet Protocol
Internet Protocol (TCP/IP)
Description
Transmission Control Protocol/Internet Protocol. The default
wide area network protocol that provides communication
across diverse interconnected networks.
OK Cancel
040322E.ai
General
Advanced...
OK Cancel
040323E.ai
3. Select [Use the following IP address] and set the IP address, subnet mask, and default
gateway for Ethernet as follows:
• When using the PC in the existing environment, enter the IP address currently used on
the network.
• When using the PC in the new environment, set the IP address in accordance with the
PC station address. The rule is as follows:
IP address: 172.17.<Domain Number>.<Station Number> (*1)
Subnet mask: 255.255.0.0
Default gateway: No setting is required
*1: Generally use this rule to set the IP address. However, other IP address can also be used.
General
Advanced...
OK Cancel
040323E.ai
IMPORTANT
• Do not set the DNS server address.
• Do not change any settings accessed by clicking the [Advanced] button.
040324E.ai
Click [OK]. A message box appears to prompt for restarting the PC.
Click [Yes] to restart the PC.
General
Advanced...
OK Cancel
040326E.ai
TIP
If you do not change the bindings, the later installed network card has higher priority in establishing network
connection than the earlier installed network card.
The Ethernet should be placed at a higher priority than the Control Bus (Vnet).
1. From [Advanced] menu on Network Connections window, choose [Advanced Settings] to
open Advanced Settings dialog box.
Advanced Settings
Connections:
Vnet
Ethernet
[Remote Access connections]
OK Cancel
040327E.ai
In the above figure, the control bus has higher priority than the Ethernet because the control
bus (Vnet) driver was installed later than the Ethernet driver.
Connections:
Ethernet
Vnet
[Remote Access connections]
OK Cancel
040328.ai
3. After setting the priority of Ethernet higher than the control bus, click [OK] to finish setting of
bindings.
After changing the bindings, there is no need to restart the PC.
IMPORTANT
• Do not change the priority of [Remote Access connections] so as to keep it at the lowest
position.
• There is no need to set the Provider Order tab.
• Do not change the bindings for Ethernet and Vnet, which are shown in the Bindings box
below the Connections box.
Computer description:
OK Cancel Apply
040329E.ai
Computer name:
HIS0124
More...
Member of
Domain:
Workgroup:
WORKGROUP
OK Cancel
040330E.ai
Click [OK]. A message box appears to prompt for restarting the PC. The new computer
name will become valid after the PC is restarted.
3. Restart the PC.
TIP
• Since DNS server is not used, Do not click [More] button on Computer Name Changes dialog box.
• Since the computer does not belong to a domain, do not click the radio button of [Domain] on Computer
Name Changes dialog box.
040331E.ai
TIP
Internet Connection Sharing (ICS) is for sharing the internet connection by the computers in a small scale office
network or home network.
n Bridge Connection
Do not use bridge connection. If bridge connection is created in the PC, not only the control bus
communication of the PC becomes abnormal, but also the communication of the whole control
bus network may be jeopardized. (If the bridge connection is already created, you need to delete
the bridge connection.)
TIP
The bridge connection is for bridging the multiple networks connected to a PC.
START
Execute Install
Click [USB driver for OPKB] on CENTUM VP installation menu
command
PC restart
END
050001E.ai
IMPORTANT
For upgrading CS 3000 R3 to CENTUM VP, you must first uninstall the USB OPKB driver for CS
3000 R3 using CS 3000 media before following the procedure for adding USB OPKB driver for
CENTUM VP.
TIP
You can connect the OPKB before you start your PC.
If you add USB OPKB driver (initial installation), the Found New Hardware dialog box
appears. But if you update the driver (i.e., the driver is already installed in the computer), the
dialog box does not appear.
050002E.ai
If the Found New Hardware dialog box appears, select “Ask me again later”.
(Do not install the driver from the Found New Hardware dialog box.)
3. Insert the CENTUM VP software medium into the drive.
Setup menu appears when you insert the CENTUM VP software media into a DVD-ROM
drive. If the Setup menu does not appear, double-click “CENTUMSetup.exe” in the top
folder in the software media using Explorer.
050003E.ai
5. Click [OK].
6. The following Windows Security dialog boxes for installing the system devices software and
for human interface devices software appear. Click “Install” respectively. Installation process
starts.
050004E.ai
050005E.ai
TIP
If you select “Always trust software from ‘Yokogawa Electric Corporation’.” in the Install System Devices Software
dialog box, the Install Human Interface Devices Software dialog box immediate above does not appear. For the
same reason, the Install System Devices Software dialog box may not appear (if you select the option in the
previous procedure). Therefore, do not select “Always trust software from ‘Yokogawa Electric Corporation’.”
050006E.ai
If any message other than the above appears, the setup failed. Confirm that the OPKB is
correctly connected and repeat the installation procedure.
8. Restart your computer.
But if you continue to install CENTUM VP software and restart the computer after that, you
can skip this step.
050007E.ai
050008E.ai
l Flow of Un-installation
START
Execute Install
command
PC restart
END
050009E.ai
IMPORTANT
You can uninstall USB OPKB driver only if the OPKB is connected to a USB port and the
connected OPKB is powered on.
050010E.ai
050011E.ai
If any message other than the above appears, the un-installation failed. Confirm that the
OPKB is correctly connected and repeat the un-installation procedure.
7. Restart your computer.
n Type of installation
• New Installation
Initially installs CENTUM VP software in a computer.
Key code for CENTUM VP is required for this installation.
• Version Up Installation
Upgrades CS 3000 software on a computer to CENTUM VP.
Key code for CENTUM VP is required for this installation.
• Revision Up Installation
Upgrades CENTUM VP software on a computer with minor changes.
If no package is added, Key code for CENTUM VP is not required for this installation.
• Upgrade Installation from CS 1000
Upgrades CS 1000 software on a computer to CENTUM VP.
Key code for CENTUM VP is required for this installation
• Add Installation
Adds software packages to a computer installed with CENTUM VP software.
A medium containing CENTUM VP software in the same version as the one on the PC is
required.
• Re-Installation
Installing the CENTUM VP software version in a computer installed with the version for
purposes such as program repairs.
Key code for CENTUM VP is not required for this installation.
n Preparation
Have the following items at hand for installation.
• CENTUM VP Software Medium (Medium model code: LHSKM30): 1 piece
• CENTUM VP Software key code FDC (Medium model code: LHSCM30)
• CENTUM VP Project ID License (LHSPJT1/LHMPJT1)
• External DVD-ROM drive (when there is only CD-ROM drive in the PC)
• Other necessary Software for CENTUM VP operation
Adobe Acrobat, Microsoft Office, etc
n Precaution
SEE
ALSO For information about administrative user, see:
“■ Administrative User” in 1, “Overview”
2. Exit all running programs including resident programs such as anti-virus software before you
start installing CENTUM VP software.
3. Insert the CENTUM VP key code FD into a floppy disk drive.
4. Insert the CENTUM VP software medium into a DVD-ROM drive.
CENTUM VP Installation Menu appears. If it does not appear, double-click “CENTUMSetup.
exe” in the top folder in the software medium using Explorer. CENTUM VP Installation Menu
appears.
060101E.ai
060102E.ai
Figure Dialog Box for Confirming Microsoft .NET Framework and MSXML
The following dialog box appears showing Microsoft .NET Framework and MSXML are
being installed.
060103E.ai
060104E.ai
7. The Welcome to the InstallShield Wizard for YOKOGAWA CENTUM VP dialog box
appears.
Click [Next].
060105E.ai
Figure Welcome to the InstallShield Wizard for YOKOGAWA CENTUM VP Dialog Box
060106E.ai
060107E.ai
TIP
If the entered Project ID does not match the Project ID contained in the key code FD, an error message appears
and installation is aborted.
060108E.ai
11. The following dialog box appears after the computer finishes loading the key code from the
key code FD.
• If you have more than one key code, insert the next FD and click [Yes].
• If you have only one key code, click [No] and move on to the next step.
060109E.ai
060110E.ai
TIP
You can change the settings for Operator keyboard in HIS Utilities after installing CENTUM VP.
060111E.ai
060112E.ai
15. If a Report package (LHS6530) is in your computer, the following dialog box appears.
Click [OK].
060113E.ai
060114E.ai
17. Start Copying Files dialog box showing User Information, ID number, Package List
appears for you to confirm the settings before copying files. Confirm them and click [Next].
Installation starts.
060115E.ai
060116E.ai
2. Redistributable Microsoft Visual C++ 2005 is installed. (If the Redistributable Microsoft Visual C++ 2005
library is not in your computer)
(It may take several minutes to process this.)
060117E.ai
18. When the installation completes, the InstallShield Wizard Complete dialog box appears.
Click [Yes, I want to restart my computer now.] and Click [Finish]. Installation completes.
060118E.ai
START
Installation of
CENTUM VP Software Refer to “6.1 New Installation”.
Rev. Up processing of
CS 3000 project database
END
060201E.ai
IMPORTANT
• CENTUM VP keycode is required for this installation.
• “_bak” is appended to the name of top folder containing CS 3000.
The “_bak” folder is used for copying project database and restoring data for each package.
We recommend you keep the folder for a certain period for maintenance purposes.
• If you open the CS 3000 project database using a builder after installing CENTUM VP, the
project database is upgraded to the one for CENTUM VP.
SEE
ALSO For details of backing up package data, see:
6.2.2 “Backup and Restoration of Package Data”
060202E.ai
060203E.ai
IMPORTANT
Delete the device driver of CS 3000, and install the latest device driver.
Device drivers for a console-type HIS are replaced with the latest device drivers in the installation
process of CENTUM VP, therefore you don’t have to uninstall them.
SEE
ALSO For details of installing device drivers, see:
4, “Setting of Network”
5, “USB driver for Operator Keyboard (OPKB)”
SEE
ALSO For details of installing CENTUM VP software, see:
6.1, “New Installation”
SEE
ALSO For Project’s Attribution Utility, see:
F2.3 “Project’s Attribution Utility” in Reference (IM 33M01A30-40E)
3. From the Start menu, select [All Programs] - [YOKOGAWA CENTUM] - [System View]. The
project database is automatically upgraded.
TIP
• When HIS is converted to CENTUM VP HIS, all CS 3000 graphic files of the station are automatically
converted to CENTUM VP graphic formats.
• You also can start “HIS Database Conversion Tool” from the Tool menu of System View by selecting “HIS
Database Conversion Tool”.
060204E.ai
TIP
You can use “Graphic File Converter” to convert a CS 3000 graphic file to a CENTUM VP graphic file. You can
then import the graphic file converted to CENTUM VP formats in the CENTUM VP Graphic Builder and edit.
1. From the Start menu, select [YOKOGAWA CENTUM] - [Graphic File Converter]. “Graphic
File Converter” starts.
060205E.ai
060206E.ai
If the file conversion is successful, “Successful” appears in the [Status] column, “Failed” if
unsuccessful, at the completion of the conversion.
060207E.ai
SEE
ALSO For details of restoring package data, see:
6.2.2, “Backup and Restoration of Package Data”
TIP
In Version-Up installation, CS 3000 Software folder is backed up. “_bak” is appended to the backup folder name.
As for these Data, after the installation of CENTUM VP, the target file or folder should be copied
to a relatively same location under the <CENTUM VP installation folder>. If a folder with the same
name already exists, overwrite it.
TIP
If you do not need CAMS historical data, you don’t have to back up files in the following folder.
CAMS historical data folder: <CS 3000 installation folder>\CAMS\hist
• Restore
You need to restore the following folders and files from the backup data to the same
locations under the <CENTUM VP installed> folder.
Folders:
CAMS\Client (CAMS for HIS Message Monitor data)
CAMS\configurator (CAMS for HIS configurator data)
CAMS\database (CAMS run-time data base)
CAMS\defhist (CAMS database backup)
CAMS\hist (CAMS for HIS Historical Data)
CAMS\ScenarioFiles (Scenario files of CAMS for HIS Alarm Generator Tools )
CAMS\Viewer (CAMS for HIS Historical Viewer data)
Files:
CAMS\CAMSCapture.bin (Setup OPC A&E server)
CAMS\ServerConfig.xml (Setup CAMS for HIS Server)
CAMS\SystemScopeDefinition.bin (Setup Equalization Scope)
3. Enable CAMS for HIS
If the HIS functions are not running, you need to restart the PC to start the HIS functions.
In HIS Utility, enable CAMS for HIS and restart your computer.
START
Refer to “4. Setting of Network”, “5.
Installation of USB driver for Operator
Keyboard (OPKB)”.
Update of device driver
Installation of CENTUM
Refer to “6.1 New Installation”.
VP Software
Revision Up processing of
Project database
END
060301E.ai
IMPORTANT
• Keycode is not required if you do not add a new Package during the Revision Up process.
• Project database is upgraded when you open the project database in a builder after the
installation.
SEE
ALSO For details of updating device drivers, see:
4, “Setting of Network”
5, “Installation of USB driver for Operator Keyboard (OPKB)”
SEE
ALSO For details of installing CENTUM VP software, see:
6.1, “New Installation”
SEE
ALSO For procedure to convert project database, see:
“■Procedure 5: Steps to convert project database “ in 6.2 “Version Up Installation (from CS 3000 to
CENTUM VP)”
START
Revision Up processing of
CS 1000 project database
Uninstallation of the
program for CS 1000
project database
Refer to “6.4.3 Migrate from CS 1000 to
CENTUM VP".
Update of device driver
Installation of CENTUM
VP Software
END
060401E.ai
IMPORTANT
• Be sure to back up the CS 1000 project database before starting this operation.
• Keycode is not required for the installation of a program for converting CS 1000 Project
Revision.
• When the conversion of the CS 1000 project database is completed, be sure to uninstall
the program for converting CS 1000 Project Revision before installing the CENTUM VP
Software.
• Keycode is required for installing CENTUM VP Software.
• The installation procedure of CENTUM VP Software is the same as the Version Up
Installation. The CENTUM VP Software is installed in a separate folder from the CS 1000
installation folder.
SEE
ALSO • For how to disable Access Control, see:
Reference Access Administrator (FDA : 21 CFR Part 11 compliant) (IM 33M01A30-40E)
• For details of backup, see:
6.4.2, “Backup and Restoration of Package Data of CS 1000”
SEE
ALSO For details of disabling HIS automatic activation, Automatic logon, and CENTUM Desktop environment setting,
see:
”Procedure 2: Disable HIS automatic activation, Automatic logon, and CENTUM Desktop environment
setting” in 6.2, “Version Up Installation (from CS 3000 to CENTUM VP)”
SEE
ALSO For details of restoring package data, see:
6.4.2, “Backup and Restoration of Package Data of CS 1000”
l Backup and Restoration work for the Operation and Monitoring function
1. Export and import HIS configuration data
Using Export function in HIS Setup, back up HIS Registry data.
For restoring HIS configuration data after installation, edit the backup file (File extension:
.reg) as follows using a text editor, and import it.
Example: Replace “BenKei” in Registry path with “CS3K”.
Before: HKEY_LOCAL_MACHINE\SOFTWARE\YOKOGAWA\BenKei\HIS\COMMON
After: HKEY_LOCAL_MACHINE\SOFTWARE\YOKOGAWA\CS3K\HIS\COMMON
2. Set Number of Tags
In the Station tab page in HIS Setup, set a new Number of Tags for CENTUM VP.
l When using the Access Control function - PHS5110, FDA function - PHS5170
• Backup
If “engineers’ account files for referencing” specified in Access Control Utilities is under the
CS 1000 installation folder, back up all files in the folder. In the backup, add Full control to
Everyone for the file EngPassword2.odc.
• Restore
Restore the file and set up in Access Control Utilities.
CS 1000 project
CS 1000 project database ready for Project database in
Revision Up For CENTUM VP
database upgrading to CENTUM VP
CENTUM VP
060404E.ai
TIP
The capability of the converting program is to convert CS 1000 Project database to CENTUM VP project
database, nothing else.
060405E.ai
4. On the menu, click [CS 1000 Project DB conversion]. Installation of the program for
converting CS 1000 project starts.
5. The following dialog box for specifying the destination of the conversion program appears.
TIP
If CS 3000 or CENTUM VP software is already in your computer, an error message appears and you cannot
install the conversion program.
060406E.ai
If you want to change “Destination Folder”, enter the destination. If you click [OK],
installation starts.
060407E.ai
Figure Dialog Box for Confirming Microsoft .NET Framework and MSXML
The following dialog box appears while Microsoft .NET Framework and MSXML are being
installed.
060408E.ai
060409E.ai
Conversion program for CS 1000 project is installed showing its progress status.
(It may take several minutes to complete installation.)
060410E.ai
060411E.ai
SEE
ALSO For Project’s Attribution Utility, see:
F2.3 “Project’s Attribution Utility” in Reference (IM 33M01A30-40E)
3. From the Start menu, select [All Programs] - [YOKOGAWA CENTUM] - [System View]. The
project database is automatically converted.
SEE
ALSO For details of un-installation, see:
10.1, “Uninstallation of CENTUM VP Software”
SEE
ALSO For details of updating device drivers, see:
4, “Setting of Network”
5, “Installation of USB driver for Operator Keyboard (OPKB)”
SEE
ALSO For details of installing CENTUM VP software, see:
6.2, “Version Up Installation (from CS 3000 to CENTUM VP)”
For security configuration, see:
7, “IT Security Settings”
Dual-Redundant Use
OK Cancel
060412E.ai
2. Choose from the options of [Dual-Redundant] or [Single], [Use] or [Not Use] by clicking the
option buttons in the setting box. And then click [OK].
3. Restart the PC.
TIP
The settings of Network Tool will take effect after restarting the PC.
TIP
Using a HIS Conversion tool, convert the project database to CENTUM VP project database.
• Converting graphic files using a HIS Conversion tool
A HIS Conversion tool automatically converts graphic formats of all graphic files to the formats for CENTUM
VP as well as control drawing smart-parts.
(It takes a few seconds to convert a graphic file.)
After converting graphic files, download them to HIS.
• Launching a HIS Conversion tool
The HIS Conversion tool is launched if
- the project database is in earlier revision when you launch System View, or
- the project database is in earlier revision when the project is opened using System View, or
- you launch the HIS Conversion tool from System View
1. From the Start menu, launch System View. The HIS Conversion tool is launched.
060413E.ai
TIP
• You cannot change project name when the project database is converted.
• The followings are shown while the HIS Conversion tool is running.
- Status bar (lower right of the window) shows name of the file being converted.
- Progress bar (lower left of the window) shows progress status.
060501E.ai
5. Click [CENTUM VP Software] on the CENTUM VP Installation Menu. The Add installation
starts.
060502E.ai
7. After the computer loads the key code from the Key Code FD, the following dialog box
appears.
If you have more than one key code, insert the next FD and click [Yes]. If not, click [No].
060503E.ai
060504E.ai
9. Dialog box for confirmation showing Destination folder, User information (Name and
Company), Project ID number, and Package list appears.
Confirm the information and click [Next]. Add installation starts.
060505E.ai
060506E.ai
10. When the installation completes, InstallShield Wizard Complete dialog box appears.
Click [Finish]. This completes Add installation.
060507E.ai
6.6 Re-Installation
Perform this installation for repairing purposes if some of the CENTUM VP software files
are damaged or deleted mistakenly.
You cannot overwrite the CENTUM VP software with another installation. You have to
uninstall the CENTUM VP first, then install the CENTUM VP software again.
n Un-installation
SEE
ALSO For details of un-installation, see:
10.1, “Uninstallation of CENTUM VP Software”
n Installation
SEE
ALSO For details of new installation, see:
6.1, “New Installation”
7. IT Security Settings
After installing the CENTUM VP software, the strengthened security settings need to be
defined for the PC.
CENTUM VP IT securities can be defined on Security Setting Utility that can be started by
clicking [Setting Security] on CENTUM VP installation menu. The security settings can be
automatically defined by simply following the guidance.
Moreover, if the project database is placed in the file server, the IT security settings also
need to be defined on the file server.
n Security Model
The security models can be categorized into three types according to the set security strength as
follows:
l Legacy Model
The access permission of shared files and the connection setting of DCOM are configured at the
same security level as the CS 3000 or earlier version. Windows Firewall is disabled.
Apply this security model when connecting to other systems such as PRM, ProSafe-RS with
security unspecified, or PC component of old revision CS 3000.
l Standard Model
The access control by the user authentication, the DCOM setting and the firewall are enabled.
Refer to the following section “n Security Setting Items” for the details.
For the standard model, the security setting can be selected from the following two types, which
are based on different user management methods:
Security Setting for Windows Domain Management
Select this when managing the user accounts and groups by the Windows domain
controller. It is necessary to create groups by the domain controller before you configure the
security setting.
Security Setting for Standalone Management
Select this when configuring IT security setting on each PC without using the Windows
domain controller. User accounts are created in each PC, but the user groups and user
management settings must be consistent among all the relevant PCs.
The following shows items for each security type selected by the Security Setting Utility.
Access to files and registries are limited for each user group that is created automatically.
Table Setting Items for Each Security Configuration Type
Type of Security Configuration Domain Standalone
Legacy Type
Setting Item Management Type Management Type
Creation of user groups O (*1) O X (*2)
Access permission of files and folders O O O (*3)
Access permission of registries O O O (*3)
Access permission of Start menu O O X
DCOM settings O O O (*3)
Firewall settings O O O (*4)
070202E.ai
O: Set/created
X: Not set/not created
*1: In the case of security setting for Domain Management, only groups CTM_OPC_LCL and CTM_MAINTENANCE_LCL are
created. Other user groups should be created in advance by the domain server.
*2: User group Everyone is created.
*3: Security setting is set as full control for Everyone.
*4: Firewall is disabled.
*1: When you add a user to the group with the administrator privilege, register the user to the Administrators group (Domain Admins
group in the case of a domain user).
*2: When you configure security setting for Windows domain management, these groups must be created with the domain server
beforehand.
n Automatically-Created Accounts
The automatically created CTM_PROCESS and CENTUM accounts will be explained below.
l CTM_PROCESS Account
CTM_PROCESS account is an automatically created account for starting the CENTUM VP
services.
CTM_PROCESS account cannot be used for logging on.
CTM_PROCESS password is hidden.
Changing password of this account is prohibited.
l CENTUM Account
CENTUM account is only created, as in CS 3000, when the Legacy Model has been selected.
The initial password is “Yokogawa1”. Set a new password as it requires changing the password
when the next time you log on.
The correspondence between the user group numbers in the following table and the user group
names are as follows.
[1] : CTM_OPERATOR
[2] : CTM_ENGINEER
[3] : CTM_ENGINEER_ADM
[4] : CTM_OPC/CTM_OPC_LCL
[5] : CTM_MAINTENANCE/CTM_MAINTENANCE_LCL
[6] : CTM_PROCESS
User Group
Function (Start Menu Items)
[1] [2] [3] [4] [5] [6]
HIS basic software (*1) ○ ○ ○ ○
HIS Utility ○
Access Control Utilities ○ ○
Graphic Builder ○ ○ ○ ○
System View ○ ○ ○
Software Configuration Viewer ○ ○ ○
Consolidated Historical Viewer ○ ○ ○
Copy Tool for Fieldbus associated files ○ ○ ○
Project Attribution Utility ○ ○ ○
Linked-Part List Window ○ ○ ○
Display Device Information ○ ○ ○
Recipe View ○ ○ ○
Report Package ○ ○ ○
[Maintenance] - [Command prompt] ○
[Maintenance] - [Projectsave] ○
[Maintenance] - [Logsave] ○ ○ ○ ○
Configurator of CAMS for HIS ○ ○ ○
Alarm Generator of CAMS for HIS ○ ○ ○
SEM OPC Interface Settings ○ ○ ○
SOE Database Backup ○ ○ ○
SOE Database Property ○ ○ ○
SOE Database Restore ○ ○ ○
SOE Server Monitoring Settings ○ ○ ○
Specify SOE Trigger ○
SOE Server Configurator ○ ○ ○
SOE Viewer ○ ○ ○ ○
070104E.ai
O: Accessible
*1: This function is not launched from the Start menu.
TIP
• Regarding PC restart
After installing CENTUM VP software, the PC needs to be restarted before configuring the
security settings. The [Setting Security] button becomes active only after the PC is restarted.
• Regarding Windows Security Alert Dialog
Before finishing security setting, if an external user is accessing the running HIS, a Windows
Security Alert dialog will be displayed as follows. In this case, you may click [Keep blocking]
button to deny the access and then complete the security setting. However, since the above
security setting was jeopardized, you need to perform the security setting all over again.
070210E.ai
TIP
Alternatively, you can configure security settings for Domain Management by first configuring as
the Standalone Management type and then changing them to Domain Management type after
performing necessary engineering works and debugging.
070201E.ai
070202E.ai
070203E.ai
7. If you select [Standalone: Set the security for Workgroup Management. (Standard Model)]
on the PC that belongs to a Windows domain, the following dialog box is displayed. Click
[OK] to continue.
070204E.ai
070205E.ai
TIP
A progress indicator bar is displayed while the security setting is in progress.
9. If there is a CENTUM account created in the past, the following message box appears. If the
CENTUM account is no longer needed, click [Yes] to delete it.
070206E.ai
070207E.ai
11. In the Windows Vista environment, the following Program Compatibility Assistant dialog box
may appear after the security setting is finished. Since the settings are correct, click [Cancel]
to close the dialog box.
070208E.ai
IMPORTANT
On group policies of domain controller server, if the client Windows Firewall policies are defined,
you need to confirm on the group policies of domain controller server to make sure that both
[Network discovery] and [File sharing] are enabled. If they are not enabled, you need to change
the settings.
070209E.ai
070302E.ai
070303E.ai
070304E.ai
5 From the Start menu, choose [Control Panel] - [Administrative Tools] - [Local Security
Policy]. Local Security Policy window appears.
070305E.ai
070306E.ai
TIP
To specify automatic starting of the file management service (BK FMS), do the following:
Log on to HIS as an administrative user, call up “Services” from Control Panel, start the BK FMS,
choose BK FMS and select “Automatic” as “Startup type”.
1 Creating a Group
In the PC where CENTUM VP is installed, create a group having the same name as the group
created by Security Setting Utility.
SEE
ALSO For more information about Security Setting Utility, see the following;
7.1 “Security Setting Utility”
070307E.ai
070308E.ai
4. Select the checkbox of [Allow incoming echo request] option. And then click [OK].
SEE
ALSO For information about installation of the SOE package, see the following:
M10. “SEM (Sequence of Events Manager) Function” in Reference Options (IM 33M01A30-40E)
SEE
ALSO For details on security setting, see the following:
7.2 “Using Security Setting Utility”
SEE
ALSO For more information about the user groups for CENTUM VP Security Setting Utility, see the following:
7, “IT Security Settings”
SEE
ALSO For more information about creating users, see the following:
11.2, “Adding a Domain User and a Domain Group”
080101E.ai
080102E.ai
080103E.ai
080104E.ai
080105E.ai
SEE
ALSO For more information about creating user accounts, see the following:
“n Standard Model: Stand Alone Type Security Management Settings”
080106E.ai
080107E.ai
SEE
ALSO For more information about Windows environment settings, see the following.
3, “Setting of Windows”
l Performance Option
In Windows XP or Windows Server 2003 environment, [Adjust for best performance] should be
selected for each user on [Performance Options] dialog box. In Windows Vista environment, no
setting is required for Performance Options.
SEE
ALSO For more information about Performance Options, see the following:
“n For Windows XP/Windows Server 2003” in 3.4 “Setting of System Properties”
l Windows Design
In Windows Vista environment, on [Appearance Settings] dialog box, choose [Windows Aero].
l Background of desktop
• In Windows Vista environment: On [Desktop Background], set [Solid Color] for [Location].
TIP
In Windows Vista, when the background color is defined as a solid color or another color after the first logon,
the background color may revert to black at the second logon. If this problem occurs, you need to define the
background color again with the same procedure.
• In Windows XP/Windows Server 2003 environment: On [Display Properties] dialog box, set
[None] for[Background].
l Screen Resolution
Set the [Color Quality] and [Screen Resolution] on Display Properties dialog box as follows:
Table Color Quality and Screen Resolution
Setting
Colors “Highest (32 bit)”
SXGA 1280 by 1024 pixels
Resolution
WXGA 1680 by 1050 pixels
l Screen Saver
Set [None] to [Screen saver].
IMPORTANT
The versions numbers of the OPC server and OPC client should be the same.
The version number of OPC client can be displayed by choosing:
[Programs] - [YOKOGAWA CENTUM] - [YOKOGAWA PACKAGE] from [Start] menu.
IMPORTANT
When using the applications (such as the packages for Report) that require OPC interface to
access batch data, the OPC server as well as the Process Management packages need to be
installed.
Using the OPC server PC and the OPC client PC, do the following.
1. Mount a formatted storage medium (such as a USB memory stick) on the server PC.
2. From Windows Explorer, select “CENTUMVP¥Program¥BKHCOPYOPC.exe”.
3. Select the medium you just mounted. Click [OK]. Client Setup data is created in the
medium.
4. Mount the medium containing the client setup data on the client PC.
5. Logon the client PC as an administrative user.
Run the installer for installing Visual Studio 2005 redistributable library included in the media
for installing CENTUM VP,
(DVD-ROM drive): \CENTUM\Redistributable\jp\vcredist_x86.exe
6. Start the setup.exe in the medium.
CENTUM VP user account is automatically created based on the client setup data.
7. Log on with a user account in the “CTM_OPC user group” and run the OPC client program.
SEE
ALSO For the details of OPC interfaces, see the following:
M2, “OPC Interface” in Reference (IM 33M01A30-40E)
TIP
UPS battery backup should be continued for about a minute.
For notifying the power failure to the users of the PC, the UPS management software can
trigger the BKHHisAcFail.exe program so as to generate [AC Fail] system message.
2. When the power failure prolonged for a time that predicated to be a longer time than the
UPS battery can backup, the UPS management software can start the [BKHAcFailShut.
exe] to shutdown the HIS functions so as to protect the HIS data. A system alarm of [AC Fail
Shutdown Execute] will be generated at the same time,
3. After a few minutes shutting down the HIS functions, the UPS management software will
start to shutdown Windows. The few minute delay to shutdown Windows after shutting
down HIS functions is for the purpose to ensure the builders and HIS applications to have
the sufficient shutdown time.
4. A few minutes after shutting down Windows, the secondary power supply of UPS will be
shutdown by the UPS management software.
5. When power supply recovers, the UPS management software can trigger the
BkHHisAcRecover.exe program so as to generate [AC Recover] system message.
TIP
On UPS, when UPS changes battery, it should trigger an event to start the BKHUpsChk.exe program so as to
display the [UPS Diagnose Error] system message. When the user sees this message, the user may check the
UPS log file to check what happens in the UPS. Therefore, the logs of UPS management software need to be
stored for analyzing power failure events afterwards.
l BKHHisAcFail.exe
Path <CENTUM VP installation folder>\his\tool\BKHHisAcFail.exe
Argument None
Function Outputs the System alarm message “AC Fail”
080202E.ai
l BkHHisAcRecover.exe
Path <CENTUM VP installation folder>\his\tool\BKHHisAcRecover.exe
Argument None
Function Outputs the System alarm message “AC Recover”
080203E.ai
l BKHAcFailShut.exe
Path <CENTUM VP installation folder>\his\tool\BKHAcFailShut.exe
Argument None
Outputs the System alarm message “AC Fail Shutdown” and shuts down
Function the HIS function
080204E.ai
l BKHHisStop.exe
Path <CENTUM VP installation folder>\his\tool\BKHHisStop.exe
Argument None
Function Shuts downs the HIS function
080205E.ai l
BKHUpsChk.exe
Path <CENTUM VP installation folder>\his\tool BKHUpsChk.exe
Argument None
Function Outputs the System alarm message “UPS Diagnose Error”
080206E.ai
l BKFApcsAcFail.exe
Path <CENTUM VP installation folder>\Fcs\tool\ BKFApcsAcFail.exe
Argument None
Function Outputs the System alarm message “AC Fail”
080207E.ai
l BKFApcsAcRecover.exe
Path <CENTUM VP installation folder>\Fcs\tool\ BKFApcsAcRecover.exe
Argument None
Function Outputs the System alarm message “AC Recover”
080208E.ai
l BKFApcsAcFailShut.exe
Path <CENTUM VP installation folder>\Fcs\tool\ BKFApcsAcFailShut.exe
Argument None
Outputs the System alarm message “AC Fail Shutdown”, and shuts down
Function “APCS/GSGW” Control function
080209E.ai
l BKVUpsAcFail.exe
Path <CENTUM VP installation folder>\Eng\tool\BKVUpsAcFail.exe
Argument None
Function Outputs the System alarm message “AC Fail”
080210E.ai
l BKVUpsAcRecover.exe
Path <CENTUM VP installation folder>\Eng\tool\BKVUpsAcRecover.exe
Argument None
Function Outputs the System alarm message “AC Recover”
080211E.ai
l BKVUpsDiagErr.exe
Path <CENTUM VP installation folder>\Eng\tool\BKVUpsDiagErr.exe
Argument None
Function Outputs the System alarm message “UPS Diagnose Error”
080212E.ai
080213E.ai
3. Click [Select] button of [Details] area so as to display the [UPS Selection] dialog box.
080214E.ai
Choose the settings for [Select manufacture], [Select model] and [On port] of the UPS, and then
click [Finish] button.
080215E.ai
Here, the actions during power failure can be defined. The settings need to be properly entered
according to the model of the connected UPS.
080216E.ai
080217E.ai
Figure Services
Path to executable:
C:\WINNT\System32\ups.exe
You can specify the start parameters that apply when you start the service
from here.
Start parameters:
OK Cancel Apply
080218E.ai
080301E.ai
080302E.ai
4. On the dropdown list of [Domain or Computer Name], choose a Windows domain name or a
local computer name.
5. Enter the user name and password for automatically start HIS functions after logging on.
6. Check [Enable Automatic Logon] and [Enable CENTUM Desktop] options and then click
[OK] button.
7. If automatic start of HIS functions is needed by more users after logging on, repeat the
above procedure step 3 to step 6 to add the uers.
8. Click [OK] button to end the HIS Utility.
The procedure is completed.
l Microsoft Excel Macro Security setting - for earlier versions than Excel 2007
The option [Trust access to Visual Basic project] on [Trusted Sources] tab needs to be checked.
IMPORTANT
The Macro Security setting is valid per user account.
1. Start Excel 2007, click the [Microsoft Office] button. And then click [Excel Options].
The Excel Options window will be displayed.
080303E.ai
2. Click [Trust Center] from the left menu on Excel Options window.
Click [Trust Center Settings] button displayed at the lower part of the window so as to
display the Trust Center window.
TIP
When Trust Center window is displayed, the dialog box for connecting the network (prompted for user name and
password) may be displayed. In this case, click Cancel button for a couple of times until the dialog box prompting
for user name and password disappears.
3. Click [Macro Settings] on the left menu of Trust Center window. And then do the following
settings.
• Select the following radio buttons of [Macro Settings] items [Enable all macros (not
recommended, potentially dangerous code can run)]
• Check this option [Trust access to the VBA project object model] for [Developer Macro
Settings] item.
4. Click [OK] button on Trust Center window
5. Click [OK] button on Excel Options window.
SEE
ALSO For the line printer support function, see the following:
E11.5, “Line Printer Output” in Reference, Human Interface Station (IM 33M01A30-40E)
l RS-232C Settings
• Setting a serial port
Make the following settings on a computer to which a printer is connected:
1. Right click [My Computer] icon, choose [Properties] in the menu.
[System Properties] dialog box displays.
2. Open [Hardware] tab and click [Device Manager] button.
[Device Manager] dialog box displays.
3. Click [Ports(COM&LPT)].
4. Right click [Communication Port (COM1)], then choose Properties in the menu.
5. Open [Port Settings] tab.
6. Enter the settings as displayed in the figure below and click [OK].
7. The dialog box closes.
Communications Port (COM1) Properties ?
Data bits: 8
Parity: None
Stop bits: 1
OK Cancel
080304E.ai
• Setting on a printer
After making sure of the proper cable connection, make settings according to the printer
manual.
After the file creation, restart the HIS. After restarting, confirm that the Control station which was
defined by the Station Status Window is being displayed now. As for the Control station which is
treated as an exclusion of monitoring, even the station name is not displayed.
If an error occurs after the IP address of HIS is changed and the download is conducted, the
following procedure will help to evade it.
1. Log in the HIS that is showing a download error with an Administrative User.
2. Open the below file by Notepad or others and correct into the appropriate IP address
corresponding to the computer name, and save it.
<CENTUM VP installation folder>\COMMON\ETC\lmhosts.cs
3. Execute the below command by the Command Prompt.
nbtstat -R : (R is an upper-case letter),Cache table of NetBIOS is updated
nbtstat -c : (c is a lower-case letter), Cache table of NetBIOS is displayed
4. Confirm that it is possible to download the project common item to HIS concerned.
1. Tick the box of [ENABLE CAMS for HIS] in CAMS for HIS tab of HIS Utility.
080305E.ai
080306E.ai
Confirm the IP address of each HIS that the CAMS for HIS operates shown in the Detailed
Setting dialog.
TIP
For the normal operation of the equalization function of CAMS for HIS, it is necessary that the IP address shown
here and the IP address configured to the actual HIS should be corresponding. Especially, pay attention when
you use the IP address of HIS by other than the default (172.17.dd.ss).
Dual-Redundant Use
OK Cancel
080307E.ai
TIP
Do not start any applications (either System View applications or HIS Functions).
2. From Start menu, choose [Control Panel]-[Network and Sharing Center] so as to display
[Network and Sharing Center].
080308E.ai
080309E.ai
080310E.ai
SEE
ALSO For more information about installing SOE package, see the following:
M10, “SEM(Sequence of Events Manager) Function” in Reference (IM 33M01A30-40E)
SEE
ALSO For more information about remote connection settings, see the instruction manuals of MicrosoftWindows.
The remote operation and monitoring terminals using Windows terminal service are also
referred to as HIS-TSE.
n Setup Procedure
The setup procedure for the remote operation and monitoring server is shown as follows:
START
Step 4
Displays HIS on
No Server?
Yes
Add HIS-TSE to
Step 5 CENTUM VP Project
END
080401E.ai
SEE
ALSO For more information about installing Windows Server, see the Installation Guide attached with Windows Server
CD-ROM.
Preliminary Steps
You can ensure that you successfully configure your server by completing the following steps before
continuing.
Before continuing, verify that the following steps have been completed.
• Install all modems and network cards.
• Attach all necessary cables.
• If you plan to use this server for Internet connectivity, connect to the Internet now.
• Turn on all peripherals, such as printers and external drives.
• Have your Windows Server 2003 Setup CD available, or know your network installation path.
When you click Next, the wizard will search for network connections.
080402E.ai
TIP
Choose [Settings] - [Control Panel] - [Administrative Tools] - [Manage Your Server] from [Start] menu can open
“Manage Your Server” window.
3. Read the terms on the “Preliminary Steps” of “Configure Your Server Wizard” and then, if
confirmed, [Next] button to continue.
Server Role
You can set up this server to perform one or more specific roles, If you want to add more than one
role to this server, you can run this wizard again.
Select a role. If the role has not been added, you can add it. If it has already been added, you can
remove it. If the role you want to add or remove is not listed, open Add or Remove Programs.
080403E.ai
Windows Components
You can add or remove components of Windows.
To add or remove a component, click the checkbox. A shaded box means that only
part of the component will be installed. To see what's included in a component, click
Details.
Components:
Remote Installation Services 2.0 MB
Terminal Server 0.0 MB
Terminal Server Licensing 0.9 MB
UDDI Services 4.9 MB
080404E.ai
IMPORTANT
In order to implement the remote operation and monitoring server service, the Terminal Server
and the Terminal Server License Server need to be installed.
The Terminal Server is the server to provide the remote operation and monitoring server service,
while the Terminal Server License Server is the server to check the licenses of the clients that
attempted to use the terminal server service.
When a client attempts to connect the terminal server, the terminal server will send a query to the
license server in the same group so as to verify the license of the client.
If both the terminal server and the license server are installed in the same PC, the query will be
handled within the PC, no need to setup group for the servers.
If terminal server and the license server need to be dual-redundantly configured in two PCs, the
installation of the two pairs of servers needs to be performed respectively.
Configuration Warning
Internet Explorer Enhanced Security Configuration will significantly restrict the ability of Users on a terminal server to
browse the Internet from their Terminal Server session. To change this setting for users, click No, go to Internet
Explorer Enhanced Security Configuration, click Details and then uncheck the box for users.
Yes No
080405E.ai
IMPORTANT
After installing the license server, the server needs to be activated. Activation of the license
server is as follows:
1. Choose [All programs] - [Administrative Tools] - [Terminal Server Licensing] from [Start]
menu so as to open Terminal Server Licensing window.
2. Choose [Activate Server] from [Action] so as to start the Terminal Server License Server
Activation Wizard.
3. Following the instructions of the wizard, the activation of the license server can be
continued.
For more information about activating the terminal server licensing, please query the service
agents of Microsoft.
The following packages cannot be used with Server for Remote Operation and Monitoring Function Package.
LHS5420 Test Function
LHS6710 FCS Data Setting / Acquisition Package (PICOT)
OK
080406E.ai
SEE
ALSO For more information about installing CENTUM VP, see the following:
6.1, “New Installation”
TIP
An example below shows how the settings of the terminal server have higher priority than the settings of the
terminal client.
When the start mode in server is Desktop mode while in client is panel mode, the settings in client will be ignored.
l Server Settings
1. Click “Server Settings” in the left pane of “Terminal Service Configuration” window. The
default settings will be displayed in the right pane.
2. Disable [Restrict each user to one session] .
Double click “Restrict each user to one session” to open the “Single Session per user” dialog
box.
Uncheck “Restrict each user to one session” option and then click [OK] button.
3. Double click “Licensing” to open “Licensing” dialog box. The licensing mode can be either
“Per Device” or “Per User” and needs to be set according the requirement for the remote
operation and monitoring server services.
SEE
ALSO For more information about licensing of terminal service, see the instruction manuals of MicrosoftWindows.
“Licensing”
080407E.ai
Properties
Help
• General Tab
Compare with this figure to confirm that the default settings are used.
RDP - Tcp Properties ?
RDP-Tcp
Transport: tcp
Comment:
Encryption
Encryption level: Client Compatible
All data sent between the client and the server is protected by
encryption based on the maximum key strength supported by the
client.
OK Cancel Apply
080409E.ai
Domain:
Password: ••••••
OK Cancel Apply
080410E.ai
TIP
• Since the settings on the server have higher priority than the settings on the client, with the above settings
in the server, the client can only use CETNTUM to logon.
• On the [Logon Settings] tab, if “Always prompt for password” option is checked while no password was
entered, a client can use a different user account other than CENTUM to logon.
Use this tab to set Terminal Services timeout and reconnection settings.
OK Cancel Apply
080411E.ai
TIP
• If the default settings on the [Sessions] tab are used, the connection to the remote operation and monitoring
server will act properly. However, the session will be kept alive when clicking the [X] (Close Mark) of the
client.
Thus the above setting is to force the session to be terminated in one minute after the client window is
closed.
• The remote connection to the server should not be severed when the builders are running.
If the session is severed during downloading, the project database may be damaged.
Initial program
Override settings from user profile and Remote Desktop
Connection or Terminal Services client
OK Cancel Apply
080412E.ai
TIP
StartDesktop.bat is a batch file for starting in desktop mode.
Level of control
View the session
Interact with the session
OK Cancel Apply
080413E.ai
Connection
Use connection settings from user settings
Connect client drives at logon
Connect client printers at logon
Default to main client printer
OK Cancel Apply
080414E.ai
TIP
If “Audio mapping” option is checked, the audio alarms on the remote operation and monitoring server will not
generate the equivalent sounds.
The options other than “Audio mapping” can be changed accordingly.
The follwing network adapters are compatible with the selected transport
type. Select the network adapter you want to use.
Network adapter:
Unlimited connections
Maximum connections: 0
OK Cancel Apply
080415E.ai
IMPORTANT
The network adapter “Yokogawa Vnet/VLnet adapter” should not be specified.
Add... Remove
OK Cancel Apply
080416E.ai
TIP
When adding a new user for accessing the remote operation and monitoring server, the user should not be added
here but added to the user group of “Remote Desktop Users”.
Hardware acceleration
All accelerations are enabled. Use this setting if your computer has no
problems. [Recommended]
OK Cancel Apply
080417E.ai
Figure Troubleshoot
TIP
To improve the display performance of HIS windows, [Hardware acceleration] needs to be adjusted to Full
position.
SEE
ALSO For more information about adding a station on the project for remote operation and monitoring, see the following:
F2.4.2, “Creating a New HIS” in Reference (IM 33M01A30-40E)
Installation Procedure
START
Refer to the
This step is not necessary if the Windows
documents Installation of Windows
service pack is already installed on the PC
provided by service package
Microsoft
Installation of Windows
Security patch
Setting of Touch panel This is not required in the Enclosed display style
Setting after the installation Refer to “8. Activities after the installation”
(Create user account, Setup
Windows environment for
that user and setup UPS)
END
090001E.ai
SEE
ALSO For more information about installing the control bus driver, see the following:
4.1 “Installation of Control Bus Driver”
RS-232C Driver
RS-232C driver needs to be installed fro connecting the operation keyboard.
SEE
ALSO For more information about installing RS-232C driver, see the following:
9.2, “Installing RS-232C Driver”
RAS Driver
RAS driver will be automatically installed for solid style console type HIS. The following dialog
box appears. Click the [Install] button to continue the installation of RAS Driver.
090101E.ai
SEE
ALSO For more information about setting the [Automatic Logon] and the [Auto Start of HIS] options, see the following:
8.3, “Specific Settings of Package”
IMPORTANT
To install the RS-232C driver, the mounting of RAS card is required.
090201E.ai
100101E.ai
100102E.ai
4. Entry the password of this user and then click [OK] button.
5. Delete all users by repeating the procedure from 3 to 4.
100201E.ai
4. Select the [Local Policies] - [Security Options] to display Policy in right pain.
100202E.ai
100203E.ai
100204E.ai
3 Select [Change the way users log on or off]. Windows shown below appears.
100205E.ai
4 Check [Use the Welcome screen] and click [Apply Options] button.
100206E.ai
100207E.ai
100208E.ai
3 Select [Change the way users log on or off]. Windows shown below appears.
100209E.ai
4 Check [Use Fast User Switching] and Click [Add Options]. ([Use the Welcome Screen]
should be checked.)
100210E.ai
3 Check [Start Sidebar when Windows starts] and click [OK] button.
IMPORTANT
In Windows Vista, this setting is for each user.
1 Log on the user who wants to be disabled for Security Center Alert.
2 Select [Control Panel] and [Security Center] from the Windows [Start] menu to display
[Security Center].
100211E.ai
100212E.ai
4 Select [Yes, notify me and display the icon (recommended)] in this dialog box.
In case of Windows XP
1 Logon as an administrative user.
2 Select [Control Panel] and [Security Center] from the Windows [Start] menu to display
[Security Center].
100213E.ai
3 Select [Change the way Security Center alerts me] in left side of the “Windows Security
Center” dialog to display [Alert Setting] dialog.
100214E.ai
100215E.ai
100216E.ai
In case of Windows XP
1 Logon as an administrative user.
2 Select [Control Panel] and [Security Center] from the Windows [Start] menu to display
[Security Center].
3 Select [Automatic Update] in the left side [Help] area of the [Windows Security Center]
dialog.
100217E.ai
100218E.ai
100219E.ai
SEE
ALSO For more Information, see the following:
10.1, “Release the setting for HIS Auto Start, Auto Log in and CENTUM Desktop”
100301E.ai
100302E.ai
100303E.ai
6. When the dialog box for confirmation of deleting the keycodes is displayed, click [Yes] to
delete or click [No] to keep the keycodes.
100304E.ai
100305E.ai
TIP
During uninstallation, a progress bar will be displayed to show the uninstallation progresses.
100306E.ai
100307E.ai
SEE
ALSO For more information about the uninstallation procedure, see the following.
4.1.3, “Removing Control Bus Driver”
SEE
ALSO For more information about the uninstallation procedure, see the following.
“ Uninstalling USB OPKB driver” in 5. “Installation of USB driver for Operator Keyboard (OPKB)”
SEE
ALSO For more information about the uninstallation procedure, see the following.
4.2.3, “Removing Vnet/IP Open Communication Driver”
Preparation
PC installed with Windows Server 2003 (for the domain controller)
Windows Server 2003 Software Medium
TIP
When you want to activate [Manage Your Server] wizard in other time, Select [Manage Your Server] from the
Windows [Start] menu.
110101E.ai
110102E.ai
3. Select [Domain Controller (Active Directory)] as a role of the server, and click [Next] button.
110102E.ai
110104E.ai
110105E.ai
2. The [Operating System Compatibility] page appears. Confirm the information, and click
[Next] button.
110106E.ai
110107E.ai
4. In the [Create New Domain] page, select [Domain in a new forest] and click [Next] button.
110108E.ai
110109E.ai
6. Enter a new domain name followed by “.local” in the box [Full DNS name for new domain]
and click [Next]. In the following example, a new domain name is “CENTUMVP”.
110110E.ai
110111E.ai
8. In the [Database and Log Folders] page, select [Database folder] and [Log folder], and click
[Next]. In the following example, “C:\WINDOWS\NTDS” is selected by default.
110112E.ai
110113E.ai
10. In the [Permissions] page, select [Permissions compatible only with Windows 2000 or
Windows Server 2003 operating systems], and click [Next].
110114E.ai
110115E.ai
Figure Active Directory Installation Wizard (Directory Services Restore Mode Administrator Password)
12. Confirm the information in the [Summary] page, and click [Next] button.
110116E.ai
110117E.ai
110201E.ai
110202E.ai
110203E.ai
4. From the [Users] folder, confirm that five groups were surely created.
110204E.ai
Figure Activate Directory Users and Computers (after creating new group)
110205E.ai
2. The following [New Object-User] dialog box is displayed. Input the necessary information.
TIP
[Full Name] and [User logon Name] have to be input in this dialog box. Additionally, if the [User Logon Name] is
input, another Logon Name which is located under the above-mentioned [User Logon Name] is automatically
input. However, the name is mutable.
110206E.ai
110207E.ai
110208E.ai
110209E.ai
Figure Activate Directory Users and Computers (confirmation of newly created user)
7. Set the appropriate group privilege to the created user. Select the created user and double-
click it. (For the “Operator” user that belongs to “CTM_OPERATOR”)
110210E.ai
110211E.ai
9. Click the [Add] button to display the [Select Group] dialog box.
110212E.ai
110213E.ai
11. Be sure to check if the [CTM_OPERATOR] group is set, and then click [OK].
110214E.ai
110215E.ai
This will complete the procedure for the usual privilege user.
The user that belongs to the group (CTM_ENGINEER_ADM / CTM_MAINTENANCE) having the
administrator privilege changes a primary group and deletes an unnecessary group in the next
section.
110216E.ai
110217E.ai
110301E.ai
110301E.ai
110303E.ai
110304E.ai
110305E.ai
Figure [Managed]
110306E.ai
7. From the [Computers] folder, confirm that the new computer was surely added.
This is the end of the Incorporating PC in the domain from the Server side.
110307E.ai
Figure Active Directory Users and Computers (confirmation of newly added computers)
110308E.ai
Figure Computer
110309E.ai
4. Choose [Computer Name] tab on System Properties dialog box, and then click [Change].
110310E.ai
110311E.ai
6. On the displayed dialog box, enter items to [Computer name] and [Password] for the
account added to as a domain member and permitted to access the domain, then click [OK].
7. On the confirmation dialog box for the changes, click [OK] to continue.
8. Click [Restart Now] on the confirmation dialog box to restart the PC.
110312E.ai
110313E.ai
4. On the displayed dialog box, enter items for [User name] and [Password] for the account
added to as a domain member and permitted to access the domain and then click [OK].
5. On the confirmation dialog box for the changes, click [OK] to continue.
6. Click [Restart Now] on the dialog box prompting for restarting the PC so as to restart the PC.
110314E.ai
12. Troubleshooting
This Chapter describes the causes of major failures and errors and their remedies.
SEE
ALSO For more information about “Set Network Location” dialog box, see the following:
“n Notice on Connecting Network” in 4.3.1, “Setting Network Connection - Windows Vista”
For more information about network troubleshooting, see the following:
4, “Setting of Network”
SEE
ALSO For downloading the Project Common Items to all the HISs, see the following:
“n Downloading the Project Common Items” in the section A2.6, “Procedure 6 Downloading the Contents
Defined” in Engineering Tutorial (IM 33M10D10-40E)
n Device Failure
The cause of failure with the sound board, SCSI board, or other adapters or devices, and the
remedies are as follows:
l Cause
IRQ number of the Control Bus interface card conflicts with other devices.
l Remedy
The Control Bus interface card is a PCI card, if the same IRQ number is used by a ISA card, the
IRQ conflict occurs. Then it is necessary to change IRQ number of the ISA card, or change IRQ
numbers for the adapter card using the PC BIOS, or remove the ISA card.
l Cause
The network binding is not correctly set, or the TCP/IP communication setup is not correct
(IP address, subnet mask, etc.)
l Remedy
• Check hardware, Ethernet adapter card, and Ethernet cable setups, and correct them as
required.
• Check the Network and Dial-up Connections on the Control Panel.
n Unstable PC Operation
l Cause
Incompatible software is installed.
l Remedy
Uninstall either previously or newly installed software.
SEE
ALSO For software compatibility, see the following:
1.3, “Software Environment”
l Cause
This phenomenon may be caused by selecting the printer spooled documents for printing out. On
printer’s properties sheet, check the option [Start printing after last page is spooled], all pages of
the document are printed out after they are spooled so that this phenomenon can be avoided.
Always available
Available form 12:00 AM To 12:00 AM
Priority 1
l Cause
Windows problem with Dell Precision Workstation 390 that appears under specific conditions.
l Procedure
If this happens, disable Themes service.
13. Backup
It is recommended to backup the system periodically as a precaution in case the system
fails. The files listed in the table below should be regularly backed up:
TIP
It is assumed that tuning parameters are saved beforehand.
SEE
ALSO For more information about backup projects, see the following:
F2.6, “Project Data Backup” in Engineering of Reference (IM 33M01A30-40E)
IMPORTANT
Be sure to delete the old folder before copying the project folder.
Overwriting files in the project folder will cause an error in the files, resulting in the inoperability of
the System View, or an unexpected error.
TIP
For the context menus in the graphic windows, the following files are used:
• Default Menu File
• Customized menu File
During installation the Default Menu File will be installed. When upgrading CS 3000, the existing
menu file will be overwritten.
<CENTUM VP Installed Folder>\HIS\CONFIG\BKHMenuDef.xml
n Report Backup
Each report can be copied to a storage medium using the copy function of the report package.
n PICOT Backup
Following directory can be copied to a storage medium using Windows explorer.
<CENTUM VP Installed Folder>\his\users\save\bkpicot
IMPORTANT
• Installing the CENTUM VP system of the same revision without using the key-coded disk,
the registry, user, and service registrations will properly be made. Using the key-coded
floppy disk will not because the installer assumes the installation is just an addition of a
package.
• A new control bus driver installed on Windows needs to be newly added.
CENTUM VP
Installation
IM 33M01A20-40E 1st Edition
INDEX
A H
Accessing Builder-Related Database Hardware Environment.......................................... 1-7
for Reference via Network.................................7-22 Hardware Setup..................................................... 2-1
Adding of Domain User and Group.................... 11-12
Add Installation.....................................................6-41 I
Administrative User................................................ 1-1
Incorporate the Client PC in the domain............ 11-23
Advanced Setup of Windows Network................4-68
Installation of Control Bus Driver........................... 4-2
Automatically-Created Accounts........................... 7-6
Installation of RS-232C Driver............................... 9-4
Automatically Start HIS Functions.......................8-21
Installation of Vnet/IP Open
Communication Driver.......................................4-21
B Installations for Console Type HIS......................... 9-2
Backup.................................................................13-1 Installing CENTUM VP Software........................... 6-1
Installing USB OPKB driver................................... 5-1
C IT Security Settings................................................ 7-1
Cautions on Setting a HIS IP Address
Other Than the Default......................................8-29 L
Cautions on Using CAMS for HIS........................3-28 Legacy Model......................................................... 7-2
CENTUM VP Installation Menu............................. 1-4
Change of the Monitoring-Target N
Control Station...................................................8-27
New Installation...................................................... 6-3
Command for UPS Management
of CENTUM VP..................................................8-13 Notes on Security Setting....................................7-15
Configuring Domain controller............................. 11-2 Notes on Starting Operation and Monitoring
Functions and Test Functions
by Administrative User.......................................7-16
D Notices on Installing CENTUM VP
Disable Scheduled Disk Defragmenter Tool........3-27 in Windows XP Environment.............................3-26
Disable Windows Security Alerts.........................3-20 Not Using Ethernet on CENTUM VP
Disable Windows Sidebar....................................3-19 Entry Class.........................................................8-33
F R
File System............................................................ 3-2 Re-Installation......................................................6-45
Flow Chart of Installation Procedures.................... 1-3 Removing Control Bus Driver..............................4-15
Removing Vnet/IP Open
Communication Driver.......................................4-30
G
Report Package...................................................8-23
Groups and Users Automatically Generated by
Restrictions on Network Setting...........................4-66
Security Setting.................................................... 7-5
Revision Up Installation.......................................6-25
T
Troubleshooting
(the causes of major failures and errors)...........12-1
Troubleshooting of control bus driber
installation..........................................................4-17
Troubleshooting of Vnet/IP Open
Communication Driver Installation.....................4-33
Revision Information
Title : CENTUM VP Installation
Manual No. : IM 33M01A20-40E
Newly published.